Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) Modbus register map

Updated 17 November 2026

Short answer

The Senva EM-RS485 is a compact three-phase energy meter that reads Senva current/voltage transducers (CVTs) and talks Modbus RTU, Modbus ASCII or BACnet MS/TP on RS-485 with auto-detected line settings. Measurements are IEEE floats in holding registers: system and per-phase voltage, current, power factor, real/reactive/apparent power, energy, demand, plus condition flags. This map covers the main reading and setup registers.

This page lists 83 Modbus registers for the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Senva’s own free documentation (linked below) and checked against it.

Manufacturer
Senva
Model
EM-RS485 networked energy meter (Modbus RTU/ASCII)
Equipment type
Energy meter
Registers
83 (18 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
v1.1.2
Also known as
EM-RS485, Senva EM-RS485, Senva protocol energy meter
Source document
EM-RS485 Modbus Protocol Guide · 154-0023-0B · rev. 2017-04-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Senva EM-RS485 networked energy meter (Modbus RTU/ASCII)

Integration in brief

Connect RS-485 to an active Modbus master and let the meter auto-detect the line, then read the float pairs at R600 (total kW), R700 (kWh), R420 (V) and R520 (A) with function 03.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 600Total real powerFLOAT32 ABCDTotal real powerRead
HR 700Total real energyFLOAT32 ABCDTotal real energyRead
HR 420Phase average RMS voltageFLOAT32 ABCDAverage voltageRead
HR 520Phase average RMS currentFLOAT32 ABCDAverage currentRead
HR 550System power factorFLOAT32 ABCDPower factorRead
HR 410Line frequencyFLOAT32 ABCDFrequencyRead
HR 400Active system conditionsBITMAP16System condition flagsRead

Enable Modbus control & writes

Modbus is on by default (protocol Auto). Lock baud/parity/protocol with R122-R128 for permanent installations.

