Power meter · Modbus register map

Northern Design Cube 350 panel power meter (Modbus RTU option) Modbus register map

Updated 17 November 2026

Short answer

The Cube 350 is a three-phase panel multifunction meter. With the Modbus option fitted it is an RS-485 Modbus RTU slave. Readings are integers: energy is a 32-bit copy of the display counter, and instantaneous values are signed 16-bit counts with power-of-ten scale registers. This map covers energy, instantaneous values, demand, THD and the setup registers.

This page lists 86 Modbus registers for the Northern Design Cube 350 panel power meter (Modbus RTU option) — 35 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Northern Design’s own free documentation (linked below) and checked against it.

Manufacturer
Northern Design
Model
Cube 350 panel power meter (Modbus RTU option)
Equipment type
Power meter
Registers
86 (35 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
Cube350, ND Cube 350, Northern Design Cube350
Source document
Cube350 Modbus Communications · rev. 2010-06 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Northern Design Cube 350 panel power meter (Modbus RTU option)

Integration in brief

Read the scale registers 2837-2840 and eScale (513) once after commissioning, then poll 2816-2836 and the energy block 514-529 with function 03 in requests of 20 words or fewer. Apply 10^(K-3) to instantaneous values and 10^(eScale-6) to energy.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2840Power scale KpINT16Power scale KpRead
HR 2816System kWINT16System kW (raw)Read
HR 2821Phase 1 voltsINT16Phase 1 volts (raw)Read
HR 2822Phase 1 ampsINT16Phase 1 amps (raw)Read
HR 2820FrequencyINT16FrequencyRead
HR 2819System PFINT16System power factorRead
HR 513eScaleUINT16Energy exponent eScaleRead
HR 514kWh (import)UINT32 ABCDImport kWh counterRead/write

Enable Modbus control & writes

Modbus is a fitted option. Two extra steps in the front-panel programming menu set the baud rate and the unique Modbus address.

Byte order & addressing

Network setup

Watch out for

Northern Design Cube 350 panel power meter (Modbus RTU option) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

