Power meter (power quality analyser) · Modbus register map

Janitza UMG 511 power quality analyser (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The UMG 511 is Janitza's power quality analyser. As a Modbus slave it serves its whole address list as big-endian values that include the CT/VT ratios. This map covers the 19000-19120 'frequently required readings' block (voltages, currents, powers, CosPhi, frequency, energies, THD), system time, internal temperature and the energy-reset commands.

This page lists 65 Modbus registers for the Janitza UMG 511 power quality analyser (Modbus RTU) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Janitza’s own free documentation (linked below) and checked against it.

Manufacturer
Janitza
Model
UMG 511 power quality analyser (Modbus RTU)
Equipment type
Power meter (power quality analyser)
Registers
65 (2 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N2
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
UMG511, UMG 511, Janitza UMG511
Source document
Power Quality Analyser UMG 511 - Modbus-address and Formulary · 1.037.021.9.g · rev. 2021-05 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Janitza UMG 511 power quality analyser (Modbus RTU)

Integration in brief

Read holding registers from 19000 (function 03): 122 registers give volts, amps, powers, CosPhi, frequency, energies and THD as big-endian floats.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 19000Voltage L1-NFLOAT32 ABCDVoltage L1-NRead
HR 19012Apparent current, L1-NFLOAT32 ABCDCurrent L1Read
HR 19026Real power sum L1-L3FLOAT32 ABCDTotal real powerRead
HR 19050Measured frequencyFLOAT32 ABCDFrequencyRead
HR 19060Real energy L1..L3FLOAT32 ABCDReal energy L1-L3Read
HR 19076Real energy L1..L3, deliveredFLOAT32 ABCDDelivered real energy L1-L3Read

Enable Modbus control & writes

Set the RS-485 Modbus address and baud rate on the device; the list gives no enable step.

Byte order & addressing

Network setup

Watch out for

Janitza UMG 511 power quality analyser (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