Byte order & addressing

Network setup

Watch out for

Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

83 of 83 shown
Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR102doc R102Reset reasonUINT16Read
HR103doc R103Reset countUINT16Read
HR104doc R104/05Up timeTime since last reset.UINT32ABCDsRead
HR111doc R111Identify meterFlash LEDs to find the meter (BOOL).UINT16Read/write0 = Inactive; 1 = Active (all LEDs blink green)
HR122doc R122RS485 protocolUINT16Read/write1 = Auto; 2 = BACnet; 3 = Modbus RTU; 4 = Modbus ASCII; 5 = BACnet + Modbus RTU; 6 = BACnet + Modbus ASCII; 7 = Modbus RTU + ASCII; 8 = Any protocol
HR123doc R123Slave address1-254; also answers global address 255.UINT16Read/write
HR124doc R124/25RS485 baud rate1200-460800; writing it turns auto-baud off.UINT32ABCDbaudRead/write
HR126doc R126RS485 parityUINT16Read/write1 = Auto; 2 = None; 3 = Odd; 4 = Even
HR127doc R127RS485 data bitsUINT16Read/write1 = Auto; 2 = 7 bits; 3 = 8 bits
HR128doc R128RS485 stop bitsUINT16Read/write1 = Auto; 2 = 1 bit; 3 = 1.5 bits; 4 = 2 bits
HR133doc R133Temperature unitsUINT16Read/write1 = °F; 2 = °C
HR153doc R153Angle unitsUINT16Read/write1 = Degrees; 2 = Radians
HR161doc R161System phase selectionWhich phases make up system totals.UINT16Read/write1 = 3 phase; 2 = R and S; 3 = S and T; 4 = R and T
HR163doc R163Power unitsReactive and apparent power follow the same scale.UINT16Read/write1 = kW; 2 = W; 3 = MW
HR170doc R170Energy data typeUINT16Read/write0 = Floating point; 1 = Unsigned integer 0-999999 (wraps)
HR173doc R173Energy unitsReactive and apparent energy follow the same scale.UINT16Read/write1 = kWh; 2 = Wh; 3 = MWh
HR194doc R194Energy reset countUINT16Read
HR200doc R200Setup buttonReads 1 while the button is pressed.UINT16Read
HR201doc R201Binary input 1Stable state of pulse input 1 (input is active low).UINT16Read
HR202doc R202Binary input 2Stable state of pulse input 2 (input is active low).UINT16Read
HR210doc R210/11Pulse input 1 countUINT32ABCDRead/write
HR220doc R220/21Pulse input 2 countUINT32ABCDRead/write
HR310doc R310/11TemperatureMeter ambient temperature; unit set by R133 (default °F).FLOAT32ABCD°F / °CRead
HR380doc R380/81Power supply voltageInternal supply voltage after rectification.FLOAT32ABCDVRead
HR400doc R400Active system conditionsBITMAP16Readbit 5 = Mismatched voltage; bit 6 = Reverse RST order; bit 7 = Not 3-phase; bit 12 = Frequency drift; bit 15 = Phase drift
HR401doc R401Previous system conditionsLatched copy of R400; write 0 to clear.BITMAP16Read/writebit 5 = Mismatched voltage; bit 6 = Reverse RST order; bit 7 = Not 3-phase; bit 12 = Frequency drift; bit 15 = Phase drift
HR410doc R410/11Line frequencyFLOAT32ABCDHzRead
HR420doc R420/21Phase average RMS voltageAverage of valid phases.FLOAT32ABCDVRead
HR450doc R450/51Phase-to-phase average RMS voltageFLOAT32ABCDVRead
HR520doc R520/21Phase average RMS currentFLOAT32ABCDARead
HR540doc R540/41Phase average current angleUnit set by R153.FLOAT32ABCDdeg / radRead
HR550doc R550/51System power factorFLOAT32ABCDRead
HR600doc R600/01Total real powerUnit set by R163 (default kW).FLOAT32ABCDkWRead
HR610doc R610/11Phase average real powerUnit set by R163.FLOAT32ABCDkWRead
HR620doc R620/21Net real powerNegative = net export. Unit set by R163.FLOAT32ABCDkWRead
HR640doc R640/41Total reactive powerUnit follows R163 (default kVAR).FLOAT32ABCDkVARRead
HR660doc R660/61Total apparent powerUnit follows R163 (default kVA).FLOAT32ABCDkVARead
HR700doc R700/01Total real energyUnit set by R173 (default kWh); type per R170.FLOAT32ABCDkWhRead
HR702doc R702/03Total real energy importFLOAT32ABCDkWhRead
HR704doc R704/05Total real energy exportFLOAT32ABCDkWhRead
HR706doc R706/07Total real energy netFLOAT32ABCDkWhRead
HR720doc R720/21System real energyFLOAT32ABCDkWhRead
HR722doc R722/23System real energy importFLOAT32ABCDkWhRead
HR724doc R724/25System real energy exportFLOAT32ABCDkWhRead
HR740doc R740/41Total reactive energyUnit follows R173 (default kVARh).FLOAT32ABCDkVARhRead
HR760doc R760/61Total apparent energyUnit follows R173 (default kVAh).FLOAT32ABCDkVAhRead
HR800doc R800/01Demand real powerCurrent demand window. Unit per R163.FLOAT32ABCDkWRead
HR806doc R806/07Maximum demand real powerFLOAT32ABCDkWRead
HR840doc R840/41Demand reactive powerFLOAT32ABCDkVARRead
HR860doc R860/61Demand apparent powerFLOAT32ABCDkVARead
HR1102doc R1102R phase CVT presentUINT16Read0 = No; 1 = Yes
HR1103doc R1103R phase CVT statusUINT16Read1 = No CVT; 2 = No error; 3 = Detection error; 4 = Communication error; 5 = Configuration error; 6 = Version error; 7 = Technology error
HR1140doc R1140/41R phase CVT voltage ratingFLOAT32ABCDVRead
HR1150doc R1150/51R phase CVT current ratingFLOAT32ABCDARead
HR1152doc R1152/53R phase current multiplierDefault 1.0.FLOAT32ABCDRead/write
