Energy meter · Modbus register map
Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) Modbus register map
Updated 17 November 2026
The EM511 is a one-module single-phase energy meter (up to 45 A direct) with an RS485 Modbus RTU port and a digital input. Readings are 32-bit integers sent low word first with fixed weights. This map covers V, A, W, VA, var, PF, frequency, demand, THD, import/export and tariff energy, run hours, I/O and alarm status, alarm and tariff setup, serial settings and resets.
This page lists 64 Modbus registers for the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Carlo Gavazzi’s own free documentation (linked below) and checked against it.
- Manufacturer
- Carlo Gavazzi
- Model
- EM511 single-phase energy meter (Modbus RTU)
- Equipment type
- Energy meter
- Registers
- 64 (23 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- Rows apply to all firmware unless noted (X 1.0, PFx 1.0)
- Also known as
- EM511-IS, EM511DINAV81XS1X, EM511DINAV81XS1PFA, EM511DINAV81XS1PFB, EM511DINAV81XS1SFA
- Source document
- EM511 Communication Protocol · rev. 1.8 · rev. 2023-05-23
Integration notes: Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)
Read input registers 0000h-0043h in one request (function 04 or 03). Decode INT32 low word first; V/W/VA/var x10, A x1000, energy x10, hours x100; PF and Hz are INT16 x1000 and x10.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | V L-N | INT32 CDAB | Voltage | Read |
| IR 2 | A | INT32 CDAB | Current | Read |
| IR 4 | W | INT32 CDAB | Active power | Read |
| IR 14 | PF (IEC convention) | INT16 | Power factor | Read |
| IR 15 | Frequency | INT16 | Frequency | Read |
| IR 16 | kWh (+) TOT | INT32 CDAB | Imported kWh total | Read |
| IR 32 | kWh (-) TOT | INT32 CDAB | Exported kWh total | Read |
Enable Modbus control & writes
Modbus RTU on RS485 is always active; serial settings are at 2000h-2004h.
Byte order & addressing
- 32-bit values are CDAB.
- Stop-bit register uses 0 = 1 stop bit, 1 = 2 stop bits (unlike other Gavazzi meters).
- Two PF conventions are published: 000Eh (IEC sign) and 0070h (L/C sign).
Network setup
- Defaults: address 1, 9600 baud, no parity, 1 stop bit.
- Max answer time 500 ms.
Watch out for
- Total reset (4003h) is not available on MID versions.
- Tariff selection by Modbus needs 1101h on and the digital input not set to tariff mode.
Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 300001 / 0000h | V L-N | INT32 | CDAB | × 0.1 | V | Read | ||
| IR | 2doc 300003 / 0002h | A | INT32 | CDAB | × 0.001 | A | Read | ||
| IR | 4doc 300005 / 0004h | W | INT32 | CDAB | × 0.1 | W | Read | ||
| IR | 6doc 300007 / 0006h | VA | INT32 | CDAB | × 0.1 | VA | Read | ||
| IR | 8doc 300009 / 0008h | var | INT32 | CDAB | × 0.1 | var | Read | ||
| IR | 10doc 300011 / 000Ah | W dmd | Demand active power. | INT32 | CDAB | × 0.1 | W | Read | |
| IR | 11doc 300012 / 000Bh | Carlo Gavazzi identification code | UINT16 | Read | 1792 = EM511DINAV81XS1X; 1793 = EM511DINAV81XS1PFA; 1794 = EM511DINAV81XS1PFB; 1795 = EM511DINAV81XS1SFA | ||||
| IR | 12doc 300013 / 000Ch | W dmd peak | INT32 | CDAB | × 0.1 | W | Read | ||
| IR | 14doc 300015 / 000Eh | PF (IEC convention) | Positive when consuming, negative when generating. | INT16 | × 0.001 | Read | |||
| IR | 15doc 300016 / 000Fh | Frequency | INT16 | × 0.1 | Hz | Read | |||
| IR | 16doc 300017 / 0010h | kWh (+) TOT | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 18doc 300019 / 0012h | kvarh (+) TOT | INT32 | CDAB | × 0.1 | kvarh | Read | ||
| IR | 20doc 300021 / 0014h | kWh (+) PARTIAL | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 22doc 300023 / 0016h | kvarh (+) PARTIAL | INT32 | CDAB | × 0.1 | kvarh | Read | ||
