- multicube modular meter, SM352 sub-metering slave (Modbus RTU)
Power meter (modular multi-circuit energy meter) · Modbus register map
Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU) Modbus register map
Updated 17 November 2026
The multicube is a modular sub-metering system: one master display unit plus up to ten SM352 modules, each holding two three-phase meters. Every slave meter answers on its own Modbus RTU ID and carries the same register set, which is the one listed here (energy, instantaneous values, THD, setup and tariff totals). The master unit's concentrator tables that summarise all slaves are not covered.
This page lists 81 Modbus registers for the Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Northern Design’s own free documentation (linked below) and checked against it.
- Manufacturer
- Northern Design
- Model
- multicube modular meter, SM352 sub-metering slave (Modbus RTU)
- Equipment type
- Power meter (modular multi-circuit energy meter)
- Registers
- 81 (17 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- MultiCube, ND multicube, SM352, RTU485
Integration notes: Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU)
Address each SM352 half by its own Modbus ID (master ID + 1, + 2, ...). Read the K scale registers 2837-2840 and eScale 513 once, then poll 2816-2836 and 514-519 with function 03; up to 128 registers fit in one read.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2840 | Power scale Kp | INT16 | Power scale Kp | Read |
| HR 2837 | Amps scale Ki | INT16 | Amps scale Ki | Read |
| HR 2816 | System kW | INT16 | System kW (raw) | Read |
| HR 2822 | Phase 1 amps | INT16 | Phase 1 amps (raw) | Read |
| HR 2821 | Phase 1 volts | INT16 | Phase 1 volts (raw) | Read |
| HR 2819 | System PF | INT16 | System power factor | Read |
| HR 513 | eScale | UINT16 | Energy exponent eScale | Read |
| HR 514 | System kWh | UINT32 ABCD | System kWh | Read/write |
Enable Modbus control & writes
Fit the RTU485 communications module. Set the master display unit's Modbus ID in its programming menu; it then gives each slave meter the next IDs in sequence.
Byte order & addressing
- One multicube can use up to 21 IDs (master + 20 slave meters). Leave a gap that large between master IDs when several systems share a bus.
- Scale exponents are offset by 3: value = raw x 10^(K-3).
Network setup
- RS-485 half duplex, two wires plus 0 V; 4800, 9600 or 19200 baud.
- Replies take up to 250 ms; wait at least 10 ms after a reply before the next request.
Watch out for
- System and per-phase energy registers are writable; a write changes billing totals.
- A slave set to three-phase returns zero in single-phase registers, and the other way round.
Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 512doc 40513 | eScale (high word) | UINT16 | Read | |||||
| HR | 513doc 40514 | eScale | Energy exponent shared by all energy registers. | UINT16 | Read | ||||
| HR | 514doc 40515 | System kWh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read/write | |||
| HR | 516doc 40517 | System kVAh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read/write | |||
| HR | 518doc 40519 | System import kvarh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read/write | |||
| HR | 768doc 40769 | eScale (high word, per-phase table) | UINT16 | Read | |||||
| HR | 769doc 40770 | eScale (per-phase table) | UINT16 | Read | |||||
| HR | 770doc 40771 | Load 1 kWh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. Single-phase mode. | UINT32 | ABCD | Read/write | |||
| HR | 772doc 40773 | Load 2 kWh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. Single-phase mode. | UINT32 | ABCD | Read/write | |||
| HR | 774doc 40775 | Load 3 kWh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. Single-phase mode. | UINT32 | ABCD | Read/write | |||
| HR | 776doc 40777 | Load 1 import kvarh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. Single-phase mode. | UINT32 | ABCD | Read/write | |||
| HR | 778doc 40779 | Load 2 import kvarh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. Single-phase mode. | UINT32 | ABCD | Read/write | |||
