- EM-RS485 networked energy meter (Modbus RTU/ASCII)
Energy meter · Modbus register map
Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) Modbus register map
Updated 17 November 2026
The Senva EM-RS485 is a compact three-phase energy meter that reads Senva current/voltage transducers (CVTs) and talks Modbus RTU, Modbus ASCII or BACnet MS/TP on RS-485 with auto-detected line settings. Measurements are IEEE floats in holding registers: system and per-phase voltage, current, power factor, real/reactive/apparent power, energy, demand, plus condition flags. This map covers the main reading and setup registers.
This page lists 83 Modbus registers for the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Senva’s own free documentation (linked below) and checked against it.
- Manufacturer
- Senva
- Model
- EM-RS485 networked energy meter (Modbus RTU/ASCII)
- Equipment type
- Energy meter
- Registers
- 83 (18 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- v1.1.2
- Also known as
- EM-RS485, Senva EM-RS485, Senva protocol energy meter
Integration notes: Senva EM-RS485 networked energy meter (Modbus RTU/ASCII)
Connect RS-485 to an active Modbus master and let the meter auto-detect the line, then read the float pairs at R600 (total kW), R700 (kWh), R420 (V) and R520 (A) with function 03.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 600 | Total real power | FLOAT32 ABCD | Total real power | Read |
| HR 700 | Total real energy | FLOAT32 ABCD | Total real energy | Read |
| HR 420 | Phase average RMS voltage | FLOAT32 ABCD | Average voltage | Read |
| HR 520 | Phase average RMS current | FLOAT32 ABCD | Average current | Read |
| HR 550 | System power factor | FLOAT32 ABCD | Power factor | Read |
| HR 410 | Line frequency | FLOAT32 ABCD | Frequency | Read |
| HR 400 | Active system conditions | BITMAP16 | System condition flags | Read |
Enable Modbus control & writes
Modbus is on by default (protocol Auto). Lock baud/parity/protocol with R122-R128 for permanent installations.
Byte order & addressing
- Read and write both registers of a 32-bit value together.
- Units change with R163/R173/R133/R153; check them before scaling.
- The meter answers the global address 255 as well as its own address.
Network setup
- Default address = 100 + last two digits of the serial number.
- Hold the Setup button while powering up to clear learned line settings.
Watch out for
- Writing a new baud rate cuts communication until the master matches it.
- On a mixed-baud network auto-detection is unpredictable; set the line settings manually.
Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 102doc R102 | Reset reason | UINT16 | Read | |||||
| HR | 103doc R103 | Reset count | UINT16 | Read | |||||
| HR | 104doc R104/05 | Up time | Time since last reset. | UINT32 | ABCD | s | Read | ||
| HR | 111doc R111 | Identify meter | Flash LEDs to find the meter (BOOL). | UINT16 | Read/write | 0 = Inactive; 1 = Active (all LEDs blink green) | |||
| HR | 122doc R122 | RS485 protocol | UINT16 | Read/write | 1 = Auto; 2 = BACnet; 3 = Modbus RTU; 4 = Modbus ASCII; 5 = BACnet + Modbus RTU; 6 = BACnet + Modbus ASCII; 7 = Modbus RTU + ASCII; 8 = Any protocol | ||||
| HR | 123doc R123 | Slave address | 1-254; also answers global address 255. | UINT16 | Read/write | ||||
| HR | 124doc R124/25 | RS485 baud rate | 1200-460800; writing it turns auto-baud off. | UINT32 | ABCD | baud | Read/write | ||
| HR | 126doc R126 | RS485 parity | UINT16 | Read/write | 1 = Auto; 2 = None; 3 = Odd; 4 = Even | ||||
| HR | 127doc R127 | RS485 data bits | UINT16 | Read/write | 1 = Auto; 2 = 7 bits; 3 = 8 bits | ||||
| HR | 128doc R128 | RS485 stop bits | UINT16 | Read/write | 1 = Auto; 2 = 1 bit; 3 = 1.5 bits; 4 = 2 bits | ||||
| HR | 133doc R133 | Temperature units | UINT16 | Read/write | 1 = °F; 2 = °C | ||||
| HR | 153doc R153 | Angle units | UINT16 | Read/write | 1 = Degrees; 2 = Radians | ||||
| HR | 161doc R161 | System phase selection | Which phases make up system totals. | UINT16 | Read/write | 1 = 3 phase; 2 = R and S; 3 = S and T; 4 = R and T | |||
| HR | 163doc R163 | Power units | Reactive and apparent power follow the same scale. | UINT16 | Read/write | 1 = kW; 2 = W; 3 = MW | |||
| HR | 170doc R170 | Energy data type | UINT16 | Read/write | 0 = Floating point; 1 = Unsigned integer 0-999999 (wraps) | ||||
