- UMG 511 power quality analyser (Modbus RTU)
Power meter (power quality analyser) · Modbus register map
Janitza UMG 511 power quality analyser (Modbus RTU) Modbus register map
Updated 17 November 2026
The UMG 511 is Janitza's power quality analyser. As a Modbus slave it serves its whole address list as big-endian values that include the CT/VT ratios. This map covers the 19000-19120 'frequently required readings' block (voltages, currents, powers, CosPhi, frequency, energies, THD), system time, internal temperature and the energy-reset commands.
This page lists 65 Modbus registers for the Janitza UMG 511 power quality analyser (Modbus RTU) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Janitza’s own free documentation (linked below) and checked against it.
- Manufacturer
- Janitza
- Model
- UMG 511 power quality analyser (Modbus RTU)
- Equipment type
- Power meter (power quality analyser)
- Registers
- 65 (2 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- UMG511, UMG 511, Janitza UMG511
Integration notes: Janitza UMG 511 power quality analyser (Modbus RTU)
Read holding registers from 19000 (function 03): 122 registers give volts, amps, powers, CosPhi, frequency, energies and THD as big-endian floats.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 19000 | Voltage L1-N | FLOAT32 ABCD | Voltage L1-N | Read |
| HR 19012 | Apparent current, L1-N | FLOAT32 ABCD | Current L1 | Read |
| HR 19026 | Real power sum L1-L3 | FLOAT32 ABCD | Total real power | Read |
| HR 19050 | Measured frequency | FLOAT32 ABCD | Frequency | Read |
| HR 19060 | Real energy L1..L3 | FLOAT32 ABCD | Real energy L1-L3 | Read |
| HR 19076 | Real energy L1..L3, delivered | FLOAT32 ABCD | Delivered real energy L1-L3 | Read |
Enable Modbus control & writes
Set the RS-485 Modbus address and baud rate on the device; the list gives no enable step.
Byte order & addressing
- Addresses are used as printed (0-based).
- Floats are ABCD; add 32768 for the little-endian copy.
- Energy is in Wh/varh/VAh, not kWh.
Network setup
- Use 8 data bits and no parity; the device sends 2 stop bits.
Watch out for
- 19068 is tariff 1 only.
- Short-format values elsewhere in the list ignore the CT/VT ratio.
Janitza UMG 511 power quality analyser (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 4 | System time (UTC) | Seconds, UTC. | INT32 | ABCD | s | Read | ||
| HR | 4209 | Internal temperature | FLOAT32 | ABCD | °C | Read | |||
| HR | 6708 | Digital output 1 status | INT16 | Read | 0 = Not active; 1 = Active | ||||
| HR | 6741 | Delete real energy counters | Write 1 to clear all real energy counters. | INT16 | Read/write | ||||
| HR | 6742 | Delete reactive energy counters | Write 1 to clear all reactive energy counters. | INT16 | Read/write | ||||
| HR | 19000 | Voltage L1-N | FLOAT32 | ABCD | V | Read | |||
| HR | 19002 | Voltage L2-N | FLOAT32 | ABCD | V | Read | |||
| HR | 19004 | Voltage L3-N | FLOAT32 | ABCD | V | Read | |||
| HR | 19006 | Voltage L1-L2 | FLOAT32 | ABCD | V | Read | |||
| HR | 19008 | Voltage L2-L3 | FLOAT32 | ABCD | V | Read | |||
| HR | 19010 | Voltage L3-L1 | FLOAT32 | ABCD | V | Read | |||
| HR | 19012 | Apparent current, L1-N | FLOAT32 | ABCD | A | Read | |||
| HR | 19014 | Apparent current, L2-N | FLOAT32 | ABCD | A | Read | |||
| HR | 19016 | Apparent current, L3-N | FLOAT32 | ABCD | A | Read | |||
| HR | 19018 | Neutral current (vector sum I1+I2+I3) | FLOAT32 | ABCD | A | Read | |||
| HR | 19020 | Real power L1-N | FLOAT32 | ABCD | W | Read | |||
| HR | 19022 | Real power L2-N | FLOAT32 | ABCD | W | Read | |||
| HR | 19024 | Real power L3-N | FLOAT32 | ABCD | W | Read | |||
| HR | 19026 | Real power sum L1-L3 | FLOAT32 | ABCD | W | Read | |||
| HR | 19028 | Apparent power L1-N | FLOAT32 | ABCD | VA | Read | |||
| HR | 19030 | Apparent power L2-N | FLOAT32 | ABCD | VA | Read | |||
| HR | 19032 | Apparent power L3-N | FLOAT32 | ABCD | VA | Read | |||
