Power meter · Modbus register map
Northern Design Cube 350 panel power meter (Modbus RTU option) Modbus register map
Updated 17 November 2026
The Cube 350 is a three-phase panel multifunction meter. With the Modbus option fitted it is an RS-485 Modbus RTU slave. Readings are integers: energy is a 32-bit copy of the display counter, and instantaneous values are signed 16-bit counts with power-of-ten scale registers. This map covers energy, instantaneous values, demand, THD and the setup registers.
This page lists 86 Modbus registers for the Northern Design Cube 350 panel power meter (Modbus RTU option) — 35 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Northern Design’s own free documentation (linked below) and checked against it.
- Manufacturer
- Northern Design
- Model
- Cube 350 panel power meter (Modbus RTU option)
- Equipment type
- Power meter
- Registers
- 86 (35 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Cube350, ND Cube 350, Northern Design Cube350
Integration notes: Northern Design Cube 350 panel power meter (Modbus RTU option)
Read the scale registers 2837-2840 and eScale (513) once after commissioning, then poll 2816-2836 and the energy block 514-529 with function 03 in requests of 20 words or fewer. Apply 10^(K-3) to instantaneous values and 10^(eScale-6) to energy.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2840 | Power scale Kp | INT16 | Power scale Kp | Read |
| HR 2816 | System kW | INT16 | System kW (raw) | Read |
| HR 2821 | Phase 1 volts | INT16 | Phase 1 volts (raw) | Read |
| HR 2822 | Phase 1 amps | INT16 | Phase 1 amps (raw) | Read |
| HR 2820 | Frequency | INT16 | Frequency | Read |
| HR 2819 | System PF | INT16 | System power factor | Read |
| HR 513 | eScale | UINT16 | Energy exponent eScale | Read |
| HR 514 | kWh (import) | UINT32 ABCD | Import kWh counter | Read/write |
Enable Modbus control & writes
Modbus is a fitted option. Two extra steps in the front-panel programming menu set the baud rate and the unique Modbus address.
Byte order & addressing
- Scale factors are exponents offset by 3 (value x 10^(K-3)), not plain SunSpec-style exponents.
- Maximum 20 words per request; split larger block reads.
- Allow at least 10 ms after each reply before the next request; replies can take up to 250 ms.
Network setup
- RS-485 half duplex, two wires plus 0 V. Baud 4800, 9600 or 19200; address 1-247, both set on the front panel.
- Fit 120 ohm terminators at the host and at the farthest meter; ground the cable shield at the host only.
Watch out for
- Energy, hours-run and peak registers are writable; a careless write resets a billing counter.
- A non-zero Security PIN (3595) locks front-panel programming.
Northern Design Cube 350 panel power meter (Modbus RTU option) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 512doc 40513 | eScale (high word) | Always reads 0. | UINT16 | Read | ||||
| HR | 513doc 40514 | eScale | Energy decimal exponent; set by the CT/PT programming. | UINT16 | Read | ||||
| HR | 514doc 40515 | kWh (import) | Raw display count; kWh = raw x 10^(eScale-6), eScale at 513. | UINT32 | ABCD | Read/write | |||
| HR | 516doc 40517 | kVAh | Raw display count; scale with eScale (register 513). | UINT32 | ABCD | Read/write | |||
| HR | 518doc 40519 | kvarh inductive | Raw display count; scale with eScale (register 513). | UINT32 | ABCD | Read/write | |||
| HR | 520doc 40521 | kvarh capacitive | Raw display count; scale with eScale (register 513). | UINT32 | ABCD | Read/write | |||
| HR | 522doc 40523 | Import kvarh | Raw display count; scale with eScale (register 513). | UINT32 | ABCD | Read/write | |||
| HR | 524doc 40525 | Export kWh | Raw display count; kWh = raw x 10^(eScale-6), eScale at 513. | UINT32 | ABCD | Read/write | |||
| HR | 526doc 40527 | Export kvarh | Raw display count; scale with eScale (register 513). | UINT32 | ABCD | Read/write | |||
| HR | 528doc 40529 | Hours run | UINT32 | ABCD | × 0.1 | h | Read/write | ||
| HR | 2816doc 42817 | System kW | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 2817doc 42818 | System kVA | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 2818doc 42819 | System kvar | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 2819doc 42820 | System PF | INT16 | × 0.001 | Read | ||||
