Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The PCC 1301 and PowerCommand 1.x are Cummins genset controls with a two-wire RS-485 Modbus RTU slave port. The map gives switch position, operating state, active fault, alternator voltages, currents, kVA and frequency, engine data, Modbus start/stop and E-stop, and the basic genset setup parameters. Settings changed over Modbus are kept only after a save command.

This page lists 49 Modbus registers for the Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Cummins’s own free documentation (linked below) and checked against it.

Manufacturer
Cummins
Model
PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)
Equipment type
Generator controller
Registers
49 (17 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
PCC 1301, PCC1301, PowerCommand 1.1, PowerCommand 1.2, PC1.1, PC1.2
Source document
Modbus Register Mapping (PCC 1301, PowerCommand 1.1/1.2/2.2/2.3/3.3, DMC 1000/1500, MCM3320) · A029X159 Issue 7 · rev. 2012-04 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)

Integration in brief

Poll 40010/40011 for switch position and state, 40012/40013 for the active fault, 40018-40044 for alternator values and 40061-40069 for engine data. Remote start/stop is 40300 (1 = start) and remote E-stop 40302.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 9Run/off/auto switch positionUINT16Switch positionRead
HR 10Genset operating stateUINT16Operating stateRead
HR 11Fault codeUINT16Active fault codeRead
HR 12Fault typeUINT16Fault typeRead
HR 25Current phase AUINT16Phase A currentRead
HR 43Alternator frequencyUINT16FrequencyRead
HR 299Genset start/stop via ModbusUINT16Start/stop commandRead/write

Enable Modbus control & writes

The section gives no enable parameter; the RS-485 port is on TB2-3 (+), TB2-4 (-) and TB2-1 (shield). Writing 40004 = 1 (save adjustments) stores the written settings in non-volatile memory.

Byte order & addressing

Network setup

Watch out for

Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

49 of 49 shown
Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR3doc 40004Save adjustmentsWrites all RW settings in this table to non-volatile memory.UINT16Read/write0 = No action; 1 = Save adjustments
HR9doc 40010Run/off/auto switch positionUINT16Read0 = Off; 1 = Run/Manual; 2 = Auto
HR10doc 40011Genset operating stateUINT16Read0 = Stopped; 1 = Start pending; 2 = Warm-up at idle; 3 = Running; 4 = Cool down at rated; 5 = Cool down at idle
HR11doc 40012Fault codeCode of the active fault; list in the service manual.UINT16Read
HR12doc 40013Fault typeUINT16Read0 = Normal; 1 = Warning; 2 = Derate; 3 = Shutdown with cool down; 4 = Shutdown
HR15doc 40016NFPA 110 fault registerBit map in section 4, Table 4-1.BITMAP16Read
HR16doc 40017Extended annunciation fault registerBit map in section 4, Table 4-2.BITMAP16Read
HR17doc 40018Voltage L-N phase AUINT16VRead
HR18doc 40019Voltage L-N phase BUINT16VRead
HR19doc 40020Voltage L-N phase CUINT16VRead
HR21doc 40022Voltage L-L A-BUINT16VRead
HR22doc 40023Voltage L-L B-CUINT16VRead
HR23doc 40024Voltage L-L C-AUINT16VRead
HR24doc 40025Regulation voltageAlternator voltage used for voltage regulation.UINT16VRead
HR25doc 40026Current phase AUINT16× 0.1ARead
HR26doc 40027Current phase BUINT16× 0.1ARead
HR27doc 40028Current phase CUINT16× 0.1ARead
HR28doc 40029Average currentUINT16× 0.1ARead
HR39doc 40040Apparent power phase AUINT16× 0.1kVARead
HR40doc 40041Apparent power phase BUINT16× 0.1kVARead
HR41doc 40042Apparent power phase CUINT16× 0.1kVARead
HR42doc 40043Apparent power totalUINT16× 0.1kVARead
HR43doc 40044Alternator frequencyUINT16× 0.1HzRead
HR57doc 40058Current phase A, % of nominalUINT16× 0.1%Read
HR58doc 40059Current, % of nominal (printed as phase A)Table labels this phase A again; probably phase B.UINT16× 0.1%Read
HR59doc 40060Current phase C, % of nominalUINT16× 0.1%Read
HR60doc 40061Control battery voltageUINT16× 0.1VRead
HR61doc 40062Engine oil pressureUINT16kPaRead
HR63doc 40064Engine coolant temperatureUINT16× 0.1°CRead
HR67doc 40068Engine speedUINT16× 0.1rpmRead
HR68doc 40069Number of engine startsUINT16Read
HR69doc 40070Engine runtime (high part)Upper half of run time in seconds; see notes.UINT16sRead
HR70doc 40071Engine runtime (low part)Lower half of run time in seconds.UINT16sRead
HR299doc 40300Genset start/stop via ModbusUINT16Read/write0 = Stop; 1 = Start
HR301doc 40302Genset E-stop via ModbusUINT16Read/write0 = E-stop not active; 1 = E-stop active
HR2999doc 43000Nominal alternator voltageUINT16VRead/write
HR3000doc 43001Nominal frequencyUINT16Read/write0 = 60 Hz; 1 = 50 Hz
HR3001doc 43002Alternator phasesUINT16Read/write0 = 1 phase; 1 = 3 phase
HR3002doc 43003Alternator connectionUINT16Read/write1 = Wye
HR3003doc 43004Glow plug driver enableUINT16Read/write0 = No; 1 = Yes
HR3004doc 43005Battery charging alternator fault enableUINT16Read/write0 = No; 1 = Yes
HR3005doc 43006Remote start time delayUINT16sRead/write
HR3006doc 43007Remote stop time delayUINT16sRead/write
HR3007doc 43008Crank attemptsStart cycle crank attempts.UINT16Read/write
HR3008doc 43009Crank timeUINT16sRead/write
HR3009doc 43010Crank rest timeUINT16sRead/write
HR3010doc 43011Fault bypass (battle short) enableUINT16Read/write0 = Inactive; 1 = Active
HR3011doc 43012Battle short switch input assignmentUINT16Read/write0 = None; 1 = Customer input 1; 2 = Customer input 2; 3 = Operator panel
HR3012doc 43013Voltage regulator (AVR) enableUINT16Read/write0 = No; 1 = Yes

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)

What Modbus registers does the Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU) have?

This map lists 49 registers: 49 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as Modicon 4xxxx holding-register numbers; 40011 is wire address 10.

What are the minimum Modbus registers to integrate the Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)?

Start with HR 9 Run/off/auto switch position (Switch position); HR 10 Genset operating state (Operating state); HR 11 Fault code (Active fault code); HR 12 Fault type (Fault type); HR 25 Current phase A (Phase A current); HR 43 Alternator frequency (Frequency); HR 299 Genset start/stop via Modbus (Start/stop command).

How do I enable Modbus control of the Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)?

The section gives no enable parameter; the RS-485 port is on TB2-3 (+), TB2-4 (-) and TB2-1 (shield). Writing 40004 = 1 (save adjustments) stores the written settings in non-volatile memory.

Where is the official Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU) Modbus documentation?

The source is Modbus Register Mapping (PCC 1301, PowerCommand 1.1/1.2/2.2/2.3/3.3, DMC 1000/1500, MCM3320) (A029X159 Issue 7), revision 2012-04. Cummins doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/modbus2300.pdf. It may be an older revision, so check it against the live unit.