Energy meter · Modbus register map
Eastron SDM630-Modbus Modbus register map
Updated 17 November 2026
The SDM630-Modbus is a three-phase, multifunction DIN-rail kWh meter with an RS485 Modbus RTU port. Every reading and every setting is a 32-bit IEEE-754 float spread over two registers. Measurements are input registers (function 04), configuration is in holding registers (function 03 to read, 16 to write). This map covers per-phase and system electrical values, THD, demand and per-phase import/export energy plus the communication and pulse settings.
This page lists 95 Modbus registers for the Eastron SDM630-Modbus — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eastron’s own free documentation (linked below) and checked against it.
- Manufacturer
- Eastron
- Model
- SDM630-Modbus
- Equipment type
- Energy meter
- Registers
- 95 (10 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- SDM630Modbus, SDM630 Modbus V2, SDM630-Modbus V2
Integration notes: Eastron SDM630-Modbus
Poll input registers with function 04 in two-register pairs starting at 0x0000; floats arrive high word first. Total power is at 0x0034, import and export kWh at 0x0048 and 0x004A.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Phase 1 line to neutral volts | FLOAT32 ABCD | Phase 1 voltage | Read |
| IR 6 | Phase 1 current | FLOAT32 ABCD | Phase 1 current | Read |
| IR 52 | Total system power | FLOAT32 ABCD | Total system power | Read |
| IR 62 | Total system power factor | FLOAT32 ABCD | Total power factor | Read |
| IR 70 | Frequency of supply voltages | FLOAT32 ABCD | Frequency | Read |
| IR 72 | Total Import kWh | FLOAT32 ABCD | Import kWh | Read |
| IR 74 | Total Export kWh | FLOAT32 ABCD | Export kWh | Read |
Enable Modbus control & writes
Modbus RTU is always on at the RS485 terminals. To change the system type, write the password (default 0000) as a float to 40025 first; it times out after one minute unless 40015 or 40025 is read.
Byte order & addressing
- Every value, including enumerations such as baud rate, is a float in two registers; write settings with function 16, one parameter per message.
- Node address and parity changes only take effect after the meter restarts.
- The reset register uses the six-digit number 461457 (hex F010) and is write-only.
Network setup
- Defaults: address 1, 9600 baud, 8 data bits, no parity, 1 stop bit.
- Selectable baud rates: 2400, 4800, 9600, 19200, 38400.
- Terminate both ends of the RS485 line with 120 ohm resistors; up to 32 nodes and 1200 m.
Watch out for
- The document says broadcast is supported in one place and not supported in another; do not rely on address 0.
- Requesting more than 40 values in one read returns an exception.
Eastron SDM630-Modbus Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Phase 1 line to neutral volts | Returns 0 on 3P3W wiring. | FLOAT32 | ABCD | V | Read | ||
| IR | 2doc 30003 | Phase 2 line to neutral volts | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | V | Read | ||
| IR | 4doc 30005 | Phase 3 line to neutral volts | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | V | Read | ||
| IR | 6doc 30007 | Phase 1 current | FLOAT32 | ABCD | A | Read | |||
| IR | 8doc 30009 | Phase 2 current | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | A | Read | ||
| IR | 10doc 30011 | Phase 3 current | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | A | Read | ||
| IR | 12doc 30013 | Phase 1 power | Returns 0 on 3P3W wiring. | FLOAT32 | ABCD | W | Read | ||
| IR | 14doc 30015 | Phase 2 power | Returns 0 on 3P3W wiring. | FLOAT32 | ABCD | W | Read | ||
| IR | 16doc 30017 | Phase 3 power | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | W | Read | ||
| IR | 18doc 30019 | Phase 1 volt amps | Returns 0 on 3P3W wiring. | FLOAT32 | ABCD | VA | Read | ||
| IR | 20doc 30021 | Phase 2 volt amps | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | VA | Read | ||
