KEBA KeContact E10 smart energy meter (Modbus) Modbus register map

Updated 17 November 2026

Short answer

The KeContact E10 is KEBA's three-phase smart energy meter for home energy management with its wallboxes. It answers Modbus with holding registers only: instantaneous power, current, voltage, power factor and frequency, 64-bit energy counters per phase, a fast block for current/voltage/power, a plug-and-play identity block, a SunSpec common + meter (203) model, and a few configuration, identify and restart registers.

This page lists 184 Modbus registers for the KEBA KeContact E10 smart energy meter (Modbus) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KEBA’s own free documentation (linked below) and checked against it.

Manufacturer
KEBA
Model
KeContact E10 smart energy meter (Modbus)
Equipment type
Energy meter
Registers
184 (17 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
E10, KEBA E10, KeContact E10
Source document
KeContact E10 - Modbus Register List · 132941/00 v1.00 · rev. 2024-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: KEBA KeContact E10 smart energy meter (Modbus)

Integration in brief

Read the 64-bit energy counters at 512 (import) and 516 (export) and the per-phase power/current/voltage block 0-147, or use the SunSpec meter model at 40070 if your system speaks SunSpec. All values are big-endian, high word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Active power+UINT32 ABCDActive power import (total)Read
HR 2Active power-UINT32 ABCDActive power export (total)Read
HR 60Current (L1)UINT32 ABCDCurrent L1Read
HR 62Voltage (L1)UINT32 ABCDVoltage L1Read
HR 26Supply frequencyUINT32 ABCDFrequencyRead
HR 512Active energy+UINT64 ABCDActive energy importRead
HR 516Active energy-UINT64 ABCDActive energy exportRead

Enable Modbus control & writes

Modbus RTU baud rate is set in register 258 (0 = 9600 ... 5 = 115200). IP address, subnet mask and DHCP are in registers 259-267 and take effect after a restart.

Byte order & addressing

Network setup

Watch out for

KEBA KeContact E10 smart energy meter (Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

