- PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)
Generator controller · Modbus register map
Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU) Modbus register map
Updated 19 November 2026
The PCC 1301 and PowerCommand 1.x are Cummins genset controls with a two-wire RS-485 Modbus RTU slave port. The map gives switch position, operating state, active fault, alternator voltages, currents, kVA and frequency, engine data, Modbus start/stop and E-stop, and the basic genset setup parameters. Settings changed over Modbus are kept only after a save command.
This page lists 49 Modbus registers for the Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Cummins’s own free documentation (linked below) and checked against it.
- Manufacturer
- Cummins
- Model
- PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)
- Equipment type
- Generator controller
- Registers
- 49 (17 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- PCC 1301, PCC1301, PowerCommand 1.1, PowerCommand 1.2, PC1.1, PC1.2
Integration notes: Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)
Poll 40010/40011 for switch position and state, 40012/40013 for the active fault, 40018-40044 for alternator values and 40061-40069 for engine data. Remote start/stop is 40300 (1 = start) and remote E-stop 40302.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 9 | Run/off/auto switch position | UINT16 | Switch position | Read |
| HR 10 | Genset operating state | UINT16 | Operating state | Read |
| HR 11 | Fault code | UINT16 | Active fault code | Read |
| HR 12 | Fault type | UINT16 | Fault type | Read |
| HR 25 | Current phase A | UINT16 | Phase A current | Read |
| HR 43 | Alternator frequency | UINT16 | Frequency | Read |
| HR 299 | Genset start/stop via Modbus | UINT16 | Start/stop command | Read/write |
Enable Modbus control & writes
The section gives no enable parameter; the RS-485 port is on TB2-3 (+), TB2-4 (-) and TB2-1 (shield). Writing 40004 = 1 (save adjustments) stores the written settings in non-volatile memory.
Byte order & addressing
- Up to 40 contiguous registers per read or write.
- Gaps in the register list are unused addresses.
Network setup
- Wire the two-wire RS-485 bus to TB2-3/TB2-4 with the shield on TB2-1.
- Address and baud settings are not given in this section; set them at the control (see the control's service manual).
Watch out for
- Older control software may not support all registers.
Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 3doc 40004 | Save adjustments | Writes all RW settings in this table to non-volatile memory. | UINT16 | Read/write | 0 = No action; 1 = Save adjustments | |||
| HR | 9doc 40010 | Run/off/auto switch position | UINT16 | Read | 0 = Off; 1 = Run/Manual; 2 = Auto | ||||
| HR | 10doc 40011 | Genset operating state | UINT16 | Read | 0 = Stopped; 1 = Start pending; 2 = Warm-up at idle; 3 = Running; 4 = Cool down at rated; 5 = Cool down at idle | ||||
| HR | 11doc 40012 | Fault code | Code of the active fault; list in the service manual. | UINT16 | Read | ||||
| HR | 12doc 40013 | Fault type | UINT16 | Read | 0 = Normal; 1 = Warning; 2 = Derate; 3 = Shutdown with cool down; 4 = Shutdown | ||||
| HR | 15doc 40016 | NFPA 110 fault register | Bit map in section 4, Table 4-1. | BITMAP16 | Read | ||||
| HR | 16doc 40017 | Extended annunciation fault register | Bit map in section 4, Table 4-2. | BITMAP16 | Read | ||||
| HR | 17doc 40018 | Voltage L-N phase A | UINT16 | V | Read | ||||
| HR | 18doc 40019 | Voltage L-N phase B | UINT16 | V | Read | ||||
| HR | 19doc 40020 | Voltage L-N phase C | UINT16 | V | Read | ||||
| HR | 21doc 40022 | Voltage L-L A-B | UINT16 | V | Read | ||||
| HR | 22doc 40023 | Voltage L-L B-C | UINT16 | V | Read | ||||
| HR | 23doc 40024 | Voltage L-L C-A | UINT16 | V | Read | ||||
| HR | 24doc 40025 | Regulation voltage | Alternator voltage used for voltage regulation. | UINT16 | V | Read | |||