| IR | 22doc 30023 | Phase 3 volt amps | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | VA | Read | ||
| IR | 24doc 30025 | Phase 1 reactive power | Returns 0 on 3P3W wiring. | FLOAT32 | ABCD | VAr | Read | ||
| IR | 26doc 30027 | Phase 2 reactive power | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | VAr | Read | ||
| IR | 28doc 30029 | Phase 3 reactive power | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | VAr | Read | ||
| IR | 30doc 30031 | Phase 1 power factor | Returns 0 on 3P3W wiring. Sign shows current direction (+ forward, - reverse). | FLOAT32 | ABCD | Read | |||
| IR | 32doc 30033 | Phase 2 power factor | Returns 0 on 3P3W and 1P2W wiring. Sign shows current direction (+ forward, - reverse). | FLOAT32 | ABCD | Read | |||
| IR | 34doc 30035 | Phase 3 power factor | Returns 0 on 3P3W and 1P2W wiring. Sign shows current direction (+ forward, - reverse). | FLOAT32 | ABCD | Read | |||
| IR | 36doc 30037 | Phase 1 phase angle | Returns 0 on 3P3W wiring. | FLOAT32 | ABCD | ° | Read | ||
| IR | 38doc 30039 | Phase 2 phase angle | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | ° | Read | ||
| IR | 40doc 30041 | Phase 3 phase angle | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | ° | Read | ||
| IR | 42doc 30043 | Average line to neutral volts | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | V | Read | ||
| IR | 46doc 30047 | Average line current | FLOAT32 | ABCD | A | Read | |||
| IR | 48doc 30049 | Sum of line currents | FLOAT32 | ABCD | A | Read | |||
| IR | 52doc 30053 | Total system power | FLOAT32 | ABCD | W | Read | |||
| IR | 56doc 30057 | Total system volt amps | FLOAT32 | ABCD | VA | Read | |||
| IR | 60doc 30061 | Total system VAr | FLOAT32 | ABCD | VAr | Read | |||
| IR | 62doc 30063 | Total system power factor | Sign shows current direction (+ forward, - reverse). | FLOAT32 | ABCD | Read | |||
| IR | 66doc 30067 | Total system phase angle | FLOAT32 | ABCD | ° | Read | |||
| IR | 70doc 30071 | Frequency of supply voltages | FLOAT32 | ABCD | Hz | Read | |||
| IR | 72doc 30073 | Total Import kWh | FLOAT32 | ABCD | kWh | Read | |||
| IR | 74doc 30075 | Total Export kWh | FLOAT32 | ABCD | kWh | Read | |||
| IR | 76doc 30077 | Total Import kVArh | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 78doc 30079 | Total Export kVArh | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 80doc 30081 | Total VAh | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 82doc 30083 | Ah | FLOAT32 | ABCD | Ah | Read | |||
| IR | 84doc 30085 | Total system power demand | Demand of import minus export power (per source note). | FLOAT32 | ABCD | W | Read | ||
| IR | 100doc 30101 | Total system VA demand | FLOAT32 | ABCD | VA | Read | |||
| IR | 102doc 30103 | Maximum total system VA demand | FLOAT32 | ABCD | VA | Read | |||
| IR | 104doc 30105 | Neutral current demand | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | A | Read | ||
| IR | 106doc 30107 | Maximum neutral current demand | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | A | Read | ||
| IR | 200doc 30201 | Line 1 to Line 2 volts | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | V | Read | ||
| IR | 202doc 30203 | Line 2 to Line 3 volts | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | V | Read | ||
| IR | 204doc 30205 | Line 3 to Line 1 volts | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | V | Read | ||
| IR | 206doc 30207 | Average line to line volts | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | V | Read | ||
| IR | 224doc 30225 | Neutral current | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | A | Read | ||
| IR | 234doc 30235 | Phase 1 L/N volts THD | Returns 0 on 3P3W wiring. | FLOAT32 | ABCD | % | Read | ||
| IR | 236doc 30237 | Phase 2 L/N volts THD | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | % | Read | ||
| IR | 238doc 30239 | Phase 3 L/N volts THD | Returns 0 on 3P3W and 1P2W wiring. | FLOAT32 | ABCD | % | Read | ||