184 of 184 shown
KEBA KeContact E10 smart energy meter (Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0Active power+OBIS 1-0:1.4.0*255.UINT32ABCD× 0.1WRead
HR2Active power-OBIS 1-0:2.4.0*255.UINT32ABCD× 0.1WRead
HR4Reactive power+OBIS 1-0:3.4.0*255.UINT32ABCD× 0.1varRead
HR6Reactive power-OBIS 1-0:4.4.0*255.UINT32ABCD× 0.1varRead
HR16Apparent power+OBIS 1-0:9.4.0*255.UINT32ABCD× 0.1VARead
HR18Apparent power-OBIS 1-0:10.4.0*255.UINT32ABCD× 0.1VARead
HR24Power factorOBIS 1-0:13.4.0*255.INT32ABCD× 0.001Read
HR26Supply frequencyOBIS 1-0:14.4.0*255.UINT32ABCD× 0.001HzRead
HR40Active power+ (L1)OBIS 1-0:21.4.0*255.UINT32ABCD× 0.1WRead
HR42Active power- (L1)OBIS 1-0:22.4.0*255.UINT32ABCD× 0.1WRead
HR44Reactive power+ (L1)OBIS 1-0:23.4.0*255.UINT32ABCD× 0.1varRead
HR46Reactive power- (L1)OBIS 1-0:24.4.0*255.UINT32ABCD× 0.1varRead
HR56Apparent power+ (L1)OBIS 1-0:29.4.0*255.UINT32ABCD× 0.1VARead
HR58Apparent power- (L1)OBIS 1-0:30.4.0*255.UINT32ABCD× 0.1VARead
HR60Current (L1)OBIS 1-0:31.4.0*255.UINT32ABCD× 0.001ARead
HR62Voltage (L1)OBIS 1-0:32.4.0*255.UINT32ABCD× 0.001VRead
HR64Power factor (L1)OBIS 1-0:33.4.0*255.INT32ABCD× 0.001Read
HR80Active power+ (L2)OBIS 1-0:41.4.0*255.UINT32ABCD× 0.1WRead
HR82Active power- (L2)OBIS 1-0:42.4.0*255.UINT32ABCD× 0.1WRead
HR84Reactive power+ (L2)OBIS 1-0:43.4.0*255.UINT32ABCD× 0.1varRead
HR86Reactive power- (L2)OBIS 1-0:44.4.0*255.UINT32ABCD× 0.1varRead
HR96Apparent power+ (L2)OBIS 1-0:49.4.0*255.UINT32ABCD× 0.1VARead
HR98Apparent power- (L2)OBIS 1-0:50.4.0*255.UINT32ABCD× 0.1VARead
HR100Current (L2)OBIS 1-0:51.4.0*255.UINT32ABCD× 0.001ARead
HR102Voltage (L2)OBIS 1-0:52.4.0*255.UINT32ABCD× 0.001VRead
HR104Power factor (L2)OBIS 1-0:53.4.0*255.INT32ABCD× 0.001Read
HR120Active power+ (L3)OBIS 1-0:61.4.0*255.UINT32ABCD× 0.1WRead
HR122Active power- (L3)OBIS 1-0:62.4.0*255.UINT32ABCD× 0.1WRead
HR124Reactive power+ (L3)OBIS 1-0:63.4.0*255.UINT32ABCD× 0.1varRead
HR126Reactive power- (L3)OBIS 1-0:64.4.0*255.UINT32ABCD× 0.1varRead
HR136Apparent power+ (L3)OBIS 1-0:69.4.0*255.UINT32ABCD× 0.1VARead
HR138Apparent power- (L3)OBIS 1-0:70.4.0*255.UINT32ABCD× 0.1VARead
HR140Current (L3)OBIS 1-0:71.4.0*255.UINT32ABCD× 0.001ARead
HR142Voltage (L3)OBIS 1-0:72.4.0*255.UINT32ABCD× 0.001VRead
HR144Power factor (L3)OBIS 1-0:73.4.0*255.INT32ABCD× 0.001Read
HR146Minimum active power+ * 3Three times the minimum active power+ (as named in the list).UINT32ABCD× 0.1WRead
HR256Measuring IntervalUINT16Read/write0 = 20 ms; 1 = 100 ms; 2 = 200 ms; 3 = 500 ms; 4 = 1000 ms
HR257Current transformer typeUINT16Read/write0 = XH-SCT-10; 1 = XH-SCT-16; 2 = XH-SCT-24; 3 = EB103
HR258Modbus RTU baud rateUINT16Read/write0 = 9600 Bd; 1 = 14400 Bd; 2 = 19200 Bd; 3 = 38400 Bd; 4 = 57600 Bd; 5 = 115200 Bd
HR259Static IP Address octet 1One octet per register; active after restart.UINT16Read/write
HR260Static IP Address octet 2One octet per register; active after restart.UINT16Read/write
HR261Static IP Address octet 3One octet per register; active after restart.UINT16Read/write
HR262Static IP Address octet 4One octet per register; active after restart.UINT16Read/write
HR263Subnet Mask octet 1One octet per register; active after restart.UINT16Read/write
HR264Subnet Mask octet 2One octet per register; active after restart.UINT16Read/write
HR265Subnet Mask octet 3One octet per register; active after restart.UINT16Read/write
HR266Subnet Mask octet 4One octet per register; active after restart.UINT16Read/write
HR267DHCP on/offActive after restart.UINT16Read/write0 = Disable DHCP; 1 = Enable DHCP
HR268Activate Read OnlyWrite 1 to lock all configuration and restart registers.UINT16Read/write
HR512Active energy+OBIS 1-0:1.8.0*255.UINT64ABCD× 0.1WhRead
HR516Active energy-OBIS 1-0:2.8.0*255.UINT64ABCD× 0.1WhRead
HR520Reactive energy+OBIS 1-0:3.8.0*255.UINT64ABCD× 0.1varhRead
HR524Reactive energy-OBIS 1-0:4.8.0*255.UINT64ABCD× 0.1varhRead
HR544Apparent energy+OBIS 1-0:9.8.0*255.UINT64ABCD× 0.1VAhRead
HR548Apparent energy-OBIS 1-0:10.8.0*255.UINT64ABCD× 0.1VAhRead
HR592Active energy+ (L1)OBIS 1-0:21.8.0*255.UINT64ABCD× 0.1WhRead
