- RISH DC2111 MOD single-channel DC energy meter
Energy meter (DC) · Modbus register map
Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter Modbus register map
Updated 17 November 2026
The RISH DC2111 MOD is a DIN-rail DC energy meter for one DC channel. Its RS-485 port speaks Modbus RTU with every reading as a 32-bit float. This map covers voltage, current, power, import/export energy and ampere-hours with their overflow counters, demands, min/max values, hour counters and the basic communication settings.
This page lists 52 Modbus registers for the Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.
- Manufacturer
- Rishabh Instruments
- Model
- RISH DC2111 MOD single-channel DC energy meter
- Equipment type
- Energy meter (DC)
- Registers
- 52 (4 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- RISH DC2111 MOD, DC2111
Integration notes: Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter
Read measured values with FC04 (or FC03 at the 4X copies) in pairs of registers and decode them as ABCD floats. Settings are floats too and are written with FC16.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Voltage | FLOAT32 ABCD | DC voltage | Read |
| IR 2 | Current | FLOAT32 ABCD | DC current | Read |
| IR 4 | Power | FLOAT32 ABCD | DC power | Read |
| IR 6 | Import Energy | FLOAT32 ABCD | Import energy | Read |
| IR 10 | Export Energy | FLOAT32 ABCD | Export energy | Read |
| IR 14 | Import Ampere Hour | FLOAT32 ABCD | Import ampere-hours | Read |
Enable Modbus control & writes
Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.
Byte order & addressing
- Each parameter is two registers; reading or writing only half of a float returns an Illegal Data Address exception.
- Addresses are Modicon-style: subtract 30001 or 40001 for the wire address.
- Limit each read to 40 parameters (80 registers) or less.
Network setup
- Slave address range 1-247; broadcast (address 0) is not supported.
- Allow about 200 ms for the meter to answer before retrying.
Watch out for
- If a password lock is set, write the valid password to the Password register before changing any 4X setting; a wrong password returns exception code 2.
Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Voltage | DC voltage. | FLOAT32 | ABCD | V | Read | ||
| IR | 2doc 30003 | Current | DC current. | FLOAT32 | ABCD | A | Read | ||
| IR | 4doc 30005 | Power | DC power (manual's example: 2000 W). | FLOAT32 | ABCD | W | Read | ||
| IR | 6doc 30007 | Import Energy | FLOAT32 | ABCD | Read | ||||
| IR | 8doc 30009 | Import Energy OF | FLOAT32 | ABCD | Read | ||||
| IR | 10doc 30011 | Export Energy | FLOAT32 | ABCD | Read | ||||
| IR | 12doc 30013 | Export Energy OF | FLOAT32 | ABCD | Read | ||||
| IR | 14doc 30015 | Import Ampere Hour | FLOAT32 | ABCD | Read | ||||
| IR | 16doc 30017 | Import Ampere Hour OF | FLOAT32 | ABCD | Read | ||||
| IR | 18doc 30019 | Export Ampere Hour | FLOAT32 | ABCD | Read | ||||
| IR | 20doc 30021 | Export Ampere Hour OF | FLOAT32 | ABCD | Read | ||||
| IR | 22doc 30023 | Import Power Demand | FLOAT32 | ABCD | Read | ||||
| IR | 24doc 30025 | Export Power Demand | FLOAT32 | ABCD | Read | ||||
| IR | 26doc 30027 | Import Current Demand | FLOAT32 | ABCD | Read | ||||
| IR | 28doc 30029 | Export Current Demand | FLOAT32 | ABCD | Read | ||||
| IR | 30doc 30031 | Max Voltage | FLOAT32 | ABCD | Read | ||||
| IR | 32doc 30033 | Min Voltage | FLOAT32 | ABCD | Read | ||||
| IR | 34doc 30035 | Max Current | FLOAT32 | ABCD | Read | ||||
| IR | 36doc 30037 | Min Current | FLOAT32 | ABCD | Read | ||||
| IR | 38doc 30039 | Max Import Power Demand | FLOAT32 | ABCD | Read | ||||
| IR | 40doc 30041 | Max Export Power Demand | FLOAT32 | ABCD | Read | ||||
| IR | 42doc 30043 | Max Import Current Demand | FLOAT32 | ABCD | Read | ||||