| HR | 2820doc 42821 | Frequency | Documented as 500 = 50.00 Hz. | INT16 | × 0.1 | Hz | Read | ||
| HR | 2821doc 42822 | Phase 1 volts | Raw signed count; V = raw x 10^(Kvp-3), Kvp at 2838. | INT16 | Read | ||||
| HR | 2822doc 42823 | Phase 1 amps | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read | ||||
| HR | 2823doc 42824 | Phase 1 kW | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 2824doc 42825 | Phase 2 volts | Raw signed count; V = raw x 10^(Kvp-3), Kvp at 2838. | INT16 | Read | ||||
| HR | 2825doc 42826 | Phase 2 amps | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read | ||||
| HR | 2826doc 42827 | Phase 2 kW | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 2827doc 42828 | Phase 3 volts | Raw signed count; V = raw x 10^(Kvp-3), Kvp at 2838. | INT16 | Read | ||||
| HR | 2828doc 42829 | Phase 3 amps | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read | ||||
| HR | 2829doc 42830 | Phase 3 kW | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 2830doc 42831 | Phase 1 PF | INT16 | × 0.001 | Read | ||||
| HR | 2831doc 42832 | Phase 2 PF | INT16 | × 0.001 | Read | ||||
| HR | 2832doc 42833 | Phase 3 PF | INT16 | × 0.001 | Read | ||||
| HR | 2833doc 42834 | Ph1-Ph2 volts | Raw signed count; V = raw x 10^(Kvl-3), Kvl at 2839. | INT16 | Read | ||||
| HR | 2834doc 42835 | Ph2-Ph3 volts | Raw signed count; V = raw x 10^(Kvl-3), Kvl at 2839. | INT16 | Read | ||||
| HR | 2835doc 42836 | Ph3-Ph1 volts | Raw signed count; V = raw x 10^(Kvl-3), Kvl at 2839. | INT16 | Read | ||||
| HR | 2836doc 42837 | Neutral current | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read | ||||
| HR | 2837doc 42838 | Amps scale Ki | Decimal exponent K used as value x 10^(K-3). | INT16 | Read | ||||
| HR | 2838doc 42839 | Phase volts scale Kvp | Decimal exponent K used as value x 10^(K-3). | INT16 | Read | ||||
| HR | 2839doc 42840 | Line volts scale Kvl | Decimal exponent K used as value x 10^(K-3). | INT16 | Read | ||||
| HR | 2840doc 42841 | Power scale Kp | Decimal exponent K used as value x 10^(K-3). | INT16 | Read | ||||
| HR | 3072doc 43073 | Phase 1 kVA | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3073doc 43074 | Phase 2 kVA | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3074doc 43075 | Phase 3 kVA | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3075doc 43076 | Phase 1 kvar | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3076doc 43077 | Phase 2 kvar | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3077doc 43078 | Phase 3 kvar | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3328doc 43329 | Peak hold Ph1 amps | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read/write | ||||
| HR | 3329doc 43330 | Peak hold Ph2 amps | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read/write | ||||
| HR | 3330doc 43331 | Peak hold Ph3 amps | Raw signed count; A = raw x 10^(Ki-3), Ki at 2837. | INT16 | Read/write | ||||
| HR | 3331doc 43332 | Peak hold Ph1 volts | Raw signed count; V = raw x 10^(Kvp-3), Kvp at 2838. | INT16 | Read/write | ||||
| HR | 3332doc 43333 | Peak hold Ph2 volts | Raw signed count; V = raw x 10^(Kvp-3), Kvp at 2838. | INT16 | Read/write | ||||
| HR | 3333doc 43334 | Peak hold Ph3 volts | Raw signed count; V = raw x 10^(Kvp-3), Kvp at 2838. | INT16 | Read/write | ||||
| HR | 3334doc 43335 | Peak hold kW demand | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read/write | ||||
| HR | 3335doc 43336 | kW demand period | Demand period, 1-60 minutes. | INT16 | min | Read/write | |||
| HR | 3336doc 43337 | kW demand | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3337doc 43338 | kVA demand | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3338doc 43339 | Peak hold kVA demand | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read/write | ||||
| HR | 3339doc 43340 | kvar demand | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read | ||||
| HR | 3340doc 43341 | Peak hold kvar demand | Raw signed count; W/VA/var = raw x 10^(Kp-3), Kp at 2840. | INT16 | Read/write | ||||