86 of 86 shown
Northern Design Cube 350 panel power meter (Modbus RTU option) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR512doc 40513eScale (high word)Always reads 0.UINT16Read
HR513doc 40514eScaleEnergy decimal exponent; set by the CT/PT programming.UINT16Read
HR514doc 40515kWh (import)Raw display count; kWh = raw x 10^(eScale-6), eScale at 513.UINT32ABCDRead/write
HR516doc 40517kVAhRaw display count; scale with eScale (register 513).UINT32ABCDRead/write
HR518doc 40519kvarh inductiveRaw display count; scale with eScale (register 513).UINT32ABCDRead/write
HR520doc 40521kvarh capacitiveRaw display count; scale with eScale (register 513).UINT32ABCDRead/write
HR522doc 40523Import kvarhRaw display count; scale with eScale (register 513).UINT32ABCDRead/write
HR524doc 40525Export kWhRaw display count; kWh = raw x 10^(eScale-6), eScale at 513.UINT32ABCDRead/write
HR526doc 40527Export kvarhRaw display count; scale with eScale (register 513).UINT32ABCDRead/write
HR528doc 40529Hours runUINT32ABCD× 0.1hRead/write
HR2816doc 42817System kWRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR2817doc 42818System kVARaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR2818doc 42819System kvarRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR2819doc 42820System PFINT16× 0.001Read
HR2820doc 42821FrequencyDocumented as 500 = 50.00 Hz.INT16× 0.1HzRead
HR2821doc 42822Phase 1 voltsRaw signed count; V = raw x 10^(Kvp-3), Kvp at 2838.INT16Read
HR2822doc 42823Phase 1 ampsRaw signed count; A = raw x 10^(Ki-3), Ki at 2837.INT16Read
HR2823doc 42824Phase 1 kWRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR2824doc 42825Phase 2 voltsRaw signed count; V = raw x 10^(Kvp-3), Kvp at 2838.INT16Read
HR2825doc 42826Phase 2 ampsRaw signed count; A = raw x 10^(Ki-3), Ki at 2837.INT16Read
HR2826doc 42827Phase 2 kWRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR2827doc 42828Phase 3 voltsRaw signed count; V = raw x 10^(Kvp-3), Kvp at 2838.INT16Read
HR2828doc 42829Phase 3 ampsRaw signed count; A = raw x 10^(Ki-3), Ki at 2837.INT16Read
HR2829doc 42830Phase 3 kWRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR2830doc 42831Phase 1 PFINT16× 0.001Read
HR2831doc 42832Phase 2 PFINT16× 0.001Read
HR2832doc 42833Phase 3 PFINT16× 0.001Read
HR2833doc 42834Ph1-Ph2 voltsRaw signed count; V = raw x 10^(Kvl-3), Kvl at 2839.INT16Read
HR2834doc 42835Ph2-Ph3 voltsRaw signed count; V = raw x 10^(Kvl-3), Kvl at 2839.INT16Read
HR2835doc 42836Ph3-Ph1 voltsRaw signed count; V = raw x 10^(Kvl-3), Kvl at 2839.INT16Read
HR2836doc 42837Neutral currentRaw signed count; A = raw x 10^(Ki-3), Ki at 2837.INT16Read
HR2837doc 42838Amps scale KiDecimal exponent K used as value x 10^(K-3).INT16Read
HR2838doc 42839Phase volts scale KvpDecimal exponent K used as value x 10^(K-3).INT16Read
HR2839doc 42840Line volts scale KvlDecimal exponent K used as value x 10^(K-3).INT16Read
HR2840doc 42841Power scale KpDecimal exponent K used as value x 10^(K-3).INT16Read
HR3072doc 43073Phase 1 kVARaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR3073doc 43074Phase 2 kVARaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR3074doc 43075Phase 3 kVARaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR3075doc 43076Phase 1 kvarRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR3076doc 43077Phase 2 kvarRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR3077doc 43078Phase 3 kvarRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR3328doc 43329Peak hold Ph1 ampsRaw signed count; A = raw x 10^(Ki-3), Ki at 2837.INT16Read/write
HR3329doc 43330Peak hold Ph2 ampsRaw signed count; A = raw x 10^(Ki-3), Ki at 2837.INT16Read/write
HR3330doc 43331Peak hold Ph3 ampsRaw signed count; A = raw x 10^(Ki-3), Ki at 2837.INT16Read/write
HR3331doc 43332Peak hold Ph1 voltsRaw signed count; V = raw x 10^(Kvp-3), Kvp at 2838.INT16Read/write
HR3332doc 43333Peak hold Ph2 voltsRaw signed count; V = raw x 10^(Kvp-3), Kvp at 2838.INT16Read/write
HR3333doc 43334Peak hold Ph3 voltsRaw signed count; V = raw x 10^(Kvp-3), Kvp at 2838.INT16Read/write
HR3334doc 43335Peak hold kW demandRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read/write
HR3335doc 43336kW demand periodDemand period, 1-60 minutes.INT16minRead/write
HR3336doc 43337kW demandRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR3337doc 43338kVA demandRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR3338doc 43339Peak hold kVA demandRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read/write
HR3339doc 43340kvar demandRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read
HR3340doc 43341Peak hold kvar demandRaw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840.INT16Read/write
HR3584doc 43585CT primary5-25,000 A.UINT16ARead/write
HR3585doc 43586Nominal volts10-55,000 V; PT primary = this x PT scaling factor.UINT16VRead/write
HR3586doc 43587Pulse 1 rateCounts per pulse, 1-1000.UINT16Read/write
HR3587doc 43588Pulse 2 rateSame as pulse 1 rate.UINT16Read/write
HR3588doc 43589Baud rateBaud / 100, e.g. 96 = 9600.UINT16Read/write
HR3589doc 43590Modbus ID0-247.UINT16Read/write
HR3590doc 43591Meter modelReads 350.UINT16Read
HR3591doc 43592Meter type1 = basic Cube350.UINT16Read
HR3592doc 43593Firmware versionHex coded, e.g. 0x14 = 1.04.UINT16Read
HR3593doc 43594Current demand periodIn 10 s steps: 1 = 10 s, 2 = 20 s.UINT16Read/write
HR3594doc 43595Pulse on timeIn 100 ms steps: 1 = 100 ms.UINT16Read/write
HR3595doc 43596Security PIN0-9999; non-zero locks front-panel programming.UINT16Read/write
HR3596doc 43597Hours run limit1-100% of mean phase current; hours count above it.UINT16%Read/write
HR3597doc 43598PT scaling factor1-10.UINT16Read/write
HR3840doc 43841Peak Ph1 amps demandRaw count; A = raw x 10^(Ki-3), Ki at 2837.UINT16Read/write
HR3841doc 43842Peak Ph2 amps demandRaw count; A = raw x 10^(Ki-3), Ki at 2837.UINT16Read/write
HR3842doc 43843Peak Ph3 amps demandRaw count; A = raw x 10^(Ki-3), Ki at 2837.UINT16Read/write
HR3843doc 43844Peak Ph1 volts demandRaw count; V = raw x 10^(Kvp-3), Kvp at 2838.UINT16Read/write
HR3844doc 43845Peak Ph2 volts demandRaw count; V = raw x 10^(Kvp-3), Kvp at 2838.UINT16Read/write
HR3845doc 43846Peak Ph3 volts demandRaw count; V = raw x 10^(Kvp-3), Kvp at 2838.UINT16Read/write
HR4096doc 44097Ph1 amps demandRaw count; A = raw x 10^(Ki-3), Ki at 2837.UINT16Read
HR4097doc 44098Ph2 amps demandRaw count; A = raw x 10^(Ki-3), Ki at 2837.UINT16Read
HR4098doc 44099Ph3 amps demandRaw count; A = raw x 10^(Ki-3), Ki at 2837.UINT16Read
HR4099doc 44100Ph1 volts demandRaw count; V = raw x 10^(Kvp-3), Kvp at 2838.UINT16Read
HR4100doc 44101Ph2 volts demandRaw count; V = raw x 10^(Kvp-3), Kvp at 2838.UINT16Read
HR4101doc 44102Ph3 volts demandRaw count; V = raw x 10^(Kvp-3), Kvp at 2838.UINT16Read
HR4352doc 44353V1 THDDocumented as 1000 = 100%.UINT16× 0.1%Read
HR4353doc 44354V2 THDDocumented as 1000 = 100%.UINT16× 0.1%Read
HR4354doc 44355V3 THDDocumented as 1000 = 100%.UINT16× 0.1%Read
HR4355doc 44356I1 THDDocumented as 1000 = 100%.UINT16× 0.1%Read
HR4356doc 44357I2 THDDocumented as 1000 = 100%.UINT16× 0.1%Read
HR4357doc 44358I3 THDDocumented as 1000 = 100%.UINT16× 0.1%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Northern Design Cube 350 panel power meter (Modbus RTU option)

