- Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)
Energy meter · Modbus register map
Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) Modbus register map
Updated 17 November 2026
Legrand's 046 77 and 046 79 are two-module DIN-rail energy meters with an RS485 port speaking Modbus/JBUS. The protocol sheet lists a small set of words: voltage, current, active power with a separate sign word, power factor with its inductive/capacitive sector, frequency, total and partial active energy, run time, a reset word and a device identifier.
This page lists 12 Modbus registers for the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Legrand’s own free documentation (linked below) and checked against it.
- Manufacturer
- Legrand
- Model
- Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)
- Equipment type
- Energy meter
- Registers
- 12 (1 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- 04677, 04679, 046 77, 046 79, Legrand 4 677, Legrand 4 679
Integration notes: Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)
Read holding registers with function 03 from 0x2000: 16 words cover voltage, current, power with its sign word, power factor, frequency, total and partial energy and run time.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8202 | Positive active energy (total) | UINT32 ABCD | Total positive active energy (0.01 kWh) | Read |
| HR 8192 | Voltage | UINT32 ABCD | Voltage (mV) | Read |
| HR 8194 | Current | UINT32 ABCD | Current (mA) | Read |
| HR 8196 | Active power (magnitude) | UINT32 ABCD | Active power magnitude | Read |
| HR 8198 | Active power sign | UINT16 | Active power sign | Read |
| HR 8201 | Frequency | UINT16 | Frequency | Read |
Enable Modbus control & writes
Set the meter's Modbus address and baud rate on the device; the protocol sheet does not describe the menu.
Byte order & addressing
- Power is unsigned with a separate sign word (0x2006).
- Voltage and current come in mV and mA.
- Hex addresses are wire addresses.
Network setup
- 8 data bits, 1 stop bit; baud rate programmable.
- Up to 32 devices per segment without repeaters.
Watch out for
- The sheet lists only function 03 for reading and 0x10 for writing.
- The reset word 0x00C8 is write-only.
Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 200doc 0x00c8 | Reset command | Write-only; set the bit to reset that counter. | BITMAP16 | Write | bit 0 = Reset partial active energy; bit 3 = Reset operating time counter | |||
| HR | 768doc 0x0300 | Device identifier | Fixed 0x0F for this meter. | UINT16 | Read | ||||
| HR | 8192doc 0x2000 | Voltage | Sent in mV. | UINT32 | ABCD | × 0.001 | V | Read | |
| HR | 8194doc 0x2002 | Current | Sent in mA. | UINT32 | ABCD | × 0.001 | A | Read | |
| HR | 8196doc 0x2004 | Active power (magnitude) | Size only; the sign is in 0x2006. | UINT32 | ABCD | × 0.01 | kW | Read | |
| HR | 8198doc 0x2006 | Active power sign | UINT16 | Read | 0 = Positive; 1 = Negative | ||||
| HR | 8199doc 0x2007 | Power factor | Magnitude; inductive or capacitive sector is in 0x2008. | UINT16 | × 0.01 | Read | |||
| HR | 8200doc 0x2008 | Power factor sector | UINT16 | Read | 0 = PF is 0 or 1; 1 = Inductive; 2 = Capacitive | ||||
| HR | 8201doc 0x2009 | Frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 8202doc 0x200a | Positive active energy (total) | UINT32 | ABCD | × 0.01 | kWh | Read | ||
| HR | 8204doc 0x200c | Positive partial active energy | Resettable via 0x00C8 bit 0. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| HR | 8206doc 0x200e | Operating time counter | UINT32 | ABCD | s | Read |
Notes on this map
- Data format (2.2): a 'long' is two words sent most significant word first, so 32-bit values are ABCD; the example answer 00 00 64 8C reads as 25740.
- The sheet calls the 32-bit format just 'long' without saying signed or unsigned. Power and power factor are magnitudes with separate sign/sector words and energies only count up, so the values are listed as unsigned; any reading below 2^31 decodes the same either way.
- Only functions 0x03 (read words) and 0x10 (write words) are supported. Address 0 is broadcast with no answer.
- The sheet's example labels the second value read from 0x200A as 'total reactive energy', but the variables table puts positive partial active energy at 0x200C; the table is followed here.
- Baud rate is programmable on the meter; the sheet gives 8 data bits and 1 stop bit but no parity or default speed.
- Timing: keep gaps between characters under 100 ms; the meter answers no sooner than 25 ms.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)
What Modbus registers does the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) have?
This map lists 12 registers: 12 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex as sent in the request. The sheet's example reads 4 words starting at 0x200A with the frame 01 03 20 0A 00 04, and writes the reset word with 01 10 00 C8 00 01 02 00 01.
What byte order does the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)?
Start with HR 8202 Positive active energy (total) (Total positive active energy (0.01 kWh)); HR 8192 Voltage (Voltage (mV)); HR 8194 Current (Current (mA)); HR 8196 Active power (magnitude) (Active power magnitude); HR 8198 Active power sign (Active power sign); HR 8201 Frequency (Frequency).
How do I enable Modbus control of the Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)?
Set the meter's Modbus address and baud rate on the device; the protocol sheet does not describe the menu.
Where is the official Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus) Modbus documentation?
The source is Communication protocol - 046 77 / 046 79 Energy meter 2 module (CP-04677-04679b), revision 2011-07-01, published free by Legrand at https://assets.legrand.com/pim/NP-FT-GT/CP-04677-04679b.pdf.
More Legrand Modbus register maps
Other power & energy meters register maps
- Power meter (panel network parameter meter)
Lumel ND31LITE network parameter meter
Lumel ND31LITE panel meter with RS-485 Modbus RTU, per user manual ND31LITE-09.
Also known as: ND31LITE - Power meter
Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP)
V2 Ethernet versions of the Cube 350I, Cube 350V, Cube 400I and Cube 400V (label 'IP.Ver: V2') and the Rail 350V, per manual revision 1.07p (December 2013).
Also known as: Cube 350I IP, Cube 350V IP, Cube 400I IP, Cube 400V IP, Rail 350V IP, Cube IP meter V2 - Energy meter
Panasonic KW8M Eco-POWER METER
Panasonic KW8M AKW8111 and AKW8111H (logging/demand version) with Modbus RTU selected, manual ARCT1F440E-8.
Also known as: AKW8111, AKW8111H - Energy meter (DC)
Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter
Rishabh RISH DC2111 MOD single-channel DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-1669 Rev. D (08/25).
Also known as: RISH DC2111 MOD, DC2111 - Energy meter
Rishabh Instruments RISH ED21XX / EC21XX / ER21XX single-phase energy meters
Rishabh RISH ED21XX (direct), EC21XX (CT) and ER21XX (RJ12 CT) single-phase meters in their Modbus versions, per operating manual DMAN-00IM-1073 Rev. M.
Also known as: RISH ED21X1, RISH EC21X1, RISH ER21X1, RISH ED21XX, RISH EC21XX, RISH ER21XX - Power meter
Rishabh Instruments RISH LM 1340 multifunction meter
Rishabh RISH LM 1340 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. D (03/2026).
Also known as: RISH LM 1340, LM1340
All power & energy meters Modbus register maps →
Source: Communication protocol - 046 77 / 046 79 Energy meter 2 module · CP-04677-04679b · rev. 2011-07-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.