Energy meter · Modbus register map
Northern Design Cube 300 panel kWh meter (Modbus RTU option) Modbus register map
Updated 19 November 2026
The Cube300 is a panel kWh meter; the Modbus option adds an RS-485 Modbus RTU port. It exposes a small set of holding registers: a 32-bit kWh count (plus a second-tariff count), instantaneous kW as a signed count, decimal-exponent scale registers and the meter setup values.
This page lists 15 Modbus registers for the Northern Design Cube 300 panel kWh meter (Modbus RTU option) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Northern Design’s own free documentation (linked below) and checked against it.
- Manufacturer
- Northern Design
- Model
- Cube 300 panel kWh meter (Modbus RTU option)
- Equipment type
- Energy meter
- Registers
- 15 (8 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Cube300, ND Cube 300, Northern Design Cube300
Integration notes: Northern Design Cube 300 panel kWh meter (Modbus RTU option)
Read eScale (513) and pScale (2817) once after commissioning, then poll kWh at 514-515 and instantaneous kW at 2816 with function 03. Apply 10^(eScale-6) to the energy count and 10^(pScale-6) to the power count to get kWh and kW.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 513 | eScale | UINT16 | Energy exponent eScale | Read |
| HR 514 | kWh | UINT32 ABCD | kWh counter | Read/write |
| HR 2816 | Instantaneous kW | INT16 | Instantaneous kW (raw) | Read |
| HR 2817 | pScale | UINT16 | Power exponent pScale | Read |
| HR 3584 | CT Primary | UINT16 | CT primary | Read/write |
| HR 3590 | Meter Model | UINT16 | Meter model check (300) | Read |
Enable Modbus control & writes
Modbus is a fitted option. Two extra steps in the front-panel programming menu set the baud rate and the unique Modbus address.
Byte order & addressing
- Scale registers are exponents offset by 3 or 6 (raw x 10^(eScale-6) for kWh), not plain power-of-ten multipliers.
- Maximum 20 words per request.
- Allow at least 10 ms after each reply before the next request; replies can take up to 250 ms.
Network setup
- RS-485 half duplex, two wires plus 0 V. Baud 4800, 9600 or 19200; address 1-247, both set on the front panel or over Modbus.
- Fit 120 ohm terminators at the host and at the farthest meter; loop in and out of the meter terminals rather than using spurs.
- Ground the cable shield at the host only and do not use it as the 0 V conductor.
Watch out for
- The kWh registers are writable; a careless write changes the billing count.
- The copied data table (7680 onward) is read-only; functions 06 and 16 are refused there.
Northern Design Cube 300 panel kWh meter (Modbus RTU option) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 512doc 40513 | eScale (high word) | Always reads 0. | UINT16 | Read | ||||
| HR | 513doc 40514 | eScale | Energy decimal exponent; fixed by the CT primary and nominal volts settings. | UINT16 | Read | ||||
| HR | 514doc 40515 | kWh | Raw display count; kWh = raw x 10^(eScale-6). | UINT32 | ABCD | Read/write | |||
| HR | 516doc 40517 | T2 kWh | Second-tariff count; reads 0 without the dual tariff option. | UINT32 | ABCD | Read/write | |||
| HR | 2816doc 42817 | Instantaneous kW | Signed raw display count; negative = export. kW = raw x 10^(pScale-6). | INT16 | Read | ||||
| HR | 2817doc 42818 | pScale | Power decimal exponent for register 2816. | UINT16 | Read | ||||
| HR | 3584doc 43585 | CT Primary | 10 to 25,000. | UINT16 | A | Read/write | |||
| HR | 3585doc 43586 | Nominal Volts | 10 to 55,000. | UINT16 | V | Read/write | |||
| HR | 3586doc 43587 | Pulse Rate | Energy register increments per output pulse, 1-1000. | UINT16 | Read/write | ||||
| HR | 3587doc 43588 | Pulse ON Time x10 | 1-100, meaning 0.1 to 10 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 3588doc 43589 | Baud | 4800, 9600 or 19200. | UINT16 | Read/write | ||||
| HR | 3589doc 43590 | Modbus ID | 1-247. | UINT16 | Read/write | ||||
| HR | 3590doc 43591 | Meter Model | Reads 300 on a Cube300. | UINT16 | Read | ||||
| HR | 3591doc 43592 | Meter Type | Variant code; basic Cube300 = 1. | UINT16 | Read | ||||
| HR | 3592doc 43593 | Meter Version | Firmware issue, e.g. 101 = version 1.01. | UINT16 | Read |
Notes on this map
- Northern Design does not host this manual publicly; the link is a copy on a distributor's file host (the same host used for the Cube 350 and multicube manuals).
- 32-bit values are a high word at the lower address followed by the low word (LONG = 65536 x high + low), so ABCD.