| IR | 24doc 300025 / 0018h | kWh (+) tariff 1 | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 26doc 300027 / 001Ah | kWh (+) tariff 2 | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 32doc 300033 / 0020h | kWh (-) TOT | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 34doc 300035 / 0022h | kvarh (-) TOT | INT32 | CDAB | × 0.1 | kvarh | Read | ||
| IR | 36doc 300037 / 0024h | kWh (-) PARTIAL | INT32 | CDAB | × 0.1 | kWh | Read | ||
| IR | 38doc 300039 / 0026h | kvarh (-) PARTIAL | INT32 | CDAB | × 0.1 | kvarh | Read | ||
| IR | 40doc 300041 / 0028h | kVAh TOT | INT32 | CDAB | × 0.1 | kVAh | Read | ||
| IR | 42doc 300043 / 002Ah | kVAh PARTIAL | INT32 | CDAB | × 0.1 | kVAh | Read | ||
| IR | 44doc 300045 / 002Ch | Hour counter | INT32 | CDAB | × 0.01 | h | Read | ||
| IR | 46doc 300047 / 002Eh | Hour counter negative energy | INT32 | CDAB | × 0.01 | h | Read | ||
| IR | 48doc 300049 / 0030h | Lifetime counter | INT32 | CDAB | × 0.01 | h | Read | ||
| IR | 50doc 300051 / 0032h | THD A | INT32 | CDAB | × 0.01 | % | Read | ||
| IR | 52doc 300053 / 0034h | THD V L-N | INT32 | CDAB | × 0.01 | % | Read | ||
| IR | 54doc 300055 / 0036h | Hour counter PARTIAL | INT32 | CDAB | × 0.01 | h | Read | ||
| IR | 56doc 300057 / 0038h | Hour counter negative PARTIAL | INT32 | CDAB | × 0.01 | h | Read | ||
| IR | 58doc 300059 / 003Ah | A dmd | INT32 | CDAB | × 0.001 | A | Read | ||
| IR | 60doc 300061 / 003Ch | A dmd peak | INT32 | CDAB | × 0.001 | A | Read | ||
| IR | 64doc 300065 / 0040h | VA dmd | INT32 | CDAB | × 0.1 | VA | Read | ||
| IR | 66doc 300067 / 0042h | VA dmd peak | INT32 | CDAB | × 0.1 | VA | Read | ||
| IR | 112doc 300113 / 0070h | PF (L/C convention) | Positive for inductive, negative for capacitive load. | INT16 | × 0.001 | Read | |||
| IR | 113doc 300114 / 0071h | Inductive/capacitive load | INT16 | Read | 1 = Inductive (L); -1 = Capacitive (C) | ||||
| IR | 768doc 300769 / 0300h | Digital input status | INT16 | Read | 0 = Input open; 1 = Input closed | ||||
| IR | 769doc 300770 / 0301h | Active tariff | INT16 | Read | 0 = None; 1 = Tariff 1; 2 = Tariff 2 | ||||
| IR | 770doc 300771 / 0302h | Firmware version and revision | High byte: bits 0-3 minor, bits 4-7 major; low byte: revision. | UINT16 | Read | ||||
| IR | 774doc 300775 / 0306h | Alarm status | INT16 | Read | 0 = Not active (or waiting for delay); 1 = Active | ||||
| HR | 4096doc 304097 / 1000h | Password | 0 = no password (default), up to 9999. | UINT16 | Read/write | ||||
| HR | 4112doc 304113 / 1010h | Demand integration time | UINT32 | CDAB | Read/write | 0 = 1 min; 1 = 5 min; 2 = 10 min; 3 = 15 min (default); 4 = 20 min; 5 = 30 min; 6 = 60 min | |||
| HR | 4116doc 304117 / 1014h | Alarm enable | UINT16 | Read/write | 0 = Disabled (default); 1 = Enabled | ||||
| HR | 4117doc 304118 / 1015h | Alarm linked variable | UINT16 | Read/write | 1 = Active power (default); 2 = Apparent power; 3 = Reactive power; 4 = Power factor; 5 = Current; 6 = Voltage | ||||
| HR | 4118doc 304119 / 1016h | Alarm set point 1 (on) | -1000.00 to +1000.00 in units of the linked variable. | INT32 | CDAB | × 0.01 | Read/write | ||
| HR | 4120doc 304121 / 1018h | Alarm set point 2 (off) | -1000.00 to +1000.00. | INT32 | CDAB | × 0.01 | Read/write | ||
| HR | 4122doc 304123 / 101Ah | Alarm delay | 0-3600 s. | UINT16 | s | Read/write | |||
| HR | 4353doc 304354 / 1101h | Tariff management via Modbus | UINT16 | Read/write | 0 = Off; 1 = On (default) | ||||
| HR | 4355doc 304356 / 1103h | Measurement mode | Fixed on MID versions. | UINT16 | Read/write | 0 = A mode - absolute (default); 1 = B mode - bidirectional | |||
| HR | 4361doc 304362 / 1109h | Quick set up at next power on | UINT16 | Read/write | 0 = Menu disabled; 1 = Menu enabled (default) | ||||
| HR | 4363doc 304360 / 110Bh | Start-up current of run hour counter | 20 (0.02 A, default) to 45000 (45 A). | UINT32 | CDAB | × 0.001 | A | Read/write | |
