Energy meter · Modbus register map

Eastron SDM630-Modbus Modbus register map

Updated 17 November 2026

Short answer

The SDM630-Modbus is a three-phase, multifunction DIN-rail kWh meter with an RS485 Modbus RTU port. Every reading and every setting is a 32-bit IEEE-754 float spread over two registers. Measurements are input registers (function 04), configuration is in holding registers (function 03 to read, 16 to write). This map covers per-phase and system electrical values, THD, demand and per-phase import/export energy plus the communication and pulse settings.

This page lists 95 Modbus registers for the Eastron SDM630-Modbus — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eastron’s own free documentation (linked below) and checked against it.

Manufacturer
Eastron
Model
SDM630-Modbus
Equipment type
Energy meter
Registers
95 (10 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
SDM630Modbus, SDM630 Modbus V2, SDM630-Modbus V2
Source document
Eastron SDM630Modbus Smart Meter Modbus Protocol Implementation V1.8 · V1.8
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Eastron SDM630-Modbus

Integration in brief

Poll input registers with function 04 in two-register pairs starting at 0x0000; floats arrive high word first. Total power is at 0x0034, import and export kWh at 0x0048 and 0x004A.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Phase 1 line to neutral voltsFLOAT32 ABCDPhase 1 voltageRead
IR 6Phase 1 currentFLOAT32 ABCDPhase 1 currentRead
IR 52Total system powerFLOAT32 ABCDTotal system powerRead
IR 62Total system power factorFLOAT32 ABCDTotal power factorRead
IR 70Frequency of supply voltagesFLOAT32 ABCDFrequencyRead
IR 72Total Import kWhFLOAT32 ABCDImport kWhRead
IR 74Total Export kWhFLOAT32 ABCDExport kWhRead

Enable Modbus control & writes

Modbus RTU is always on at the RS485 terminals. To change the system type, write the password (default 0000) as a float to 40025 first; it times out after one minute unless 40015 or 40025 is read.

