- ALE3 three-phase 65 A energy meter (Modbus RTU)
Energy meter · Modbus register map
Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) Modbus register map
Updated 17 November 2026
The ALE3 is a Saia Burgess Controls DIN-rail three-phase active energy meter for direct connection up to 65 A, with an RS-485 Modbus RTU interface. Baud rate and parity are detected automatically. This map covers identification, status and error registers, the two total and two resettable partial energy counters, and per-phase voltage and current.
This page lists 18 Modbus registers for the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Saia Burgess Controls’s own free documentation (linked below) and checked against it.
- Manufacturer
- Saia Burgess Controls
- Model
- ALE3 three-phase 65 A energy meter (Modbus RTU)
- Equipment type
- Energy meter
- Registers
- 18 (2 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- ALE3D5FD10C3A00, ALE3B5FD00C3A00, ALE3D5FD10, ALE3B5FD00, SBC ALE3 Modbus
Integration notes: Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU)
Read holding registers 28-33 (wire 27-32) for the energy counters as 32-bit high-word-first values in 0.01 kWh, and 36-47 for voltages and currents; keep each request at 20 registers or fewer.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 27 | Counter total energy WT1 | UINT32 ABCD | Total energy WT1, 0.01 kWh | Read |
| HR 31 | Counter total energy WT2 | UINT32 ABCD | Total energy WT2, 0.01 kWh | Read |
| HR 35 | Voltage phase 1 (URMS) | UINT16 | Voltage L1 | Read |
| HR 36 | Current phase 1 (IRMS) | UINT16 | Current L1, 0.1 A | Read |
| HR 24 | Error register | UINT16 | Error register | Read |
Enable Modbus control & writes
Set the Modbus address on the meter (press the touch key for 3 s, then step the address) or write register 24; baud rate and parity are detected automatically.
Byte order & addressing
- Register R is wire address R - 1.
- Max 20 registers per read; only FC03 and FC16.
- Address register cannot be written by broadcast.
Network setup
- The interface has no built-in terminating resistor; fit one externally.
- Up to 247 meters per bus; use a repeater beyond 128.
Watch out for
- Reset partial counter WT1 by writing 0 to both of its registers (30-31) in one FC16 message.
- Data refreshes every 10 s; the sheet advises not polling one meter faster than that.
- The interface works only with phase 1 connected and answers 30 s after power-up.
Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Firmware version | e.g. 11 = FW 1.1. | UINT16 | Read | ||||
| HR | 1doc 2 | Number of supported registers | Reads 52. | UINT16 | Read | ||||
| HR | 3doc 4-5 | Baud rate | Detected baud rate, e.g. 115200. | UINT32 | ABCD | bps | Read | ||
| HR | 14doc 15 | Hardware version | e.g. 11 = HW 1.1. | UINT16 | Read | ||||
| HR | 21doc 22 | Status / protect | UINT16 | Read | 0 = No problem; 1 = Problem with last communication request | ||||
| HR | 22doc 23 | Response timeout | UINT16 | ms | Read | ||||
| HR | 23doc 24 | Modbus address | 1-247; cannot be written by broadcast. | UINT16 | Read/write | ||||
| HR | 24doc 25 | Error register | UINT16 | Read | 0 = No error; 1 = Error phase 1; 2 = Error phase 2; 3 = Error phase 1 + 2; 4 = Error phase 3; 5 = Error phase 1 + 3; 6 = Error phase 2 + 3; 7 = Error phase 1, 2 + 3 | ||||
| HR | 26doc 27 | Tariff register | UINT16 | Read | 0 = Tariff 1 (bidirectional: forward); 4 = Tariff 2 (bidirectional: reverse) | ||||
| HR | 27doc 28-29 | Counter total energy WT1 | Tariff 1 total; see notes for the bidirectional type. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| HR | 29doc 30-31 | Counter partial energy WT1 | Resettable: write 0 to both registers in one FC16 message. | UINT32 | ABCD | × 0.01 | kWh | Read/write | |
| HR | 31doc 32-33 | Counter total energy WT2 | Tariff 2 total; see notes for the bidirectional type. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| HR | 35doc 36 | Voltage phase 1 (URMS) | UINT16 | V | Read | ||||
| HR | 36doc 37 | Current phase 1 (IRMS) | UINT16 | × 0.1 | A | Read | |||
| HR | 40doc 41 | Voltage phase 2 (URMS) | UINT16 | V | Read | ||||
| HR | 41doc 42 | Current phase 2 (IRMS) | UINT16 | × 0.1 | A | Read | |||
| HR | 45doc 46 | Voltage phase 3 (URMS) | UINT16 | V | Read | ||||
| HR | 46doc 47 | Current phase 3 (IRMS) | UINT16 | × 0.1 | A | Read |
Notes on this map
- This is an unaltered copy of the SBC instruction sheet posted on the Viessmann community forum; an official public SBC URL for this revision was not found in the time available.