65 of 65 shown
Janitza UMG 511 power quality analyser (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR4System time (UTC)Seconds, UTC.INT32ABCDsRead
HR4209Internal temperatureFLOAT32ABCD°CRead
HR6708Digital output 1 statusINT16Read0 = Not active; 1 = Active
HR6741Delete real energy countersWrite 1 to clear all real energy counters.INT16Read/write
HR6742Delete reactive energy countersWrite 1 to clear all reactive energy counters.INT16Read/write
HR19000Voltage L1-NFLOAT32ABCDVRead
HR19002Voltage L2-NFLOAT32ABCDVRead
HR19004Voltage L3-NFLOAT32ABCDVRead
HR19006Voltage L1-L2FLOAT32ABCDVRead
HR19008Voltage L2-L3FLOAT32ABCDVRead
HR19010Voltage L3-L1FLOAT32ABCDVRead
HR19012Apparent current, L1-NFLOAT32ABCDARead
HR19014Apparent current, L2-NFLOAT32ABCDARead
HR19016Apparent current, L3-NFLOAT32ABCDARead
HR19018Neutral current (vector sum I1+I2+I3)FLOAT32ABCDARead
HR19020Real power L1-NFLOAT32ABCDWRead
HR19022Real power L2-NFLOAT32ABCDWRead
HR19024Real power L3-NFLOAT32ABCDWRead
HR19026Real power sum L1-L3FLOAT32ABCDWRead
HR19028Apparent power L1-NFLOAT32ABCDVARead
HR19030Apparent power L2-NFLOAT32ABCDVARead
HR19032Apparent power L3-NFLOAT32ABCDVARead
HR19034Apparent power sum L1-L3FLOAT32ABCDVARead
HR19036Reactive power L1 (fundamental comp.)FLOAT32ABCDvarRead
HR19038Reactive power L2 (fundamental comp.)FLOAT32ABCDvarRead
HR19040Reactive power L3 (fundamental comp.)FLOAT32ABCDvarRead
HR19042Reactive power sum L1-L3 (fundamental comp.)FLOAT32ABCDvarRead
HR19044CosPhi; UL1 IL1 (fundamental comp.)FLOAT32ABCDRead
HR19046CosPhi; UL2 IL2 (fundamental comp.)FLOAT32ABCDRead
HR19048CosPhi; UL3 IL3 (fundamental comp.)FLOAT32ABCDRead
HR19050Measured frequencyFLOAT32ABCDHzRead
HR19052Rotation field; 1=right, 0=none, -1=leftFloat: 1 = clockwise, 0 = none, -1 = anticlockwise.FLOAT32ABCDRead
HR19054Real energy L1FLOAT32ABCDWhRead
HR19056Real energy L2FLOAT32ABCDWhRead
HR19058Real energy L3FLOAT32ABCDWhRead
HR19060Real energy L1..L3FLOAT32ABCDWhRead
HR19062Real energy L1, consumedFLOAT32ABCDWhRead
HR19064Real energy L2, consumedFLOAT32ABCDWhRead
HR19066Real energy L3, consumedFLOAT32ABCDWhRead
HR19070Real energy L1, deliveredFLOAT32ABCDWhRead
HR19072Real energy L2, deliveredFLOAT32ABCDWhRead
HR19074Real energy L3, deliveredFLOAT32ABCDWhRead
HR19076Real energy L1..L3, deliveredFLOAT32ABCDWhRead
HR19078Apparent energy L1FLOAT32ABCDVAhRead
HR19080Apparent energy L2FLOAT32ABCDVAhRead
HR19082Apparent energy L3FLOAT32ABCDVAhRead
HR19084Apparent energy L1..L3FLOAT32ABCDVAhRead
HR19086Reactive energy L1 (fundamental comp.)FLOAT32ABCDvarhRead
HR19088Reactive energy L2 (fundamental comp.)FLOAT32ABCDvarhRead
HR19090Reactive energy L3 (fundamental comp.)FLOAT32ABCDvarhRead
HR19092Reactive energy L1..L3 (fundamental comp.)FLOAT32ABCDvarhRead
HR19094Reactive energy, inductive, L1 (fundamental comp.)FLOAT32ABCDvarhRead
HR19096Reactive energy, inductive, L2 (fundamental comp.)FLOAT32ABCDvarhRead
HR19098Reactive energy, inductive, L3 (fundamental comp.)FLOAT32ABCDvarhRead
HR19100Reactive energy L1..L3, ind. (fundamental comp.)FLOAT32ABCDvarhRead
HR19102Reactive energy, capacitive, L1 (fundamental comp.)FLOAT32ABCDvarhRead
HR19104Reactive energy, capacitive, L2 (fundamental comp.)FLOAT32ABCDvarhRead
HR19106Reactive energy, capacitive, L3 (fundamental comp.)FLOAT32ABCDvarhRead
HR19108Reactive energy L1..L3, cap. (fundamental comp.)FLOAT32ABCDvarhRead
HR19110Harmonic, THD,U L1-NFLOAT32ABCD%Read
HR19112Harmonic, THD,U L2-NFLOAT32ABCD%Read
HR19114Harmonic, THD,U L3-NFLOAT32ABCD%Read
HR19116Harmonic, THD,I L1FLOAT32ABCD%Read
HR19118Harmonic, THD,I L2FLOAT32ABCD%Read
HR19120Harmonic, THD,I L3FLOAT32ABCD%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Janitza UMG 511 power quality analyser (Modbus RTU)

What Modbus registers does the Janitza UMG 511 power quality analyser (Modbus RTU) have?

This map lists 65 registers: 65 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Janitza UMG 511 power quality analyser (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as the protocol address and sent unchanged: 19000 is requested as 19000. The date/time list starts at address 0 (_REALTIME), which only fits 0-based numbering. In a 1-based or Modicon tool enter 19001 / 419001.

What byte order does the Janitza UMG 511 power quality analyser (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Janitza UMG 511 power quality analyser (Modbus RTU)?

Start with HR 19000 Voltage L1-N (Voltage L1-N); HR 19012 Apparent current, L1-N (Current L1); HR 19026 Real power sum L1-L3 (Total real power); HR 19050 Measured frequency (Frequency); HR 19060 Real energy L1..L3 (Real energy L1-L3); HR 19076 Real energy L1..L3, delivered (Delivered real energy L1-L3).

How do I enable Modbus control of the Janitza UMG 511 power quality analyser (Modbus RTU)?

Set the RS-485 Modbus address and baud rate on the device; the list gives no enable step.

Where is the official Janitza UMG 511 power quality analyser (Modbus RTU) Modbus documentation?

The source is Power Quality Analyser UMG 511 - Modbus-address and Formulary (1.037.021.9.g), revision 2021-05. Janitza doesn't publish it on its own website, so this map was re-typed from a free copy at https://shop.fortop.co.uk/files/umg511fortopjanitzamodbusaddressliste1295013212757.pdf. It may be an older revision, so check it against the live unit.