Energy meter · Modbus register map

Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The EM580 is a DIN-rail three-phase AC energy meter for AC charging stations, with signed (Eichrecht) energy data and an RS485 Modbus RTU port. Readings are 32-bit integers sent low word first with fixed weights. This map covers per-phase and system V, A, W, VA, var, PF, frequency, energy totals, the device state word, serial settings and the main OCMF charging-session registers.

This page lists 68 Modbus registers for the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Carlo Gavazzi’s own free documentation (linked below) and checked against it.

Manufacturer
Carlo Gavazzi
Model
EM580 three-phase AC energy meter for EV chargers (Modbus RTU)
Equipment type
Energy meter
Registers
68 (15 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Firmware
Display-string and transaction-ID registers need firmware 1.5.3 onward
Also known as
EM580-IS, EM580DINAV23XS2DEB, EM580DINAV23XS3DEB, EM580DINAV23XS2DET, EM580DINAV23XS3DET, EM580DINAV23XS2DEA, EM580DINAV23XS3DEA
Source document
EM580 Modbus Communication Protocol - Public version · Version 1.11 · rev. 2025-04-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)

Integration in brief

Read input registers 0000h-0057h in one request (function 04 or 03): INT32 values low word first, V/W/VA/var x10, A x1000, PF and Hz as INT16 x1000 and x10. Use 7040h/7045h/7100h for OCMF signed sessions.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0V L1-NINT32 CDABV L1-NRead
IR 12A L1INT32 CDABA L1Read
IR 40W sysINT32 CDABW sysRead
IR 49PF sysINT16PF sysRead
IR 51FrequencyINT16FrequencyRead
IR 52kWh (+) TOTINT32 CDABImported kWh totalRead
IR 78kWh (-) TOTINT32 CDABExported kWh totalRead
HR 28741Charging statusUINT16Charging session statusRead

Enable Modbus control & writes

Modbus RTU on the RS485 port is always active; set address and line settings at 2000h-2004h and write 1 to 2010h to apply.