HR596Active energy- (L1)OBIS 1-0:22.8.0*255.UINT64ABCD× 0.1WhRead
HR600Reactive energy+ (L1)OBIS 1-0:23.8.0*255.UINT64ABCD× 0.1varhRead
HR604Reactive energy- (L1)OBIS 1-0:24.8.0*255.UINT64ABCD× 0.1varhRead
HR624Apparent energy+ (L1)OBIS 1-0:29.8.0*255.UINT64ABCD× 0.1VAhRead
HR628Apparent energy- (L1)OBIS 1-0:30.8.0*255.UINT64ABCD× 0.1VAhRead
HR672Active energy+ (L2)OBIS 1-0:41.8.0*255.UINT64ABCD× 0.1WhRead
HR676Active energy- (L2)OBIS 1-0:42.8.0*255.UINT64ABCD× 0.1WhRead
HR680Reactive energy+ (L2)OBIS 1-0:43.8.0*255.UINT64ABCD× 0.1varhRead
HR684Reactive energy- (L2)OBIS 1-0:44.8.0*255.UINT64ABCD× 0.1varhRead
HR704Apparent energy+ (L2)OBIS 1-0:49.8.0*255.UINT64ABCD× 0.1VAhRead
HR708Apparent energy- (L2)OBIS 1-0:50.8.0*255.UINT64ABCD× 0.1VAhRead
HR752Active energy+ (L3)OBIS 1-0:61.8.0*255.UINT64ABCD× 0.1WhRead
HR756Active energy- (L3)OBIS 1-0:62.8.0*255.UINT64ABCD× 0.1WhRead
HR760Reactive energy+ (L3)OBIS 1-0:63.8.0*255.UINT64ABCD× 0.1varhRead
HR764Reactive energy- (L3)OBIS 1-0:64.8.0*255.UINT64ABCD× 0.1varhRead
HR784Apparent energy+ (L3)OBIS 1-0:69.8.0*255.UINT64ABCD× 0.1VAhRead
HR788Apparent energy- (L3)OBIS 1-0:70.8.0*255.UINT64ABCD× 0.1VAhRead
HR8192ManufacturerIDFixed value 0x5233.UINT16Read
HR8193ProductIDHardware type code (SU103/SU106 variants).UINT16Read1 = SU103 R; 2 = SU103 L; 3 = SU103 LR; 17 = SU106 R; 18 = SU106 L; 19 = SU106 LR
HR8194ProductVersionHardware revision, e.g. 0x0103 = 1.3.x.UINT16Read
HR8195FirmwareVersionFirmware revision, e.g. 0x0103 = 1.3.x.UINT16Read
HR8196VendorName32 characters, NUL padded.STRING[32]Read
HR8212ProductName32 characters, NUL padded.STRING[32]Read
HR8228SerialNumber32 characters, NUL padded.STRING[32]Read
HR8244MeasuringIntervalMeasuring interval in ms.UINT16msRead
HR8245SubSwVersionPatch level and release-candidate number.UINT16Read
HR40000C_SunSpec_ID0x53756E53 ('SunS') marks a SunSpec map.UINT32ABCDRead
HR40002C_SunSpec_DIDCommon model: ID 1, length 66.UINT16Read
HR40003C_SunSpec_LengthCommon model: ID 1, length 66.UINT16Read
HR40004C_ManufacturerSunSpec common model text; 16 registers.STRING[32]Read
HR40020C_ModelSunSpec common model text; 16 registers.STRING[32]Read
HR40036C_OptionsSunSpec common model text; 8 registers.STRING[16]Read
HR40044C_VersionSunSpec common model text; 8 registers.STRING[16]Read
HR40052C_SerialNumberSunSpec common model text; 16 registers.STRING[32]Read
HR40068C_DeviceAddressModbus unit ID.UINT16Read
HR40070C_SunSpec_DIDMeter model ID 203.UINT16Read
HR40071C_SunSpec_LengthMeter model length 105.UINT16Read
HR40072M_AC_CurrentINT16× 10^SF (HR 40076)ARead
HR40073M_AC_Current_AINT16× 10^SF (HR 40076)ARead
HR40074M_AC_Current_BINT16× 10^SF (HR 40076)ARead
HR40075M_AC_Current_CINT16× 10^SF (HR 40076)ARead
HR40076M_AC_Current_SFPower-of-ten scale factor for the related values.INT16Read
HR40077M_AC_Voltage_LNINT16× 10^SF (HR 40085)VRead
HR40078M_AC_Voltage_ANINT16× 10^SF (HR 40085)VRead
HR40079M_AC_Voltage_BNINT16× 10^SF (HR 40085)VRead
HR40080M_AC_Voltage_CNINT16× 10^SF (HR 40085)VRead
HR40081M_AC_Voltage_LLINT16× 10^SF (HR 40085)VRead
HR40082M_AC_Voltage_ABINT16× 10^SF (HR 40085)VRead
HR40083M_AC_Voltage_BCINT16× 10^SF (HR 40085)VRead
HR40084M_AC_Voltage_CAINT16× 10^SF (HR 40085)VRead
HR40085M_AC_Voltage_SFPower-of-ten scale factor for the related values.INT16Read
HR40086M_AC_FreqINT16× 10^SF (HR 40087)HzRead
HR40087M_AC_Freq_SFPower-of-ten scale factor for the related values.INT16Read
HR40088M_AC_PowerINT16× 10^SF (HR 40092)WRead
HR40089M_AC_Power_AINT16× 10^SF (HR 40092)WRead
HR40090M_AC_Power_BINT16× 10^SF (HR 40092)WRead
HR40091M_AC_Power_CINT16× 10^SF (HR 40092)WRead
HR40092M_AC_Power_SFPower-of-ten scale factor for the related values.INT16Read
HR40093M_AC_VAINT16× 10^SF (HR 40097)VARead
HR40094M_AC_VA_AINT16× 10^SF (HR 40097)VARead
HR40095M_AC_VA_BINT16× 10^SF (HR 40097)VARead
HR40096M_AC_VA_CINT16× 10^SF (HR 40097)VARead
HR40097M_AC_VA_SFPower-of-ten scale factor for the related values.INT16Read
HR40098M_AC_VARINT16× 10^SF (HR 40102)varRead
HR40099M_AC_VAR_AINT16× 10^SF (HR 40102)varRead
HR40100M_AC_VAR_BINT16× 10^SF (HR 40102)varRead
