Energy meter · Modbus register map

Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The ALE3 is a Saia Burgess Controls DIN-rail three-phase active energy meter for direct connection up to 65 A, with an RS-485 Modbus RTU interface. Baud rate and parity are detected automatically. This map covers identification, status and error registers, the two total and two resettable partial energy counters, and per-phase voltage and current.

This page lists 18 Modbus registers for the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Saia Burgess Controls’s own free documentation (linked below) and checked against it.

Manufacturer
Saia Burgess Controls
Model
ALE3 three-phase 65 A energy meter (Modbus RTU)
Equipment type
Energy meter
Registers
18 (2 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
ALE3D5FD10C3A00, ALE3B5FD00C3A00, ALE3D5FD10, ALE3B5FD00, SBC ALE3 Modbus
Source document
ALE3 Modbus - Assembly and operating instructions (unidirectional ALE3D5FD10, bidirectional ALE3B5FD00) · 4 319 5113 0 H (file MI-UG ALE3 Modbus UniBiDi 02) · rev. 2022-02-25 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU)

Integration in brief

Read holding registers 28-33 (wire 27-32) for the energy counters as 32-bit high-word-first values in 0.01 kWh, and 36-47 for voltages and currents; keep each request at 20 registers or fewer.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 27Counter total energy WT1UINT32 ABCDTotal energy WT1, 0.01 kWhRead
HR 31Counter total energy WT2UINT32 ABCDTotal energy WT2, 0.01 kWhRead
HR 35Voltage phase 1 (URMS)UINT16Voltage L1Read
HR 36Current phase 1 (IRMS)UINT16Current L1, 0.1 ARead
HR 24Error registerUINT16Error registerRead

Enable Modbus control & writes

Set the Modbus address on the meter (press the touch key for 3 s, then step the address) or write register 24; baud rate and parity are detected automatically.

Byte order & addressing

Network setup

Watch out for

Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

18 of 18 shown
Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Firmware versione.g. 11 = FW 1.1.UINT16Read
HR1doc 2Number of supported registersReads 52.UINT16Read
HR3doc 4-5Baud rateDetected baud rate, e.g. 115200.UINT32ABCDbpsRead
HR14doc 15Hardware versione.g. 11 = HW 1.1.UINT16Read
HR21doc 22Status / protectUINT16Read0 = No problem; 1 = Problem with last communication request
HR22doc 23Response timeoutUINT16msRead
HR23doc 24Modbus address1-247; cannot be written by broadcast.UINT16Read/write
HR24doc 25Error registerUINT16Read0 = No error; 1 = Error phase 1; 2 = Error phase 2; 3 = Error phase 1 + 2; 4 = Error phase 3; 5 = Error phase 1 + 3; 6 = Error phase 2 + 3; 7 = Error phase 1, 2 + 3
HR26doc 27Tariff registerUINT16Read0 = Tariff 1 (bidirectional: forward); 4 = Tariff 2 (bidirectional: reverse)
HR27doc 28-29Counter total energy WT1Tariff 1 total; see notes for the bidirectional type.UINT32ABCD× 0.01kWhRead
HR29doc 30-31Counter partial energy WT1Resettable: write 0 to both registers in one FC16 message.UINT32ABCD× 0.01kWhRead/write
HR31doc 32-33Counter total energy WT2Tariff 2 total; see notes for the bidirectional type.UINT32ABCD× 0.01kWhRead
HR35doc 36Voltage phase 1 (URMS)UINT16VRead
HR36doc 37Current phase 1 (IRMS)UINT16× 0.1ARead
HR40doc 41Voltage phase 2 (URMS)UINT16VRead
HR41doc 42Current phase 2 (IRMS)UINT16× 0.1ARead
HR45doc 46Voltage phase 3 (URMS)UINT16VRead
HR46doc 47Current phase 3 (IRMS)UINT16× 0.1ARead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU)

What Modbus registers does the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) have?

This map lists 18 registers: 18 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register list numbers registers from 1, and the manual states that register R is sent as R - 1: register 28 (energy total) is wire address 27.

What byte order does the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU)?

Start with HR 27 Counter total energy WT1 (Total energy WT1, 0.01 kWh); HR 31 Counter total energy WT2 (Total energy WT2, 0.01 kWh); HR 35 Voltage phase 1 (URMS) (Voltage L1); HR 36 Current phase 1 (IRMS) (Current L1, 0.1 A); HR 24 Error register (Error register).

How do I enable Modbus control of the Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU)?

Set the Modbus address on the meter (press the touch key for 3 s, then step the address) or write register 24; baud rate and parity are detected automatically.

Where is the official Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU) Modbus documentation?

The source is ALE3 Modbus - Assembly and operating instructions (unidirectional ALE3D5FD10, bidirectional ALE3B5FD00) (4 319 5113 0 H (file MI-UG ALE3 Modbus UniBiDi 02)), revision 2022-02-25. Saia Burgess Controls doesn't publish it on its own website, so this map was re-typed from a free copy at https://community.viessmann.de/viessmann/attachments/viessmann/customers-heatpump-hybrid/52600/1/431951130s_MI-UG_ALE3_Modbus-UniBiDi_02.pdf. It may be an older revision, so check it against the live unit.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: ALE3 Modbus - Assembly and operating instructions (unidirectional ALE3D5FD10, bidirectional ALE3B5FD00) · 4 319 5113 0 H (file MI-UG ALE3 Modbus UniBiDi 02) · rev. 2022-02-25 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.