| HR | 780doc 40781 | Load 3 import kvarh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. Single-phase mode. | UINT32 | ABCD | Read/write | |||
| HR | 2816doc 42817 | System kW | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 2817doc 42818 | System kVA | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 2818doc 42819 | System kvar | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 2819doc 42820 | System PF | INT16 | × 0.001 | Read | ||||
| HR | 2820doc 42821 | Frequency | Documented as 500 = 50.00 Hz. | INT16 | × 0.1 | Hz | Read | ||
| HR | 2821doc 42822 | Phase 1 volts | Raw signed count; V = raw x 10^(Kvp-3), Kvp at 2838. | INT16 | Read | ||||
| HR | 2822doc 42823 | Phase 1 amps | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read | ||||
| HR | 2823doc 42824 | Phase 1 kW | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 2824doc 42825 | Phase 2 volts | Raw signed count; V = raw x 10^(Kvp-3), Kvp at 2838. | INT16 | Read | ||||
| HR | 2825doc 42826 | Phase 2 amps | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read | ||||
| HR | 2826doc 42827 | Phase 2 kW | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 2827doc 42828 | Phase 3 volts | Raw signed count; V = raw x 10^(Kvp-3), Kvp at 2838. | INT16 | Read | ||||
| HR | 2828doc 42829 | Phase 3 amps | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read | ||||
| HR | 2829doc 42830 | Phase 3 kW | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 2830doc 42831 | Phase 1 PF | INT16 | × 0.001 | Read | ||||
| HR | 2831doc 42832 | Phase 2 PF | INT16 | × 0.001 | Read | ||||
| HR | 2832doc 42833 | Phase 3 PF | INT16 | × 0.001 | Read | ||||
| HR | 2833doc 42834 | Ph1-Ph2 volts | Raw signed count; V = raw x 10^(Kvl-3), Kvl at 2839. | INT16 | Read | ||||
| HR | 2834doc 42835 | Ph2-Ph3 volts | Raw signed count; V = raw x 10^(Kvl-3), Kvl at 2839. | INT16 | Read | ||||
| HR | 2835doc 42836 | Ph3-Ph1 volts | Raw signed count; V = raw x 10^(Kvl-3), Kvl at 2839. | INT16 | Read | ||||
| HR | 2836doc 42837 | Neutral current | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read | ||||
| HR | 2837doc 42838 | Amps scale Ki | Decimal exponent K used as value x 10^(K-3). | INT16 | Read | ||||
| HR | 2838doc 42839 | Phase volts scale Kvp | Decimal exponent K used as value x 10^(K-3). | INT16 | Read | ||||
| HR | 2839doc 42840 | Line volts scale Kvl | Decimal exponent K used as value x 10^(K-3). | INT16 | Read | ||||
| HR | 2840doc 42841 | Power scale Kp | Decimal exponent K used as value x 10^(K-3). | INT16 | Read | ||||
| HR | 3072doc 43073 | Phase 1 kVA | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3073doc 43074 | Phase 2 kVA | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3074doc 43075 | Phase 3 kVA | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3075doc 43076 | Phase 1 kvar | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3076doc 43077 | Phase 2 kvar | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3077doc 43078 | Phase 3 kvar | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3078doc 43079 | Peak hold Ph1 amps | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read | ||||
| HR | 3079doc 43080 | Peak hold Ph2 amps | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read | ||||
| HR | 3080doc 43081 | Peak hold Ph3 amps | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read | ||||
| HR | 3081doc 43082 | I1 THD | Documented as 1000 = 100%. | INT16 | × 0.1 | % | Read | ||
| HR | 3082doc 43083 | I2 THD | Documented as 1000 = 100%. | INT16 | × 0.1 | % | Read | ||
| HR | 3083doc 43084 | I3 THD | Documented as 1000 = 100%. | INT16 | × 0.1 | % | Read | ||
| HR | 3584doc 43585 | Meter model | Reads 352 for an SM352. | UINT16 | Read | ||||
| HR | 3585doc 43586 | Meter type | UINT16 | Read | 0 = 1 x three-phase meter; 1 = 3 x single-phase meters | ||||
| HR | 3586doc 43587 | Firmware version | Hex coded, e.g. 0x14 = 1.04. | UINT16 | Read | ||||
| HR | 3587doc 43588 | CT primary | 5-25,000 A. | UINT16 | A | Read/write | |||
| HR | 3588doc 43589 | CT secondary | Documented as 33,333 = 0.33333 V. | UINT16 | × 0.00001 | V | Read/write | ||