| HR | 173doc R173 | Energy units | Reactive and apparent energy follow the same scale. | UINT16 | Read/write | 1 = kWh; 2 = Wh; 3 = MWh | |||
| HR | 194doc R194 | Energy reset count | UINT16 | Read | |||||
| HR | 200doc R200 | Setup button | Reads 1 while the button is pressed. | UINT16 | Read | ||||
| HR | 201doc R201 | Binary input 1 | Stable state of pulse input 1 (input is active low). | UINT16 | Read | ||||
| HR | 202doc R202 | Binary input 2 | Stable state of pulse input 2 (input is active low). | UINT16 | Read | ||||
| HR | 210doc R210/11 | Pulse input 1 count | UINT32 | ABCD | Read/write | ||||
| HR | 220doc R220/21 | Pulse input 2 count | UINT32 | ABCD | Read/write | ||||
| HR | 310doc R310/11 | Temperature | Meter ambient temperature; unit set by R133 (default °F). | FLOAT32 | ABCD | °F / °C | Read | ||
| HR | 380doc R380/81 | Power supply voltage | Internal supply voltage after rectification. | FLOAT32 | ABCD | V | Read | ||
| HR | 400doc R400 | Active system conditions | BITMAP16 | Read | bit 5 = Mismatched voltage; bit 6 = Reverse RST order; bit 7 = Not 3-phase; bit 12 = Frequency drift; bit 15 = Phase drift | ||||
| HR | 401doc R401 | Previous system conditions | Latched copy of R400; write 0 to clear. | BITMAP16 | Read/write | bit 5 = Mismatched voltage; bit 6 = Reverse RST order; bit 7 = Not 3-phase; bit 12 = Frequency drift; bit 15 = Phase drift | |||
| HR | 410doc R410/11 | Line frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 420doc R420/21 | Phase average RMS voltage | Average of valid phases. | FLOAT32 | ABCD | V | Read | ||
| HR | 450doc R450/51 | Phase-to-phase average RMS voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 520doc R520/21 | Phase average RMS current | FLOAT32 | ABCD | A | Read | |||
| HR | 540doc R540/41 | Phase average current angle | Unit set by R153. | FLOAT32 | ABCD | deg / rad | Read | ||
| HR | 550doc R550/51 | System power factor | FLOAT32 | ABCD | Read | ||||
| HR | 600doc R600/01 | Total real power | Unit set by R163 (default kW). | FLOAT32 | ABCD | kW | Read | ||
| HR | 610doc R610/11 | Phase average real power | Unit set by R163. | FLOAT32 | ABCD | kW | Read | ||
| HR | 620doc R620/21 | Net real power | Negative = net export. Unit set by R163. | FLOAT32 | ABCD | kW | Read | ||
| HR | 640doc R640/41 | Total reactive power | Unit follows R163 (default kVAR). | FLOAT32 | ABCD | kVAR | Read | ||
| HR | 660doc R660/61 | Total apparent power | Unit follows R163 (default kVA). | FLOAT32 | ABCD | kVA | Read | ||
| HR | 700doc R700/01 | Total real energy | Unit set by R173 (default kWh); type per R170. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 702doc R702/03 | Total real energy import | FLOAT32 | ABCD | kWh | Read | |||
| HR | 704doc R704/05 | Total real energy export | FLOAT32 | ABCD | kWh | Read | |||
| HR | 706doc R706/07 | Total real energy net | FLOAT32 | ABCD | kWh | Read | |||
| HR | 720doc R720/21 | System real energy | FLOAT32 | ABCD | kWh | Read | |||
| HR | 722doc R722/23 | System real energy import | FLOAT32 | ABCD | kWh | Read | |||
| HR | 724doc R724/25 | System real energy export | FLOAT32 | ABCD | kWh | Read | |||
| HR | 740doc R740/41 | Total reactive energy | Unit follows R173 (default kVARh). | FLOAT32 | ABCD | kVARh | Read | ||
| HR | 760doc R760/61 | Total apparent energy | Unit follows R173 (default kVAh). | FLOAT32 | ABCD | kVAh | Read | ||
| HR | 800doc R800/01 | Demand real power | Current demand window. Unit per R163. | FLOAT32 | ABCD | kW | Read | ||
| HR | 806doc R806/07 | Maximum demand real power | FLOAT32 | ABCD | kW | Read | |||
| HR | 840doc R840/41 | Demand reactive power | FLOAT32 | ABCD | kVAR | Read | |||
| HR | 860doc R860/61 | Demand apparent power | FLOAT32 | ABCD | kVA | Read | |||
| HR | 1102doc R1102 | R phase CVT present | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 1103doc R1103 | R phase CVT status | UINT16 | Read | 1 = No CVT; 2 = No error; 3 = Detection error; 4 = Communication error; 5 = Configuration error; 6 = Version error; 7 = Technology error | ||||
| HR | 1140doc R1140/41 | R phase CVT voltage rating | FLOAT32 | ABCD | V | Read | |||
| HR | 1150doc R1150/51 | R phase CVT current rating | FLOAT32 | ABCD | A | Read | |||