| HR | 4438doc 304439 / 1156h | Current direction | X (non-MID) version only. | UINT16 | Read/write | 0 = Direct (default); 1 = Inverse | |||
| HR | 4608doc 304609 / 1200h | Digital input function | UINT16 | Read/write | 0 = Tariff selection; 1 = Remote status input only (default); 2 = Partial meter enable; 3 = Reset partial counters | ||||
| HR | 4609doc 304610 / 1201h | Tariff selection via serial | UINT16 | Read/write | 1 = Tariff 1 (default); 2 = Tariff 2 | ||||
| HR | 8192doc 308193 / 2000h | RS485 instrument address | 1-247, default 1. | UINT16 | Read/write | ||||
| HR | 8193doc 308194 / 2001h | RS485 baud rate | UINT16 | Read/write | 1 = 9.6 kbps (default); 2 = 19.2 kbps; 3 = 38.4 kbps; 4 = 57.6 kbps; 5 = 115.2 kbps | ||||
| HR | 8194doc 308195 / 2002h | RS485 parity | UINT16 | Read/write | 1 = No parity (default); 2 = Even parity | ||||
| HR | 8195doc 308196 / 2003h | RS485 stop bit | UINT16 | Read/write | 0 = 1 stop bit (default); 1 = 2 stop bits | ||||
| HR | 8196doc 308197 / 2004h | RS485 delay on reply | 0-1000, default 0. | UINT16 | ms | Read/write | |||
| HR | 16387doc 316388 / 4003h | Reset total counters | Write 1: totals, run hours and offsets (not lifetime). Not on MID versions. | UINT16 | Read/write | ||||
| HR | 16388doc 316389 / 4004h | Reset partial counters | Write 1: partial energy and partial run hours. | UINT16 | Read/write | ||||
| HR | 16389doc 316390 / 4005h | Reset demand values | Write 1: demand and demand max. | UINT16 | Read/write | ||||
| HR | 16390doc 316391 / 4006h | Reset tariff counters | Write 1. | UINT16 | Read/write | ||||
| HR | 20487doc 320488 / 5007h | Production year | Four digits. | UINT16 | Read | ||||
| HR | 20498doc 320499 / 5012h | Device state | UINT16 | Read | 0 = Run; 1 = Fault |
Notes on this map
- Word order: INT32, UINT32 and UINT64 values are sent least significant word first, bytes MSB first (CDAB).
- The document is labelled 'internal version' but is published on Carlo Gavazzi's own site.
- Rows marked n.a. in the source always read 0 and are left out.
- Left out: the mirror block at 0100h-017Eh, the INT64 energy block at 0500h-0532h (no word order stated for INT64), the run-hour/frequency rows that sit inside that block (0534h-053Eh), energy offsets (4100h-4210h), page filter and display settings, serial-number and name ASCII words, and reserved rows.
- The part-number table shows hex 0702 for both PFB (1794) and SFA (1795); the decimal codes are used here.
- 4020h is factory reset: write 0x0A0A then 0xC1A0 within one second.
- Start-up current of run hour counter is printed as Modicon 304360 next to hex 110Bh; the hex address (wire 4363) is used.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)
What Modbus registers does the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) have?
This map lists 64 registers: 39 input registers, 25 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Rows give a 6-digit Modicon number (3xxxxx, function 04) and the hex physical address used in the frame; 300001 / 0000h is wire address 0. Function 03 reads the same values (replace the leading 3 with 4).
What byte order does the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)?
Start with IR 0 V L-N (Voltage); IR 2 A (Current); IR 4 W (Active power); IR 14 PF (IEC convention) (Power factor); IR 15 Frequency (Frequency); IR 16 kWh (+) TOT (Imported kWh total); IR 32 kWh (-) TOT (Exported kWh total).
How do I enable Modbus control of the Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)?
Modbus RTU on RS485 is always active; serial settings are at 2000h-2004h.
Where is the official Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU) Modbus documentation?
The source is EM511 Communication Protocol (rev. 1.8), revision 2023-05-23, published free by Carlo Gavazzi at https://www.gavazziautomation.com/fileadmin/images/PIM/OTHERSTUFF/COMPRO/EM511%20CP%20Rev1.8.pdf.
