- EM580 three-phase AC energy meter for EV chargers (Modbus RTU)
Energy meter · Modbus register map
Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) Modbus register map
Updated 17 November 2026
The EM580 is a DIN-rail three-phase AC energy meter for AC charging stations, with signed (Eichrecht) energy data and an RS485 Modbus RTU port. Readings are 32-bit integers sent low word first with fixed weights. This map covers per-phase and system V, A, W, VA, var, PF, frequency, energy totals, the device state word, serial settings and the main OCMF charging-session registers.
This page lists 68 Modbus registers for the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Carlo Gavazzi’s own free documentation (linked below) and checked against it.
- Manufacturer
- Carlo Gavazzi
- Model
- EM580 three-phase AC energy meter for EV chargers (Modbus RTU)
- Equipment type
- Energy meter
- Registers
- 68 (15 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- Display-string and transaction-ID registers need firmware 1.5.3 onward
- Also known as
- EM580-IS, EM580DINAV23XS2DEB, EM580DINAV23XS3DEB, EM580DINAV23XS2DET, EM580DINAV23XS3DET, EM580DINAV23XS2DEA, EM580DINAV23XS3DEA
Integration notes: Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)
Read input registers 0000h-0057h in one request (function 04 or 03): INT32 values low word first, V/W/VA/var x10, A x1000, PF and Hz as INT16 x1000 and x10. Use 7040h/7045h/7100h for OCMF signed sessions.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | V L1-N | INT32 CDAB | V L1-N | Read |
| IR 12 | A L1 | INT32 CDAB | A L1 | Read |
| IR 40 | W sys | INT32 CDAB | W sys | Read |
| IR 49 | PF sys | INT16 | PF sys | Read |
| IR 51 | Frequency | INT16 | Frequency | Read |
| IR 52 | kWh (+) TOT | INT32 CDAB | Imported kWh total | Read |
| IR 78 | kWh (-) TOT | INT32 CDAB | Exported kWh total | Read |
| HR 28741 | Charging status | UINT16 | Charging session status | Read |
Enable Modbus control & writes
Modbus RTU on the RS485 port is always active; set address and line settings at 2000h-2004h and write 1 to 2010h to apply.
Byte order & addressing
- 32-bit values are CDAB.
- PF sign shows import/export; the separate L/C words give lead/lag.
Network setup
- Defaults: address 1, 9600 baud, no parity, 1 stop bit.
- Max answer time 500 ms, typical 40 ms.
Watch out for
- Write 0 to 7100h after reading the OCMF file or a new session will not start.
- Sync the clock (7031h/7032h) at least every 24 h for signed data.
Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 300001 / 0000h | V L1-N | INT32 | CDAB | × 0.1 | V | Read | ||
| IR | 2doc 300003 / 0002h | V L2-N | INT32 | CDAB | × 0.1 | V | Read | ||
| IR | 4doc 300005 / 0004h | V L3-N | INT32 | CDAB | × 0.1 | V | Read | ||
| IR | 6doc 300007 / 0006h | V L1-L2 | INT32 | CDAB | × 0.1 | V | Read | ||
| IR | 8doc 300009 / 0008h | V L2-L3 | INT32 | CDAB | × 0.1 | V | Read | ||
| IR | 10doc 300011 / 000Ah | V L3-L1 | INT32 | CDAB | × 0.1 | V | Read | ||
| IR | 11doc 300012 / 000Bh | Carlo Gavazzi identification code | UINT16 | Read | 1840 = EM580DINAV23XS2DEB; 1841 = EM580DINAV23XS3DEB; 1842 = EM580DINAV23XS2DET; 1843 = EM580DINAV23XS3DET; 1844 = EM580DINAV23XS2DEA; 1845 = EM580DINAV23XS3DEA | ||||
| IR | 12doc 300013 / 000Ch | A L1 | INT32 | CDAB | × 0.001 | A | Read | ||
| IR | 14doc 300015 / 000Eh | A L2 | INT32 | CDAB | × 0.001 | A | Read | ||