| HR | 3589doc 43590 | CT phase angle | Documented as +/-10 = +/-1.0 degree. | INT16 | × 0.1 | deg | Read/write | ||
| HR | 3590doc 43591 | CT multiplier | 1-20. | UINT16 | Read/write | ||||
| HR | 3591doc 43592 | CT auto rotate | UINT16 | Read/write | 0 = No rotate; 1 = Rotate | ||||
| HR | 3592doc 43593 | PT primary / system volts | 5-50,000 V. | UINT16 | V | Read | |||
| HR | 3593doc 43594 | Meter nominal voltage | 10-600 V. | UINT16 | V | Read | |||
| HR | 3597doc 43598 | System power demand period | Documented as 1 = 10 s, 20 = 200 s. | UINT16 | × 10 | s | Read/write | ||
| HR | 3601doc 43602 | Modbus ID | 2-247; assigned by the main display unit. | UINT16 | Read | ||||
| HR | 3602doc 43603 | Baud rate | Baud / 100, e.g. 96 = 9600. | UINT16 | Read/write | ||||
| HR | 3603doc 43604 | Parity | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | ||||
| HR | 4352doc 44353 | Tariff 1 system kWh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4354doc 44355 | Tariff 1 system kvarh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4356doc 44357 | Tariff 2 system kWh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4358doc 44359 | Tariff 2 system kvarh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4360doc 44361 | Tariff 3 system kWh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4362doc 44363 | Tariff 3 system kvarh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4364doc 44365 | Tariff 4 system kWh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4366doc 44367 | Tariff 4 system kvarh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4368doc 44369 | Tariff 5 system kWh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4370doc 44371 | Tariff 5 system kvarh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4372doc 44373 | Tariff 6 system kWh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4374doc 44375 | Tariff 6 system kvarh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4376doc 44377 | Tariff 7 system kWh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4378doc 44379 | Tariff 7 system kvarh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4380doc 44381 | Tariff 8 system kWh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 4382doc 44383 | Tariff 8 system kvarh | Raw display count; real value = raw x 10^(eScale-6) in kWh / kvarh units. | UINT32 | ABCD | Read | |||
| HR | 7168doc 47169 | Slave module serial number | UINT32 | ABCD | Read |
Notes on this map
- Northern Design does not host this manual publicly; the link is an unaltered copy on a distributor's file host.
- 32-bit values are LONG = 65536 x high word + low word, with the high word at the lower address (ABCD).
- Energy values are the LCD digits with no decimal point. Scale them with eScale (513): factor = 10^(eScale-6) kWh, e.g. eScale 5 gives x0.1. Instantaneous values use value = raw x 10^(K-3) with K from 2837-2840. Both are listed here with scale 1 and no unit, so the map shows raw counts.
- The manual titles tariff table 17 'single phase' but its rows are system totals and its note says three-phase totals; table 16 (per-phase tariff energy, 4096-4191) is left out.
- Left out: current demand periods 1-3 and power demand periods 1-3 (3594-3596, 3598-3600) because no unit is printed, the load-name ASCII registers (7170-7190), the amalgamated tables 30/31 (copies) and all master display unit tables (concentrator copies, logging and tariff structures).
- The serial number at 7168 is printed as a high word / low word pair; it is listed as UINT32 high word first like the other LONG values.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU)
What Modbus registers does the Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU) have?
This map lists 81 registers: 81 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print a 0-based data address beside the Modicon register (512 = 40513). The data address goes on the wire. Each table starts at a multiple of 256, so the table number is the high byte of the address (table 11 = 2816).
What byte order does the Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU)?