Byte order & addressing

Network setup

Watch out for

Eastron SDM630-Modbus Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

95 of 95 shown
Eastron SDM630-Modbus Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Phase 1 line to neutral voltsReturns 0 on 3P3W wiring.FLOAT32ABCDVRead
IR2doc 30003Phase 2 line to neutral voltsReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCDVRead
IR4doc 30005Phase 3 line to neutral voltsReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCDVRead
IR6doc 30007Phase 1 currentFLOAT32ABCDARead
IR8doc 30009Phase 2 currentReturns 0 on 1P2W wiring.FLOAT32ABCDARead
IR10doc 30011Phase 3 currentReturns 0 on 1P2W wiring.FLOAT32ABCDARead
IR12doc 30013Phase 1 powerReturns 0 on 3P3W wiring.FLOAT32ABCDWRead
IR14doc 30015Phase 2 powerReturns 0 on 3P3W wiring.FLOAT32ABCDWRead
IR16doc 30017Phase 3 powerReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCDWRead
IR18doc 30019Phase 1 volt ampsReturns 0 on 3P3W wiring.FLOAT32ABCDVARead
IR20doc 30021Phase 2 volt ampsReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCDVARead
IR22doc 30023Phase 3 volt ampsReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCDVARead
IR24doc 30025Phase 1 reactive powerReturns 0 on 3P3W wiring.FLOAT32ABCDVArRead
IR26doc 30027Phase 2 reactive powerReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCDVArRead
IR28doc 30029Phase 3 reactive powerReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCDVArRead
IR30doc 30031Phase 1 power factorReturns 0 on 3P3W wiring. Sign shows current direction (+ forward, - reverse).FLOAT32ABCDRead
IR32doc 30033Phase 2 power factorReturns 0 on 3P3W and 1P2W wiring. Sign shows current direction (+ forward, - reverse).FLOAT32ABCDRead
IR34doc 30035Phase 3 power factorReturns 0 on 3P3W and 1P2W wiring. Sign shows current direction (+ forward, - reverse).FLOAT32ABCDRead
IR36doc 30037Phase 1 phase angleReturns 0 on 3P3W wiring.FLOAT32ABCD°Read
IR38doc 30039Phase 2 phase angleReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCD°Read
IR40doc 30041Phase 3 phase angleReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCD°Read
IR42doc 30043Average line to neutral voltsReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCDVRead
IR46doc 30047Average line currentFLOAT32ABCDARead
IR48doc 30049Sum of line currentsFLOAT32ABCDARead
IR52doc 30053Total system powerFLOAT32ABCDWRead
IR56doc 30057Total system volt ampsFLOAT32ABCDVARead
IR60doc 30061Total system VArFLOAT32ABCDVArRead
IR62doc 30063Total system power factorSign shows current direction (+ forward, - reverse).FLOAT32ABCDRead
IR66doc 30067Total system phase angleFLOAT32ABCD°Read
IR70doc 30071Frequency of supply voltagesFLOAT32ABCDHzRead
IR72doc 30073Total Import kWhFLOAT32ABCDkWhRead
IR74doc 30075Total Export kWhFLOAT32ABCDkWhRead
IR76doc 30077Total Import kVArhFLOAT32ABCDkVArhRead
IR78doc 30079Total Export kVArhFLOAT32ABCDkVArhRead
IR80doc 30081Total VAhFLOAT32ABCDkVAhRead
IR82doc 30083AhFLOAT32ABCDAhRead
IR84doc 30085Total system power demandDemand of import minus export power (per source note).FLOAT32ABCDWRead
IR100doc 30101Total system VA demandFLOAT32ABCDVARead
IR102doc 30103Maximum total system VA demandFLOAT32ABCDVARead
IR104doc 30105Neutral current demandReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCDARead
IR106doc 30107Maximum neutral current demandReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCDARead
IR200doc 30201Line 1 to Line 2 voltsReturns 0 on 1P2W wiring.FLOAT32ABCDVRead
IR202doc 30203Line 2 to Line 3 voltsReturns 0 on 1P2W wiring.FLOAT32ABCDVRead
IR204doc 30205Line 3 to Line 1 voltsReturns 0 on 1P2W wiring.FLOAT32ABCDVRead
IR206doc 30207Average line to line voltsReturns 0 on 1P2W wiring.FLOAT32ABCDVRead
IR224doc 30225Neutral currentReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCDARead
IR234doc 30235Phase 1 L/N volts THDReturns 0 on 3P3W wiring.FLOAT32ABCD%Read
IR236doc 30237Phase 2 L/N volts THDReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCD%Read
IR238doc 30239Phase 3 L/N volts THDReturns 0 on 3P3W and 1P2W wiring.FLOAT32ABCD%Read
IR240doc 30241Phase 1 Current THDFLOAT32ABCD%Read
IR242doc 30243Phase 2 Current THDReturns 0 on 1P2W wiring.FLOAT32ABCD%Read
IR244doc 30245Phase 3 Current THDReturns 0 on 1P2W wiring.FLOAT32ABCD%Read
IR248doc 30249Average line to neutral volts THDReturns 0 on 3P3W wiring.FLOAT32ABCD%Read
IR250doc 30251Average line current THDFLOAT32ABCD%Read
IR258doc 30259Phase 1 current demandFLOAT32ABCDARead
IR260doc 30261Phase 2 current demandReturns 0 on 1P2W wiring.FLOAT32ABCDARead
IR262doc 30263Phase 3 current demandReturns 0 on 1P2W wiring.FLOAT32ABCDARead
IR264doc 30265Maximum phase 1 current demandFLOAT32ABCDARead
IR266doc 30267Maximum phase 2 current demandReturns 0 on 1P2W wiring.FLOAT32ABCDARead
IR268doc 30269Maximum phase 3 current demandReturns 0 on 1P2W wiring.FLOAT32ABCDARead
IR334doc 30335Line 1 to line 2 volts THDReturns 0 on 1P2W wiring.FLOAT32ABCD%Read
IR336doc 30337Line 2 to line 3 volts THDReturns 0 on 1P2W wiring.FLOAT32ABCD%Read
IR338doc 30339Line 3 to line 1 volts THDReturns 0 on 1P2W wiring.FLOAT32ABCD%Read
IR340doc 30341Average line to line volts THDReturns 0 on 1P2W wiring.FLOAT32ABCD%Read
IR342doc 30343Total kWh (import + export)FLOAT32ABCDkWhRead
IR344doc 30345Total kVArh (import + export)FLOAT32ABCDkVArhRead
IR346doc 30347L1 import kWhFLOAT32ABCDkWhRead
IR348doc 30349L2 import kWhFLOAT32ABCDkWhRead
IR350doc 30351L3 import kWhFLOAT32ABCDkWhRead
IR352doc 30353L1 export kWhFLOAT32ABCDkWhRead
IR354doc 30355L2 export kWhFLOAT32ABCDkWhRead
IR356doc 30357L3 export kWhFLOAT32ABCDkWhRead
IR358doc 30359L1 total kWh (import + export)FLOAT32ABCDkWhRead
IR360doc 30361L2 total kWh (import + export)FLOAT32ABCDkWhRead
IR362doc 30363L3 total kWh (import + export)FLOAT32ABCDkWhRead
IR364doc 30365L1 import kVArhFLOAT32ABCDkVArhRead
IR366doc 30367L2 import kVArhFLOAT32ABCDkVArhRead
IR368doc 30369L3 import kVArhFLOAT32ABCDkVArhRead
IR370doc 30371L1 export kVArhFLOAT32ABCDkVArhRead
IR372doc 30373L2 export kVArhFLOAT32ABCDkVArhRead
IR374doc 30375L3 export kVArhFLOAT32ABCDkVArhRead
IR376doc 30377L1 total kVArh (import + export)FLOAT32ABCDkVArhRead
IR378doc 30379L2 total kVArh (import + export)FLOAT32ABCDkVArhRead
IR380doc 30381L3 total kVArh (import + export)FLOAT32ABCDkVArhRead
HR2doc 40003Demand period0, 5, 8, 10, 15, 20, 30 or 60 (default 60). 0 shows instantaneous values.FLOAT32ABCDminRead/write
HR10doc 40011System typeWiring system; password required to change.FLOAT32ABCDRead/write1 = 1P2W; 2 = 3P3W; 3 = 3P4W
HR12doc 40013Pulse 1 width60, 100 or 200 ms (default 100).FLOAT32ABCDmsRead/write
HR14doc 40015Password lock0 = locked, 1 = unlocked; reading restarts the 1-minute password timeout.FLOAT32ABCDRead0 = Locked; 1 = Unlocked
HR18doc 40019Network parity / stop bitsTakes effect after restart.FLOAT32ABCDRead/write0 = No parity, 1 stop bit (default); 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit; 3 = No parity, 2 stop bits
HR20doc 40021Network node address1-247, default 1. Takes effect after restart.FLOAT32ABCDRead/write
HR22doc 40023Pulse 1 divisorPulse output constant index.FLOAT32ABCDRead/write0 = 0.0025 kWh(kVArh)/imp; 1 = 0.01 kWh(kVArh)/imp; 2 = 0.1 kWh(kVArh)/imp; 3 = 1 kWh(kVArh)/imp; 4 = 10 kWh(kVArh)/imp; 5 = 100 kWh(kVArh)/imp
HR24doc 40025PasswordWrite the password here to unlock protected registers (default 0000).FLOAT32ABCDRead/write
HR28doc 40029Network baud rateFLOAT32ABCDRead/write0 = 2400; 1 = 4800; 2 = 9600 (default); 3 = 19200; 4 = 38400
HR86doc 40087Pulse 1 energy typeEnergy quantity driving pulse output 1.FLOAT32ABCDRead/write1 = Import active energy; 2 = Total active energy; 4 = Export active energy (default); 5 = Import reactive energy; 6 = Total reactive energy; 8 = Export reactive energy
HR61456doc 461457ResetWrite 0x0000 to reset maximum demand values.UINT16Write0 = Reset maximum demand