| IR | 16doc 300017 / 0010h | A L3 | INT32 | CDAB | × 0.001 | A | Read | ||
| IR | 18doc 300019 / 0012h | W L1 | INT32 | CDAB | × 0.1 | W | Read | ||
| IR | 20doc 300021 / 0014h | W L2 | INT32 | CDAB | × 0.1 | W | Read | ||
| IR | 22doc 300023 / 0016h | W L3 | INT32 | CDAB | × 0.1 | W | Read | ||
| IR | 24doc 300025 / 0018h | VA L1 | INT32 | CDAB | × 0.1 | VA | Read | ||
| IR | 26doc 300027 / 001Ah | VA L2 | INT32 | CDAB | × 0.1 | VA | Read | ||
| IR | 28doc 300029 / 001Ch | VA L3 | INT32 | CDAB | × 0.1 | VA | Read | ||
| IR | 30doc 300031 / 001Eh | var L1 | INT32 | CDAB | × 0.1 | var | Read | ||
| IR | 32doc 300033 / 0020h | var L2 | INT32 | CDAB | × 0.1 | var | Read | ||
| IR | 34doc 300035 / 0022h | var L3 | INT32 | CDAB | × 0.1 | var | Read | ||
| IR | 36doc 300037 / 0024h | V L-N sys | INT32 | CDAB | × 0.1 | V | Read | ||
| IR | 38doc 300039 / 0026h | V L-L sys | INT32 | CDAB | × 0.1 | V | Read | ||
| IR | 40doc 300041 / 0028h | W sys | INT32 | CDAB | × 0.1 | W | Read | ||
| IR | 42doc 300043 / 002Ah | VA sys | INT32 | CDAB | × 0.1 | VA | Read | ||
| IR | 44doc 300045 / 002Ch | var sys | INT32 | CDAB | × 0.1 | var | Read | ||
| IR | 46doc 300047 / 002Eh | PF L1 | Negative = exported active power; lead/lag flag is at 0076h-0079h. | INT16 | × 0.001 | Read | |||
| IR | 47doc 300048 / 002Fh | PF L2 | Negative = exported active power; lead/lag flag is at 0076h-0079h. | INT16 | × 0.001 | Read | |||
| IR | 48doc 300049 / 0030h | PF L3 | Negative = exported active power; lead/lag flag is at 0076h-0079h. | INT16 | × 0.001 | Read | |||
| IR | 49doc 300050 / 0031h | PF sys | Negative = exported active power; lead/lag flag is at 0076h-0079h. | INT16 | × 0.001 | Read | |||
| IR | 50doc 300051 / 0032h | Phase sequence | Meaningful on 3-phase systems only. | INT16 | Read | 1 = L1-L2-L3; -1 = L1-L3-L2 | |||
| IR | 51doc 300052 / 0033h | Frequency | INT16 | × 0.1 | Hz | Read | |||
| IR | 52doc 300053 / 0034h | kWh (+) TOT | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 54doc 300055 / 0036h | kvarh (+) TOT | INT32 | CDAB | × 0.1 | kvarh | Read | ||
| IR | 78doc 300079 / 004Eh | kWh (-) TOT | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 80doc 300081 / 0050h | kvarh (-) TOT | INT32 | CDAB | × 0.1 | kvarh | Read | ||
| IR | 86doc 300087 / 0056h | kVAh TOT | INT32 | CDAB | × 0.1 | kVAh | Read | ||
| IR | 118doc 300119 / 0076h | Inductive/capacitive load phase 1 | INT16 | Read | 1 = Inductive (L); -1 = Capacitive (C) | ||||
| IR | 119doc 300120 / 0077h | Inductive/capacitive load phase 2 | INT16 | Read | 1 = Inductive (L); -1 = Capacitive (C) | ||||
| IR | 120doc 300121 / 0078h | Inductive/capacitive load phase 3 | INT16 | Read | 1 = Inductive (L); -1 = Capacitive (C) | ||||
| IR | 121doc 300122 / 0079h | Inductive/capacitive load sys | INT16 | Read | 1 = Inductive (L); -1 = Capacitive (C) | ||||
| IR | 770doc 300771 / 0302h | Firmware version measure module | High byte: bits 0-3 minor, bits 4-7 major; low byte: revision. | UINT16 | Read | ||||
| IR | 771doc 300772 / 0303h | Firmware version communication module | Same packing as 0302h. | UINT16 | Read | ||||
| IR | 775doc 300776 / 0307h | Internal temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 4096doc 304097 / 1000h | Password | 0 = no password (default), up to 9999. | UINT16 | Read/write | ||||
| HR | 4098doc 304099 / 1002h | Measuring system | UINT16 | Read/write | 0 = 3Pn - 3-phase with neutral (default); 1 = 1P - single phase with neutral | ||||