| HR | 19034 | Apparent power sum L1-L3 | FLOAT32 | ABCD | VA | Read | |||
| HR | 19036 | Reactive power L1 (fundamental comp.) | FLOAT32 | ABCD | var | Read | |||
| HR | 19038 | Reactive power L2 (fundamental comp.) | FLOAT32 | ABCD | var | Read | |||
| HR | 19040 | Reactive power L3 (fundamental comp.) | FLOAT32 | ABCD | var | Read | |||
| HR | 19042 | Reactive power sum L1-L3 (fundamental comp.) | FLOAT32 | ABCD | var | Read | |||
| HR | 19044 | CosPhi; UL1 IL1 (fundamental comp.) | FLOAT32 | ABCD | Read | ||||
| HR | 19046 | CosPhi; UL2 IL2 (fundamental comp.) | FLOAT32 | ABCD | Read | ||||
| HR | 19048 | CosPhi; UL3 IL3 (fundamental comp.) | FLOAT32 | ABCD | Read | ||||
| HR | 19050 | Measured frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 19052 | Rotation field; 1=right, 0=none, -1=left | Float: 1 = clockwise, 0 = none, -1 = anticlockwise. | FLOAT32 | ABCD | Read | |||
| HR | 19054 | Real energy L1 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19056 | Real energy L2 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19058 | Real energy L3 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19060 | Real energy L1..L3 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19062 | Real energy L1, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19064 | Real energy L2, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19066 | Real energy L3, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19070 | Real energy L1, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19072 | Real energy L2, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19074 | Real energy L3, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19076 | Real energy L1..L3, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19078 | Apparent energy L1 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 19080 | Apparent energy L2 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 19082 | Apparent energy L3 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 19084 | Apparent energy L1..L3 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 19086 | Reactive energy L1 (fundamental comp.) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19088 | Reactive energy L2 (fundamental comp.) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19090 | Reactive energy L3 (fundamental comp.) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19092 | Reactive energy L1..L3 (fundamental comp.) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19094 | Reactive energy, inductive, L1 (fundamental comp.) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19096 | Reactive energy, inductive, L2 (fundamental comp.) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19098 | Reactive energy, inductive, L3 (fundamental comp.) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19100 | Reactive energy L1..L3, ind. (fundamental comp.) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19102 | Reactive energy, capacitive, L1 (fundamental comp.) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19104 | Reactive energy, capacitive, L2 (fundamental comp.) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19106 | Reactive energy, capacitive, L3 (fundamental comp.) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19108 | Reactive energy L1..L3, cap. (fundamental comp.) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19110 | Harmonic, THD,U L1-N | FLOAT32 | ABCD | % | Read | |||
| HR | 19112 | Harmonic, THD,U L2-N | FLOAT32 | ABCD | % | Read | |||
| HR | 19114 | Harmonic, THD,U L3-N | FLOAT32 | ABCD | % | Read | |||
| HR | 19116 | Harmonic, THD,I L1 | FLOAT32 | ABCD | % | Read | |||
| HR | 19118 | Harmonic, THD,I L2 | FLOAT32 | ABCD | % | Read | |||
| HR | 19120 | Harmonic, THD,I L3 | FLOAT32 | ABCD | % | Read |
Notes on this map
- Janitza does not appear to host this address list at a public URL; this is an unaltered copy of the Janitza document (doc. no. 1.037.021.9.g) on a UK distributor's site.
