Crompton Instruments Integra 1530 / 1560 / 1580 Modbus register map

Updated 19 November 2026

Short answer

The Integra 1530, 1560 and 1580 are Crompton Instruments panel digital meters. With the RS485 option they act as a Modbus RTU slave. Every value, readings and settings alike, is an IEEE-754 float in two registers: readings are input registers (function 04) and settings are holding registers (functions 03 and 16).

This page lists 83 Modbus registers for the Crompton Instruments Integra 1530 / 1560 / 1580 — 24 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Crompton Instruments’s own free documentation (linked below) and checked against it.

Manufacturer
Crompton Instruments
Model
Integra 1530 / 1560 / 1580
Equipment type
Power meter
Registers
83 (24 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
Integra 1530, Integra 1560, Integra 1580
Source document
Crompton Integra 1530, 1560, 1580 Communications Guide · Integra Comms Issue 1 · rev. 2006-01 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Crompton Instruments Integra 1530 / 1560 / 1580

Integration in brief

Read input registers with function 04 in two-register pairs; floats come high word first unless the Register Order setting was changed. Total power is at wire address 52 (30053), frequency at 70 and import energy at 72.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 6Current 1FLOAT32 ABCDPhase 1 currentRead
IR 42Volts AveFLOAT32 ABCDAverage phase voltageRead
IR 52Watts SumFLOAT32 ABCDTotal active powerRead
IR 62Power Factor AveFLOAT32 ABCDAverage power factorRead
IR 70FrequencyFLOAT32 ABCDFrequencyRead
IR 72Wh ImportFLOAT32 ABCDImported active energyRead
HR 40Register OrderFLOAT32 ABCDRegister orderRead/write

Enable Modbus control & writes

Modbus RTU exists only on meters built with the RS485 option. Settings marked password-protected need the password written to 40025 first; writing it again, or a power cycle, locks them again.

Byte order & addressing

Network setup

Watch out for

Crompton Instruments Integra 1530 / 1560 / 1580 Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