Start with HR 2840 Power scale Kp (Power scale Kp); HR 2837 Amps scale Ki (Amps scale Ki); HR 2816 System kW (System kW (raw)); HR 2822 Phase 1 amps (Phase 1 amps (raw)); HR 2821 Phase 1 volts (Phase 1 volts (raw)); HR 2819 System PF (System power factor); HR 513 eScale (Energy exponent eScale); HR 514 System kWh (System kWh).
How do I enable Modbus control of the Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU)?
Fit the RTU485 communications module. Set the master display unit's Modbus ID in its programming menu; it then gives each slave meter the next IDs in sequence.
Where is the official Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU) Modbus documentation?
The source is multicube Modular Metering System Modbus Communications Manual (Revision Beta 1.02), revision 2011-03. Northern Design doesn't publish it on its own website, so this map was re-typed from a free copy at https://res.cloudinary.com/fastron-electronics/image/upload/v1533449721/Northern%20Design/Modular%20Multicube/ND_MultiCube_modular_meter_Modbus_Comms_Manual_March_2011.pdf. It may be an older revision, so check it against the live unit.
More Northern Design Modbus register maps
- Power meter
Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP)
V2 Ethernet versions of the Cube 350I, Cube 350V, Cube 400I and Cube 400V (label 'IP.Ver: V2') and the Rail 350V, per manual revision 1.07p (December 2013).
Also known as: Cube 350I IP, Cube 350V IP, Cube 400I IP, Cube 400V IP, Rail 350V IP, Cube IP meter V2 - Energy meter
Northern Design Cube 300 panel kWh meter (Modbus RTU option)
Cube300 meters fitted with the RS-485 Modbus option, per the October 2005 Modbus Communications manual.
Also known as: Cube300, ND Cube 300, Northern Design Cube300 - Power meter
Northern Design Cube 350 panel power meter (Modbus RTU option)
Cube 350 three-phase panel meters fitted with the RS-485 Modbus option, per the June 2010 comms manual.
Also known as: Cube350, ND Cube 350, Northern Design Cube350
Other power & energy meters register maps
- Sensor / multi-parameter controller
ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)
diaLog DACa controllers with the Modbus RTU interface option, per software manual BA DM 212 12/15.
Also known as: DACa, diaLog DACa, DULCOMETER DACa - Power meter
Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter
Rishabh RISH Delta VAF NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0118 Rev. F.
Also known as: RISH Delta VAF NX, Delta VAF NX, RISH Delta VAF - Energy meter
Rishabh Instruments RISH EM 3490 SS single-phase energy meter
Rishabh RISH EM 3490 SS single-phase energy meters with the optional RS-485 Modbus output, per the 1-phase manual Rev D.
Also known as: RISH EM 3490 SS 1P, EM3490SS 1P, EM 3490 SS single-phase - Power meter
Rishabh Instruments RISH LM1360+ RJ12 smart energy meter
Rishabh RISH LM1360 PLUS RJ12 smart energy meters (RJ12 CT inputs) with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. A (01/2026).
Also known as: RISH LM 1360+, LM1360 PLUS RJ12, LM1360+ - Power meter (multi-circuit branch feeder monitor)
SATEC BFM136/036 branch feeder monitor
SATEC BFM136 and BFM036 multi-circuit meters per Modbus reference guide BG0395 Rev. A8 (July 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM136, BFM036, BFM 136, SATEC BFM136 - Power meter (circuit breaker trip unit)
Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)
Standard dataset registers 32000-32341 served by the IFM (Modbus RTU) or IFE (Modbus TCP) interface for ComPact NSX; the same table lists availability for ComPact NS / MasterPact NT/NW and MasterPact MTZ. Per DOCA0091EN-09 (07/2022).
Also known as: ComPact NSX, Compact NSX, MicroLogic 5.2 E, MicroLogic 6.2 E, MicroLogic 7.2 E, MicroLogic 5.3 A, MicroLogic 6.3 E, IFM LV434000, IFE LV434001, IFE LV434002, ComPact NS, MasterPact NT, MasterPact NW, MasterPact MTZ
All power & energy meters Modbus register maps →
Source: multicube Modular Metering System Modbus Communications Manual · Revision Beta 1.02 · rev. 2011-03 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.