Power meter (universal measuring / power quality device) · Modbus register map

Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP) Modbus register map

Updated 17 November 2026

Short answer

The SINEAX CAM is a Swiss universal measurement device for heavy-current networks with plug-in I/O modules. With the Modbus/TCP bus card it publishes its measurements as holding registers (mostly IEEE 754 floats), relay and digital output states as coils and digital inputs as discrete inputs. This map covers firmware info, the full instantaneous value block, THD/TDD, symmetrical components, analog inputs and the I/O states.

This page lists 108 Modbus registers for the Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Camille Bauer Metrawatt’s own free documentation (linked below) and checked against it.

Manufacturer
Camille Bauer Metrawatt
Model
SINEAX CAM universal measurement device (Modbus/TCP)
Equipment type
Power meter (universal measuring / power quality device)
Registers
108 (16 writable)
Transport
Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Firmware
Analysis firmware 1.32+ (timestamp), 1.37+ (system analysis block), 1.39+ (tariff register 41485)
Also known as
SINEAX CAM, CAM
Source document
Modbus/TCP interface SINEAX CAM · W 157471 (modification 2014-018, 18.06.14) · rev. 2014-06-18 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP)

Integration in brief

Connect to TCP port 502 and read 40100-40187 in one FC3 request: 44 floats with voltage, current, power, frequency and power factor, low word first. THD/TDD sit in 40190-40196 as tenths of a percent.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 101U1NFLOAT32 CDABVoltage L1-NRead
HR 117I1FLOAT32 CDABCurrent L1Read
HR 133PFLOAT32 CDABActive power systemRead
HR 157FFLOAT32 CDABFrequencyRead
HR 159PFFLOAT32 CDABPower factor systemRead
HR 190THD_U1XUINT16Voltage THD phase 1Read

Enable Modbus control & writes

Assign IP address, mask and gateway with the CB-Manager software (factory IP 192.168.1.101). The Modbus/TCP port can be changed there, but 502 is always supported.

