Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The DSZ15DZMOD is Eltako's MID-approved bidirectional three-phase energy meter for direct connection up to 80 A, with an RS485 Modbus RTU interface. Values are 32-bit integers sent high word first: voltages, currents, power factors and import/export energy (total and partial) with fixed decimals.

This page lists 19 Modbus registers for the Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eltako’s own free documentation (linked below) and checked against it.

Manufacturer
Eltako
Model
DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU)
Equipment type
Energy meter
Registers
19 (1 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
DSZ15DZMOD, DSZ15DZMOD-3x80A, DSZ15DZMOD-3x80A MID, 28380516
Source document
Modbus-RTU protocol specification for DSZ15DZMOD V1.6 (English version) · V1.6 · rev. 2023-06
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU)

Integration in brief

Read input registers (function 04) at 0x0000-0x0063 for voltages, currents, power factors and energy; each value is 2 registers, high word first. Total import energy is at 0x0048 in 0.01 kWh.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 72Total import active energyUINT32 ABCDTotal import active energy (0.01 kWh)Read
IR 74Total export active energyUINT32 ABCDTotal export active energyRead
IR 0Voltage L1-NUINT32 ABCDVoltage L1-NRead
IR 6Current L1UINT32 ABCDCurrent L1Read
IR 62Total power factorINT32 ABCDTotal power factorRead

Enable Modbus control & writes

The spec does not describe enabling Modbus. Change the Modbus address by writing register 0x0014 with function 16 (the spec's example sets 0x2A).

Byte order & addressing

Network setup

Watch out for

Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

19 of 19 shown
Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001 (0x0000)Voltage L1-NUINT32ABCD× 0.01VRead
IR2doc 30003 (0x0002)Voltage L2-NUINT32ABCD× 0.01VRead
IR4doc 30005 (0x0004)Voltage L3-NUINT32ABCD× 0.01VRead
IR6doc 30007 (0x0006)Current L1UINT32ABCD× 0.01ARead
IR8doc 30009 (0x0008)Current L2UINT32ABCD× 0.01ARead
IR10doc 30011 (0x000A)Current L3UINT32ABCD× 0.01ARead
IR30doc 30031 (0x001E)Power factor L1Signed, 3 decimals.INT32ABCD× 0.001Read
IR32doc 30033 (0x0020)Power factor L2Signed, 3 decimals.INT32ABCD× 0.001Read
IR34doc 30035 (0x0022)Power factor L3Signed, 3 decimals.INT32ABCD× 0.001Read
IR62doc 30063 (0x003E)Total power factorSigned, 3 decimals.INT32ABCD× 0.001Read
IR72doc 30073 (0x0048)Total import active energyThe manual's example reads 0x000001CD = 4.61 kWh here.UINT32ABCD× 0.01kWhRead
IR74doc 30075 (0x004A)Total export active energyUINT32ABCD× 0.01kWhRead
IR96doc 30097 (0x0060)Partial import active energyUINT32ABCD× 0.01kWhRead
IR98doc 30099 (0x0062)Partial export active energyUINT32ABCD× 0.01kWhRead
HR18doc 40019 (0x0012)Parity / stop bitsINT32ABCDRead0 = 1 stop bit, no parity
HR20doc 40021 (0x0014)Modbus address1-250; the manual's example writes 0x2A with function 16.INT32ABCDRead/write
HR28doc 40029 (0x001C)Baud rateDefault 2 (9600).INT32ABCDRead0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200; 5 = 1200
HR86doc 40087 (0x0056)Pulse output modeDefault 2; read with function 03 in the manual's example.INT32ABCDRead
HR64514doc 464515 (0xFC02)Meter codeFixed code; the table shows 0x0000000D.INT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU)

What Modbus registers does the Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU) have?

This map lists 19 registers: 14 input registers, 5 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row gives a 3xxxx/4xxxx reference and a hex start address; the hex value is the wire address (30073 = 0x0048). The manual's example frame CC 04 00 48 00 04 reads total import and export energy at 0x0048.

What byte order does the Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU)?

Start with IR 72 Total import active energy (Total import active energy (0.01 kWh)); IR 74 Total export active energy (Total export active energy); IR 0 Voltage L1-N (Voltage L1-N); IR 6 Current L1 (Current L1); IR 62 Total power factor (Total power factor).

How do I enable Modbus control of the Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU)?

The spec does not describe enabling Modbus. Change the Modbus address by writing register 0x0014 with function 16 (the spec's example sets 0x2A).

Where is the official Eltako DSZ15DZMOD-3x80A MID three-phase energy meter (Modbus RTU) Modbus documentation?

The source is Modbus-RTU protocol specification for DSZ15DZMOD V1.6 (English version) (V1.6), revision 2023-06, published free by Eltako at https://www.eltako.com/fileadmin/downloads/de/_bedienung/Modbus-RTU_protocol_specification_for_DSZ15DZMOD_V1.6_English_version.pdf.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Modbus-RTU protocol specification for DSZ15DZMOD V1.6 (English version) · V1.6 · rev. 2023-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.