More Carlo Gavazzi Modbus register maps
- Energy meter (DC)
Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP)
DCM1 300 A / 600 A, 1000 V DC meters (MID, Eichrecht and LNE variants) with RS485 and Ethernet, protocol version 1.11.
Also known as: DCM1A60V10L20S1PFA, DCM1A60V10L20S1PFB, DCM1A60V10L20S2DEB, DCM1A60V10L20S3DEB, DCM1A60V10L20S2DEBF, DCM1A60V10L20S3DEBF, DCM1A30V10L20S1PFA, DCM1A30V10L20S1PFB, DCM1A30V10L20S2DEB, DCM1A30V10L20S3DEB, DCM1A30V10L20S2DEBF, DCM1A30V10L20S3DEBF, DCM1A60V10L20S1ULB, DCM1A30V10L20S1ULB - Energy meter (DC)
Carlo Gavazzi DCT1 DC energy meter (Modbus RTU)
DCT1 300 A and 600 A / 1000 V DC meters, with and without signed data (S1/S2/S3), protocol version 1.1.
Also known as: DCT1A60V10LS1X, DCT1A60V10LS2EC, DCT1A60V10LS3EC, DCT1A30V10LS1X, DCT1A30V10LS2EC, DCT1A30V10LS3EC - Energy meter
Carlo Gavazzi EM100 / ET100 series (EM111, EM112, ET112)
Single-phase EM111, EM112 energy meters and ET112 bidirectional meter with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 14.
Also known as: EM111, EM112, ET112, EM110, EM111-DIN, EM112-DIN, ET112-DIN, EM111DINAV81XS1X, EM112DINAV01XS1X, ET112DINAV01XS1X - Energy meter (energy analyzer)
Carlo Gavazzi EM210 (AV versions)
EM210 three-phase energy analyzers, AV input versions with the RS485 Modbus RTU option, protocol version 4 revision 3 (newest variables need firmware A.5/A.6).
Also known as: EM210, EM210-72D, EM210 AV - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN (PFA, PFB and X models)
EM24-DIN three-phase energy analyzers, PFA/PFB (MID) and X models with the RS485 Modbus RTU port (IS option), protocol version 4 revision 0.
Also known as: EM24, EM24DIN, EM24DINAV93XISPFA, EM24DINAV93XISPFB, EM24DINAV93XISX, EM24DINAV53XISX, EM24DINAV23XISX, EM24 DIN AV9, EM24 DIN AV5 - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN Ethernet (E1)
EM24-DIN energy analyzers with the E1 Ethernet (RJ45) Modbus TCP port, AV2 and AV5 inputs, X/PFA/PFB, protocol version 0 revision 1.3 (FW 1.0).
Also known as: EM24 E1, EM24_E1, EM24DINAV23XE1X, EM24DINAV23XE1PFA, EM24DINAV23XE1PFB, EM24DINAV53XE1X, EM24DINAV53XE1PFA, EM24DINAV53XE1PFB - Energy meter
Carlo Gavazzi EM24-IS (SFA and SFB models)
EM24-DIN AV2/AV5 IS SFA and SFB versions (identification codes 1696-1699), protocol revision 2.0.
Also known as: EM24DINAV23XISSFA, EM24DINAV53XISSFA, EM24DINAV23XISSFB, EM24DINAV53XISSFB, EM24 SFA, EM24 SFB - Energy meter
Carlo Gavazzi EM270 / EM280 dual three-phase energy meters with TCD current sensors
EM270 X (firmware r.b0+), EM270 W (r.C0+) and EM280 (r.E0+) on RS485 Modbus RTU, per communication protocol version 5 revision 1 (2018-01-29).
Also known as: EM270, EM280, EM270 X, EM270 W, EM27072DMV53X2SX, EM28072DMV53X2SX - Energy meter
Carlo Gavazzi EM271 dual three-phase energy meter with TCD current sensors
EM271 (firmware r.d0+, PF values from r.d2) on RS485 Modbus RTU, per communication protocol version 1 revision 2 (2018-01-29).
Also known as: EM271, EM27172DMV53X2SX, EM27172DMV63X2SX - Energy meter
Carlo Gavazzi EM300 / ET300 series (EM330, EM340, ET330, ET340)
EM330, EM331, EM340, EM341 energy meters and ET330/ET340 bidirectional meters with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 17.
