- UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP)
Power meter (power quality analyser) · Modbus register map
Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP) Modbus register map
Updated 17 November 2026
The UMG 604 is a Janitza power quality analyser. Its address list serves measurements as big-endian 32-bit floats; the 19000-19120 'frequently required readings' block holds volts, amps, power, CosPhi, frequency, energy and THD. This map covers that block plus the fourth channel, energy totals, digital I/O, energy resets, transformer settings and identity/network values.
This page lists 75 Modbus registers for the Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Janitza’s own free documentation (linked below) and checked against it.
- Manufacturer
- Janitza
- Model
- UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP)
- Equipment type
- Power meter (power quality analyser)
- Registers
- 75 (4 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Release 2.x and higher
- Also known as
- UMG604, UMG 604-E, UMG 604-EP, Janitza UMG 604 (non-PRO)
Integration notes: Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP)
Read holding registers (function 03) from 19000: the 122-register block gives volts, amps, power, CosPhi, frequency and energy as big-endian floats. Read 9851 and 9863 for consumed and delivered real energy totals.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 19000 | Voltage L1-N | FLOAT32 ABCD | Voltage L1-N | Read |
| HR 19012 | Current L1 | FLOAT32 ABCD | Current L1 | Read |
| HR 19026 | Real power total L1-L3 | FLOAT32 ABCD | Total real power | Read |
| HR 19034 | Apparent power total L1-L3 | FLOAT32 ABCD | Total apparent power | Read |
| HR 19050 | Frequency | FLOAT32 ABCD | Frequency | Read |
| HR 9851 | Real energy L1-L3, consumed | FLOAT32 ABCD | Consumed energy total | Read |
| HR 9863 | Real energy L1-L3, delivered (9863 block) | FLOAT32 ABCD | Delivered energy total | Read |
| HR 19044 | CosPhi L1 (fundamental) | FLOAT32 ABCD | CosPhi L1 | Read |
Enable Modbus control & writes
The list holds the Modbus address at 10180 and IP settings at 10190-10194 (read-only here); set them on the device.
Byte order & addressing
- Addresses are used as printed (0-based).
- Floats are ABCD; add 32768 to an address for little-endian.
- Energy is in Wh and varh, not kWh.
- Rotation field (19052) is a float: 1, 0 or -1.
Network setup
- RS-485: 8 data bits, no parity, the device sends 2 stop bits.
- Write 1 to 9997 to clear real/apparent energy, 9998 for reactive energy.
- CT and VT ratios are at 10032-10056 (read-only here); set them on the device.
Watch out for
- 19068 is tariff 1 only; use 9851 for the consumed total.
Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1323 | Voltage L4-N | Fourth voltage input. | FLOAT32 | ABCD | V | Read | ||
| HR | 1331 | Current L4 | Fourth current input. | FLOAT32 | ABCD | A | Read | ||
| HR | 1461 | Temperature input | Value of the external temperature sensor input. | FLOAT32 | ABCD | °C | Read | ||
| HR | 9827 | Real energy L1-L3 (9827 block) | Real energy L1+L2+L3 from the main energy block. | FLOAT32 | ABCD | Wh | Read | ||
| HR | 9839 | Reactive energy L1-L3 (9839 block) | FLOAT32 | ABCD | varh | Read | |||
| HR | 9851 | Real energy L1-L3, consumed | Three-phase consumed (import) energy total. | FLOAT32 | ABCD | Wh | Read | ||
| HR | 9863 | Real energy L1-L3, delivered (9863 block) | FLOAT32 | ABCD | Wh | Read | |||
| HR | 9973 | Digital output 1 status | Marked read/write in the list. | INT16 | Read/write | ||||
| HR | 9974 | Digital output 2 status | Marked read/write in the list. | INT16 | Read/write | ||||
| HR | 9975 | Digital input 1 status | INT16 | Read | |||||
| HR | 9976 | Digital input 2 status | INT16 | Read | |||||
| HR | 9997 | Delete real and apparent energy | Write 1 to clear all real and apparent energy counters. | INT16 | Write | ||||
| HR | 9998 | Delete reactive energy | Write 1 to clear all reactive energy counters. | INT16 | Write | ||||
| HR | 10032 | CT primary L1 | Current transformer primary setting. | FLOAT32 | ABCD | A | Read | ||
| HR | 10034 | CT primary L2 | Current transformer primary setting. | FLOAT32 | ABCD | A | Read | ||
| HR | 10036 | CT primary L3 | Current transformer primary setting. | FLOAT32 | ABCD | A | Read | ||
| HR | 10040 | CT secondary L1 | Current transformer secondary setting. | FLOAT32 | ABCD | A | Read | ||
| HR | 10042 | CT secondary L2 | Current transformer secondary setting. | FLOAT32 | ABCD | A | Read | ||
| HR | 10044 | CT secondary L3 | Current transformer secondary setting. | FLOAT32 | ABCD | A | Read | ||
