Energy meter · Modbus register map

Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The EM511 is a one-module single-phase energy meter (up to 45 A direct) with an RS485 Modbus RTU port and a digital input. Readings are 32-bit integers sent low word first with fixed weights. This map covers V, A, W, VA, var, PF, frequency, demand, THD, import/export and tariff energy, run hours, I/O and alarm status, alarm and tariff setup, serial settings and resets.

This page lists 64 Modbus registers for the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Carlo Gavazzi’s own free documentation (linked below) and checked against it.

Manufacturer
Carlo Gavazzi
Model
EM511 single-phase energy meter (Modbus RTU)
Equipment type
Energy meter
Registers
64 (23 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Firmware
Rows apply to all firmware unless noted (X 1.0, PFx 1.0)
Also known as
EM511-IS, EM511DINAV81XS1X, EM511DINAV81XS1PFA, EM511DINAV81XS1PFB, EM511DINAV81XS1SFA
Source document
EM511 Communication Protocol · rev. 1.8 · rev. 2023-05-23
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)

Integration in brief

Read input registers 0000h-0043h in one request (function 04 or 03). Decode INT32 low word first; V/W/VA/var x10, A x1000, energy x10, hours x100; PF and Hz are INT16 x1000 and x10.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0V L-NINT32 CDABVoltageRead
IR 2AINT32 CDABCurrentRead
IR 4WINT32 CDABActive powerRead
IR 14PF (IEC convention)INT16Power factorRead
IR 15FrequencyINT16FrequencyRead
IR 16kWh (+) TOTINT32 CDABImported kWh totalRead
IR 32kWh (-) TOTINT32 CDABExported kWh totalRead

Enable Modbus control & writes

Modbus RTU on RS485 is always active; serial settings are at 2000h-2004h.

