Northern Design Cube 300 panel kWh meter (Modbus RTU option) Modbus register map

Updated 19 November 2026

Short answer

The Cube300 is a panel kWh meter; the Modbus option adds an RS-485 Modbus RTU port. It exposes a small set of holding registers: a 32-bit kWh count (plus a second-tariff count), instantaneous kW as a signed count, decimal-exponent scale registers and the meter setup values.

This page lists 15 Modbus registers for the Northern Design Cube 300 panel kWh meter (Modbus RTU option) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Northern Design’s own free documentation (linked below) and checked against it.

Manufacturer
Northern Design
Model
Cube 300 panel kWh meter (Modbus RTU option)
Equipment type
Energy meter
Registers
15 (8 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
Cube300, ND Cube 300, Northern Design Cube300
Source document
Cube300 Modbus Communications · rev. 2005-10 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Northern Design Cube 300 panel kWh meter (Modbus RTU option)

Integration in brief

Read eScale (513) and pScale (2817) once after commissioning, then poll kWh at 514-515 and instantaneous kW at 2816 with function 03. Apply 10^(eScale-6) to the energy count and 10^(pScale-6) to the power count to get kWh and kW.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 513eScaleUINT16Energy exponent eScaleRead
HR 514kWhUINT32 ABCDkWh counterRead/write
HR 2816Instantaneous kWINT16Instantaneous kW (raw)Read
HR 2817pScaleUINT16Power exponent pScaleRead
HR 3584CT PrimaryUINT16CT primaryRead/write
HR 3590Meter ModelUINT16Meter model check (300)Read

Enable Modbus control & writes

Modbus is a fitted option. Two extra steps in the front-panel programming menu set the baud rate and the unique Modbus address.

Byte order & addressing

Network setup

Watch out for

Northern Design Cube 300 panel kWh meter (Modbus RTU option) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

15 of 15 shown
Northern Design Cube 300 panel kWh meter (Modbus RTU option) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR512doc 40513eScale (high word)Always reads 0.UINT16Read
HR513doc 40514eScaleEnergy decimal exponent; fixed by the CT primary and nominal volts settings.UINT16Read
HR514doc 40515kWhRaw display count; kWh = raw x 10^(eScale-6).UINT32ABCDRead/write
HR516doc 40517T2 kWhSecond-tariff count; reads 0 without the dual tariff option.UINT32ABCDRead/write
HR2816doc 42817Instantaneous kWSigned raw display count; negative = export. kW = raw x 10^(pScale-6).INT16Read
HR2817doc 42818pScalePower decimal exponent for register 2816.UINT16Read
HR3584doc 43585CT Primary10 to 25,000.UINT16ARead/write
HR3585doc 43586Nominal Volts10 to 55,000.UINT16VRead/write
HR3586doc 43587Pulse RateEnergy register increments per output pulse, 1-1000.UINT16Read/write
HR3587doc 43588Pulse ON Time x101-100, meaning 0.1 to 10 s.UINT16× 0.1sRead/write
HR3588doc 43589Baud4800, 9600 or 19200.UINT16Read/write
HR3589doc 43590Modbus ID1-247.UINT16Read/write
HR3590doc 43591Meter ModelReads 300 on a Cube300.UINT16Read
HR3591doc 43592Meter TypeVariant code; basic Cube300 = 1.UINT16Read
HR3592doc 43593Meter VersionFirmware issue, e.g. 101 = version 1.01.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Northern Design Cube 300 panel kWh meter (Modbus RTU option)

What Modbus registers does the Northern Design Cube 300 panel kWh meter (Modbus RTU option) have?

This map lists 15 registers: 15 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Northern Design Cube 300 panel kWh meter (Modbus RTU option) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each table prints a 0-based data address next to the Modicon register number (512 = 40513). The data address is what goes on the wire: request 512 to read 40513.

What byte order does the Northern Design Cube 300 panel kWh meter (Modbus RTU option) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Northern Design Cube 300 panel kWh meter (Modbus RTU option)?

Start with HR 513 eScale (Energy exponent eScale); HR 514 kWh (kWh counter); HR 2816 Instantaneous kW (Instantaneous kW (raw)); HR 2817 pScale (Power exponent pScale); HR 3584 CT Primary (CT primary); HR 3590 Meter Model (Meter model check (300)).

How do I enable Modbus control of the Northern Design Cube 300 panel kWh meter (Modbus RTU option)?

Modbus is a fitted option. Two extra steps in the front-panel programming menu set the baud rate and the unique Modbus address.

Where is the official Northern Design Cube 300 panel kWh meter (Modbus RTU option) Modbus documentation?

The source is Cube300 Modbus Communications, revision 2005-10. Northern Design doesn't publish it on its own website, so this map was re-typed from a free copy at https://res.cloudinary.com/fastron-electronics/image/upload/v1533451092/Northern%20Design/Cube_300_Modbus_Comms_Manual_2005.10.pdf. It may be an older revision, so check it against the live unit.

More Northern Design Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Cube300 Modbus Communications · rev. 2005-10 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.