Energy meter · Modbus register map

Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) Modbus register map

Updated 17 November 2026

Short answer

Legrand's 046 77 and 046 79 are two-module DIN-rail energy meters with an RS485 port speaking Modbus/JBUS. The protocol sheet lists a small set of words: voltage, current, active power with a separate sign word, power factor with its inductive/capacitive sector, frequency, total and partial active energy, run time, a reset word and a device identifier.

This page lists 12 Modbus registers for the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Legrand’s own free documentation (linked below) and checked against it.

Manufacturer
Legrand
Model
Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)
Equipment type
Energy meter
Registers
12 (1 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
04677, 04679, 046 77, 046 79, Legrand 4 677, Legrand 4 679
Source document
Communication protocol - 046 77 / 046 79 Energy meter 2 module · CP-04677-04679b · rev. 2011-07-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)

Integration in brief

Read holding registers with function 03 from 0x2000: 16 words cover voltage, current, power with its sign word, power factor, frequency, total and partial energy and run time.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 8202Positive active energy (total)UINT32 ABCDTotal positive active energy (0.01 kWh)Read
HR 8192VoltageUINT32 ABCDVoltage (mV)Read
HR 8194CurrentUINT32 ABCDCurrent (mA)Read
HR 8196Active power (magnitude)UINT32 ABCDActive power magnitudeRead
HR 8198Active power signUINT16Active power signRead
HR 8201FrequencyUINT16FrequencyRead

Enable Modbus control & writes

Set the meter's Modbus address and baud rate on the device; the protocol sheet does not describe the menu.

Byte order & addressing

Network setup

Watch out for

Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

12 of 12 shown
Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR200doc 0x00c8Reset commandWrite-only; set the bit to reset that counter.BITMAP16Writebit 0 = Reset partial active energy; bit 3 = Reset operating time counter
HR768doc 0x0300Device identifierFixed 0x0F for this meter.UINT16Read
HR8192doc 0x2000VoltageSent in mV.UINT32ABCD× 0.001VRead
HR8194doc 0x2002CurrentSent in mA.UINT32ABCD× 0.001ARead
HR8196doc 0x2004Active power (magnitude)Size only; the sign is in 0x2006.UINT32ABCD× 0.01kWRead
HR8198doc 0x2006Active power signUINT16Read0 = Positive; 1 = Negative
HR8199doc 0x2007Power factorMagnitude; inductive or capacitive sector is in 0x2008.UINT16× 0.01Read
HR8200doc 0x2008Power factor sectorUINT16Read0 = PF is 0 or 1; 1 = Inductive; 2 = Capacitive
HR8201doc 0x2009FrequencyUINT16× 0.1HzRead
HR8202doc 0x200aPositive active energy (total)UINT32ABCD× 0.01kWhRead
HR8204doc 0x200cPositive partial active energyResettable via 0x00C8 bit 0.UINT32ABCD× 0.01kWhRead
HR8206doc 0x200eOperating time counterUINT32ABCDsRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)

What Modbus registers does the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) have?

This map lists 12 registers: 12 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex as sent in the request. The sheet's example reads 4 words starting at 0x200A with the frame 01 03 20 0A 00 04, and writes the reset word with 01 10 00 C8 00 01 02 00 01.

What byte order does the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)?

Start with HR 8202 Positive active energy (total) (Total positive active energy (0.01 kWh)); HR 8192 Voltage (Voltage (mV)); HR 8194 Current (Current (mA)); HR 8196 Active power (magnitude) (Active power magnitude); HR 8198 Active power sign (Active power sign); HR 8201 Frequency (Frequency).

How do I enable Modbus control of the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)?

Set the meter's Modbus address and baud rate on the device; the protocol sheet does not describe the menu.

Where is the official Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) Modbus documentation?

The source is Communication protocol - 046 77 / 046 79 Energy meter 2 module (CP-04677-04679b), revision 2011-07-01, published free by Legrand at https://assets.legrand.com/pim/NP-FT-GT/CP-04677-04679b.pdf.

More Legrand Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Communication protocol - 046 77 / 046 79 Energy meter 2 module · CP-04677-04679b · rev. 2011-07-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.