| HR | 10048 | VT primary L1 | Voltage transformer primary setting. | FLOAT32 | ABCD | V | Read | ||
| HR | 10056 | VT secondary L1 | Voltage transformer secondary setting. | FLOAT32 | ABCD | V | Read | ||
| HR | 10176 | Serial number | UINT32 | ABCD | Read | ||||
| HR | 10180 | Modbus address | RS-485 slave address. | INT32 | ABCD | Read | |||
| HR | 10190 | IP address | Packed 32-bit IPv4 address. | UINT32 | ABCD | Read | |||
| HR | 10192 | Subnet mask | Packed 32-bit IPv4 mask. | UINT32 | ABCD | Read | |||
| HR | 10194 | Gateway address | Packed 32-bit IPv4 gateway. | UINT32 | ABCD | Read | |||
| HR | 13437 | Firmware release | Text, 16 characters (8 registers). | STRING[16] | Read | ||||
| HR | 19000 | Voltage L1-N | FLOAT32 | ABCD | V | Read | |||
| HR | 19002 | Voltage L2-N | FLOAT32 | ABCD | V | Read | |||
| HR | 19004 | Voltage L3-N | FLOAT32 | ABCD | V | Read | |||
| HR | 19006 | Voltage L1-L2 | FLOAT32 | ABCD | V | Read | |||
| HR | 19008 | Voltage L2-L3 | FLOAT32 | ABCD | V | Read | |||
| HR | 19010 | Voltage L3-L1 | FLOAT32 | ABCD | V | Read | |||
| HR | 19012 | Current L1 | FLOAT32 | ABCD | A | Read | |||
| HR | 19014 | Current L2 | FLOAT32 | ABCD | A | Read | |||
| HR | 19016 | Current L3 | FLOAT32 | ABCD | A | Read | |||
| HR | 19018 | Neutral current (vector sum L1-L3) | Calculated vector sum of the three phase currents. | FLOAT32 | ABCD | A | Read | ||
| HR | 19020 | Real power L1 | FLOAT32 | ABCD | W | Read | |||
| HR | 19022 | Real power L2 | FLOAT32 | ABCD | W | Read | |||
| HR | 19024 | Real power L3 | FLOAT32 | ABCD | W | Read | |||
| HR | 19026 | Real power total L1-L3 | FLOAT32 | ABCD | W | Read | |||
| HR | 19028 | Apparent power L1 | FLOAT32 | ABCD | VA | Read | |||
| HR | 19030 | Apparent power L2 | FLOAT32 | ABCD | VA | Read | |||
| HR | 19032 | Apparent power L3 | FLOAT32 | ABCD | VA | Read | |||
| HR | 19034 | Apparent power total L1-L3 | FLOAT32 | ABCD | VA | Read | |||
| HR | 19036 | Reactive power L1 (fundamental) | FLOAT32 | ABCD | var | Read | |||
| HR | 19038 | Reactive power L2 (fundamental) | FLOAT32 | ABCD | var | Read | |||
| HR | 19040 | Reactive power L3 (fundamental) | FLOAT32 | ABCD | var | Read | |||
| HR | 19042 | Reactive power total L1-L3 (fundamental) | FLOAT32 | ABCD | var | Read | |||
| HR | 19044 | CosPhi L1 (fundamental) | FLOAT32 | ABCD | Read | ||||
| HR | 19046 | CosPhi L2 (fundamental) | FLOAT32 | ABCD | Read | ||||
| HR | 19048 | CosPhi L3 (fundamental) | FLOAT32 | ABCD | Read | ||||
| HR | 19050 | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 19052 | Rotation field | Float: 1 = clockwise, 0 = none, -1 = anticlockwise. | FLOAT32 | ABCD | Read | |||
| HR | 19054 | Real energy L1 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19056 | Real energy L2 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19058 | Real energy L3 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19060 | Real energy L1-L3 | Three-phase total, not split into consumed and delivered. | FLOAT32 | ABCD | Wh | Read | ||
| HR | 19062 | Real energy L1, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19064 | Real energy L2, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19066 | Real energy L3, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19070 | Real energy L1, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19072 | Real energy L2, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19074 | Real energy L3, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19076 | Real energy L1-L3, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19084 | Apparent energy L1-L3 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 19092 | Reactive energy L1-L3 (fundamental) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19100 | Reactive energy inductive L1-L3 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19108 | Reactive energy capacitive L1-L3 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19110 | THD voltage L1-N | FLOAT32 | ABCD | % | Read | |||
| HR | 19112 | THD voltage L2-N | FLOAT32 | ABCD | % | Read | |||
| HR | 19114 | THD voltage L3-N | FLOAT32 | ABCD | % | Read | |||
| HR | 19116 | THD current L1 | FLOAT32 | ABCD | % | Read | |||
| HR | 19118 | THD current L2 | FLOAT32 | ABCD | % | Read | |||
| HR | 19120 | THD current L3 | FLOAT32 | ABCD | % | Read |
Notes on this map
- Word order: the list says every address in it supplies its data big-endian (high byte before low byte), with a separate little-endian copy at address + 32768. That defines the format of the 32-bit values themselves, so the high word is in the lower register: ABCD.