Also known as: EM330, EM340, ET330, ET340, EM331, EM341, EM330-DIN, EM340-DIN, ET340-DIN, EM340DINAV23XS1X, EM340DINAV23XS1PFA, EM340DINAV23XS1PFB - Energy meter
Carlo Gavazzi EM530 / EM540 three-phase energy meters (RS485 Modbus)
EM530 (CT-connected) and EM540 (direct-connected) with the S1 RS485 port, X and MID (PFA/PFB/PFC) versions, protocol document version 1.3.
Also known as: EM530, EM540, EM530DINAV53XS1X, EM530DINAV53XS1PFA, EM530DINAV53XS1PFB, EM530DINAV53XS1PFC, EM540DINAV23XS1X, EM540DINAV23XS1PFA, EM540DINAV23XS1PFB, EM540DINAV23XS1PFC, EM500 series - Energy meter
Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)
EM580-IS MID/Eichrecht AC meters (DEB, DET, DEA variants, 256/384-bit signatures), protocol version 1.11.
Also known as: EM580-IS, EM580DINAV23XS2DEB, EM580DINAV23XS3DEB, EM580DINAV23XS2DET, EM580DINAV23XS3DET, EM580DINAV23XS2DEA, EM580DINAV23XS3DEA - Power meter (power analyzer)
Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)
WM14 Advanced (revision 5 onward) and CPT-DIN Advanced (revision 6 onward) with RS485 (or RS232 on CPT-DIN), protocol version 2 revision 2 (2008-01-09).
Also known as: WM14-96 Advanced, WM14 A, CPT-DIN Advanced, CPT A, CPT-DIN A - Power meter (power analyzer)
Carlo Gavazzi WM15 power analyzer
WM15-96 three-phase panel power analyzers with RS485 Modbus RTU (OS / OSPF / HOS versions), protocol version 1.2.
Also known as: WM15, WM15-96, WM1596AV53XOSX, WM1596AV53XOSPFB, WM1596AV53HOSX - Power meter (power analyzer)
Carlo Gavazzi WM20 / WM30 / WM40 power analyzers
WM20, WM30 and WM40 modular power analyzers with an RS485 (or Ethernet) Modbus module, protocol internal version rev. 4.0 (2018-03-28); WM30 = firmware letter X, WM40 = Y, WM20 = Z.
Also known as: WM20, WM30, WM40, WM20-96, WM30-96, WM40-96 - Power meter (power analyzer)
Carlo Gavazzi WM50 power analyzer with TCD branch channels
WM50 base unit (firmware X0, i.e. all A and B versions) with an MC485232 or MCETH communication module, plus TCD branch channels, per communication protocol user version rev. 1.0.0 (2017-09-27).
Also known as: WM50, WM50AV5, WM50-96, WM50 AV5
Other power & energy meters register maps
- Power meter (power factor regulator with network analyzer)
Circutor Computer SMART III
Circutor Computer SMART III reactive energy regulators (6 and 12 step models), RS-485 Modbus RTU, manual M015B01-03-25B.
Also known as: Computer SMART III 6, Computer SMART III 12, SMART III - Power meter
Crompton Instruments Integra 1530 / 1560 / 1580
Crompton Instruments (Tyco Electronics) Integra 1530, 1560 and 1580 panel meters fitted with the RS485 Modbus RTU option, per Integra Comms Issue 1 (Jan 2006).
Also known as: Integra 1530, Integra 1560, Integra 1580 - Energy meter
Eastron SDM230-DI
Eastron SDM230-DI single-phase 100 A DIN-rail meter with two digital inputs and RS485 Modbus RTU, manual 2025 V1.00.
Also known as: SDM230 DI - Energy meter
Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU)
Eltako DSZ15DZMOD-3x80A MID bidirectional three-phase DIN-rail meter (art. no. 28380516), per Modbus-RTU protocol specification V1.6.
Also known as: DSZ15DZMOD, DSZ15DZMOD-3x80A, DSZ15DZMOD-3x80A MID, 28380516 - Energy meter
Finder 7M.38 three-phase energy meter (Modbus RS485)
Finder 7M.38 three-phase meters with serial RS485 communication (7M.38.8.400.XXXX serial versions); the 7M.24 single-phase meter in the same document is not covered.
Also known as: 7M.38, 7M38, 7M.38.8.400.0212, 7M3884000212, Finder 7M38 Modbus - Power meter
IME Nemo 96HDe multifunction meter (MF96E06)
IME Nemo 96HDe panel meter MF96E06 with RS-485, per protocol PR145.
Also known as: MF96E06, Nemo 96HDe
All power & energy meters Modbus register maps →
Source: EM511 Communication Protocol · rev. 1.8 · rev. 2023-05-23. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.