What Modbus registers does the Northern Design Cube 350 panel power meter (Modbus RTU option) have?

This map lists 86 registers: 86 holding registers. 35 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Northern Design Cube 350 panel power meter (Modbus RTU option) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each table prints a 0-based data address next to its Modicon register number (512 = 40513). This map records the Modicon number; the data address is what goes on the wire, so request 512 to read 40513.

What byte order does the Northern Design Cube 350 panel power meter (Modbus RTU option) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Northern Design Cube 350 panel power meter (Modbus RTU option)?

Start with HR 2840 Power scale Kp (Power scale Kp); HR 2816 System kW (System kW (raw)); HR 2821 Phase 1 volts (Phase 1 volts (raw)); HR 2822 Phase 1 amps (Phase 1 amps (raw)); HR 2820 Frequency (Frequency); HR 2819 System PF (System power factor); HR 513 eScale (Energy exponent eScale); HR 514 kWh (import) (Import kWh counter).

How do I enable Modbus control of the Northern Design Cube 350 panel power meter (Modbus RTU option)?

Modbus is a fitted option. Two extra steps in the front-panel programming menu set the baud rate and the unique Modbus address.

Where is the official Northern Design Cube 350 panel power meter (Modbus RTU option) Modbus documentation?

The source is Cube350 Modbus Communications, revision 2010-06. Northern Design doesn't publish it on its own website, so this map was re-typed from a free copy at https://res.cloudinary.com/fastron-electronics/image/upload/v1533451885/Northern%20Design/Cube_350_Modbus_Comms_Manual_2010.06.pdf. It may be an older revision, so check it against the live unit.

More Northern Design Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Cube350 Modbus Communications · rev. 2010-06 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.