| HR | 4355doc 304356 / 1103h | Easy connection | UINT16 | Read/write | 0 = Disabled (default); 1 = Enabled | ||||
| HR | 4361doc 304362 / 1109h | Quick set up at next power on | UINT16 | Read/write | 0 = Menu disabled; 1 = Menu enabled (default) | ||||
| HR | 8192doc 308193 / 2000h | RS485 instrument address | 1-247, default 1. | UINT16 | Read/write | ||||
| HR | 8193doc 308194 / 2001h | RS485 baud rate | UINT16 | Read/write | 1 = 9.6 kbps (default); 2 = 19.2 kbps; 3 = 38.4 kbps; 4 = 57.6 kbps; 5 = 115.2 kbps | ||||
| HR | 8194doc 308195 / 2002h | RS485 parity | UINT16 | Read/write | 1 = No parity (default); 2 = Even parity | ||||
| HR | 8195doc 308196 / 2003h | Stop bit | UINT16 | Read/write | 1 = 1 (default); 2 = 2 | ||||
| HR | 8196doc 308197 / 2004h | RS485 delay on reply | 0-1000, default 0. | UINT16 | ms | Read/write | |||
| HR | 8208doc 308209 / 2010h | Update serial communication settings | Write 1 to apply new serial settings. | UINT16 | Read/write | ||||
| HR | 9471doc 309472 / 24FFh | Signature type | UINT16 | Read | 0 = 256-bit signature; 1 = 384-bit signature; 2 = No signature | ||||
| HR | 20487doc 320488 / 5007h | Production year | Four digits. | UINT16 | Read | ||||
| HR | 20498doc 320499 / 5012h | Device state | BITMAP16 | Read | bit 0 = V1N over range; bit 1 = V2N over range; bit 2 = V3N over range; bit 3 = V12 over range; bit 4 = V23 over range; bit 5 = V31 over range; bit 6 = I1 over range; bit 7 = I2 over range; bit 8 = I3 over range; bit 9 = Frequency outside validity range; bit 12 = EVCS module internal fault; bit 13 = Measure module internal fault | ||||
| HR | 20736doc 320737 / 5100h | Cable loss value | Cable resistance used to correct energy; max 500. | INT32 | CDAB | mOhm | Read | ||
| HR | 28721doc 328722 / 7031h | Local time delta | Offset from UTC, -1440 to 1440. | INT16 | min | Read/write | |||
| HR | 28726doc 328727 / 7036h | Display charging direction | UINT16 | Read/write | 0 = Charging vehicle; 1 = Vehicle to grid; 2 = Bidirectional | ||||
| HR | 28736doc 328737 / 7040h | OCMF command | Write ASCII 'B' to begin, 'E' to end, 'A' to abort a transaction. | UINT16 | Read/write | ||||
| HR | 28741doc 328742 / 7045h | Charging status | UINT16 | Read | 0 = No charging; 1 = Charging; 2 = End of last transaction; 3 = End of last transaction with error | ||||
| HR | 28752doc 328753 / 7050h | Charging session end page duration | 60-300, default 300. | UINT16 | s | Read/write | |||
| HR | 28768doc 328769 / 7060h | Time synchronization status | UINT16 | Read | 0 = Time not synchronized; 1 = Time synchronized | ||||
| HR | 28928doc 328929 / 7100h | OCMF state | Write 0 after reading the OCMF file to allow a new session. | UINT16 | Read/write | 0 = Not ready; 1 = Running; 2 = Ready; 3 = Saved file corrupted | |||
| HR | 28929doc 328930 / 7101h | OCMF file length | UINT16 | words | Read | ||||
| HR | 28930doc 328931 / 7102h | OCMF last transaction id | UINT32 | CDAB | Read | ||||
| HR | 31232doc 331233 / 7A00h | Session delta kWh+ | UINT64 | CDAB | Wh | Read | |||
| HR | 31236doc 331237 / 7A04h | Session delta kWh- | UINT64 | CDAB | Wh | Read | |||
| HR | 31240doc 331241 / 7A08h | Session duration | UINT64 | CDAB | s | Read |
Notes on this map
- Word order: INT32, UINT32 and UINT64 values are least significant word first with bytes MSB first (CDAB).