- Data types in the list: short = signed 16-bit, int = signed 32-bit, uint = unsigned 32-bit, float = IEEE 754 32-bit, long64 = signed 64-bit.
- Left out: 19068 (consumed L1-L3, tariff 1 only). The consumed and delivered totals are at 9851 and 9863.
- Left out: harmonics, min/max/mean blocks, events and transients, logging, tariffs and peak values; baud rate and RS-485/RS-232 mode rows (10182-10188) because the list gives no value coding.
- The list has no read/write column. Only rows the list marks as writable (digital outputs 'r/w', delete commands '=1') get write access; CT/VT and network rows are listed read-only although they are device settings.
- Transfer parameters (p. 5): 9.6-921.6 kbps, 8 data bits, no parity, the UMG 604 sends 2 stop bits. The list gives no default address, baud rate or TCP port.
- Every row kept here sits at the same address in the Janitza UMG 604-PRO address list (also in this library); the PRO-only average-PF and transformer-lock rows are not in this list.
- Left out: 1373 (_COS_SUM3). The list describes it only as 'Sum CosL1 + CosL2 + CosL3', so it is unclear whether it is a total power factor or a plain sum.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP)
What Modbus registers does the Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP) have?
This map lists 75 registers: 75 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as the protocol address and sent unchanged: 19000 is requested as 19000. The list starts at address 0 (_REALTIME), which only fits 0-based numbering. In a 1-based or Modicon tool enter 19001 / 419001.
What byte order does the Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP)?
Start with HR 19000 Voltage L1-N (Voltage L1-N); HR 19012 Current L1 (Current L1); HR 19026 Real power total L1-L3 (Total real power); HR 19034 Apparent power total L1-L3 (Total apparent power); HR 19050 Frequency (Frequency); HR 9851 Real energy L1-L3, consumed (Consumed energy total); HR 9863 Real energy L1-L3, delivered (9863 block) (Delivered energy total); HR 19044 CosPhi L1 (fundamental) (CosPhi L1).
How do I enable Modbus control of the Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP)?
The list holds the Modbus address at 10180 and IP settings at 10190-10194 (read-only here); set them on the device.
Where is the official Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP) Modbus documentation?
The source is Power Analyser UMG 604 - Modbus-address and Formulary (firmware release 2.x) (1.033.033.g), published free by Janitza at https://www.janitza.com/files/download/manuals/current/UMG604/janitza-mal-umg604-en.pdf.
More Janitza Modbus register maps
- Power meter (power analyser)
Janitza UMG 104 power analyser (RS-485 Modbus RTU)
UMG 104 DIN-rail power analyser, firmware 1.268, per address list 1.041.006.1.e (01/2023).
Also known as: UMG104, UMG 104, Janitza UMG104 - Power meter (power analyser)
Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP)
UMG 508 power analyser from firmware release 2.x, per Modbus address list 1.042.008.9.b (08/2022).
Also known as: UMG508, UMG 508, Janitza UMG508 - Power meter (power analyser)
Janitza UMG 509 power analyser (Modbus RTU)
UMG 509 (the original, non-PRO model), per Modbus address list 1.059.004.2.d. For the UMG 509-PRO use its own map.
Also known as: UMG509, UMG 509, Janitza UMG509 - Power meter (power quality analyser)
Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 509-PRO per Modbus address list 1.059.004.2.n (06/2024).