- Byte order: the listed addresses return big-endian data (high word first = ABCD); adding 32768 to an address returns the same value little-endian.
- Transfer parameters (p. 5): 9.6-921.6 kbps, 8 data bits, no parity; the UMG 511 sends 2 stop bits. No default baud rate or device address is given.
- 19068 in the frequently-read block is the tariff 1 (rate 1) consumed total only, so it is left out.
- Left out: the per-channel energy arrays from 6546 (only element [0] is labelled, so the meaning of the other elements is not stated), the 64-bit _REALTIME at 0, min/max/mean blocks, harmonics and configuration registers.
- The digital-output and delete rows have no RD/WR column in the 'Other values' table; access is taken from their descriptions.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Janitza UMG 511 power quality analyser (Modbus RTU)
What Modbus registers does the Janitza UMG 511 power quality analyser (Modbus RTU) have?
This map lists 65 registers: 65 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Janitza UMG 511 power quality analyser (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as the protocol address and sent unchanged: 19000 is requested as 19000. The date/time list starts at address 0 (_REALTIME), which only fits 0-based numbering. In a 1-based or Modicon tool enter 19001 / 419001.
What byte order does the Janitza UMG 511 power quality analyser (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Janitza UMG 511 power quality analyser (Modbus RTU)?
Start with HR 19000 Voltage L1-N (Voltage L1-N); HR 19012 Apparent current, L1-N (Current L1); HR 19026 Real power sum L1-L3 (Total real power); HR 19050 Measured frequency (Frequency); HR 19060 Real energy L1..L3 (Real energy L1-L3); HR 19076 Real energy L1..L3, delivered (Delivered real energy L1-L3).
How do I enable Modbus control of the Janitza UMG 511 power quality analyser (Modbus RTU)?
Set the RS-485 Modbus address and baud rate on the device; the list gives no enable step.
Where is the official Janitza UMG 511 power quality analyser (Modbus RTU) Modbus documentation?
The source is Power Quality Analyser UMG 511 - Modbus-address and Formulary (1.037.021.9.g), revision 2021-05. Janitza doesn't publish it on its own website, so this map was re-typed from a free copy at https://shop.fortop.co.uk/files/umg511fortopjanitzamodbusaddressliste1295013212757.pdf. It may be an older revision, so check it against the live unit.
More Janitza Modbus register maps
- Power meter (power analyser)
Janitza UMG 104 power analyser (RS-485 Modbus RTU)
UMG 104 DIN-rail power analyser, firmware 1.268, per address list 1.041.006.1.e (01/2023).
Also known as: UMG104, UMG 104, Janitza UMG104 - Power meter (power analyser)
Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP)
UMG 508 power analyser from firmware release 2.x, per Modbus address list 1.042.008.9.b (08/2022).
Also known as: UMG508, UMG 508, Janitza UMG508 - Power meter (power analyser)
Janitza UMG 509 power analyser (Modbus RTU)
UMG 509 (the original, non-PRO model), per Modbus address list 1.059.004.2.d. For the UMG 509-PRO use its own map.
Also known as: UMG509, UMG 509, Janitza UMG509 - Power meter (power quality analyser)
Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 509-PRO per Modbus address list 1.059.004.2.n (06/2024).
Also known as: UMG509-PRO, UMG 509PRO, UMG509PRO, Janitza UMG 509 - Power meter (power quality analyser)
Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 512-PRO power quality analyser, per address list 1.054.016.3.k (08/2023).
Also known as: UMG512-PRO, UMG 512, UMG512, UMG 512 PRO, Janitza UMG512-PRO - Power meter (power quality analyser)
Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP)
UMG 604 (non-PRO) from firmware release 2.x, per address list 1.033.033.g.
Also known as: UMG604, UMG 604-E, UMG 604-EP, Janitza UMG 604 (non-PRO) - Power meter (power quality analyser)
Janitza UMG 604-PRO power analyser (Modbus RTU / Modbus TCP)
UMG 604-PRO from firmware release 5.028, per address list 1.033.034.e (08/2023).