- Left out: the mirror INT32 block at 0102h-0146h (same values, different layout), INT64 energy at 0500h-052Ch and the INT64 UTC timestamp at 7032h (no stated word order for signed 64-bit), the 32-bit frequency at 053Ch (part of the INT64 block), signed OBIS maps at 0800h, public keys and signatures, serial number and device tag ASCII words, page filters, OCMF identification and custom-string fields, the OCMF buffer, maintenance mode and the cable-loss datalogger.
- The display shows EEE when the high word of a variable is 7FFFh (over range).
- No total-energy reset register is published for this meter; 4020h is factory reset (write 0x0A0A, then 0xC1A0 within 5 s).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)
What Modbus registers does the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) have?
This map lists 68 registers: 42 input registers, 26 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Rows give a 6-digit Modicon number (3xxxxx with function 04, 4xxxxx with function 03) and the hex physical address used in the frame; 300001 / 0000h is wire address 0. Functions 03 and 04 are equivalent.
What byte order does the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)?
Start with IR 0 V L1-N (V L1-N); IR 12 A L1 (A L1); IR 40 W sys (W sys); IR 49 PF sys (PF sys); IR 51 Frequency (Frequency); IR 52 kWh (+) TOT (Imported kWh total); IR 78 kWh (-) TOT (Exported kWh total); HR 28741 Charging status (Charging session status).
How do I enable Modbus control of the Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)?
Modbus RTU on the RS485 port is always active; set address and line settings at 2000h-2004h and write 1 to 2010h to apply.
Where is the official Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU) Modbus documentation?
The source is EM580 Modbus Communication Protocol - Public version (Version 1.11), revision 2025-04-08, published free by Carlo Gavazzi at https://www.gavazziautomation.com/fileadmin/images/PIM/OTHERSTUFF/COMPRO/EM580_CPP.pdf.
More Carlo Gavazzi Modbus register maps
- Energy meter (DC)
Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP)
DCM1 300 A / 600 A, 1000 V DC meters (MID, Eichrecht and LNE variants) with RS485 and Ethernet, protocol version 1.11.
Also known as: DCM1A60V10L20S1PFA, DCM1A60V10L20S1PFB, DCM1A60V10L20S2DEB, DCM1A60V10L20S3DEB, DCM1A60V10L20S2DEBF, DCM1A60V10L20S3DEBF, DCM1A30V10L20S1PFA, DCM1A30V10L20S1PFB, DCM1A30V10L20S2DEB, DCM1A30V10L20S3DEB, DCM1A30V10L20S2DEBF, DCM1A30V10L20S3DEBF, DCM1A60V10L20S1ULB, DCM1A30V10L20S1ULB - Energy meter (DC)
Carlo Gavazzi DCT1 DC energy meter (Modbus RTU)
DCT1 300 A and 600 A / 1000 V DC meters, with and without signed data (S1/S2/S3), protocol version 1.1.