| HR | 1152doc R1152/53 | R phase current multiplier | Default 1.0. | FLOAT32 | ABCD | Read/write | |||
| HR | 1400doc R1400 | R phase active conditions | BITMAP16 | Read | bit 0 = Sensor fault; bit 1 = No load; bit 2 = Negative power; bit 3 = Phase loss; bit 4 = Bad frequency; bit 5 = Low power factor; bit 6 = Over current; bit 7 = Over voltage; bit 8 = High harmonics; bit 9 = Unexpected sensor; bit 10 = Missing sensor; bit 11 = Surge voltage; bit 13 = Brown-out voltage | ||||
| HR | 1401doc R1401 | R phase previous conditions | Write 0 to clear. | BITMAP16 | Read/write | bit 0 = Sensor fault; bit 1 = No load; bit 2 = Negative power; bit 3 = Phase loss; bit 4 = Bad frequency; bit 5 = Low power factor; bit 6 = Over current; bit 7 = Over voltage; bit 8 = High harmonics; bit 9 = Unexpected sensor; bit 10 = Missing sensor; bit 11 = Surge voltage; bit 13 = Brown-out voltage | |||
| HR | 1420doc R1420/21 | R phase RMS voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 1450doc R1450/51 | R phase-to-phase RMS voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 1520doc R1520/21 | R phase RMS current | Includes current multiplier; always positive. | FLOAT32 | ABCD | A | Read | ||
| HR | 1540doc R1540/41 | R phase current angle | Unit set by R153. | FLOAT32 | ABCD | deg / rad | Read | ||
| HR | 1550doc R1550/51 | R phase power factor | FLOAT32 | ABCD | Read | ||||
| HR | 1600doc R1600/01 | R phase real power | Unit per R163. | FLOAT32 | ABCD | kW | Read | ||
| HR | 1640doc R1640/41 | R phase reactive power | FLOAT32 | ABCD | kVAR | Read | |||
| HR | 1660doc R1660/61 | R phase apparent power | FLOAT32 | ABCD | kVA | Read | |||
| HR | 1700doc R1700/01 | R phase total real energy | Unit per R173; type per R170. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 1740doc R1740/41 | R phase total reactive energy | FLOAT32 | ABCD | kVARh | Read | |||
| HR | 1760doc R1760/61 | R phase total apparent energy | FLOAT32 | ABCD | kVAh | Read | |||
| HR | 1800doc R1800/01 | R phase demand real power | FLOAT32 | ABCD | kW | Read | |||
| HR | 2103doc R2103 | S phase CVT status | UINT16 | Read | 1 = No CVT; 2 = No error; 3 = Detection error; 4 = Communication error; 5 = Configuration error; 6 = Version error; 7 = Technology error | ||||
| HR | 2400doc R2400 | S phase active conditions | BITMAP16 | Read | bit 0 = Sensor fault; bit 1 = No load; bit 2 = Negative power; bit 3 = Phase loss; bit 4 = Bad frequency; bit 5 = Low power factor; bit 6 = Over current; bit 7 = Over voltage; bit 8 = High harmonics; bit 9 = Unexpected sensor; bit 10 = Missing sensor; bit 11 = Surge voltage; bit 13 = Brown-out voltage | ||||
| HR | 2420doc R2420/21 | S phase RMS voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 2520doc R2520/21 | S phase RMS current | FLOAT32 | ABCD | A | Read | |||
| HR | 2550doc R2550/51 | S phase power factor | FLOAT32 | ABCD | Read | ||||
| HR | 2600doc R2600/01 | S phase real power | Unit per R163. | FLOAT32 | ABCD | kW | Read | ||
| HR | 2700doc R2700/01 | S phase total real energy | Unit per R173. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 3103doc R3103 | T phase CVT status | UINT16 | Read | 1 = No CVT; 2 = No error; 3 = Detection error; 4 = Communication error; 5 = Configuration error; 6 = Version error; 7 = Technology error | ||||
| HR | 3400doc R3400 | T phase active conditions | BITMAP16 | Read | bit 0 = Sensor fault; bit 1 = No load; bit 2 = Negative power; bit 3 = Phase loss; bit 4 = Bad frequency; bit 5 = Low power factor; bit 6 = Over current; bit 7 = Over voltage; bit 8 = High harmonics; bit 9 = Unexpected sensor; bit 10 = Missing sensor; bit 11 = Surge voltage; bit 13 = Brown-out voltage | ||||
| HR | 3420doc R3420/21 | T phase RMS voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 3520doc R3520/21 | T phase RMS current | FLOAT32 | ABCD | A | Read | |||
| HR | 3550doc R3550/51 | T phase power factor | FLOAT32 | ABCD | Read | ||||
| HR | 3600doc R3600/01 | T phase real power | Unit per R163. | FLOAT32 | ABCD | kW | Read | ||
| HR | 3700doc R3700/01 | T phase total real energy | Unit per R173. | FLOAT32 | ABCD | kWh | Read |
Notes on this map
- Word order: the data-types section says UINT32 and FLOAT use two registers in network byte order and gives byte examples (0xAABBCCDD sent as AA BB CC DD across registers r and r+1), so the high word comes first (ABCD).