| IR | 44doc 30045 | Max Export Current Demand | FLOAT32 | ABCD | Read | ||||
| IR | 46doc 30047 | Import Energy on update rate | FLOAT32 | ABCD | Read | ||||
| IR | 48doc 30049 | Import Energy on update rate OF | FLOAT32 | ABCD | Read | ||||
| IR | 50doc 30051 | Export Energy on update rate | FLOAT32 | ABCD | Read | ||||
| IR | 52doc 30053 | Export Energy on update rate OF | FLOAT32 | ABCD | Read | ||||
| IR | 54doc 30055 | On Hour | FLOAT32 | ABCD | Read | ||||
| IR | 56doc 30057 | Run Hour | FLOAT32 | ABCD | Read | ||||
| IR | 58doc 30059 | No. of Interruptions | FLOAT32 | ABCD | Read | ||||
| IR | 60doc 30061 | Partial Import Energy | FLOAT32 | ABCD | Read | ||||
| IR | 62doc 30063 | Partial Import Energy OF | FLOAT32 | ABCD | Read | ||||
| IR | 64doc 30065 | Partial Export Energy | FLOAT32 | ABCD | Read | ||||
| IR | 66doc 30067 | Partial Export Energy OF | FLOAT32 | ABCD | Read | ||||
| IR | 68doc 30069 | Partial Import Ampere Hour | FLOAT32 | ABCD | Read | ||||
| IR | 70doc 30071 | Partial Import Ampere Hour OF | FLOAT32 | ABCD | Read | ||||
| IR | 72doc 30073 | Partial Export Ampere Hour | FLOAT32 | ABCD | Read | ||||
| IR | 74doc 30075 | Partial Export Ampere Hour OF | FLOAT32 | ABCD | Read | ||||
| IR | 76doc 30077 | Max Power | FLOAT32 | ABCD | Read | ||||
| IR | 78doc 30079 | Min Power | FLOAT32 | ABCD | Read | ||||
| IR | 80doc 30081 | Total energy | FLOAT32 | ABCD | Read | ||||
| IR | 82doc 30083 | Total energy OF | FLOAT32 | ABCD | Read | ||||
| IR | 88doc 30089 | Total Ampere Hour | FLOAT32 | ABCD | Read | ||||
| IR | 90doc 30091 | Total Ampere Hour OF | FLOAT32 | ABCD | Read | ||||
| IR | 96doc 30097 | Partial Total energy | FLOAT32 | ABCD | Read | ||||
| IR | 98doc 30099 | Partial Total energy OF | FLOAT32 | ABCD | Read | ||||
| IR | 104doc 30105 | Partial Total Ampere Hour | FLOAT32 | ABCD | Read | ||||
| IR | 106doc 30107 | Partial Total Ampere Hour OF | FLOAT32 | ABCD | Read | ||||
| HR | 2doc 40003 | Demand Period | Demand period in minutes (5, 10, 15, 30 or 60). | FLOAT32 | ABCD | Read/write | |||
| HR | 4doc 40005 | Reset parameters | Write a code to reset counters (see manual Table 5). | FLOAT32 | ABCD | Read/write | |||
| HR | 6doc 40007 | RS485 Setup Code | Baud rate / parity / stop bit code (manual Table 6). | FLOAT32 | ABCD | Read/write | |||
| HR | 8doc 40009 | Modbus address | Modbus slave address, 1-247. | FLOAT32 | ABCD | Read/write |
Notes on this map
- Measured values are IEEE-754 32-bit floats in two registers. The manual's example responses (e.g. data bytes 43 5B 41 21 for a current reading) put the most significant register first, so ABCD is the default order.
- Rows whose printed hex address does not match the decimal 3X/4X address in the manual were left out rather than guessed.
- Left out: the 32-bit integer energy tables (their integer word order is not demonstrated in the manual), user-assignable registers and data-log blocks.
- Where the register table has no unit column, units are left blank; energy registers follow the energy unit (Wh/kWh/MWh) configured on the meter, and 'OF' / overflow registers count roll-overs of the matching energy register.
- The manual's 4X copies of measured values start at 44097 (hex 0x1000), not at 40001; this map lists the 3X addresses only.
- In Table 3 only the first four setup rows have a hex address that matches the decimal address; the rest (from 40027 Nominal Voltage on) disagree by several registers and were left out.
- Units are only given where the manual states them (V, A and W from the example frames); energy registers follow the meter's Energy Output setting (Wh, kWh or MWh).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter
What Modbus registers does the Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter have?