Also known as: DCT1A60V10LS1X, DCT1A60V10LS2EC, DCT1A60V10LS3EC, DCT1A30V10LS1X, DCT1A30V10LS2EC, DCT1A30V10LS3EC - Energy meter
Carlo Gavazzi EM100 / ET100 series (EM111, EM112, ET112)
Single-phase EM111, EM112 energy meters and ET112 bidirectional meter with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 14.
Also known as: EM111, EM112, ET112, EM110, EM111-DIN, EM112-DIN, ET112-DIN, EM111DINAV81XS1X, EM112DINAV01XS1X, ET112DINAV01XS1X - Energy meter (energy analyzer)
Carlo Gavazzi EM210 (AV versions)
EM210 three-phase energy analyzers, AV input versions with the RS485 Modbus RTU option, protocol version 4 revision 3 (newest variables need firmware A.5/A.6).
Also known as: EM210, EM210-72D, EM210 AV - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN (PFA, PFB and X models)
EM24-DIN three-phase energy analyzers, PFA/PFB (MID) and X models with the RS485 Modbus RTU port (IS option), protocol version 4 revision 0.
Also known as: EM24, EM24DIN, EM24DINAV93XISPFA, EM24DINAV93XISPFB, EM24DINAV93XISX, EM24DINAV53XISX, EM24DINAV23XISX, EM24 DIN AV9, EM24 DIN AV5 - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN Ethernet (E1)
EM24-DIN energy analyzers with the E1 Ethernet (RJ45) Modbus TCP port, AV2 and AV5 inputs, X/PFA/PFB, protocol version 0 revision 1.3 (FW 1.0).
Also known as: EM24 E1, EM24_E1, EM24DINAV23XE1X, EM24DINAV23XE1PFA, EM24DINAV23XE1PFB, EM24DINAV53XE1X, EM24DINAV53XE1PFA, EM24DINAV53XE1PFB - Energy meter
Carlo Gavazzi EM24-IS (SFA and SFB models)
EM24-DIN AV2/AV5 IS SFA and SFB versions (identification codes 1696-1699), protocol revision 2.0.
Also known as: EM24DINAV23XISSFA, EM24DINAV53XISSFA, EM24DINAV23XISSFB, EM24DINAV53XISSFB, EM24 SFA, EM24 SFB - Energy meter
Carlo Gavazzi EM270 / EM280 dual three-phase energy meters with TCD current sensors
EM270 X (firmware r.b0+), EM270 W (r.C0+) and EM280 (r.E0+) on RS485 Modbus RTU, per communication protocol version 5 revision 1 (2018-01-29).
Also known as: EM270, EM280, EM270 X, EM270 W, EM27072DMV53X2SX, EM28072DMV53X2SX - Energy meter
Carlo Gavazzi EM271 dual three-phase energy meter with TCD current sensors
EM271 (firmware r.d0+, PF values from r.d2) on RS485 Modbus RTU, per communication protocol version 1 revision 2 (2018-01-29).
Also known as: EM271, EM27172DMV53X2SX, EM27172DMV63X2SX - Energy meter
Carlo Gavazzi EM300 / ET300 series (EM330, EM340, ET330, ET340)
EM330, EM331, EM340, EM341 energy meters and ET330/ET340 bidirectional meters with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 17.
Also known as: EM330, EM340, ET330, ET340, EM331, EM341, EM330-DIN, EM340-DIN, ET340-DIN, EM340DINAV23XS1X, EM340DINAV23XS1PFA, EM340DINAV23XS1PFB - Energy meter
Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)
EM511 direct-connected single-phase DIN meters with RS485 and digital input (X, PFA, PFB, SFA versions), protocol rev. 1.8.
Also known as: EM511-IS, EM511DINAV81XS1X, EM511DINAV81XS1PFA, EM511DINAV81XS1PFB, EM511DINAV81XS1SFA - Energy meter
Carlo Gavazzi EM530 / EM540 three-phase energy meters (RS485 Modbus)
EM530 (CT-connected) and EM540 (direct-connected) with the S1 RS485 port, X and MID (PFA/PFB/PFC) versions, protocol document version 1.3.