Byte order & addressing

Network setup

Watch out for

Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

64 of 64 shown
Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 300001 / 0000hV L-NINT32CDAB× 0.1VRead
IR2doc 300003 / 0002hAINT32CDAB× 0.001ARead
IR4doc 300005 / 0004hWINT32CDAB× 0.1WRead
IR6doc 300007 / 0006hVAINT32CDAB× 0.1VARead
IR8doc 300009 / 0008hvarINT32CDAB× 0.1varRead
IR10doc 300011 / 000AhW dmdDemand active power.INT32CDAB× 0.1WRead
IR11doc 300012 / 000BhCarlo Gavazzi identification codeUINT16Read1792 = EM511DINAV81XS1X; 1793 = EM511DINAV81XS1PFA; 1794 = EM511DINAV81XS1PFB; 1795 = EM511DINAV81XS1SFA
IR12doc 300013 / 000ChW dmd peakINT32CDAB× 0.1WRead
IR14doc 300015 / 000EhPF (IEC convention)Positive when consuming, negative when generating.INT16× 0.001Read
IR15doc 300016 / 000FhFrequencyINT16× 0.1HzRead
IR16doc 300017 / 0010hkWh (+) TOTINT32CDAB× 0.1kWhRead
IR18doc 300019 / 0012hkvarh (+) TOTINT32CDAB× 0.1kvarhRead
IR20doc 300021 / 0014hkWh (+) PARTIALINT32CDAB× 0.1kWhRead
IR22doc 300023 / 0016hkvarh (+) PARTIALINT32CDAB× 0.1kvarhRead
IR24doc 300025 / 0018hkWh (+) tariff 1INT32CDAB× 0.1kWhRead
IR26doc 300027 / 001AhkWh (+) tariff 2INT32CDAB× 0.1kWhRead
IR32doc 300033 / 0020hkWh (-) TOTINT32CDAB× 0.1kWhRead
IR34doc 300035 / 0022hkvarh (-) TOTINT32CDAB× 0.1kvarhRead
IR36doc 300037 / 0024hkWh (-) PARTIALINT32CDAB× 0.1kWhRead
IR38doc 300039 / 0026hkvarh (-) PARTIALINT32CDAB× 0.1kvarhRead
IR40doc 300041 / 0028hkVAh TOTINT32CDAB× 0.1kVAhRead
IR42doc 300043 / 002AhkVAh PARTIALINT32CDAB× 0.1kVAhRead
IR44doc 300045 / 002ChHour counterINT32CDAB× 0.01hRead
IR46doc 300047 / 002EhHour counter negative energyINT32CDAB× 0.01hRead
IR48doc 300049 / 0030hLifetime counterINT32CDAB× 0.01hRead
IR50doc 300051 / 0032hTHD AINT32CDAB× 0.01%Read
IR52doc 300053 / 0034hTHD V L-NINT32CDAB× 0.01%Read
IR54doc 300055 / 0036hHour counter PARTIALINT32CDAB× 0.01hRead
IR56doc 300057 / 0038hHour counter negative PARTIALINT32CDAB× 0.01hRead
IR58doc 300059 / 003AhA dmdINT32CDAB× 0.001ARead
IR60doc 300061 / 003ChA dmd peakINT32CDAB× 0.001ARead
IR64doc 300065 / 0040hVA dmdINT32CDAB× 0.1VARead
IR66doc 300067 / 0042hVA dmd peakINT32CDAB× 0.1VARead
IR112doc 300113 / 0070hPF (L/C convention)Positive for inductive, negative for capacitive load.INT16× 0.001Read
IR113doc 300114 / 0071hInductive/capacitive loadINT16Read1 = Inductive (L); -1 = Capacitive (C)
IR768doc 300769 / 0300hDigital input statusINT16Read0 = Input open; 1 = Input closed
IR769doc 300770 / 0301hActive tariffINT16Read0 = None; 1 = Tariff 1; 2 = Tariff 2
IR770doc 300771 / 0302hFirmware version and revisionHigh byte: bits 0-3 minor, bits 4-7 major; low byte: revision.UINT16Read
IR774doc 300775 / 0306hAlarm statusINT16Read0 = Not active (or waiting for delay); 1 = Active
HR4096doc 304097 / 1000hPassword0 = no password (default), up to 9999.UINT16Read/write
HR4112doc 304113 / 1010hDemand integration timeUINT32CDABRead/write0 = 1 min; 1 = 5 min; 2 = 10 min; 3 = 15 min (default); 4 = 20 min; 5 = 30 min; 6 = 60 min
HR4116doc 304117 / 1014hAlarm enableUINT16Read/write0 = Disabled (default); 1 = Enabled
HR4117doc 304118 / 1015hAlarm linked variableUINT16Read/write1 = Active power (default); 2 = Apparent power; 3 = Reactive power; 4 = Power factor; 5 = Current; 6 = Voltage
HR4118doc 304119 / 1016hAlarm set point 1 (on)-1000.00 to +1000.00 in units of the linked variable.INT32CDAB× 0.01Read/write
HR4120doc 304121 / 1018hAlarm set point 2 (off)-1000.00 to +1000.00.INT32CDAB× 0.01Read/write
HR4122doc 304123 / 101AhAlarm delay0-3600 s.UINT16sRead/write
HR4353doc 304354 / 1101hTariff management via ModbusUINT16Read/write0 = Off; 1 = On (default)
HR4355doc 304356 / 1103hMeasurement modeFixed on MID versions.UINT16Read/write0 = A mode - absolute (default); 1 = B mode - bidirectional
HR4361doc 304362 / 1109hQuick set up at next power onUINT16Read/write0 = Menu disabled; 1 = Menu enabled (default)
HR4363doc 304360 / 110BhStart-up current of run hour counter20 (0.02 A, default) to 45000 (45 A).UINT32CDAB× 0.001ARead/write
HR4438doc 304439 / 1156hCurrent directionX (non-MID) version only.UINT16Read/write0 = Direct (default); 1 = Inverse
HR4608doc 304609 / 1200hDigital input functionUINT16Read/write0 = Tariff selection; 1 = Remote status input only (default); 2 = Partial meter enable; 3 = Reset partial counters
HR4609doc 304610 / 1201hTariff selection via serialUINT16Read/write1 = Tariff 1 (default); 2 = Tariff 2
HR8192doc 308193 / 2000hRS485 instrument address1-247, default 1.UINT16Read/write
HR8193doc 308194 / 2001hRS485 baud rateUINT16Read/write1 = 9.6 kbps (default); 2 = 19.2 kbps; 3 = 38.4 kbps; 4 = 57.6 kbps; 5 = 115.2 kbps
HR8194doc 308195 / 2002hRS485 parityUINT16Read/write1 = No parity (default); 2 = Even parity
HR8195doc 308196 / 2003hRS485 stop bitUINT16Read/write0 = 1 stop bit (default); 1 = 2 stop bits
HR8196doc 308197 / 2004hRS485 delay on reply0-1000, default 0.UINT16msRead/write
HR16387doc 316388 / 4003hReset total countersWrite 1: totals, run hours and offsets (not lifetime). Not on MID versions.UINT16Read/write
HR16388doc 316389 / 4004hReset partial countersWrite 1: partial energy and partial run hours.UINT16Read/write
HR16389doc 316390 / 4005hReset demand valuesWrite 1: demand and demand max.UINT16Read/write
HR16390doc 316391 / 4006hReset tariff countersWrite 1.UINT16Read/write
HR20487doc 320488 / 5007hProduction yearFour digits.UINT16Read
HR20498doc 320499 / 5012hDevice stateUINT16Read0 = Run; 1 = Fault

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)

What Modbus registers does the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) have?

This map lists 64 registers: 39 input registers, 25 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Rows give a 6-digit Modicon number (3xxxxx, function 04) and the hex physical address used in the frame; 300001 / 0000h is wire address 0. Function 03 reads the same values (replace the leading 3 with 4).

What byte order does the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)?

Start with IR 0 V L-N (Voltage); IR 2 A (Current); IR 4 W (Active power); IR 14 PF (IEC convention) (Power factor); IR 15 Frequency (Frequency); IR 16 kWh (+) TOT (Imported kWh total); IR 32 kWh (-) TOT (Exported kWh total).

How do I enable Modbus control of the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)?

Modbus RTU on RS485 is always active; serial settings are at 2000h-2004h.

Where is the official Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) Modbus documentation?

The source is EM511 Communication Protocol (rev. 1.8), revision 2023-05-23, published free by Carlo Gavazzi at https://www.gavazziautomation.com/fileadmin/images/PIM/OTHERSTUFF/COMPRO/EM511%20CP%20Rev1.8.pdf.

More Carlo Gavazzi Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: EM511 Communication Protocol · rev. 1.8 · rev. 2023-05-23. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.