- The sheet lists the double registers sent high register first (big-endian, ABCD) as 4-5, 16-17, 28-29, 30-31 and 32-33. Example from the sheet: high 13, low 60383 = 912351 = 9123.51 kWh.
- Energy counters are 0.01 kWh per count. Voltage is 1 V per count, current 0.1 A per count.
- On the unidirectional type registers 28-35 are tariff 1 and tariff 2 counters. On the bidirectional type the sheet's display section describes the second counter set as feed-back (delivered) energy; the tariff register's arrows mark direction.
- Left out: active and reactive power and cos phi per phase and total (registers 38-40, 43-45, 48-52), because the sheet does not say whether these 16-bit values are signed, which matters on the bidirectional type; the serial number (16-18), whose word layout is printed inconsistently; type/ASN text registers 7-14.
- Left out: partial energy WT2 (registers 34-35). The sheet names it a resettable partial counter but leaves it off its list of high-register-first pairs, so its word order is not stated.
- Only functions 03 and 16 are accepted, and at most 20 registers per request.
- Serial format: baud rate (4800-115200) and parity are auto-detected; even or odd parity use 1 stop bit, no parity uses 2 stop bits.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU)
What Modbus registers does the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) have?
This map lists 18 registers: 18 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register list numbers registers from 1, and the manual states that register R is sent as R - 1: register 28 (energy total) is wire address 27.
What byte order does the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU)?
Start with HR 27 Counter total energy WT1 (Total energy WT1, 0.01 kWh); HR 31 Counter total energy WT2 (Total energy WT2, 0.01 kWh); HR 35 Voltage phase 1 (URMS) (Voltage L1); HR 36 Current phase 1 (IRMS) (Current L1, 0.1 A); HR 24 Error register (Error register).
How do I enable Modbus control of the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU)?
Set the Modbus address on the meter (press the touch key for 3 s, then step the address) or write register 24; baud rate and parity are detected automatically.
Where is the official Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) Modbus documentation?
The source is ALE3 Modbus - Assembly and operating instructions (unidirectional ALE3D5FD10, bidirectional ALE3B5FD00) (4 319 5113 0 H (file MI-UG ALE3 Modbus UniBiDi 02)), revision 2022-02-25. Saia Burgess Controls doesn't publish it on its own website, so this map was re-typed from a free copy at https://community.viessmann.de/viessmann/attachments/viessmann/customers-heatpump-hybrid/52600/1/431951130s_MI-UG_ALE3_Modbus-UniBiDi_02.pdf. It may be an older revision, so check it against the live unit.
Other power & energy meters register maps
- Power meter (power quality analyzer)
SATEC PM180 expertmeter high performance analyzer
SATEC PM180 expertmeter, per Modbus reference guide BG0527 Rev. A11 (Sep 2024).
Also known as: PM180, expertmeter PM180, SATEC PM180 - Power meter (multi-circuit)
Setra Systems Setra Power Meter (SPM) multi-circuit power meter
Setra Power Meter (SPM) family, per Modbus register master list SS-SPM-MODBUS_G; this map covers the device block, both voltage inputs and Load 1.
Also known as: SPM, Setra Power Meter, SS-SPM-MODBUS_G - Energy meter (heat / cooling meter)
Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module
Sontex Modbus EIA-485 plug-in module in a Supercal 531 integrator or Superstatic 440/449 heat meter, integrator firmware 3.7 or later; user manual V05 (2019-09).
Also known as: Supercal 531, Superstatic 440, Superstatic 449, Sontex Modbus EIA-485 module, 0531P217 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Power meter
Accuenergy AcuRev 1310 series DIN-rail power meter
Accuenergy AcuRev 1310 series (1312/1313/1314) DIN-rail meters, Modbus map workbook revision 1.1.
Also known as: AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310 - Power meter (universal measuring / power quality device)
Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP)
SINEAX CAM with Ethernet (Modbus/TCP) bus card; document W 157471, change 2014-018. Instantaneous values, THD/TDD, system analysis, analog inputs, I/O states.
Also known as: SINEAX CAM, CAM
All power & energy meters Modbus register maps →