- Units are settable: power follows R163 (default kW), energy R173 (default kWh), temperature R133 (default °F), angles R153 (default degrees). The units listed here are the defaults.
- Energy registers (R700-R765, R1700-R1765) read as floats by default; with R170 = 1 they read as unsigned integers 0-999999 that wrap. They are listed as FLOAT32 here (the default).
- Most analog measurements also have Instantaneous, Minimum, Maximum and Average copies in the next registers (for example R422 instantaneous, R424 min, R426 max, R428 average for R420); those copies are not listed. Writing 0 resets a statistic.
- Default slave address is 100 plus the last two digits of the serial number. Baud (9600-115200), parity, data bits and protocol are auto-detected out of the box.
- Strings (CVT serial/model, location) and the remaining PowerPrint, pulse-input and multiplier settings are left out for length.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII)
What Modbus registers does the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) have?
This map lists 83 registers: 83 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints raw protocol addresses with an R prefix (R420 = wire address 420; Modicon 40421). R420/21 marks a two-register value starting at 420. S phase registers are R phase + 1000, T phase + 2000.
What byte order does the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII)?
Start with HR 600 Total real power (Total real power); HR 700 Total real energy (Total real energy); HR 420 Phase average RMS voltage (Average voltage); HR 520 Phase average RMS current (Average current); HR 550 System power factor (Power factor); HR 410 Line frequency (Frequency); HR 400 Active system conditions (System condition flags).
How do I enable Modbus control of the Senva EM-RS485 networked energy meter (Modbus RTU/ASCII)?
Modbus is on by default (protocol Auto). Lock baud/parity/protocol with R122-R128 for permanent installations.
Where is the official Senva EM-RS485 networked energy meter (Modbus RTU/ASCII) Modbus documentation?
The source is EM-RS485 Modbus Protocol Guide (154-0023-0B), revision 2017-04-10, published free by Senva at https://senvainc.com/catalog/documents/downloadcenter/EM-RS485%20Modbus%20Protocol%20Guide.pdf.
More Senva Modbus register maps
Other power & energy meters register maps
- Sensor (geotechnical: inclinometer, tiltmeter, piezometer, extensometer)
SISGEO SISGEO digital instruments, RS-485 Modbus (firmware 3.x normal mode)
SISGEO digital instruments with firmware 0x0300 or later running in normal (non-legacy) mode, protocol manual EN 05/20.
Also known as: SISGEO digital in-place inclinometer, SISGEO digital tiltmeter, SISGEO digital piezometer, SISGEO DEX, SISGEO digital extensometer - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS - Power meter
BTicino PM multifunction meter F3N200 (Modbus RTU)
BTicino PM multifunction meter catalogue number F3N200 with RS-485, per Modbus table IDP000024 v1.01.
Also known as: F3N200, BTicino PM F3N200 - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN Ethernet (E1)
EM24-DIN energy analyzers with the E1 Ethernet (RJ45) Modbus TCP port, AV2 and AV5 inputs, X/PFA/PFB, protocol version 0 revision 1.3 (FW 1.0).
Also known as: EM24 E1, EM24_E1, EM24DINAV23XE1X, EM24DINAV23XE1PFA, EM24DINAV23XE1PFB, EM24DINAV53XE1X, EM24DINAV53XE1PFA, EM24DINAV53XE1PFB - Energy meter
Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)
EM580-IS MID/Eichrecht AC meters (DEB, DET, DEA variants, 256/384-bit signatures), protocol version 1.11.
Also known as: EM580-IS, EM580DINAV23XS2DEB, EM580DINAV23XS3DEB, EM580DINAV23XS2DET, EM580DINAV23XS3DET, EM580DINAV23XS2DEA, EM580DINAV23XS3DEA
All power & energy meters Modbus register maps →
Source: EM-RS485 Modbus Protocol Guide · 154-0023-0B · rev. 2017-04-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.