Crompton Instruments Integra 1530 / 1560 / 1580 Modbus register map
Updated 19 November 2026
The Integra 1530, 1560 and 1580 are Crompton Instruments panel digital meters. With the RS485 option they act as a Modbus RTU slave. Every value, readings and settings alike, is an IEEE-754 float in two registers: readings are input registers (function 04) and settings are holding registers (functions 03 and 16).
This page lists 83 Modbus registers for the Crompton Instruments Integra 1530 / 1560 / 1580 — 24 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Crompton Instruments’s own free documentation (linked below) and checked against it.
- Manufacturer
- Crompton Instruments
- Model
- Integra 1530 / 1560 / 1580
- Equipment type
- Power meter
- Registers
- 83 (24 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Integra 1530, Integra 1560, Integra 1580
Integration notes: Crompton Instruments Integra 1530 / 1560 / 1580
Read input registers with function 04 in two-register pairs; floats come high word first unless the Register Order setting was changed. Total power is at wire address 52 (30053), frequency at 70 and import energy at 72.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 6 | Current 1 | FLOAT32 ABCD | Phase 1 current | Read |
| IR 42 | Volts Ave | FLOAT32 ABCD | Average phase voltage | Read |
| IR 52 | Watts Sum | FLOAT32 ABCD | Total active power | Read |
| IR 62 | Power Factor Ave | FLOAT32 ABCD | Average power factor | Read |
| IR 70 | Frequency | FLOAT32 ABCD | Frequency | Read |
| IR 72 | Wh Import | FLOAT32 ABCD | Imported active energy | Read |
| HR 40 | Register Order | FLOAT32 ABCD | Register order | Read/write |
Enable Modbus control & writes
Modbus RTU exists only on meters built with the RS485 option. Settings marked password-protected need the password written to 40025 first; writing it again, or a power cycle, locks them again.
Byte order & addressing
- Every value, settings included, is a two-register float; write settings with function 16.
- Register Order (40041) is set by writing 2141.0 in the word order the meter should use from then on.
- One request may cover at most 40 parameters; more returns an exception.
Network setup
- Address range 1-247; broadcast address 0 is not supported.
- Baud 2400, 4800, 9600 or 19200 with even, odd or no parity, chosen by the RS485 set-up code (40019).
- Two-wire RS485 with 120 ohm termination at both ends of a line; up to 32 nodes and 1200 m.
- Allow up to 150 ms for the meter to start replying.
Watch out for
- An RS485 set-up code not in the table can leave the meter unreachable; the guide recommends the front panel or the Integra configurator for comms changes.
- Demand Time and Energy Reset accept only 0; any other value returns an error.
Crompton Instruments Integra 1530 / 1560 / 1580 Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 2doc 30003 | Volts 2 | L2-N (4-wire) or L2-L3 (3-wire). | FLOAT32 | ABCD | V | Read | ||
| IR | 4doc 30005 | Volts 3 | L3-N (4-wire) or L3-L1 (3-wire). | FLOAT32 | ABCD | V | Read | ||
| IR | 6doc 30007 | Current 1 | FLOAT32 | ABCD | A | Read | |||
| IR | 8doc 30009 | Current 2 | FLOAT32 | ABCD | A | Read | |||
| IR | 10doc 30011 | Current 3 | FLOAT32 | ABCD | A | Read | |||
| IR | 12doc 30013 | W Phase 1 | FLOAT32 | ABCD | W | Read | |||
| IR | 14doc 30015 | W Phase 2 | FLOAT32 | ABCD | W | Read | |||
| IR | 16doc 30017 | W Phase 3 | FLOAT32 | ABCD | W | Read | |||
| IR | 18doc 30019 | VA Phase 1 | FLOAT32 | ABCD | VA | Read | |||
| IR | 20doc 30021 | VA Phase 2 | FLOAT32 | ABCD | VA | Read | |||
| IR | 22doc 30023 | VA Phase 3 | FLOAT32 | ABCD | VA | Read | |||
| IR | 24doc 30025 | var Phase 1 | FLOAT32 | ABCD | var | Read | |||