This map lists 52 registers: 48 input registers, 4 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 30001/40001-style addresses next to the hex start address actually sent (30001 = 0x0000). Wire address = printed number - 30001 (input registers) or - 40001 (holding registers); every value here was cross-checked against the printed hex address.
What byte order does the Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter?
Start with IR 0 Voltage (DC voltage); IR 2 Current (DC current); IR 4 Power (DC power); IR 6 Import Energy (Import energy); IR 10 Export Energy (Export energy); IR 14 Import Ampere Hour (Import ampere-hours).
How do I enable Modbus control of the Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter?
Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.
Where is the official Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter Modbus documentation?
The source is RISH DC2111 MOD - Interface Definition Manual (DMAN-00IM-1669 Rev. D), revision 2025-08, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/rish-dc2111-mod-single-channel-dc-energy-meter-268/RISH%20DC2111%20MOD%20-%20INTERFACE_DEFINATION_MANUAL_REV_D.pdf.
More Rishabh Instruments Modbus register maps
- Energy meter
Rishabh Instruments RISH Delta Energy NX multifunction energy meter
Rishabh RISH Delta Energy NX panel energy meters with RS-485 Modbus RTU, per the operating manual on the product page (standard CT version).
Also known as: RISH Delta Energy NX, Delta Energy NX, RISH Delta Energy - Power meter
Rishabh Instruments RISH Delta Power NX multifunction power meter
Rishabh RISH Delta Power NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0117 Rev. E.
Also known as: RISH Delta Power NX, Delta Power NX, RISH Delta Power - Power meter
Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter
Rishabh RISH Delta VAF NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0118 Rev. F.
Also known as: RISH Delta VAF NX, Delta VAF NX, RISH Delta VAF - Power meter (demand controller)
Rishabh Instruments RISH DMCi touch-screen demand controller with TOD
Rishabh RISH DMCi 96 x 96 mm touch-screen demand controllers with the optional RS-485 Modbus output, per interface definition DMAN-00IM-0578 Rev. A (09/16).
Also known as: RISH DMCi, DMCi, Rish DMCi demand controller - Energy meter
Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters
Rishabh RISH EC43xx and ER43xx DIN-rail digital energy meters with RS-485 Modbus, per interface definition DMAN-00IM-09xx Rev. F (11/25).
Also known as: EC4311, EC4321, ER4311, ER4321, RISH EC43X1, EC43XX, ER43XX - Energy meter
Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters
Rishabh RISH ED11XX (direct), EC11XX (CT) and ER11XX (RJ12 CT) single-phase DIN-rail meters in their Modbus (x1) versions, per operating manual DMAN-00IM-1071 Rev. M.
Also known as: RISH ED11X1, RISH EC11X1, RISH ER11X1, ED1111, EC1111, ER1111, RISH ED11XX, RISH EC11XX, RISH ER11XX - Energy meter
Rishabh Instruments RISH ED21XX / EC21XX / ER21XX single-phase energy meters
Rishabh RISH ED21XX (direct), EC21XX (CT) and ER21XX (RJ12 CT) single-phase meters in their Modbus versions, per operating manual DMAN-00IM-1073 Rev. M.
Also known as: RISH ED21X1, RISH EC21X1, RISH ER21X1, RISH ED21XX, RISH EC21XX, RISH ER21XX - Energy meter
Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters
Rishabh RISH EM 1320/1330/1340 and EM 2320/2330/2340 panel energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0721 Rev. B (06/2020). Rows marked 'only 2340' apply to the dual-source EM 2340.
Also known as: RISH EM 1320, RISH EM 1330, RISH EM 1340, RISH EM 2320, RISH EM 2330, RISH EM 2340, EM2340DS - Energy meter
Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter
Rishabh RISH EM 3490 DS dual-source energy meters (separate utility and generator energy) with RS-485 Modbus, per manual Rev G.
Also known as: RISH EM 3490 DS, EM3490DS, EM 3490DS - Energy meter
Rishabh Instruments RISH EM 3490 SS single-phase energy meter
Rishabh RISH EM 3490 SS single-phase energy meters with the optional RS-485 Modbus output, per the 1-phase manual Rev D.
Also known as: RISH EM 3490 SS 1P, EM3490SS 1P, EM 3490 SS single-phase - Energy meter
Rishabh Instruments RISH EM 3490 SS three-phase single-source energy meter
Rishabh RISH EM 3490 SS three-phase energy meters with the optional RS-485 Modbus output, per the 3-phase manual Rev E.