| HR | 3584doc 43585 | CT primary | 5-25,000 A. | UINT16 | A | Read/write | |||
| HR | 3585doc 43586 | Nominal volts | 10-55,000 V; PT primary = this x PT scaling factor. | UINT16 | V | Read/write | |||
| HR | 3586doc 43587 | Pulse 1 rate | Counts per pulse, 1-1000. | UINT16 | Read/write | ||||
| HR | 3587doc 43588 | Pulse 2 rate | Same as pulse 1 rate. | UINT16 | Read/write | ||||
| HR | 3588doc 43589 | Baud rate | Baud / 100, e.g. 96 = 9600. | UINT16 | Read/write | ||||
| HR | 3589doc 43590 | Modbus ID | 0-247. | UINT16 | Read/write | ||||
| HR | 3590doc 43591 | Meter model | Reads 350. | UINT16 | Read | ||||
| HR | 3591doc 43592 | Meter type | 1 = basic Cube350. | UINT16 | Read | ||||
| HR | 3592doc 43593 | Firmware version | Hex coded, e.g. 0x14 = 1.04. | UINT16 | Read | ||||
| HR | 3593doc 43594 | Current demand period | In 10 s steps: 1 = 10 s, 2 = 20 s. | UINT16 | Read/write | ||||
| HR | 3594doc 43595 | Pulse on time | In 100 ms steps: 1 = 100 ms. | UINT16 | Read/write | ||||
| HR | 3595doc 43596 | Security PIN | 0-9999; non-zero locks front-panel programming. | UINT16 | Read/write | ||||
| HR | 3596doc 43597 | Hours run limit | 1-100% of mean phase current; hours count above it. | UINT16 | % | Read/write | |||
| HR | 3597doc 43598 | PT scaling factor | 1-10. | UINT16 | Read/write | ||||
| HR | 3840doc 43841 | Peak Ph1 amps demand | Raw count; A = raw x 10^(Ki-3), Ki at 2837. | UINT16 | Read/write | ||||
| HR | 3841doc 43842 | Peak Ph2 amps demand | Raw count; A = raw x 10^(Ki-3), Ki at 2837. | UINT16 | Read/write | ||||
| HR | 3842doc 43843 | Peak Ph3 amps demand | Raw count; A = raw x 10^(Ki-3), Ki at 2837. | UINT16 | Read/write | ||||
| HR | 3843doc 43844 | Peak Ph1 volts demand | Raw count; V = raw x 10^(Kvp-3), Kvp at 2838. | UINT16 | Read/write | ||||
| HR | 3844doc 43845 | Peak Ph2 volts demand | Raw count; V = raw x 10^(Kvp-3), Kvp at 2838. | UINT16 | Read/write | ||||
| HR | 3845doc 43846 | Peak Ph3 volts demand | Raw count; V = raw x 10^(Kvp-3), Kvp at 2838. | UINT16 | Read/write | ||||
| HR | 4096doc 44097 | Ph1 amps demand | Raw count; A = raw x 10^(Ki-3), Ki at 2837. | UINT16 | Read | ||||
| HR | 4097doc 44098 | Ph2 amps demand | Raw count; A = raw x 10^(Ki-3), Ki at 2837. | UINT16 | Read | ||||
| HR | 4098doc 44099 | Ph3 amps demand | Raw count; A = raw x 10^(Ki-3), Ki at 2837. | UINT16 | Read | ||||
| HR | 4099doc 44100 | Ph1 volts demand | Raw count; V = raw x 10^(Kvp-3), Kvp at 2838. | UINT16 | Read | ||||
| HR | 4100doc 44101 | Ph2 volts demand | Raw count; V = raw x 10^(Kvp-3), Kvp at 2838. | UINT16 | Read | ||||
| HR | 4101doc 44102 | Ph3 volts demand | Raw count; V = raw x 10^(Kvp-3), Kvp at 2838. | UINT16 | Read | ||||
| HR | 4352doc 44353 | V1 THD | Documented as 1000 = 100%. | UINT16 | × 0.1 | % | Read | ||
| HR | 4353doc 44354 | V2 THD | Documented as 1000 = 100%. | UINT16 | × 0.1 | % | Read | ||
| HR | 4354doc 44355 | V3 THD | Documented as 1000 = 100%. | UINT16 | × 0.1 | % | Read | ||
| HR | 4355doc 44356 | I1 THD | Documented as 1000 = 100%. | UINT16 | × 0.1 | % | Read | ||
| HR | 4356doc 44357 | I2 THD | Documented as 1000 = 100%. | UINT16 | × 0.1 | % | Read | ||
| HR | 4357doc 44358 | I3 THD | Documented as 1000 = 100%. | UINT16 | × 0.1 | % | Read |
Notes on this map
- Northern Design does not host this manual publicly; the link is an unaltered copy on a distributor's file host.
- 32-bit values are a high word at the lower address followed by the low word (LONG = 65536 x high + low), so ABCD.
- Energy registers hold the display digits without a decimal point. kWh = raw x 10^(eScale-6) and Wh = raw x 10^(eScale-3), with eScale read from register 513 (40514). The manual's formula names register 40513, which is the eScale high word; the worked example shows it means the energy count.
- Instantaneous values are signed counts with no fixed scale: real value = raw x 10^(K-3), where K is Ki (2837), Kvp (2838), Kvl (2839) or Kp (2840). The K values follow the CT/PT programming and stay fixed once the meter is set up. These registers are listed with scale 1 and no unit, so the map shows raw counts.