| IR | 240doc 30241 | Phase 1 Current THD | FLOAT32 | ABCD | % | Read | |||
| IR | 242doc 30243 | Phase 2 Current THD | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | % | Read | ||
| IR | 244doc 30245 | Phase 3 Current THD | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | % | Read | ||
| IR | 248doc 30249 | Average line to neutral volts THD | Returns 0 on 3P3W wiring. | FLOAT32 | ABCD | % | Read | ||
| IR | 250doc 30251 | Average line current THD | FLOAT32 | ABCD | % | Read | |||
| IR | 258doc 30259 | Phase 1 current demand | FLOAT32 | ABCD | A | Read | |||
| IR | 260doc 30261 | Phase 2 current demand | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | A | Read | ||
| IR | 262doc 30263 | Phase 3 current demand | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | A | Read | ||
| IR | 264doc 30265 | Maximum phase 1 current demand | FLOAT32 | ABCD | A | Read | |||
| IR | 266doc 30267 | Maximum phase 2 current demand | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | A | Read | ||
| IR | 268doc 30269 | Maximum phase 3 current demand | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | A | Read | ||
| IR | 334doc 30335 | Line 1 to line 2 volts THD | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | % | Read | ||
| IR | 336doc 30337 | Line 2 to line 3 volts THD | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | % | Read | ||
| IR | 338doc 30339 | Line 3 to line 1 volts THD | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | % | Read | ||
| IR | 340doc 30341 | Average line to line volts THD | Returns 0 on 1P2W wiring. | FLOAT32 | ABCD | % | Read | ||
| IR | 342doc 30343 | Total kWh (import + export) | FLOAT32 | ABCD | kWh | Read | |||
| IR | 344doc 30345 | Total kVArh (import + export) | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 346doc 30347 | L1 import kWh | FLOAT32 | ABCD | kWh | Read | |||
| IR | 348doc 30349 | L2 import kWh | FLOAT32 | ABCD | kWh | Read | |||
| IR | 350doc 30351 | L3 import kWh | FLOAT32 | ABCD | kWh | Read | |||
| IR | 352doc 30353 | L1 export kWh | FLOAT32 | ABCD | kWh | Read | |||
| IR | 354doc 30355 | L2 export kWh | FLOAT32 | ABCD | kWh | Read | |||
| IR | 356doc 30357 | L3 export kWh | FLOAT32 | ABCD | kWh | Read | |||
| IR | 358doc 30359 | L1 total kWh (import + export) | FLOAT32 | ABCD | kWh | Read | |||
| IR | 360doc 30361 | L2 total kWh (import + export) | FLOAT32 | ABCD | kWh | Read | |||
| IR | 362doc 30363 | L3 total kWh (import + export) | FLOAT32 | ABCD | kWh | Read | |||
| IR | 364doc 30365 | L1 import kVArh | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 366doc 30367 | L2 import kVArh | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 368doc 30369 | L3 import kVArh | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 370doc 30371 | L1 export kVArh | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 372doc 30373 | L2 export kVArh | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 374doc 30375 | L3 export kVArh | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 376doc 30377 | L1 total kVArh (import + export) | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 378doc 30379 | L2 total kVArh (import + export) | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 380doc 30381 | L3 total kVArh (import + export) | FLOAT32 | ABCD | kVArh | Read | |||
| HR | 2doc 40003 | Demand period | 0, 5, 8, 10, 15, 20, 30 or 60 (default 60). 0 shows instantaneous values. | FLOAT32 | ABCD | min | Read/write | ||
| HR | 10doc 40011 | System type | Wiring system; password required to change. | FLOAT32 | ABCD | Read/write | 1 = 1P2W; 2 = 3P3W; 3 = 3P4W | ||
| HR | 12doc 40013 | Pulse 1 width | 60, 100 or 200 ms (default 100). | FLOAT32 | ABCD | ms | Read/write | ||
| HR | 14doc 40015 | Password lock | 0 = locked, 1 = unlocked; reading restarts the 1-minute password timeout. | FLOAT32 | ABCD | Read | 0 = Locked; 1 = Unlocked | ||
