  4. Energy meter 4 120 68 (RS-485 Modbus)

Energy meter · Modbus register map

Legrand Energy meter 4 120 68 (RS-485 Modbus) Modbus register map

Updated 17 November 2026

Short answer

Legrand's 4 120 68 is a meter with an RS-485 Modbus RTU port. Its short Modbus table gives voltage, current, frequency, active/reactive/apparent power and power factor as 16-bit words, two 32-bit energy counters, the internal temperature, a date/time block and the baud-rate and address settings. The energy counters are left out of this map because the table does not say which word comes first.

This page lists 10 Modbus registers for the Legrand Energy meter 4 120 68 (RS-485 Modbus) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Legrand’s own free documentation (linked below) and checked against it.

Manufacturer
Legrand
Model
Energy meter 4 120 68 (RS-485 Modbus)
Equipment type
Energy meter
Registers
10 (2 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
412068, 4 120 68, Legrand 412068
Source document
Modbus table F02230EN-01 (4 120 68) · F02230EN-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Legrand Energy meter 4 120 68 (RS-485 Modbus)

Integration in brief

Read holding registers with function 03 from address 0: 7 words give voltage, current, frequency, active/reactive/apparent power and power factor. Address 37 is the internal temperature.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0VoltageUINT16VoltageRead
HR 1CurrentUINT16CurrentRead
HR 3Active powerUINT16Active powerRead
HR 2FrequencyUINT16FrequencyRead
HR 6Power factorUINT16Power factorRead

Enable Modbus control & writes

Modbus RTU is active on the RS-485 port; baud rate (register 42) and address (register 43) can be written with function 16, e.g. ADDR 10 002A 0001 02 0002 sets 2400 baud.

Byte order & addressing

Network setup

Watch out for

Legrand Energy meter 4 120 68 (RS-485 Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

10 of 10 shown
Legrand Energy meter 4 120 68 (RS-485 Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0VoltageUINT16× 0.1VRead
HR1CurrentUINT16× 0.1ARead
HR2FrequencyUINT16× 0.1HzRead
HR3Active powerUINT16WRead
HR4Reactive powerUINT16varRead
HR5Apparent powerUINT16VARead
HR6Power factorUINT16× 0.001Read
HR37Internal temperatureUINT16°CRead
HR42Baud rateUINT16Read/write1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600
HR43Modbus address1-247.UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Legrand Energy meter 4 120 68 (RS-485 Modbus)

What Modbus registers does the Legrand Energy meter 4 120 68 (RS-485 Modbus) have?

This map lists 10 registers: 10 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Legrand Energy meter 4 120 68 (RS-485 Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table gives a 1-based register number and the 0-based register address in decimal and hex (voltage: number 1, address 0). The address is sent on the wire: the date/time example reads register number 34 with the frame ADDR 03 0021 0004.

What are the minimum Modbus registers to integrate the Legrand Energy meter 4 120 68 (RS-485 Modbus)?

Start with HR 0 Voltage (Voltage); HR 1 Current (Current); HR 3 Active power (Active power); HR 2 Frequency (Frequency); HR 6 Power factor (Power factor).

How do I enable Modbus control of the Legrand Energy meter 4 120 68 (RS-485 Modbus)?

Modbus RTU is active on the RS-485 port; baud rate (register 42) and address (register 43) can be written with function 16, e.g. ADDR 10 002A 0001 02 0002 sets 2400 baud.

Where is the official Legrand Energy meter 4 120 68 (RS-485 Modbus) Modbus documentation?

The source is Modbus table F02230EN-01 (4 120 68) (F02230EN-01), published free by Legrand at https://assets.legrand.com/pim/NP-FT-GT/F02230EN-01%20(4%20120%2068).pdf.

More Legrand Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Modbus table F02230EN-01 (4 120 68) · F02230EN-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.