- Export kWh reads 0 on meters without export metering.
- Left out: the amalgamated block 7680-7737 (copies of the main values; one row is an unqualified 'Kvarh'), the V/I harmonic tables 7936-9229 and the custom table 19200-19487, which only repeats registers you choose.
- Supported functions: 03, 04, 06, 08 (loop-back only) and 16. A request returns at most 20 words.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Northern Design Cube 350 panel power meter (Modbus RTU option)
What Modbus registers does the Northern Design Cube 350 panel power meter (Modbus RTU option) have?
This map lists 86 registers: 86 holding registers. 35 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Northern Design Cube 350 panel power meter (Modbus RTU option) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each table prints a 0-based data address next to its Modicon register number (512 = 40513). This map records the Modicon number; the data address is what goes on the wire, so request 512 to read 40513.
What byte order does the Northern Design Cube 350 panel power meter (Modbus RTU option) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Northern Design Cube 350 panel power meter (Modbus RTU option)?
Start with HR 2840 Power scale Kp (Power scale Kp); HR 2816 System kW (System kW (raw)); HR 2821 Phase 1 volts (Phase 1 volts (raw)); HR 2822 Phase 1 amps (Phase 1 amps (raw)); HR 2820 Frequency (Frequency); HR 2819 System PF (System power factor); HR 513 eScale (Energy exponent eScale); HR 514 kWh (import) (Import kWh counter).
How do I enable Modbus control of the Northern Design Cube 350 panel power meter (Modbus RTU option)?
Modbus is a fitted option. Two extra steps in the front-panel programming menu set the baud rate and the unique Modbus address.
Where is the official Northern Design Cube 350 panel power meter (Modbus RTU option) Modbus documentation?
The source is Cube350 Modbus Communications, revision 2010-06. Northern Design doesn't publish it on its own website, so this map was re-typed from a free copy at https://res.cloudinary.com/fastron-electronics/image/upload/v1533451885/Northern%20Design/Cube_350_Modbus_Comms_Manual_2010.06.pdf. It may be an older revision, so check it against the live unit.
More Northern Design Modbus register maps
- Power meter
Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP)
V2 Ethernet versions of the Cube 350I, Cube 350V, Cube 400I and Cube 400V (label 'IP.Ver: V2') and the Rail 350V, per manual revision 1.07p (December 2013).
Also known as: Cube 350I IP, Cube 350V IP, Cube 400I IP, Cube 400V IP, Rail 350V IP, Cube IP meter V2 - Energy meter
Northern Design Cube 300 panel kWh meter (Modbus RTU option)
Cube300 meters fitted with the RS-485 Modbus option, per the October 2005 Modbus Communications manual.
Also known as: Cube300, ND Cube 300, Northern Design Cube300 - Power meter (modular multi-circuit energy meter)
Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU)
Each SM352 slave meter in a multicube system with the RTU485 Modbus module, per comms manual Rev Beta 1.02 (March 2011).
Also known as: MultiCube, ND multicube, SM352, RTU485
Other power & energy meters register maps
- Energy meter module
Peacefair PZEM-014 / PZEM-016
Peacefair PZEM-014 (10 A shunt) and PZEM-016 (100 A CT) single-phase AC RS485 modules; the PZEM-004T V3.0 (TTL UART) datasheet prints the identical register map.
Also known as: PZEM-014, PZEM-016, PZEM-004T V3.0, PZEM-004T-10A, PZEM-004T-100A - Power meter
Rishabh Instruments RISH Delta Power NX multifunction power meter
Rishabh RISH Delta Power NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0117 Rev. E.
Also known as: RISH Delta Power NX, Delta Power NX, RISH Delta Power - Energy meter
Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter
Rishabh RISH EM 3490 DS dual-source energy meters (separate utility and generator energy) with RS-485 Modbus, per manual Rev G.
Also known as: RISH EM 3490 DS, EM3490DS, EM 3490DS - Power meter
Rishabh Instruments RISH LM 1380 multifunction meter
Rishabh RISH LM 1380 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0925 Rev. A (04/2022).
Also known as: RISH LM 1380, LM1380 - Power meter (multi-circuit branch feeder monitor)
SATEC BFM-II branch feeder monitor
SATEC BFM-II multi-circuit meter per Modbus reference guide BG0589 Rev. A12 (May 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM II, BFM2, SATEC BFM-II - Energy meter (pulse and status concentrator)
Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator
Acti 9 Smartlink Modbus RS-485 module A9XMSB11, per user manual DOCA0004EN-06 (04/2016).
Also known as: Acti 9 Smartlink, Smartlink Modbus, A9XMSB11, Acti9 Smartlink
All power & energy meters Modbus register maps →
Source: Cube350 Modbus Communications · rev. 2010-06 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.