- Energy registers hold the displayed digits without a decimal point. kWh = raw x 10^(eScale-6) and Wh = raw x 10^(eScale-3), with eScale read from 513 (40514). The manual's formula and worked example both name 40513 (the eScale high word) as the energy value, but the paragraph before them puts the energy count at 40515-40516, so the formula is applied to 514-515.
- Instantaneous kW is a signed count of the displayed digits: kW = raw x 10^(pScale-6), W = raw x 10^(pScale-3), with pScale at 2817. Both are listed with scale 1 and no unit.
- Left out: the read-only copied data table 7680-7699, which repeats the registers above in one block so they can be read with a single function 03 request.
- Supported functions: 03, 04, 06, 08 (sub-function 00 loop-back only) and 16. A request returns at most 20 words.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Northern Design Cube 300 panel kWh meter (Modbus RTU option)
What Modbus registers does the Northern Design Cube 300 panel kWh meter (Modbus RTU option) have?
This map lists 15 registers: 15 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Northern Design Cube 300 panel kWh meter (Modbus RTU option) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each table prints a 0-based data address next to the Modicon register number (512 = 40513). The data address is what goes on the wire: request 512 to read 40513.
What byte order does the Northern Design Cube 300 panel kWh meter (Modbus RTU option) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Northern Design Cube 300 panel kWh meter (Modbus RTU option)?
Start with HR 513 eScale (Energy exponent eScale); HR 514 kWh (kWh counter); HR 2816 Instantaneous kW (Instantaneous kW (raw)); HR 2817 pScale (Power exponent pScale); HR 3584 CT Primary (CT primary); HR 3590 Meter Model (Meter model check (300)).
How do I enable Modbus control of the Northern Design Cube 300 panel kWh meter (Modbus RTU option)?
Modbus is a fitted option. Two extra steps in the front-panel programming menu set the baud rate and the unique Modbus address.
Where is the official Northern Design Cube 300 panel kWh meter (Modbus RTU option) Modbus documentation?
The source is Cube300 Modbus Communications, revision 2005-10. Northern Design doesn't publish it on its own website, so this map was re-typed from a free copy at https://res.cloudinary.com/fastron-electronics/image/upload/v1533451092/Northern%20Design/Cube_300_Modbus_Comms_Manual_2005.10.pdf. It may be an older revision, so check it against the live unit.
More Northern Design Modbus register maps
- Power meter
Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP)
V2 Ethernet versions of the Cube 350I, Cube 350V, Cube 400I and Cube 400V (label 'IP.Ver: V2') and the Rail 350V, per manual revision 1.07p (December 2013).
Also known as: Cube 350I IP, Cube 350V IP, Cube 400I IP, Cube 400V IP, Rail 350V IP, Cube IP meter V2 - Power meter
Northern Design Cube 350 panel power meter (Modbus RTU option)
Cube 350 three-phase panel meters fitted with the RS-485 Modbus option, per the June 2010 comms manual.
Also known as: Cube350, ND Cube 350, Northern Design Cube350 - Power meter (modular multi-circuit energy meter)
Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU)
Each SM352 slave meter in a multicube system with the RTU485 Modbus module, per comms manual Rev Beta 1.02 (March 2011).
Also known as: MultiCube, ND multicube, SM352, RTU485
Other power & energy meters register maps
- Energy meter (multi-circuit power monitor)
Panasonic KW9M Eco-POWER METER
Panasonic KW9M (AKW91110) with the Modbus RTU protocol selected, user manual WUME-KW9M-10.
Also known as: AKW91110 - Energy meter
Rishabh Instruments RISH Delta Energy NX multifunction energy meter
Rishabh RISH Delta Energy NX panel energy meters with RS-485 Modbus RTU, per the operating manual on the product page (standard CT version).
Also known as: RISH Delta Energy NX, Delta Energy NX, RISH Delta Energy - Energy meter
Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters
Rishabh RISH EM 1320/1330/1340 and EM 2320/2330/2340 panel energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0721 Rev. B (06/2020). Rows marked 'only 2340' apply to the dual-source EM 2340.
Also known as: RISH EM 1320, RISH EM 1330, RISH EM 1340, RISH EM 2320, RISH EM 2330, RISH EM 2340, EM2340DS - Power meter
Rishabh Instruments RISH LM 1360 load manager (LM 13xx)
Rishabh RISH LM 1360 panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0662 Rev. D (01/2024).
Also known as: RISH LM 1360, LM1360, LM 13xx, LM1360 RJ12 - Energy meter
Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU)
ALE3 unidirectional (ALE3D5FD10C3A00) and bidirectional (ALE3B5FD00C3A00) Modbus types, assembly and operating instructions 431951130.
Also known as: ALE3D5FD10C3A00, ALE3B5FD00C3A00, ALE3D5FD10, ALE3B5FD00, SBC ALE3 Modbus - Power meter (power quality analyzer)
SATEC PM180 expertmeter high performance analyzer
SATEC PM180 expertmeter, per Modbus reference guide BG0527 Rev. A11 (Sep 2024).
Also known as: PM180, expertmeter PM180, SATEC PM180