HR1400doc R1400R phase active conditionsBITMAP16Readbit 0 = Sensor fault; bit 1 = No load; bit 2 = Negative power; bit 3 = Phase loss; bit 4 = Bad frequency; bit 5 = Low power factor; bit 6 = Over current; bit 7 = Over voltage; bit 8 = High harmonics; bit 9 = Unexpected sensor; bit 10 = Missing sensor; bit 11 = Surge voltage; bit 13 = Brown-out voltage
HR1401doc R1401R phase previous conditionsWrite 0 to clear.BITMAP16Read/writebit 0 = Sensor fault; bit 1 = No load; bit 2 = Negative power; bit 3 = Phase loss; bit 4 = Bad frequency; bit 5 = Low power factor; bit 6 = Over current; bit 7 = Over voltage; bit 8 = High harmonics; bit 9 = Unexpected sensor; bit 10 = Missing sensor; bit 11 = Surge voltage; bit 13 = Brown-out voltage
HR1420doc R1420/21R phase RMS voltageFLOAT32ABCDVRead
HR1450doc R1450/51R phase-to-phase RMS voltageFLOAT32ABCDVRead
HR1520doc R1520/21R phase RMS currentIncludes current multiplier; always positive.FLOAT32ABCDARead
HR1540doc R1540/41R phase current angleUnit set by R153.FLOAT32ABCDdeg / radRead
HR1550doc R1550/51R phase power factorFLOAT32ABCDRead
HR1600doc R1600/01R phase real powerUnit per R163.FLOAT32ABCDkWRead
HR1640doc R1640/41R phase reactive powerFLOAT32ABCDkVARRead
HR1660doc R1660/61R phase apparent powerFLOAT32ABCDkVARead
HR1700doc R1700/01R phase total real energyUnit per R173; type per R170.FLOAT32ABCDkWhRead
HR1740doc R1740/41R phase total reactive energyFLOAT32ABCDkVARhRead
HR1760doc R1760/61R phase total apparent energyFLOAT32ABCDkVAhRead
HR1800doc R1800/01R phase demand real powerFLOAT32ABCDkWRead
HR2103doc R2103S phase CVT statusUINT16Read1 = No CVT; 2 = No error; 3 = Detection error; 4 = Communication error; 5 = Configuration error; 6 = Version error; 7 = Technology error
HR2400doc R2400S phase active conditionsBITMAP16Readbit 0 = Sensor fault; bit 1 = No load; bit 2 = Negative power; bit 3 = Phase loss; bit 4 = Bad frequency; bit 5 = Low power factor; bit 6 = Over current; bit 7 = Over voltage; bit 8 = High harmonics; bit 9 = Unexpected sensor; bit 10 = Missing sensor; bit 11 = Surge voltage; bit 13 = Brown-out voltage
HR2420doc R2420/21S phase RMS voltageFLOAT32ABCDVRead
HR2520doc R2520/21S phase RMS currentFLOAT32ABCDARead
HR2550doc R2550/51S phase power factorFLOAT32ABCDRead
HR2600doc R2600/01S phase real powerUnit per R163.FLOAT32ABCDkWRead
HR2700doc R2700/01S phase total real energyUnit per R173.FLOAT32ABCDkWhRead
HR3103doc R3103T phase CVT statusUINT16Read1 = No CVT; 2 = No error; 3 = Detection error; 4 = Communication error; 5 = Configuration error; 6 = Version error; 7 = Technology error
HR3400doc R3400T phase active conditionsBITMAP16Readbit 0 = Sensor fault; bit 1 = No load; bit 2 = Negative power; bit 3 = Phase loss; bit 4 = Bad frequency; bit 5 = Low power factor; bit 6 = Over current; bit 7 = Over voltage; bit 8 = High harmonics; bit 9 = Unexpected sensor; bit 10 = Missing sensor; bit 11 = Surge voltage; bit 13 = Brown-out voltage
HR3420doc R3420/21T phase RMS voltageFLOAT32ABCDVRead
HR3520doc R3520/21T phase RMS currentFLOAT32ABCDARead
HR3550doc R3550/51T phase power factorFLOAT32ABCDRead
HR3600doc R3600/01T phase real powerUnit per R163.FLOAT32ABCDkWRead
HR3700doc R3700/01T phase total real energyUnit per R173.FLOAT32ABCDkWhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII)

What Modbus registers does the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) have?

This map lists 83 registers: 83 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints raw protocol addresses with an R prefix (R420 = wire address 420; Modicon 40421). R420/21 marks a two-register value starting at 420. S phase registers are R phase + 1000, T phase + 2000.

What byte order does the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII)?

Start with HR 600 Total real power (Total real power); HR 700 Total real energy (Total real energy); HR 420 Phase average RMS voltage (Average voltage); HR 520 Phase average RMS current (Average current); HR 550 System power factor (Power factor); HR 410 Line frequency (Frequency); HR 400 Active system conditions (System condition flags).

How do I enable Modbus control of the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII)?

Modbus is on by default (protocol Auto). Lock baud/parity/protocol with R122-R128 for permanent installations.

Where is the official Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) Modbus documentation?

The source is EM-RS485 Modbus Protocol Guide (154-0023-0B), revision 2017-04-10, published free by Senva at https://senvainc.com/catalog/documents/downloadcenter/EM-RS485%20Modbus%20Protocol%20Guide.pdf.

More Senva Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: EM-RS485 Modbus Protocol Guide · 154-0023-0B · rev. 2017-04-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.