Byte order & addressing

Network setup

Watch out for

Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

108 of 108 shown
Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 1RELAY1 stateBITRead/write
CO1doc 2RELAY2 stateBITRead/write
CO2doc 3DIGOUT1.1 stateDigital output on I/O module 1.BITRead/write
CO3doc 4DIGOUT1.2 stateDigital output on I/O module 1.BITRead/write
CO4doc 5DIGOUT1.3 stateDigital output on I/O module 1.BITRead/write
CO5doc 6DIGOUT2.1 stateDigital output on I/O module 2.BITRead/write
CO6doc 7DIGOUT2.2 stateDigital output on I/O module 2.BITRead/write
CO7doc 8DIGOUT2.3 stateDigital output on I/O module 2.BITRead/write
CO8doc 9DIGOUT3.1 stateDigital output on I/O module 3.BITRead/write
CO9doc 10DIGOUT3.2 stateDigital output on I/O module 3.BITRead/write
CO10doc 11DIGOUT3.3 stateDigital output on I/O module 3.BITRead/write
CO11doc 12DIGOUT4.1 stateDigital output on I/O module 4.BITRead/write
CO12doc 13DIGOUT4.2 stateDigital output on I/O module 4.BITRead/write
CO13doc 14DIGOUT4.3 stateDigital output on I/O module 4.BITRead/write
CO499doc 500Reset maximum value UCoils 500-541 reset each min/max value with its timestamp.BITWrite
CO1024doc 1025CNT_TARIF - tariff switchBITRead/write0 = High tariff; 1 = Low tariff
DI2doc 10003DIGIN1.1 stateDigital input on I/O module 1.BITRead
DI3doc 10004DIGIN1.2 stateDigital input on I/O module 1.BITRead
DI4doc 10005DIGIN1.3 stateDigital input on I/O module 1.BITRead
DI5doc 10006DIGIN2.1 stateDigital input on I/O module 2.BITRead
DI6doc 10007DIGIN2.2 stateDigital input on I/O module 2.BITRead
DI7doc 10008DIGIN2.3 stateDigital input on I/O module 2.BITRead
DI8doc 10009DIGIN3.1 stateDigital input on I/O module 3.BITRead
DI9doc 10010DIGIN3.2 stateDigital input on I/O module 3.BITRead
DI10doc 10011DIGIN3.3 stateDigital input on I/O module 3.BITRead
DI11doc 10012DIGIN4.1 stateDigital input on I/O module 4.BITRead
DI12doc 10013DIGIN4.2 stateDigital input on I/O module 4.BITRead
DI13doc 10014DIGIN4.3 stateDigital input on I/O module 4.BITRead
HR5doc 40006FV_INPUT - firmware measurement partHex coded, e.g. 0x0106 = 1.06.UINT16Read
HR6doc 40007FV_OUTPUT - firmware analysis unitHex coded, e.g. 0x0137 = 1.37. Several blocks need a minimum version.UINT16Read
HR7doc 40008FV_COM - firmware communication unitHex coded.UINT16Read
HR14doc 40015HW_FREQ - calibration frequency5000 = 50.00 Hz.UINT16× 0.01HzRead
HR99doc 40100USystem voltageFLOAT32CDABVRead
HR101doc 40102U1NVoltage L1-NFLOAT32CDABVRead
HR103doc 40104U2NVoltage L2-NFLOAT32CDABVRead
HR105doc 40106U3NVoltage L3-NFLOAT32CDABVRead
HR107doc 40108U12Voltage L1-L2FLOAT32CDABVRead
HR109doc 40110U23Voltage L2-L3FLOAT32CDABVRead
HR111doc 40112U31Voltage L3-L1FLOAT32CDABVRead
HR113doc 40114UNEZero displacement voltage (4-wire)FLOAT32CDABVRead
HR115doc 40116ISystem currentFLOAT32CDABARead
HR117doc 40118I1Current L1FLOAT32CDABARead
HR119doc 40120I2Current L2FLOAT32CDABARead
HR121doc 40122I3Current L3FLOAT32CDABARead
HR123doc 40124INNeutral currentFLOAT32CDABARead
HR125doc 40126IBBimetal current (balanced systems)FLOAT32CDABARead
HR127doc 40128IB1Bimetal current L1FLOAT32CDABARead
HR129doc 40130IB2Bimetal current L2FLOAT32CDABARead
HR131doc 40132IB3Bimetal current L3FLOAT32CDABARead
HR133doc 40134PActive power system (P1+P2+P3)FLOAT32CDABRead
HR135doc 40136P1Active power L1FLOAT32CDABRead
HR137doc 40138P2Active power L2FLOAT32CDABRead
HR139doc 40140P3Active power L3FLOAT32CDABRead
HR141doc 40142QReactive power systemFLOAT32CDABRead
HR143doc 40144Q1Reactive power L1FLOAT32CDABRead
HR145doc 40146Q2Reactive power L2FLOAT32CDABRead
HR147doc 40148Q3Reactive power L3FLOAT32CDABRead
HR149doc 40150SApparent power systemFLOAT32CDABRead
HR151doc 40152S1Apparent power L1FLOAT32CDABRead
HR153doc 40154S2Apparent power L2FLOAT32CDABRead
HR155doc 40156S3Apparent power L3FLOAT32CDABRead
HR157doc 40158FSystem frequencyFLOAT32CDABHzRead
HR159doc 40160PFActive power factor system (P/S)FLOAT32CDABRead
HR161doc 40162PF1Power factor L1FLOAT32CDABRead
HR163doc 40164PF2Power factor L2FLOAT32CDABRead
HR165doc 40166PF3Power factor L3FLOAT32CDABRead
HR167doc 40168QFReactive power factor system (Q/S)FLOAT32CDABRead
HR169doc 40170QF1Reactive power factor L1FLOAT32CDABRead
HR171doc 40172QF2Reactive power factor L2FLOAT32CDABRead
HR173doc 40174QF3Reactive power factor L3FLOAT32CDABRead
HR175doc 40176LFLoad factor systemFLOAT32CDABRead
HR177doc 40178LF1Load factor L1FLOAT32CDABRead
HR179doc 40180LF2Load factor L2FLOAT32CDABRead
HR181doc 40182LF3Load factor L3FLOAT32CDABRead
HR183doc 40184U_MEANAverage of U1N, U2N, U3NFLOAT32CDABVRead
HR185doc 40186I_MEANAverage of I1, I2, I3FLOAT32CDABARead
HR189doc 40190UNB_UVoltage unbalance factor (4-wire); 1000 = 100 %.UINT16× 0.1%Read
HR190doc 40191THD_U1XVoltage THD phase 1; 1000 = 100 %.UINT16× 0.1%Read
HR191doc 40192THD_U2XVoltage THD phase 2; 1000 = 100 %.UINT16× 0.1%Read
HR192doc 40193THD_U3XVoltage THD phase 3; 1000 = 100 %.UINT16× 0.1%Read
HR193doc 40194TDD_I1Current TDD phase 1; 1000 = 100 %.UINT16× 0.1%Read
HR194doc 40195TDD_I2Current TDD phase 2; 1000 = 100 %.UINT16× 0.1%Read
HR195doc 40196TDD_I3Current TDD phase 3; 1000 = 100 %.UINT16× 0.1%Read
HR989doc 40990UR1Voltage positive sequence (FW 1.37+)FLOAT32CDABVRead
HR991doc 40992UR2Voltage negative sequenceFLOAT32CDABVRead
HR993doc 40994U0Voltage zero sequenceFLOAT32CDABVRead
HR995doc 40996IR1Current positive sequenceFLOAT32CDABARead
HR997doc 40998IR2Current negative sequenceFLOAT32CDABARead
HR999doc 41000I0Current zero sequenceFLOAT32CDABARead
HR1001doc 41002UNB_UR2_UR1Voltage unbalance UR2/UR1FLOAT32CDAB%Read
HR1003doc 41004UNB_IR2_IR1Current unbalance IR2/IR1FLOAT32CDAB%Read
HR1005doc 41006UNB_U0_UR1Voltage unbalance U0/UR1FLOAT32CDAB%Read
HR1007doc 41008UNB_I0_IR1Current unbalance I0/IR1FLOAT32CDAB%Read
HR1009doc 41010THD_U1X (float)Voltage THD phase 1FLOAT32CDABRead
HR1011doc 41012THD_U2X (float)Voltage THD phase 2FLOAT32CDABRead
HR1013doc 41014THD_U3X (float)Voltage THD phase 3FLOAT32CDABRead
HR1015doc 41016TDD_I1 (float)Current TDD phase 1FLOAT32CDABRead
HR1017doc 41018TDD_I2 (float)Current TDD phase 2FLOAT32CDABRead
HR1019doc 41020TDD_I3 (float)Current TDD phase 3FLOAT32CDABRead
HR1329doc 41330AIN1.1 analog input valueValue of analog input module 1 channel 1 (unit as configured).FLOAT32CDABRead
HR1331doc 41332AIN1.2 analog input valueValue of analog input module 1 channel 2 (unit as configured).FLOAT32CDABRead
HR1333doc 41334AIN2.1 analog input valueValue of analog input module 2 channel 1 (unit as configured).FLOAT32CDABRead
HR1335doc 41336AIN2.2 analog input valueValue of analog input module 2 channel 2 (unit as configured).FLOAT32CDABRead
HR1337doc 41338AIN3.1 analog input valueValue of analog input module 3 channel 1 (unit as configured).FLOAT32CDABRead
HR1339doc 41340AIN3.2 analog input valueValue of analog input module 3 channel 2 (unit as configured).FLOAT32CDABRead
HR1341doc 41342AIN4.1 analog input valueValue of analog input module 4 channel 1 (unit as configured).FLOAT32CDABRead
HR1343doc 41344AIN4.2 analog input valueValue of analog input module 4 channel 2 (unit as configured).FLOAT32CDABRead
HR1484doc 41485CNTR_TARIF - tariff in useFirmware 1.39 and later.UINT16Read0 = High tariff; 1 = Low tariff