Byte order & addressing

Network setup

Watch out for

Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

68 of 68 shown
Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 300001 / 0000hV L1-NINT32CDAB× 0.1VRead
IR2doc 300003 / 0002hV L2-NINT32CDAB× 0.1VRead
IR4doc 300005 / 0004hV L3-NINT32CDAB× 0.1VRead
IR6doc 300007 / 0006hV L1-L2INT32CDAB× 0.1VRead
IR8doc 300009 / 0008hV L2-L3INT32CDAB× 0.1VRead
IR10doc 300011 / 000AhV L3-L1INT32CDAB× 0.1VRead
IR11doc 300012 / 000BhCarlo Gavazzi identification codeUINT16Read1840 = EM580DINAV23XS2DEB; 1841 = EM580DINAV23XS3DEB; 1842 = EM580DINAV23XS2DET; 1843 = EM580DINAV23XS3DET; 1844 = EM580DINAV23XS2DEA; 1845 = EM580DINAV23XS3DEA
IR12doc 300013 / 000ChA L1INT32CDAB× 0.001ARead
IR14doc 300015 / 000EhA L2INT32CDAB× 0.001ARead
IR16doc 300017 / 0010hA L3INT32CDAB× 0.001ARead
IR18doc 300019 / 0012hW L1INT32CDAB× 0.1WRead
IR20doc 300021 / 0014hW L2INT32CDAB× 0.1WRead
IR22doc 300023 / 0016hW L3INT32CDAB× 0.1WRead
IR24doc 300025 / 0018hVA L1INT32CDAB× 0.1VARead
IR26doc 300027 / 001AhVA L2INT32CDAB× 0.1VARead
IR28doc 300029 / 001ChVA L3INT32CDAB× 0.1VARead
IR30doc 300031 / 001Ehvar L1INT32CDAB× 0.1varRead
IR32doc 300033 / 0020hvar L2INT32CDAB× 0.1varRead
IR34doc 300035 / 0022hvar L3INT32CDAB× 0.1varRead
IR36doc 300037 / 0024hV L-N sysINT32CDAB× 0.1VRead
IR38doc 300039 / 0026hV L-L sysINT32CDAB× 0.1VRead
IR40doc 300041 / 0028hW sysINT32CDAB× 0.1WRead
IR42doc 300043 / 002AhVA sysINT32CDAB× 0.1VARead
IR44doc 300045 / 002Chvar sysINT32CDAB× 0.1varRead
IR46doc 300047 / 002EhPF L1Negative = exported active power; lead/lag flag is at 0076h-0079h.INT16× 0.001Read
IR47doc 300048 / 002FhPF L2Negative = exported active power; lead/lag flag is at 0076h-0079h.INT16× 0.001Read
IR48doc 300049 / 0030hPF L3Negative = exported active power; lead/lag flag is at 0076h-0079h.INT16× 0.001Read
IR49doc 300050 / 0031hPF sysNegative = exported active power; lead/lag flag is at 0076h-0079h.INT16× 0.001Read
IR50doc 300051 / 0032hPhase sequenceMeaningful on 3-phase systems only.INT16Read1 = L1-L2-L3; -1 = L1-L3-L2
IR51doc 300052 / 0033hFrequencyINT16× 0.1HzRead
IR52doc 300053 / 0034hkWh (+) TOTINT32CDAB× 0.1kWhRead
IR54doc 300055 / 0036hkvarh (+) TOTINT32CDAB× 0.1kvarhRead
IR78doc 300079 / 004EhkWh (-) TOTINT32CDAB× 0.1kWhRead
IR80doc 300081 / 0050hkvarh (-) TOTINT32CDAB× 0.1kvarhRead
IR86doc 300087 / 0056hkVAh TOTINT32CDAB× 0.1kVAhRead
IR118doc 300119 / 0076hInductive/capacitive load phase 1INT16Read1 = Inductive (L); -1 = Capacitive (C)
IR119doc 300120 / 0077hInductive/capacitive load phase 2INT16Read1 = Inductive (L); -1 = Capacitive (C)
IR120doc 300121 / 0078hInductive/capacitive load phase 3INT16Read1 = Inductive (L); -1 = Capacitive (C)
IR121doc 300122 / 0079hInductive/capacitive load sysINT16Read1 = Inductive (L); -1 = Capacitive (C)
IR770doc 300771 / 0302hFirmware version measure moduleHigh byte: bits 0-3 minor, bits 4-7 major; low byte: revision.UINT16Read
IR771doc 300772 / 0303hFirmware version communication moduleSame packing as 0302h.UINT16Read
IR775doc 300776 / 0307hInternal temperatureINT16× 0.1°CRead
HR4096doc 304097 / 1000hPassword0 = no password (default), up to 9999.UINT16Read/write
HR4098doc 304099 / 1002hMeasuring systemUINT16Read/write0 = 3Pn - 3-phase with neutral (default); 1 = 1P - single phase with neutral
HR4355doc 304356 / 1103hEasy connectionUINT16Read/write0 = Disabled (default); 1 = Enabled
HR4361doc 304362 / 1109hQuick set up at next power onUINT16Read/write0 = Menu disabled; 1 = Menu enabled (default)
HR8192doc 308193 / 2000hRS485 instrument address1-247, default 1.UINT16Read/write
HR8193doc 308194 / 2001hRS485 baud rateUINT16Read/write1 = 9.6 kbps (default); 2 = 19.2 kbps; 3 = 38.4 kbps; 4 = 57.6 kbps; 5 = 115.2 kbps
HR8194doc 308195 / 2002hRS485 parityUINT16Read/write1 = No parity (default); 2 = Even parity
HR8195doc 308196 / 2003hStop bitUINT16Read/write1 = 1 (default); 2 = 2
HR8196doc 308197 / 2004hRS485 delay on reply0-1000, default 0.UINT16msRead/write
HR8208doc 308209 / 2010hUpdate serial communication settingsWrite 1 to apply new serial settings.UINT16Read/write
HR9471doc 309472 / 24FFhSignature typeUINT16Read0 = 256-bit signature; 1 = 384-bit signature; 2 = No signature
HR20487doc 320488 / 5007hProduction yearFour digits.UINT16Read
HR20498doc 320499 / 5012hDevice stateBITMAP16Readbit 0 = V1N over range; bit 1 = V2N over range; bit 2 = V3N over range; bit 3 = V12 over range; bit 4 = V23 over range; bit 5 = V31 over range; bit 6 = I1 over range; bit 7 = I2 over range; bit 8 = I3 over range; bit 9 = Frequency outside validity range; bit 12 = EVCS module internal fault; bit 13 = Measure module internal fault
HR20736doc 320737 / 5100hCable loss valueCable resistance used to correct energy; max 500.INT32CDABmOhmRead
HR28721doc 328722 / 7031hLocal time deltaOffset from UTC, -1440 to 1440.INT16minRead/write
HR28726doc 328727 / 7036hDisplay charging directionUINT16Read/write0 = Charging vehicle; 1 = Vehicle to grid; 2 = Bidirectional
HR28736doc 328737 / 7040hOCMF commandWrite ASCII 'B' to begin, 'E' to end, 'A' to abort a transaction.UINT16Read/write
HR28741doc 328742 / 7045hCharging statusUINT16Read0 = No charging; 1 = Charging; 2 = End of last transaction; 3 = End of last transaction with error
HR28752doc 328753 / 7050hCharging session end page duration60-300, default 300.UINT16sRead/write
HR28768doc 328769 / 7060hTime synchronization statusUINT16Read0 = Time not synchronized; 1 = Time synchronized
HR28928doc 328929 / 7100hOCMF stateWrite 0 after reading the OCMF file to allow a new session.UINT16Read/write0 = Not ready; 1 = Running; 2 = Ready; 3 = Saved file corrupted
HR28929doc 328930 / 7101hOCMF file lengthUINT16wordsRead
HR28930doc 328931 / 7102hOCMF last transaction idUINT32CDABRead
HR31232doc 331233 / 7A00hSession delta kWh+UINT64CDABWhRead
HR31236doc 331237 / 7A04hSession delta kWh-UINT64CDABWhRead
HR31240doc 331241 / 7A08hSession durationUINT64CDABsRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)