Also known as: UMG509-PRO, UMG 509PRO, UMG509PRO, Janitza UMG 509 - Power meter (power quality analyser)
Janitza UMG 511 power quality analyser (Modbus RTU)
UMG 511 per Modbus address list 1.037.021.9.g (05/2021).
Also known as: UMG511, UMG 511, Janitza UMG511 - Power meter (power quality analyser)
Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 512-PRO power quality analyser, per address list 1.054.016.3.k (08/2023).
Also known as: UMG512-PRO, UMG 512, UMG512, UMG 512 PRO, Janitza UMG512-PRO - Power meter (power quality analyser)
Janitza UMG 604-PRO power analyser (Modbus RTU / Modbus TCP)
UMG 604-PRO from firmware release 5.028, per address list 1.033.034.e (08/2023).
Also known as: UMG604-PRO, UMG 604PRO, UMG604PRO, UMG 604-EP PRO, Janitza UMG 604 - Power meter (power analyser)
Janitza UMG 605 power quality analyser (Modbus RTU)
UMG 605 (the original, non-PRO model), per Modbus address list 1.038.009.7.a. For the UMG 605-PRO use its own map.
Also known as: UMG605, UMG 605, Janitza UMG605 - Power meter (power quality analyser)
Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 605-PRO from firmware release 5.028, per address list 1.038.009.7.h (09/2022).
Also known as: UMG605-PRO, UMG 605PRO, UMG605PRO, Janitza UMG 605 - Power meter (energy analyser)
Janitza UMG 96-S2 energy analyser (serial Modbus)
UMG 96-S2 energy analyser, per address list 2.062.026.1.b (10/2019).
Also known as: UMG96-S2, UMG 96 S2, UMG96S2, Janitza UMG96-S2 - Power meter (power analyser)
Janitza UMG 96RM power analyser (basic device, RS-485 Modbus RTU)
UMG 96RM basic device from firmware release 1.14, per address list 1.040.034.t; the same list covers the shared registers of the -P, -CBM and -PN extensions. Other UMG 96RM variants (e.g. the Ethernet -E / -EL) are not covered by this list.
Also known as: UMG96RM, UMG 96 RM, UMG 96RM-P, UMG 96RM-CBM, UMG 96RM-PN, Janitza UMG96RM - Power meter (power analyser)
Janitza UMG 96RM-E power analyser (Ethernet, Modbus TCP / RTU)
UMG 96RM-E from firmware 3.01 / hardware release 104, per address list 1.040.085.8.n (06/2024).
Also known as: UMG96RM-E, UMG 96 RM-E, UMG96RME, Janitza UMG96RM-E
Other power & energy meters register maps
- Energy meter
KEBA KeContact E10 smart energy meter (Modbus)
KEBA KeContact E10 energy meter (companion meter for KeContact wallboxes and PV home systems), register list v1.00 (03.2024).
Also known as: E10, KEBA E10, KeContact E10 - Energy meter
Legrand Energy meter 4 120 68 (RS-485 Modbus)
Legrand energy meter cat. no. 4 120 68 with RS-485 Modbus RTU, per Modbus table F02230EN-01.
Also known as: 412068, 4 120 68, Legrand 412068 - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID08 / NMID09 / NMID10 single-phase energy meter
Modbus RTU versions of the NMID08 (1/5 A CT), NMID09 (100 mA CT) and NMID10 (100 A direct) meters; the LITE and MBUS versions have no Modbus port.
Also known as: NMID08, NMID09, NMID10 - Energy meter
Northern Design Cube 300 panel kWh meter (Modbus RTU option)
Cube300 meters fitted with the RS-485 Modbus option, per the October 2005 Modbus Communications manual.
Also known as: Cube300, ND Cube 300, Northern Design Cube300 - Energy meter (multi-circuit power monitor)
Panasonic KW9M Eco-POWER METER
Panasonic KW9M (AKW91110) with the Modbus RTU protocol selected, user manual WUME-KW9M-10.
Also known as: AKW91110 - Energy meter
Rishabh Instruments RISH Delta Energy NX multifunction energy meter
Rishabh RISH Delta Energy NX panel energy meters with RS-485 Modbus RTU, per the operating manual on the product page (standard CT version).
Also known as: RISH Delta Energy NX, Delta Energy NX, RISH Delta Energy
All power & energy meters Modbus register maps →
Source: Power Analyser UMG 604 - Modbus-address and Formulary (firmware release 2.x) · 1.033.033.g. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.