83 of 83 shown
Crompton Instruments Integra 1530 / 1560 / 1580 Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR2doc 30003Volts 2L2-N (4-wire) or L2-L3 (3-wire).FLOAT32ABCDVRead
IR4doc 30005Volts 3L3-N (4-wire) or L3-L1 (3-wire).FLOAT32ABCDVRead
IR6doc 30007Current 1FLOAT32ABCDARead
IR8doc 30009Current 2FLOAT32ABCDARead
IR10doc 30011Current 3FLOAT32ABCDARead
IR12doc 30013W Phase 1FLOAT32ABCDWRead
IR14doc 30015W Phase 2FLOAT32ABCDWRead
IR16doc 30017W Phase 3FLOAT32ABCDWRead
IR18doc 30019VA Phase 1FLOAT32ABCDVARead
IR20doc 30021VA Phase 2FLOAT32ABCDVARead
IR22doc 30023VA Phase 3FLOAT32ABCDVARead
IR24doc 30025var Phase 1FLOAT32ABCDvarRead
IR26doc 30027var Phase 2FLOAT32ABCDvarRead
IR28doc 30029var Phase 3FLOAT32ABCDvarRead
IR30doc 30031Power Factor Phase 1FLOAT32ABCDRead
IR32doc 30033Power Factor Phase 2FLOAT32ABCDRead
IR34doc 30035Power Factor Phase 3FLOAT32ABCDRead
IR36doc 30037Phase Angle Phase 1FLOAT32ABCD°Read
IR38doc 30039Phase Angle Phase 2FLOAT32ABCD°Read
IR40doc 30041Phase Angle Phase 3FLOAT32ABCD°Read
IR42doc 30043Volts AveAverage of the phase voltages.FLOAT32ABCDVRead
IR46doc 30047Current AveFLOAT32ABCDARead
IR48doc 30049Current SumFLOAT32ABCDARead
IR52doc 30053Watts SumTotal active power.FLOAT32ABCDWRead
IR56doc 30057VA SumFLOAT32ABCDVARead
IR60doc 30061var SumFLOAT32ABCDvarRead
IR62doc 30063Power Factor AveFLOAT32ABCDRead
IR66doc 30067Average Phase AngleFLOAT32ABCD°Read
IR70doc 30071FrequencyFLOAT32ABCDHzRead
IR72doc 30073Wh ImportImported active energy counter; unit not printed in the table.FLOAT32ABCDRead
IR74doc 30075Wh ExportExported active energy counter; unit not printed in the table.FLOAT32ABCDRead
IR76doc 30077varh ImportUnit not printed in the table.FLOAT32ABCDRead
IR78doc 30079varh ExportUnit not printed in the table.FLOAT32ABCDRead
IR80doc 30081VAhUnit not printed in the table.FLOAT32ABCDRead
IR84doc 30085W Demand ImportFLOAT32ABCDWRead
IR86doc 30087W Max. Demand ImportFLOAT32ABCDWRead
IR104doc 30105A DemandFLOAT32ABCDARead
IR106doc 30107A Max. DemandFLOAT32ABCDARead
IR200doc 30201V L1-L2FLOAT32ABCDVRead
IR202doc 30203V L2-L3FLOAT32ABCDVRead
IR204doc 30205V L3-L1FLOAT32ABCDVRead
IR206doc 30207Average Line to Line VoltsFLOAT32ABCDVRead
IR224doc 30225Neutral CurrentFLOAT32ABCDARead
IR234doc 30235THD Volts 1FLOAT32ABCD%Read
IR236doc 30237THD Volts 2FLOAT32ABCD%Read
IR238doc 30239THD Volts 3FLOAT32ABCD%Read
IR240doc 30241THD Current 1FLOAT32ABCD%Read
IR242doc 30243THD Current 2FLOAT32ABCD%Read
IR244doc 30245THD Current 3FLOAT32ABCD%Read
IR248doc 30249THD Voltage MeanFLOAT32ABCD%Read
IR250doc 30251THD Current MeanFLOAT32ABCD%Read
IR254doc 30255Power Factor (+Ind/-Cap)Signed: positive inductive, negative capacitive.FLOAT32ABCDRead
HR0doc 40001Demand TimeWrite 0 to restart the demand period; reads minutes of demand data so far.FLOAT32ABCDminRead/write
HR2doc 40003Demand PeriodDemand window in minutes: 8, 15, 20 or 30 (the table also lists 60).FLOAT32ABCDminRead/write
HR6doc 40007System VoltageVT primary voltage (1 V to 400 kV). Password needed to write.FLOAT32ABCDVRead/write
HR8doc 40009System CurrentCT primary current (1-9999 A). Password needed to write.FLOAT32ABCDARead/write
HR10doc 40011System TypePassword needed to write.FLOAT32ABCDRead/write1 = Single phase 2 wire; 2 = 3 phase 3 wire; 3 = 3 phase 4 wire; 4 = Single phase 3 wire
HR12doc 40013Relay Pulse WidthMultiples of 20 ms; only 3, 5 or 10 accepted.FLOAT32ABCDRead/write3 = 60 ms; 5 = 100 ms; 10 = 200 ms
HR14doc 40015Energy ResetWrite 0 to reset the energy counters.FLOAT32ABCDWrite
HR18doc 40019RS485 set-up codeBaud/parity/stop-bit code; unlisted codes can lose communication.FLOAT32ABCDRead/write0 = 2400, even, 1 stop; 1 = 2400, odd, 1 stop; 2 = 2400, no parity, 1 stop; 4 = 4800, even, 1 stop; 5 = 4800, odd, 1 stop; 6 = 4800, no parity, 1 stop; 8 = 9600, even, 1 stop; 9 = 9600, odd, 1 stop; 10 = 9600, no parity, 1 stop; 12 = 19200, even, 1 stop; 13 = 19200, odd, 1 stop; 14 = 19200, no parity, 1 stop; 18 = 2400, no parity, 2 stop; 22 = 4800, no parity, 2 stop; 26 = 9600, no parity, 2 stop; 30 = 19200, no parity, 2 stop
HR20doc 40021Node AddressModbus (or N2) slave address, 1-247.FLOAT32ABCDRead/write
HR22doc 40023Pulse DivisorOnly 1, 10, 100 or 1000 accepted.FLOAT32ABCDRead/write
HR24doc 40025Password0000-9999. Reads 1 when unlocked, 0 when protected.FLOAT32ABCDRead/write
HR36doc 40037System PowerMaximum system power worked out from type, volts and current.FLOAT32ABCDRead
HR40doc 40041Register OrderWrite 2141.0; the meter adopts the word order used for that write.FLOAT32ABCDRead/write
HR298doc 40299Secondary VoltsVT secondary voltage. Password needed to write.FLOAT32ABCDVRead/write
HR306doc 40307Max Energy CountDigits before energy counters roll over: 6, 7 or 8. Password needed.FLOAT32ABCDRead/write
HR308doc 40309Analogue Hardware MaxHighest output current the analogue hardware can give.FLOAT32ABCDRead
HR310doc 40311Analogue Hardware MinLowest output current the analogue hardware can give.FLOAT32ABCDRead
HR312doc 40313Analogue 1 Output ParameterInput parameter number sent to analogue output 1; 0 = unused.FLOAT32ABCDRead/write
HR314doc 40315Analogue 1 Parameter MaxFLOAT32ABCDRead
HR316doc 40317Analogue 1 Parameter MinFLOAT32ABCDRead
HR318doc 40319Analogue 1 Reading TopReading that maps to Output Top.FLOAT32ABCDRead/write
HR320doc 40321Analogue 1 Reading BottomReading that maps to Output Bottom.FLOAT32ABCDRead/write
HR322doc 40323Analogue 1 Output TopFLOAT32ABCDRead/write
HR324doc 40325Analogue 1 Output BottomFLOAT32ABCDRead/write
HR328doc 40329Analogue 2 Output ParameterInput parameter number sent to analogue output 2; 0 = unused.FLOAT32ABCDRead/write
HR330doc 40331Analogue 2 Parameter MaxFLOAT32ABCDRead
HR332doc 40333Analogue 2 Parameter MinFLOAT32ABCDRead
HR334doc 40335Analogue 2 Reading TopFLOAT32ABCDRead/write
HR336doc 40337Analogue 2 Reading BottomFLOAT32ABCDRead/write
HR338doc 40339Analogue 2 Output TopFLOAT32ABCDRead/write
HR340doc 40341Analogue 2 Output BottomFLOAT32ABCDRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Crompton Instruments Integra 1530 / 1560 / 1580