What Modbus registers does the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) have?

This map lists 68 registers: 42 input registers, 26 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Rows give a 6-digit Modicon number (3xxxxx with function 04, 4xxxxx with function 03) and the hex physical address used in the frame; 300001 / 0000h is wire address 0. Functions 03 and 04 are equivalent.

What byte order does the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)?

Start with IR 0 V L1-N (V L1-N); IR 12 A L1 (A L1); IR 40 W sys (W sys); IR 49 PF sys (PF sys); IR 51 Frequency (Frequency); IR 52 kWh (+) TOT (Imported kWh total); IR 78 kWh (-) TOT (Exported kWh total); HR 28741 Charging status (Charging session status).

How do I enable Modbus control of the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)?

Modbus RTU on the RS485 port is always active; set address and line settings at 2000h-2004h and write 1 to 2010h to apply.

Where is the official Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) Modbus documentation?

The source is EM580 Modbus Communication Protocol - Public version (Version 1.11), revision 2025-04-08, published free by Carlo Gavazzi at https://www.gavazziautomation.com/fileadmin/images/PIM/OTHERSTUFF/COMPRO/EM580_CPP.pdf.

More Carlo Gavazzi Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: EM580 Modbus Communication Protocol - Public version · Version 1.11 · rev. 2025-04-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.