| IR | 26doc 30027 | var Phase 2 | FLOAT32 | ABCD | var | Read | |||
| IR | 28doc 30029 | var Phase 3 | FLOAT32 | ABCD | var | Read | |||
| IR | 30doc 30031 | Power Factor Phase 1 | FLOAT32 | ABCD | Read | ||||
| IR | 32doc 30033 | Power Factor Phase 2 | FLOAT32 | ABCD | Read | ||||
| IR | 34doc 30035 | Power Factor Phase 3 | FLOAT32 | ABCD | Read | ||||
| IR | 36doc 30037 | Phase Angle Phase 1 | FLOAT32 | ABCD | ° | Read | |||
| IR | 38doc 30039 | Phase Angle Phase 2 | FLOAT32 | ABCD | ° | Read | |||
| IR | 40doc 30041 | Phase Angle Phase 3 | FLOAT32 | ABCD | ° | Read | |||
| IR | 42doc 30043 | Volts Ave | Average of the phase voltages. | FLOAT32 | ABCD | V | Read | ||
| IR | 46doc 30047 | Current Ave | FLOAT32 | ABCD | A | Read | |||
| IR | 48doc 30049 | Current Sum | FLOAT32 | ABCD | A | Read | |||
| IR | 52doc 30053 | Watts Sum | Total active power. | FLOAT32 | ABCD | W | Read | ||
| IR | 56doc 30057 | VA Sum | FLOAT32 | ABCD | VA | Read | |||
| IR | 60doc 30061 | var Sum | FLOAT32 | ABCD | var | Read | |||
| IR | 62doc 30063 | Power Factor Ave | FLOAT32 | ABCD | Read | ||||
| IR | 66doc 30067 | Average Phase Angle | FLOAT32 | ABCD | ° | Read | |||
| IR | 70doc 30071 | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| IR | 72doc 30073 | Wh Import | Imported active energy counter; unit not printed in the table. | FLOAT32 | ABCD | Read | |||
| IR | 74doc 30075 | Wh Export | Exported active energy counter; unit not printed in the table. | FLOAT32 | ABCD | Read | |||
| IR | 76doc 30077 | varh Import | Unit not printed in the table. | FLOAT32 | ABCD | Read | |||
| IR | 78doc 30079 | varh Export | Unit not printed in the table. | FLOAT32 | ABCD | Read | |||
| IR | 80doc 30081 | VAh | Unit not printed in the table. | FLOAT32 | ABCD | Read | |||
| IR | 84doc 30085 | W Demand Import | FLOAT32 | ABCD | W | Read | |||
| IR | 86doc 30087 | W Max. Demand Import | FLOAT32 | ABCD | W | Read | |||
| IR | 104doc 30105 | A Demand | FLOAT32 | ABCD | A | Read | |||
| IR | 106doc 30107 | A Max. Demand | FLOAT32 | ABCD | A | Read | |||
| IR | 200doc 30201 | V L1-L2 | FLOAT32 | ABCD | V | Read | |||
| IR | 202doc 30203 | V L2-L3 | FLOAT32 | ABCD | V | Read | |||
| IR | 204doc 30205 | V L3-L1 | FLOAT32 | ABCD | V | Read | |||
| IR | 206doc 30207 | Average Line to Line Volts | FLOAT32 | ABCD | V | Read | |||
| IR | 224doc 30225 | Neutral Current | FLOAT32 | ABCD | A | Read | |||
| IR | 234doc 30235 | THD Volts 1 | FLOAT32 | ABCD | % | Read | |||
| IR | 236doc 30237 | THD Volts 2 | FLOAT32 | ABCD | % | Read | |||
| IR | 238doc 30239 | THD Volts 3 | FLOAT32 | ABCD | % | Read | |||
| IR | 240doc 30241 | THD Current 1 | FLOAT32 | ABCD | % | Read | |||
| IR | 242doc 30243 | THD Current 2 | FLOAT32 | ABCD | % | Read | |||
| IR | 244doc 30245 | THD Current 3 | FLOAT32 | ABCD | % | Read | |||
| IR | 248doc 30249 | THD Voltage Mean | FLOAT32 | ABCD | % | Read | |||
| IR | 250doc 30251 | THD Current Mean | FLOAT32 | ABCD | % | Read | |||
| IR | 254doc 30255 | Power Factor (+Ind/-Cap) | Signed: positive inductive, negative capacitive. | FLOAT32 | ABCD | Read | |||
| HR | 0doc 40001 | Demand Time | Write 0 to restart the demand period; reads minutes of demand data so far. | FLOAT32 | ABCD | min | Read/write | ||
| HR | 2doc 40003 | Demand Period | Demand window in minutes: 8, 15, 20 or 30 (the table also lists 60). | FLOAT32 | ABCD | min | Read/write | ||
| HR | 6doc 40007 | System Voltage | VT primary voltage (1 V to 400 kV). Password needed to write. | FLOAT32 | ABCD | V | Read/write | ||
| HR | 8doc 40009 | System Current | CT primary current (1-9999 A). Password needed to write. | FLOAT32 | ABCD | A | Read/write | ||