HR40101M_AC_VAR_CINT16× 10^SF (HR 40102)varRead
HR40102M_AC_VAR_SFPower-of-ten scale factor for the related values.INT16Read
HR40103M_AC_PFINT16× 10^SF (HR 40107)%Read
HR40104M_AC_PF_AINT16× 10^SF (HR 40107)%Read
HR40105M_AC_PF_BINT16× 10^SF (HR 40107)%Read
HR40106M_AC_PF_CINT16× 10^SF (HR 40107)%Read
HR40107M_AC_PF_SFPower-of-ten scale factor for the related values.INT16Read
HR40108M_ExportedUINT32ABCD× 10^SF (HR 40124)WhRead
HR40110M_Exported_AUINT32ABCD× 10^SF (HR 40124)WhRead
HR40112M_Exported_BUINT32ABCD× 10^SF (HR 40124)WhRead
HR40114M_Exported_CUINT32ABCD× 10^SF (HR 40124)WhRead
HR40116M_ImportedUINT32ABCD× 10^SF (HR 40124)WhRead
HR40118M_Imported_AUINT32ABCD× 10^SF (HR 40124)WhRead
HR40120M_Imported_BUINT32ABCD× 10^SF (HR 40124)WhRead
HR40122M_Imported_CUINT32ABCD× 10^SF (HR 40124)WhRead
HR40124M_Energy_W_SFPower-of-ten scale factor for the related values.INT16Read
HR40125M_Exported_VAUINT32ABCD× 10^SF (HR 40141)VAhRead
HR40127M_Exported_VA_AUINT32ABCD× 10^SF (HR 40141)VAhRead
HR40129M_Exported_VA_BUINT32ABCD× 10^SF (HR 40141)VAhRead
HR40131M_Exported_VA_CUINT32ABCD× 10^SF (HR 40141)VAhRead
HR40133M_Imported_VAUINT32ABCD× 10^SF (HR 40141)VAhRead
HR40135M_Imported_VA_AUINT32ABCD× 10^SF (HR 40141)VAhRead
HR40137M_Imported_VA_BUINT32ABCD× 10^SF (HR 40141)VAhRead
HR40139M_Imported_VA_CUINT32ABCD× 10^SF (HR 40141)VAhRead
HR40141M_Energy_VA_SFPower-of-ten scale factor for the related values.INT16Read
HR40142M_Import_VARh_Q1UINT32ABCD× 10^SF (HR 40174)VARhRead
HR40144M_Import_VARh_Q1AUINT32ABCD× 10^SF (HR 40174)VARhRead
HR40146M_Import_VARh_Q1BUINT32ABCD× 10^SF (HR 40174)VARhRead
HR40148M_Import_VARh_Q1CUINT32ABCD× 10^SF (HR 40174)VARhRead
HR40150M_Import_VARh_Q2UINT32ABCD× 10^SF (HR 40174)VARhRead
HR40152M_Import_VARh_Q2AUINT32ABCD× 10^SF (HR 40174)VARhRead
HR40154M_Import_VARh_Q2BUINT32ABCD× 10^SF (HR 40174)VARhRead
HR40156M_Import_VARh_Q2CUINT32ABCD× 10^SF (HR 40174)VARhRead
HR40158M_Export_VARh_Q3UINT32ABCD× 10^SF (HR 40174)VARhRead
HR40160M_Export_VARh_Q3AUINT32ABCD× 10^SF (HR 40174)VARhRead
HR40162M_Export_VARh_Q3BUINT32ABCD× 10^SF (HR 40174)VARhRead
HR40164M_Export_VARh_Q3CUINT32ABCD× 10^SF (HR 40174)VARhRead
HR40166M_Export_VARh_Q4UINT32ABCD× 10^SF (HR 40174)VARhRead
HR40168M_Export_VARh_Q4AUINT32ABCD× 10^SF (HR 40174)VARhRead
HR40170M_Export_VARh_Q4BUINT32ABCD× 10^SF (HR 40174)VARhRead
HR40172M_Export_VARh_Q4CUINT32ABCD× 10^SF (HR 40174)VARhRead
HR40174M_Energy_VAR_SFPower-of-ten scale factor for the related values.INT16Read
HR40175M_EventsUINT32ABCDRead
HR40177C_SunSpec_DIDEnd model marker (0xFFFF, length 0).UINT16Read
HR40178C_SunSpec_LengthEnd model marker (0xFFFF, length 0).UINT16Read
HR61440Active power+ (L1) (fast block)OBIS 1-0:21.4.0*255.UINT32ABCD× 0.1WRead
HR61442Active power- (L1) (fast block)OBIS 1-0:22.4.0*255.UINT32ABCD× 0.1WRead
HR61444Current (L1) (fast block)OBIS 1-0:31.4.0*255.UINT32ABCD× 0.001ARead
HR61446Voltage (L1) (fast block)OBIS 1-0:32.4.0*255.UINT32ABCD× 0.001VRead
HR61448Active power+ (L2) (fast block)OBIS 1-0:41.4.0*255.UINT32ABCD× 0.1WRead
HR61450Active power- (L2) (fast block)OBIS 1-0:42.4.0*255.UINT32ABCD× 0.1WRead
HR61452Current (L2) (fast block)OBIS 1-0:51.4.0*255.UINT32ABCD× 0.001ARead
HR61454Voltage (L2) (fast block)OBIS 1-0:52.4.0*255.UINT32ABCD× 0.001VRead
HR61456Active power+ (L3) (fast block)OBIS 1-0:61.4.0*255.UINT32ABCD× 0.1WRead
HR61458Active power- (L3) (fast block)OBIS 1-0:62.4.0*255.UINT32ABCD× 0.1WRead
HR61460Current (L3) (fast block)OBIS 1-0:71.4.0*255.UINT32ABCD× 0.001ARead
HR61462Voltage (L3) (fast block)OBIS 1-0:72.4.0*255.UINT32ABCD× 0.001VRead
HR61464Number of measurements (fast block)Count of measurements taken.UINT64ABCDRead
HR61613Identify: blink frequency100-10000 mHz, default 1000.UINT16mHzRead/write
HR61614Identify: blink durationNon-zero starts the identify blink, 0 stops it (0-600 s).UINT16sRead/write
HR61615RestartWrite 0x1 to restart the meter.UINT16Write
HR61616Start bootloaderWrite 0xA0B1 to start the bootloader.UINT16Write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the KEBA KeContact E10 smart energy meter (Modbus)

