Energy meter · Modbus register map
Legrand Energy meter 4 120 68 (RS-485 Modbus) Modbus register map
Updated 17 November 2026
Legrand's 4 120 68 is a meter with an RS-485 Modbus RTU port. Its short Modbus table gives voltage, current, frequency, active/reactive/apparent power and power factor as 16-bit words, two 32-bit energy counters, the internal temperature, a date/time block and the baud-rate and address settings. The energy counters are left out of this map because the table does not say which word comes first.
This page lists 10 Modbus registers for the Legrand Energy meter 4 120 68 (RS-485 Modbus) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Legrand’s own free documentation (linked below) and checked against it.
- Manufacturer
- Legrand
- Model
- Energy meter 4 120 68 (RS-485 Modbus)
- Equipment type
- Energy meter
- Registers
- 10 (2 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- 412068, 4 120 68, Legrand 412068
- Source document
- Modbus table F02230EN-01 (4 120 68) · F02230EN-01
Integration notes: Legrand Energy meter 4 120 68 (RS-485 Modbus)
Read holding registers with function 03 from address 0: 7 words give voltage, current, frequency, active/reactive/apparent power and power factor. Address 37 is the internal temperature.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Voltage | UINT16 | Voltage | Read |
| HR 1 | Current | UINT16 | Current | Read |
| HR 3 | Active power | UINT16 | Active power | Read |
| HR 2 | Frequency | UINT16 | Frequency | Read |
| HR 6 | Power factor | UINT16 | Power factor | Read |
Enable Modbus control & writes
Modbus RTU is active on the RS-485 port; baud rate (register 42) and address (register 43) can be written with function 16, e.g. ADDR 10 002A 0001 02 0002 sets 2400 baud.
Byte order & addressing
- Register numbers in the table are address + 1; send the address.
- Power values are unsigned 16-bit.
Network setup
- Baud codes: 1 = 1200, 2 = 2400, 3 = 4800, 4 = 9600.
Watch out for
- Active power is 16-bit whole watts, so it tops out at 65535 W.
Legrand Energy meter 4 120 68 (RS-485 Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | Voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 1 | Current | UINT16 | × 0.1 | A | Read | |||
| HR | 2 | Frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 3 | Active power | UINT16 | W | Read | ||||
| HR | 4 | Reactive power | UINT16 | var | Read | ||||
| HR | 5 | Apparent power | UINT16 | VA | Read | ||||
| HR | 6 | Power factor | UINT16 | × 0.001 | Read | ||||
| HR | 37 | Internal temperature | UINT16 | °C | Read | ||||
| HR | 42 | Baud rate | UINT16 | Read/write | 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600 | ||||
| HR | 43 | Modbus address | 1-247. | UINT16 | Read/write |
Notes on this map
- Left out: positive active energy (address 7, 2 words, x10 Wh) and positive reactive energy (address 17, 2 words, x10 varh). The table only says data are 'Big Endian' (most significant byte first), which fixes the byte order inside a word but not which of the two words is sent first.
- Supported functions: 03 (read) and 16 (write). Exception codes 1, 2 and 3.
- Serial details: RS-485 two-wire, RTU, address 1-247, programmable baud rate, 8 data bits, no parity, 1 stop bit.
- Timing: inter-character time-out 25 ms, response delay 25-100 ms, wait more than 25 ms between master requests.
- Left out: the 4-register date/day-of-week/time block at 33 (packed BCD-style digits per the example).
- The table heads the measurement page 'Input registers' but gives read function code 3, so they are listed here as holding registers (function 03).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Legrand Energy meter 4 120 68 (RS-485 Modbus)
What Modbus registers does the Legrand Energy meter 4 120 68 (RS-485 Modbus) have?
This map lists 10 registers: 10 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Legrand Energy meter 4 120 68 (RS-485 Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table gives a 1-based register number and the 0-based register address in decimal and hex (voltage: number 1, address 0). The address is sent on the wire: the date/time example reads register number 34 with the frame ADDR 03 0021 0004.
What are the minimum Modbus registers to integrate the Legrand Energy meter 4 120 68 (RS-485 Modbus)?
Start with HR 0 Voltage (Voltage); HR 1 Current (Current); HR 3 Active power (Active power); HR 2 Frequency (Frequency); HR 6 Power factor (Power factor).
How do I enable Modbus control of the Legrand Energy meter 4 120 68 (RS-485 Modbus)?
Modbus RTU is active on the RS-485 port; baud rate (register 42) and address (register 43) can be written with function 16, e.g. ADDR 10 002A 0001 02 0002 sets 2400 baud.
Where is the official Legrand Energy meter 4 120 68 (RS-485 Modbus) Modbus documentation?
The source is Modbus table F02230EN-01 (4 120 68) (F02230EN-01), published free by Legrand at https://assets.legrand.com/pim/NP-FT-GT/F02230EN-01%20(4%20120%2068).pdf.
More Legrand Modbus register maps
Other power & energy meters register maps
- Energy meter (DIN-rail, single-phase, MID)
Lumel NMID08 / NMID09 / NMID10 single-phase energy meter
Modbus RTU versions of the NMID08 (1/5 A CT), NMID09 (100 mA CT) and NMID10 (100 A direct) meters; the LITE and MBUS versions have no Modbus port.
Also known as: NMID08, NMID09, NMID10 - Energy meter
Northern Design Cube 300 panel kWh meter (Modbus RTU option)
Cube300 meters fitted with the RS-485 Modbus option, per the October 2005 Modbus Communications manual.
Also known as: Cube300, ND Cube 300, Northern Design Cube300 - Energy meter (multi-circuit power monitor)
Panasonic KW9M Eco-POWER METER
Panasonic KW9M (AKW91110) with the Modbus RTU protocol selected, user manual WUME-KW9M-10.
Also known as: AKW91110 - Energy meter
Rishabh Instruments RISH Delta Energy NX multifunction energy meter
Rishabh RISH Delta Energy NX panel energy meters with RS-485 Modbus RTU, per the operating manual on the product page (standard CT version).
Also known as: RISH Delta Energy NX, Delta Energy NX, RISH Delta Energy - Energy meter
Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters
Rishabh RISH EM 1320/1330/1340 and EM 2320/2330/2340 panel energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0721 Rev. B (06/2020). Rows marked 'only 2340' apply to the dual-source EM 2340.
Also known as: RISH EM 1320, RISH EM 1330, RISH EM 1340, RISH EM 2320, RISH EM 2330, RISH EM 2340, EM2340DS - Power meter
Rishabh Instruments RISH LM 1360 load manager (LM 13xx)
Rishabh RISH LM 1360 panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0662 Rev. D (01/2024).
Also known as: RISH LM 1360, LM1360, LM 13xx, LM1360 RJ12
All power & energy meters Modbus register maps →
Source: Modbus table F02230EN-01 (4 120 68) · F02230EN-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.