| HR | 10doc 40011 | System Type | Password needed to write. | FLOAT32 | ABCD | Read/write | 1 = Single phase 2 wire; 2 = 3 phase 3 wire; 3 = 3 phase 4 wire; 4 = Single phase 3 wire | ||
| HR | 12doc 40013 | Relay Pulse Width | Multiples of 20 ms; only 3, 5 or 10 accepted. | FLOAT32 | ABCD | Read/write | 3 = 60 ms; 5 = 100 ms; 10 = 200 ms | ||
| HR | 14doc 40015 | Energy Reset | Write 0 to reset the energy counters. | FLOAT32 | ABCD | Write | |||
| HR | 18doc 40019 | RS485 set-up code | Baud/parity/stop-bit code; unlisted codes can lose communication. | FLOAT32 | ABCD | Read/write | 0 = 2400, even, 1 stop; 1 = 2400, odd, 1 stop; 2 = 2400, no parity, 1 stop; 4 = 4800, even, 1 stop; 5 = 4800, odd, 1 stop; 6 = 4800, no parity, 1 stop; 8 = 9600, even, 1 stop; 9 = 9600, odd, 1 stop; 10 = 9600, no parity, 1 stop; 12 = 19200, even, 1 stop; 13 = 19200, odd, 1 stop; 14 = 19200, no parity, 1 stop; 18 = 2400, no parity, 2 stop; 22 = 4800, no parity, 2 stop; 26 = 9600, no parity, 2 stop; 30 = 19200, no parity, 2 stop | ||
| HR | 20doc 40021 | Node Address | Modbus (or N2) slave address, 1-247. | FLOAT32 | ABCD | Read/write | |||
| HR | 22doc 40023 | Pulse Divisor | Only 1, 10, 100 or 1000 accepted. | FLOAT32 | ABCD | Read/write | |||
| HR | 24doc 40025 | Password | 0000-9999. Reads 1 when unlocked, 0 when protected. | FLOAT32 | ABCD | Read/write | |||
| HR | 36doc 40037 | System Power | Maximum system power worked out from type, volts and current. | FLOAT32 | ABCD | Read | |||
| HR | 40doc 40041 | Register Order | Write 2141.0; the meter adopts the word order used for that write. | FLOAT32 | ABCD | Read/write | |||
| HR | 298doc 40299 | Secondary Volts | VT secondary voltage. Password needed to write. | FLOAT32 | ABCD | V | Read/write | ||
| HR | 306doc 40307 | Max Energy Count | Digits before energy counters roll over: 6, 7 or 8. Password needed. | FLOAT32 | ABCD | Read/write | |||
| HR | 308doc 40309 | Analogue Hardware Max | Highest output current the analogue hardware can give. | FLOAT32 | ABCD | Read | |||
| HR | 310doc 40311 | Analogue Hardware Min | Lowest output current the analogue hardware can give. | FLOAT32 | ABCD | Read | |||
| HR | 312doc 40313 | Analogue 1 Output Parameter | Input parameter number sent to analogue output 1; 0 = unused. | FLOAT32 | ABCD | Read/write | |||
| HR | 314doc 40315 | Analogue 1 Parameter Max | FLOAT32 | ABCD | Read | ||||
| HR | 316doc 40317 | Analogue 1 Parameter Min | FLOAT32 | ABCD | Read | ||||
| HR | 318doc 40319 | Analogue 1 Reading Top | Reading that maps to Output Top. | FLOAT32 | ABCD | Read/write | |||
| HR | 320doc 40321 | Analogue 1 Reading Bottom | Reading that maps to Output Bottom. | FLOAT32 | ABCD | Read/write | |||
| HR | 322doc 40323 | Analogue 1 Output Top | FLOAT32 | ABCD | Read/write | ||||
| HR | 324doc 40325 | Analogue 1 Output Bottom | FLOAT32 | ABCD | Read/write | ||||
| HR | 328doc 40329 | Analogue 2 Output Parameter | Input parameter number sent to analogue output 2; 0 = unused. | FLOAT32 | ABCD | Read/write | |||
| HR | 330doc 40331 | Analogue 2 Parameter Max | FLOAT32 | ABCD | Read | ||||
| HR | 332doc 40333 | Analogue 2 Parameter Min | FLOAT32 | ABCD | Read | ||||
| HR | 334doc 40335 | Analogue 2 Reading Top | FLOAT32 | ABCD | Read/write | ||||
| HR | 336doc 40337 | Analogue 2 Reading Bottom | FLOAT32 | ABCD | Read/write | ||||
| HR | 338doc 40339 | Analogue 2 Output Top | FLOAT32 | ABCD | Read/write | ||||
| HR | 340doc 40341 | Analogue 2 Output Bottom | FLOAT32 | ABCD | Read/write |
Notes on this map
- Source host: a copy served by Control Concepts (ccontrols.com), an integrator. TE Connectivity's document site refused automated requests and no public TE copy was found, so the unofficial flag is set.