| HR | 25doc 40026 | Current phase A | UINT16 | × 0.1 | A | Read | |||
| HR | 26doc 40027 | Current phase B | UINT16 | × 0.1 | A | Read | |||
| HR | 27doc 40028 | Current phase C | UINT16 | × 0.1 | A | Read | |||
| HR | 28doc 40029 | Average current | UINT16 | × 0.1 | A | Read | |||
| HR | 39doc 40040 | Apparent power phase A | UINT16 | × 0.1 | kVA | Read | |||
| HR | 40doc 40041 | Apparent power phase B | UINT16 | × 0.1 | kVA | Read | |||
| HR | 41doc 40042 | Apparent power phase C | UINT16 | × 0.1 | kVA | Read | |||
| HR | 42doc 40043 | Apparent power total | UINT16 | × 0.1 | kVA | Read | |||
| HR | 43doc 40044 | Alternator frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 57doc 40058 | Current phase A, % of nominal | UINT16 | × 0.1 | % | Read | |||
| HR | 58doc 40059 | Current, % of nominal (printed as phase A) | Table labels this phase A again; probably phase B. | UINT16 | × 0.1 | % | Read | ||
| HR | 59doc 40060 | Current phase C, % of nominal | UINT16 | × 0.1 | % | Read | |||
| HR | 60doc 40061 | Control battery voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 61doc 40062 | Engine oil pressure | UINT16 | kPa | Read | ||||
| HR | 63doc 40064 | Engine coolant temperature | UINT16 | × 0.1 | °C | Read | |||
| HR | 67doc 40068 | Engine speed | UINT16 | × 0.1 | rpm | Read | |||
| HR | 68doc 40069 | Number of engine starts | UINT16 | Read | |||||
| HR | 69doc 40070 | Engine runtime (high part) | Upper half of run time in seconds; see notes. | UINT16 | s | Read | |||
| HR | 70doc 40071 | Engine runtime (low part) | Lower half of run time in seconds. | UINT16 | s | Read | |||
| HR | 299doc 40300 | Genset start/stop via Modbus | UINT16 | Read/write | 0 = Stop; 1 = Start | ||||
| HR | 301doc 40302 | Genset E-stop via Modbus | UINT16 | Read/write | 0 = E-stop not active; 1 = E-stop active | ||||
| HR | 2999doc 43000 | Nominal alternator voltage | UINT16 | V | Read/write | ||||
| HR | 3000doc 43001 | Nominal frequency | UINT16 | Read/write | 0 = 60 Hz; 1 = 50 Hz | ||||
| HR | 3001doc 43002 | Alternator phases | UINT16 | Read/write | 0 = 1 phase; 1 = 3 phase | ||||
| HR | 3002doc 43003 | Alternator connection | UINT16 | Read/write | 1 = Wye | ||||
| HR | 3003doc 43004 | Glow plug driver enable | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 3004doc 43005 | Battery charging alternator fault enable | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 3005doc 43006 | Remote start time delay | UINT16 | s | Read/write | ||||
| HR | 3006doc 43007 | Remote stop time delay | UINT16 | s | Read/write | ||||
| HR | 3007doc 43008 | Crank attempts | Start cycle crank attempts. | UINT16 | Read/write | ||||
| HR | 3008doc 43009 | Crank time | UINT16 | s | Read/write | ||||
| HR | 3009doc 43010 | Crank rest time | UINT16 | s | Read/write | ||||
| HR | 3010doc 43011 | Fault bypass (battle short) enable | UINT16 | Read/write | 0 = Inactive; 1 = Active | ||||
| HR | 3011doc 43012 | Battle short switch input assignment | UINT16 | Read/write | 0 = None; 1 = Customer input 1; 2 = Customer input 2; 3 = Operator panel | ||||
| HR | 3012doc 43013 | Voltage regulator (AVR) enable | UINT16 | Read/write | 0 = No; 1 = Yes |
Notes on this map
- Cummins does not host this document publicly; the link is a copy on an integrator's site (Control Concepts). A dealer site lists a newer Issue 26 (2020) that could not be downloaded here; registers may have been added since Issue 7.
- Only section 1 (PCC 1301 / PowerCommand 1.x) is covered. PowerCommand 2.x/3.x, DMC and MCM3320 use other register maps in the same document.
- Engine runtime is split over 40070 (named high byte) and 40071 (named low byte), 1 s units. Section 1 does not give a combining rule, so they are listed as two separate words; section 2 of the same document uses value = high x 65536 + low for its 32-bit pairs.