What Modbus registers does the KEBA KeContact E10 smart energy meter (Modbus) have?

This map lists 184 registers: 184 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the KEBA KeContact E10 smart energy meter (Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list gives start addresses, not register numbers: the first block starts at address 0 and the SunSpec block at 40000. The sheet itself warns that SunSpec register 40001 is read at address 40000.

What byte order does the KEBA KeContact E10 smart energy meter (Modbus) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the KEBA KeContact E10 smart energy meter (Modbus)?

Start with HR 0 Active power+ (Active power import (total)); HR 2 Active power- (Active power export (total)); HR 60 Current (L1) (Current L1); HR 62 Voltage (L1) (Voltage L1); HR 26 Supply frequency (Frequency); HR 512 Active energy+ (Active energy import); HR 516 Active energy- (Active energy export).

How do I enable Modbus control of the KEBA KeContact E10 smart energy meter (Modbus)?

Modbus RTU baud rate is set in register 258 (0 = 9600 ... 5 = 115200). IP address, subnet mask and DHCP are in registers 259-267 and take effect after a restart.

Where is the official KEBA KeContact E10 smart energy meter (Modbus) Modbus documentation?

The source is KeContact E10 - Modbus Register List (132941/00 v1.00), revision 2024-03, published free by KEBA at https://www.keba.com/download/x/052f09a75c/e10_modbus_register_list_v100.xlsx.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: KeContact E10 - Modbus Register List · 132941/00 v1.00 · rev. 2024-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.