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP)

What Modbus registers does the Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP) have?

This map lists 108 registers: 16 coils, 12 discrete inputs, 80 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed 4xxxx and coils/inputs 0xxxx/1xxxx. The manual's own example: U1N at 40102 is sent as address 101 (0x65). Coil 1 is address 0, discrete input 10003 is address 2.

What byte order does the Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP)?

Start with HR 101 U1N (Voltage L1-N); HR 117 I1 (Current L1); HR 133 P (Active power system); HR 157 F (Frequency); HR 159 PF (Power factor system); HR 190 THD_U1X (Voltage THD phase 1).

How do I enable Modbus control of the Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP)?

Assign IP address, mask and gateway with the CB-Manager software (factory IP 192.168.1.101). The Modbus/TCP port can be changed there, but 502 is always supported.

Where is the official Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP) Modbus documentation?

The source is Modbus/TCP interface SINEAX CAM (W 157471 (modification 2014-018, 18.06.14)), revision 2014-06-18. Camille Bauer Metrawatt doesn't publish it on its own website, so this map was re-typed from a free copy at https://api-usa.com/pdf/cb/Modbus_TCP_Interface_CAM.pdf. It may be an older revision, so check it against the live unit.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Modbus/TCP interface SINEAX CAM · W 157471 (modification 2014-018, 18.06.14) · rev. 2014-06-18 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.