What Modbus registers does the Crompton Instruments Integra 1530 / 1560 / 1580 have?

This map lists 83 registers: 52 input registers, 31 holding registers. 24 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Crompton Instruments Integra 1530 / 1560 / 1580 Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print 30001/40001-style register numbers next to the hex start address used on the wire, e.g. Current 1 = 30007 = 0x0006 (the guide's own read example uses start 0006). Wire address = printed number minus 30001 or 40001, which also equals 2 x (parameter number - 1).

What byte order does the Crompton Instruments Integra 1530 / 1560 / 1580 use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Crompton Instruments Integra 1530 / 1560 / 1580?

Start with IR 6 Current 1 (Phase 1 current); IR 42 Volts Ave (Average phase voltage); IR 52 Watts Sum (Total active power); IR 62 Power Factor Ave (Average power factor); IR 70 Frequency (Frequency); IR 72 Wh Import (Imported active energy); HR 40 Register Order (Register order).

How do I enable Modbus control of the Crompton Instruments Integra 1530 / 1560 / 1580?

Modbus RTU exists only on meters built with the RS485 option. Settings marked password-protected need the password written to 40025 first; writing it again, or a power cycle, locks them again.

Where is the official Crompton Instruments Integra 1530 / 1560 / 1580 Modbus documentation?

The source is Crompton Integra 1530, 1560, 1580 Communications Guide (Integra Comms Issue 1), revision 2006-01. Crompton Instruments doesn't publish it on its own website, so this map was re-typed from a free copy at https://arccontrol.ccontrols.com/support/dp/Integra15xx.pdf. It may be an older revision, so check it against the live unit.