Also known as: UMG604-PRO, UMG 604PRO, UMG604PRO, UMG 604-EP PRO, Janitza UMG 604 - Power meter (power analyser)
Janitza UMG 605 power quality analyser (Modbus RTU)
UMG 605 (the original, non-PRO model), per Modbus address list 1.038.009.7.a. For the UMG 605-PRO use its own map.
Also known as: UMG605, UMG 605, Janitza UMG605 - Power meter (power quality analyser)
Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 605-PRO from firmware release 5.028, per address list 1.038.009.7.h (09/2022).
Also known as: UMG605-PRO, UMG 605PRO, UMG605PRO, Janitza UMG 605 - Power meter (energy analyser)
Janitza UMG 96-S2 energy analyser (serial Modbus)
UMG 96-S2 energy analyser, per address list 2.062.026.1.b (10/2019).
Also known as: UMG96-S2, UMG 96 S2, UMG96S2, Janitza UMG96-S2 - Power meter (power analyser)
Janitza UMG 96RM power analyser (basic device, RS-485 Modbus RTU)
UMG 96RM basic device from firmware release 1.14, per address list 1.040.034.t; the same list covers the shared registers of the -P, -CBM and -PN extensions. Other UMG 96RM variants (e.g. the Ethernet -E / -EL) are not covered by this list.
Also known as: UMG96RM, UMG 96 RM, UMG 96RM-P, UMG 96RM-CBM, UMG 96RM-PN, Janitza UMG96RM - Power meter (power analyser)
Janitza UMG 96RM-E power analyser (Ethernet, Modbus TCP / RTU)
UMG 96RM-E from firmware 3.01 / hardware release 104, per address list 1.040.085.8.n (06/2024).
Also known as: UMG96RM-E, UMG 96 RM-E, UMG96RME, Janitza UMG96RM-E
Other power & energy meters register maps
- Sensor (ultrasonic flowmeter)
KROHNE UFC 400 ultrasonic flow converter (Modbus RTU)
UFC 400 signal converter with Modbus, electronic revision ER 2.2.0_, Modbus version 2.1.0_, supplementary instructions 4002744801 R01 (05/2013).
Also known as: UFC400, KROHNE UFC 400, UFC 400 Modbus - Power meter (panel network parameter meter)
Lumel ND20LITE network parameter meter
Lumel ND20LITE 96x96 panel meter with RS-485 Modbus RTU (not the ND20 or ND20CT, which have their own maps).
Also known as: ND20LITE - Energy meter
Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC)
Measurlogic DTS AC and DC sub-meters and transducers with Modbus RTU or Modbus TCP, per DTS Modbus Map version 2.7U (Oct 2012). Registers depend on model and wiring.
Also known as: DTS 101, DTS 105, DTS 305, DTS 310, DTS SMX, DTS SKT, DTS DC - Energy meter
Panasonic KW7M Eco-POWER METER
Panasonic KW7M (AKW7111 / AKW7111B) with Modbus RTU selected, user manual ARCT1F434E-6.
Also known as: AKW7111, AKW7111B - Sensor (counter / rate panel meter)
Red Lion PAXI counter / rate panel meter (Modbus)
PAXI counter/rate meters with a Modbus serial card, per register table LP0897A (revised 7/10/12).
Also known as: PAXI, PAX I, Red Lion PAXI counter - Energy meter
Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters
Rishabh RISH ED11XX (direct), EC11XX (CT) and ER11XX (RJ12 CT) single-phase DIN-rail meters in their Modbus (x1) versions, per operating manual DMAN-00IM-1071 Rev. M.
Also known as: RISH ED11X1, RISH EC11X1, RISH ER11X1, ED1111, EC1111, ER1111, RISH ED11XX, RISH EC11XX, RISH ER11XX
All power & energy meters Modbus register maps →
Source: Power Quality Analyser UMG 511 - Modbus-address and Formulary · 1.037.021.9.g · rev. 2021-05 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.