Also known as: RISH EM 3490 SS 3P, EM3490SS 3P, EM 3490 SS three-phase - Energy meter (DC)
Rishabh Instruments RISH EM DC 6000 programmable DC energy meter
Rishabh RISH EM DC 6000 single-channel programmable DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0862 Rev. 0 (12/2020).
Also known as: RISH EM DC 6000, EMDC 6000, EM DC6000 - Energy meter (DC)
Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter
Rishabh RISH EM DC 6001 / 6002 multi-channel DC energy meters with RS-485 Modbus, per interface definition 2-60-006-00-00627 Rev. 0 (10/2015).
Also known as: RISH EM DC 6001, RISH EM DC 6002, EM DC 6001, EM DC 6002 - Power meter
Rishabh Instruments RISH LM 1340 multifunction meter
Rishabh RISH LM 1340 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. D (03/2026).
Also known as: RISH LM 1340, LM1340 - Power meter
Rishabh Instruments RISH LM 1360 load manager (LM 13xx)
Rishabh RISH LM 1360 panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0662 Rev. D (01/2024).
Also known as: RISH LM 1360, LM1360, LM 13xx, LM1360 RJ12 - Power meter
Rishabh Instruments RISH LM 1380 multifunction meter
Rishabh RISH LM 1380 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0925 Rev. A (04/2022).
Also known as: RISH LM 1380, LM1380 - Power meter
Rishabh Instruments RISH LM1360+ RJ12 smart energy meter
Rishabh RISH LM1360 PLUS RJ12 smart energy meters (RJ12 CT inputs) with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. A (01/2026).
Also known as: RISH LM 1360+, LM1360 PLUS RJ12, LM1360+ - Power meter
Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter
Rishabh RISH Master 3440 class 0.2S panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0711 Rev. C (05/2019).
Also known as: RISH Master 3440, RM3440, Master 3440 0.2S - Power meter
Rishabh Instruments RISH Master 3440i / 3440iDL (class 0.2S) touch-screen meter
Rishabh RISH Master 3440i and 3440iDL touch-screen class 0.2S meters with RS-485 Modbus, per interface definition DMAN-00IM-0712 Rev. F (10/2026).
Also known as: RISH Master 3440i, RISH Master 3440iDL, RM3440i, RM3440iDL - Power meter (multi-circuit energy meter)
Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)
RISH Multiload Monitor (12 current channels, 4 voltage channels) per interface definition DMAN-00IM-0795 Rev A (08/2020).
Also known as: RISH ML 1400, RISH ML 1410, RISH MLM, Multiload Monitor - Power meter (power factor controller)
Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller
Rishabh RISH PFC 96 and PFC 144 automatic power factor (APFC) controllers with RS-485 Modbus RTU, per interface definition version D (12/18).
Also known as: RISH PFC 96, RISH PFC 144, PFC96, PFC144, RISH PFC-12, APFC
Other power & energy meters register maps
- Power meter (power quality analyzer)
SATEC PM175 powermeter and power quality analyzer
SATEC PM175 from firmware 25.2.6, per Modbus reference guide BG0416 Rev. A7 (Nov 2009).
Also known as: PM175, SATEC PM175, PM 175 - Energy meter
Senva EM-RS485 networked energy meter (Modbus RTU/ASCII)
Senva EM-RS485 three-phase energy meters with Senva CVT sensors, firmware v1.1.2, Modbus Protocol Guide 154-0023-0B (2017-04-10).
Also known as: EM-RS485, Senva EM-RS485, Senva protocol energy meter - Sensor (geotechnical: inclinometer, tiltmeter, piezometer, extensometer)
SISGEO SISGEO digital instruments, RS-485 Modbus (firmware 3.x normal mode)
SISGEO digital instruments with firmware 0x0300 or later running in normal (non-legacy) mode, protocol manual EN 05/20.
Also known as: SISGEO digital in-place inclinometer, SISGEO digital tiltmeter, SISGEO digital piezometer, SISGEO DEX, SISGEO digital extensometer - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS - Power meter
BTicino PM multifunction meter F3N200 (Modbus RTU)
BTicino PM multifunction meter catalogue number F3N200 with RS-485, per Modbus table IDP000024 v1.01.
Also known as: F3N200, BTicino PM F3N200
All power & energy meters Modbus register maps →
Source: RISH DC2111 MOD - Interface Definition Manual · DMAN-00IM-1669 Rev. D · rev. 2025-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.