- Word order: the guide says floats go most significant register first by default (ABCD). Writing 2141.0 to Register Order (40041) using the other order switches the meter to low word first for all float traffic.
- Volts 1 (parameter 1, wire address 0) has a blank row in the printed input table, so it is left out even though the numbering pattern implies it.
- The energy registers (Wh, varh, VAh) carry no unit in the table; the set-up text calls the counters kWh and kvarh, so compare a reading with the front panel before scaling.
- Phase rows return zero when the wiring system does not have that phase; the table marks which rows apply to 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire and 1-phase 2-wire.
- Left out: the analogue output 3 and 4 holding registers (40345 onward). Their printed register numbers and hex addresses disagree and several rows are duplicated. Outputs 3 and 4 exist on the 1560/1580 only.
- Holding registers not in the table are reserved for the maker; do not write them.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Crompton Instruments Integra 1530 / 1560 / 1580
What Modbus registers does the Crompton Instruments Integra 1530 / 1560 / 1580 have?
This map lists 83 registers: 52 input registers, 31 holding registers. 24 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Crompton Instruments Integra 1530 / 1560 / 1580 Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print 30001/40001-style register numbers next to the hex start address used on the wire, e.g. Current 1 = 30007 = 0x0006 (the guide's own read example uses start 0006). Wire address = printed number minus 30001 or 40001, which also equals 2 x (parameter number - 1).
What byte order does the Crompton Instruments Integra 1530 / 1560 / 1580 use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Crompton Instruments Integra 1530 / 1560 / 1580?
Start with IR 6 Current 1 (Phase 1 current); IR 42 Volts Ave (Average phase voltage); IR 52 Watts Sum (Total active power); IR 62 Power Factor Ave (Average power factor); IR 70 Frequency (Frequency); IR 72 Wh Import (Imported active energy); HR 40 Register Order (Register order).
How do I enable Modbus control of the Crompton Instruments Integra 1530 / 1560 / 1580?
Modbus RTU exists only on meters built with the RS485 option. Settings marked password-protected need the password written to 40025 first; writing it again, or a power cycle, locks them again.
Where is the official Crompton Instruments Integra 1530 / 1560 / 1580 Modbus documentation?
The source is Crompton Integra 1530, 1560, 1580 Communications Guide (Integra Comms Issue 1), revision 2006-01. Crompton Instruments doesn't publish it on its own website, so this map was re-typed from a free copy at https://arccontrol.ccontrols.com/support/dp/Integra15xx.pdf. It may be an older revision, so check it against the live unit.
Other power & energy meters register maps
- Energy meter
Eastron SDM230-DI
Eastron SDM230-DI single-phase 100 A DIN-rail meter with two digital inputs and RS485 Modbus RTU, manual 2025 V1.00.
Also known as: SDM230 DI - Energy meter
Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU)
Eltako DSZ15DZMOD-3x80A MID bidirectional three-phase DIN-rail meter (art. no. 28380516), per Modbus-RTU protocol specification V1.6.
Also known as: DSZ15DZMOD, DSZ15DZMOD-3x80A, DSZ15DZMOD-3x80A MID, 28380516 - Energy meter
Finder 7M.38 three-phase energy meter (Modbus RS485)
Finder 7M.38 three-phase meters with serial RS485 communication (7M.38.8.400.XXXX serial versions); the 7M.24 single-phase meter in the same document is not covered.
Also known as: 7M.38, 7M38, 7M.38.8.400.0212, 7M3884000212, Finder 7M38 Modbus - Power meter
IME Nemo 96HDe multifunction meter (MF96E06)
IME Nemo 96HDe panel meter MF96E06 with RS-485, per protocol PR145.
Also known as: MF96E06, Nemo 96HDe - Energy meter
inepro Metering PRO1-Mod single-phase energy meter (PRO1 series, manual V3.02)
PRO1-Mod of the PRO1 series (PRO1-S/-2T/-Mb/-Mod), register map of user manual version 302 (2025).
Also known as: PRO1-Mod, PRO1 Mod, PRO1 MID, inepro PRO1 legacy - Power meter (power analyser)
Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP)
UMG 508 power analyser from firmware release 2.x, per Modbus address list 1.042.008.9.b (08/2022).
Also known as: UMG508, UMG 508, Janitza UMG508
All power & energy meters Modbus register maps →
Source: Crompton Integra 1530, 1560, 1580 Communications Guide · Integra Comms Issue 1 · rev. 2006-01 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.