| HR | 18doc 40019 | Network parity / stop bits | Takes effect after restart. | FLOAT32 | ABCD | Read/write | 0 = No parity, 1 stop bit (default); 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit; 3 = No parity, 2 stop bits | ||
| HR | 20doc 40021 | Network node address | 1-247, default 1. Takes effect after restart. | FLOAT32 | ABCD | Read/write | |||
| HR | 22doc 40023 | Pulse 1 divisor | Pulse output constant index. | FLOAT32 | ABCD | Read/write | 0 = 0.0025 kWh(kVArh)/imp; 1 = 0.01 kWh(kVArh)/imp; 2 = 0.1 kWh(kVArh)/imp; 3 = 1 kWh(kVArh)/imp; 4 = 10 kWh(kVArh)/imp; 5 = 100 kWh(kVArh)/imp | ||
| HR | 24doc 40025 | Password | Write the password here to unlock protected registers (default 0000). | FLOAT32 | ABCD | Read/write | |||
| HR | 28doc 40029 | Network baud rate | FLOAT32 | ABCD | Read/write | 0 = 2400; 1 = 4800; 2 = 9600 (default); 3 = 19200; 4 = 38400 | |||
| HR | 86doc 40087 | Pulse 1 energy type | Energy quantity driving pulse output 1. | FLOAT32 | ABCD | Read/write | 1 = Import active energy; 2 = Total active energy; 4 = Export active energy (default); 5 = Import reactive energy; 6 = Total reactive energy; 8 = Export reactive energy | ||
| HR | 61456doc 461457 | Reset | Write 0x0000 to reset maximum demand values. | UINT16 | Write | 0 = Reset maximum demand |
Notes on this map
- Word order: the document states floats are sent most significant register first by default, and its read example returns 43 66 33 34 for 230.2 V. All values here are ABCD. A 'Register Order' holding register can reverse this, but the document gives no address for it, so it is not listed.
- Each input value is valid only for some wiring systems; values marked unavailable for the configured system read zero. The per-register descriptions say which systems return 0.
- Left out: 30087 'Maximum total system power demand', because the table gives its unit as VA while the matching demand register is in W.
- Left out: the serial number (464513), an unsigned 32-bit integer whose word order the document does not state.
- Read and write in register pairs: start on an even address and request an even number of registers; odd counts return an exception (a single-register read is instead answered with an instrument-type value). At most 40 values (80 registers) per request.
- Total kWh/kVArh registers (30343, 30345 and the per-phase totals) equal import plus export, per the source note.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Eastron SDM630-Modbus
What Modbus registers does the Eastron SDM630-Modbus have?
This map lists 95 registers: 84 input registers, 11 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Eastron SDM630-Modbus Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print 30001/40001-style register numbers next to the hex start address that goes on the wire; the two always differ by 30001 or 40001 (e.g. 30007 = 0x0006, which matches the document's example of reading Amps 1 at start address 0006). The reset register is printed 461457 with hex F010.
What byte order does the Eastron SDM630-Modbus use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Eastron SDM630-Modbus?
Start with IR 0 Phase 1 line to neutral volts (Phase 1 voltage); IR 6 Phase 1 current (Phase 1 current); IR 52 Total system power (Total system power); IR 62 Total system power factor (Total power factor); IR 70 Frequency of supply voltages (Frequency); IR 72 Total Import kWh (Import kWh); IR 74 Total Export kWh (Export kWh).
How do I enable Modbus control of the Eastron SDM630-Modbus?
Modbus RTU is always on at the RS485 terminals. To change the system type, write the password (default 0000) as a float to 40025 first; it times out after one minute unless 40015 or 40025 is read.
Where is the official Eastron SDM630-Modbus Modbus documentation?
The source is Eastron SDM630Modbus Smart Meter Modbus Protocol Implementation V1.8 (V1.8), published free by Eastron at https://www.eastroneurope.com/images/uploads/products/protocol/SDM630_MODBUS_Protocol.pdf.