- 40059 is printed as 'phase a' a second time; it sits between phase A (40058) and phase C (40060).
- Coolant temperature (40064) is printed as unsigned 0.1 °C and engine speed (40068) as 0.1 rpm; transcribed as printed.
- The NFPA 110 and extended annunciation bit maps (40016/40017) are in section 4, Tables 4-1/4-2. Those tables label bit 0 as the MSB and bit 15 as the LSB, while the MCM3320 section of the same document calls bit 15 the most significant, so the bit positions are not expanded here.
- Left out: the governor/AVR tuning, model/serial number characters, metering calibration and configurable I/O settings (43014-43090).
- Not every control software version supports every register; an unsupported register may simply not answer while others do.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)
What Modbus registers does the Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU) have?
This map lists 49 registers: 49 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as Modicon 4xxxx holding-register numbers; 40011 is wire address 10.
What are the minimum Modbus registers to integrate the Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)?
Start with HR 9 Run/off/auto switch position (Switch position); HR 10 Genset operating state (Operating state); HR 11 Fault code (Active fault code); HR 12 Fault type (Fault type); HR 25 Current phase A (Phase A current); HR 43 Alternator frequency (Frequency); HR 299 Genset start/stop via Modbus (Start/stop command).
How do I enable Modbus control of the Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)?
The section gives no enable parameter; the RS-485 port is on TB2-3 (+), TB2-4 (-) and TB2-1 (shield). Writing 40004 = 1 (save adjustments) stores the written settings in non-volatile memory.
Where is the official Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU) Modbus documentation?
The source is Modbus Register Mapping (PCC 1301, PowerCommand 1.1/1.2/2.2/2.3/3.3, DMC 1000/1500, MCM3320) (A029X159 Issue 7), revision 2012-04. Cummins doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/modbus2300.pdf. It may be an older revision, so check it against the live unit.
More Cummins Modbus register maps
- Generator controller (paralleling master control)
Cummins MCM3320 master control module (Modbus RTU)
Cummins MCM3320 master control modules on their RS-485 Modbus RTU port, per section 10 of A029X159 Issue 7.
Also known as: MCM3320, MCM 3320, PowerCommand MCM3320 - Generator controller
Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU)
Cummins PowerCommand 2.x and 3.x generator set controls (PC 2.2, 2.3, 3.3), per section 2 of A029X159 Issue 7; registers marked PC 3.x only are absent on PC 2.x.
Also known as: PowerCommand 2.2, PowerCommand 2.3, PowerCommand 3.3, PC2.2, PC2.3, PC3.3
Other generator controllers register maps
- Generator controller
DEIF AGC-4 Automatic Genset Controller
AGC-4 software 4.83.0 (Modbus tables revision I), genset (DG) application; mains and BTB variants share many addresses but are not covered.
Also known as: AGC-4 DG, AGC 4, Multi-line 2 AGC-4 - Generator controller
Kohler Decision-Maker 6000 generator set controller
Kohler Decision-Maker 6000 generator set controllers, Modbus RTU on the controller's RS-485/RS-232 port, per section 8 of TP-6113.
Also known as: Decision-Maker 6000, DEC 6000, Kohler 6000 controller - Generator controller
Lovato Electric RGK700 AMF genset controller
RGK700, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700, RGK700 AMF - Generator controller
Lovato Electric RGK900SA genset paralleling controller (stand-alone)
RGK900SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900SA, RGK900 SA - Generator controller
Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500)
easYgen-2200/2300/2500, data protocol 5100 (basic visualization), per manual 37535D.
Also known as: easYgen-2200, easYgen-2300, easYgen-2500, easYgen-2000 Series - Generator controller
DEIF AGC 200 Advanced Genset Controller
AGC 200 series software 4.68.2.x, genset (DG) application only.
Also known as: AGC 222, AGC 242, AGC 243, AGC 244, AGC 245, AGC 246, AGC-200
All generator controllers Modbus register maps →
Source: Modbus Register Mapping (PCC 1301, PowerCommand 1.1/1.2/2.2/2.3/3.3, DMC 1000/1500, MCM3320) · A029X159 Issue 7 · rev. 2012-04 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.