Also known as: EM530, EM540, EM530DINAV53XS1X, EM530DINAV53XS1PFA, EM530DINAV53XS1PFB, EM530DINAV53XS1PFC, EM540DINAV23XS1X, EM540DINAV23XS1PFA, EM540DINAV23XS1PFB, EM540DINAV23XS1PFC, EM500 series - Power meter (power analyzer)
Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)
WM14 Advanced (revision 5 onward) and CPT-DIN Advanced (revision 6 onward) with RS485 (or RS232 on CPT-DIN), protocol version 2 revision 2 (2008-01-09).
Also known as: WM14-96 Advanced, WM14 A, CPT-DIN Advanced, CPT A, CPT-DIN A - Power meter (power analyzer)
Carlo Gavazzi WM15 power analyzer
WM15-96 three-phase panel power analyzers with RS485 Modbus RTU (OS / OSPF / HOS versions), protocol version 1.2.
Also known as: WM15, WM15-96, WM1596AV53XOSX, WM1596AV53XOSPFB, WM1596AV53HOSX - Power meter (power analyzer)
Carlo Gavazzi WM20 / WM30 / WM40 power analyzers
WM20, WM30 and WM40 modular power analyzers with an RS485 (or Ethernet) Modbus module, protocol internal version rev. 4.0 (2018-03-28); WM30 = firmware letter X, WM40 = Y, WM20 = Z.
Also known as: WM20, WM30, WM40, WM20-96, WM30-96, WM40-96 - Power meter (power analyzer)
Carlo Gavazzi WM50 power analyzer with TCD branch channels
WM50 base unit (firmware X0, i.e. all A and B versions) with an MC485232 or MCETH communication module, plus TCD branch channels, per communication protocol user version rev. 1.0.0 (2017-09-27).
Also known as: WM50, WM50AV5, WM50-96, WM50 AV5
Other power & energy meters register maps
- Power meter
Circutor CVM-C10
Circutor CVM-C10 panel power analyzer, RS-485 versions (ITF, MC, mV, ITF-IN), manual M001B01-03-23A.
Also known as: CVM-C10-ITF-485, CVM-C10-MC-485, CVM-C10-mV-485, CVM-C10-ITF-IN-485 - Energy meter (heat / cooling meter)
Diehl Metering SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module
Modbus RTU plug-in communication module (Sylop M/N 11024, firmware 1.0) in a Diehl SHARKY 775 compact heat meter or SCYLAR INT 8 calculator.
Also known as: SHARKY 775, SCYLAR INT 8, Sylop M/N 11024, Diehl Modbus RTU module - Energy meter
Eastron SDM630-DI
Eastron SDM630-DI three-phase DIN-rail meter (100 A direct, two digital inputs, RS485 Modbus RTU), manual V1.02.
Also known as: SDM630 DI - Sensor (electromagnetic flowmeter)
Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)
Proline Promag 400 transmitters with the Modbus RS485 output, as described in GP01045D/06/EN/02.21.
Also known as: Promag D 400, Promag L 400, Promag W 400, Proline 400 Modbus RS485 - Energy meter
Fronius Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)
A Fronius Smart Meter wired to a GEN24 or Tauro inverter over Modbus RTU and republished by the inverter over Modbus TCP, with SunSpec Model Type set to int+SF (meter model 201/202/203).
Also known as: Fronius Smart Meter 63A, Fronius Smart Meter 50kA, Fronius Smart Meter TS, SunSpec meter model 201/202/203 - Power meter
IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD)
IME Nemo 96HDLe for Rogowski coils, code KRNEMOHD, per protocol PR139 (software 1.03).
Also known as: KRNEMOHD
All power & energy meters Modbus register maps →
Source: EM580 Modbus Communication Protocol - Public version · Version 1.11 · rev. 2025-04-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.