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Eastron SDM630-Modbus

What Modbus registers does the Eastron SDM630-Modbus have?

This map lists 95 registers: 84 input registers, 11 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Eastron SDM630-Modbus Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print 30001/40001-style register numbers next to the hex start address that goes on the wire; the two always differ by 30001 or 40001 (e.g. 30007 = 0x0006, which matches the document's example of reading Amps 1 at start address 0006). The reset register is printed 461457 with hex F010.

What byte order does the Eastron SDM630-Modbus use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Eastron SDM630-Modbus?

Start with IR 0 Phase 1 line to neutral volts (Phase 1 voltage); IR 6 Phase 1 current (Phase 1 current); IR 52 Total system power (Total system power); IR 62 Total system power factor (Total power factor); IR 70 Frequency of supply voltages (Frequency); IR 72 Total Import kWh (Import kWh); IR 74 Total Export kWh (Export kWh).

How do I enable Modbus control of the Eastron SDM630-Modbus?

Modbus RTU is always on at the RS485 terminals. To change the system type, write the password (default 0000) as a float to 40025 first; it times out after one minute unless 40015 or 40025 is read.

Where is the official Eastron SDM630-Modbus Modbus documentation?

The source is Eastron SDM630Modbus Smart Meter Modbus Protocol Implementation V1.8 (V1.8), published free by Eastron at https://www.eastroneurope.com/images/uploads/products/protocol/SDM630_MODBUS_Protocol.pdf.

More Eastron Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Eastron SDM630Modbus Smart Meter Modbus Protocol Implementation V1.8 · V1.8. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.