More Eastron Modbus register maps
- Energy meter
Eastron SDM120-Modbus
Eastron SDM120Modbus single-phase DIN-rail meter (direct connected), protocol implementation V2.4.
Also known as: SDM120M, SDM120Modbus, SDM120-M - Energy meter
Eastron SDM120CT-40mA
Eastron SDM120CT-40mA single-phase CT-connected DIN-rail meter with RS485 Modbus RTU, user manual V1.0 (2026-07-16).
Also known as: SDM120CT-M-40mA, SDM120CT-M 40mA - Energy meter
Eastron SDM120CT-M
Eastron SDM120CTM single-phase CT-operated DIN-rail meter (1 A / 5 A CT secondary), protocol implementation V1.3. Not the SDM120CT-40mA.
Also known as: SDM120CTM, SDM120CT Modbus, SDM120CT-MV - Energy meter
Eastron SDM230-DI
Eastron SDM230-DI single-phase 100 A DIN-rail meter with two digital inputs and RS485 Modbus RTU, manual 2025 V1.00.
Also known as: SDM230 DI - Energy meter
Eastron SDM230-Modbus
Eastron SDM230-Modbus (two-tariff SDM230-2T protocol) single-phase two-module DIN-rail meter, protocol V1.1.
Also known as: SDM230Modbus, SDM230-2T, SDM230-M - Energy meter
Eastron SDM630-DI
Eastron SDM630-DI three-phase DIN-rail meter (100 A direct, two digital inputs, RS485 Modbus RTU), manual V1.02.
Also known as: SDM630 DI - Energy meter
Eastron SDM630MCT
Eastron SDM630MCT three-phase CT-connected DIN-rail meter with RS485 Modbus RTU, protocol implementation V1.7.
Also known as: SDM630 MCT
Other power & energy meters register maps
- Sensor (ultrasonic gas flowmeter)
Endress+Hauser Proline Prosonic Flow G 300 ultrasonic gas flowmeter (Modbus RS485)
Prosonic Flow G 300 with the Modbus RS485 communication option, parameter description GP01131D/06/EN/02.24-00.
Also known as: Prosonic Flow G 300 - Power meter (power quality meter)
GE Multilin Multilin PQMII power quality meter
Multilin PQMII per instruction manual GEK-113532 (communications guide chapter).
Also known as: PQM II, GE Multilin PQMII, PQM2 - Power meter (DIN-rail)
IME Nemo D4-Le multifunction meter (MFD44)
IME Nemo D4-Le DIN-rail meter MFD44 with RS-485, per protocol PR129 (software 2.05).
Also known as: MFD44, Nemo D4-Le - Energy meter
inepro Metering PRO3 three-phase energy meter (2026 PRO line)
PRO3-Mod (art. 1301) and PRO3-Mod-Ba (art. 1302, with RTC tariffs) from the 2026 PRO3 user manual version 1.3; the PRO3-S has no Modbus.
Also known as: PRO3-Mod, PRO3-Mod-Ba, PRO3 1U AC 100A Mod T MID, PRO3 1U AC 100A Mod T Ba MID, 1301, 1302 - Power meter (power quality analyser)
Janitza UMG 511 power quality analyser (Modbus RTU)
UMG 511 per Modbus address list 1.037.021.9.g (05/2021).
Also known as: UMG511, UMG 511, Janitza UMG511 - Power meter (power analyser)
Janitza UMG 96RM power analyser (basic device, RS-485 Modbus RTU)
UMG 96RM basic device from firmware release 1.14, per address list 1.040.034.t; the same list covers the shared registers of the -P, -CBM and -PN extensions. Other UMG 96RM variants (e.g. the Ethernet -E / -EL) are not covered by this list.
Also known as: UMG96RM, UMG 96 RM, UMG 96RM-P, UMG 96RM-CBM, UMG 96RM-PN, Janitza UMG96RM
All power & energy meters Modbus register maps →
Source: Eastron SDM630Modbus Smart Meter Modbus Protocol Implementation V1.8 · V1.8. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.