Easy Modbus
  1. Home
  2. Modbus register maps
  3. KOSTAL
  4. KOSTAL Smart Energy Meter (KSEM G1 / G2)

Energy meter · Modbus register map

KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2) Modbus register map

Updated 17 November 2026

Short answer

The KSEM is a three-phase energy meter and energy manager. As a Modbus RTU slave (RS485 A/B) or Modbus TCP slave (port 502, TLS on 802) it exposes OBIS-coded power and energy registers, a plug-and-play identification block and a SunSpec meter block. This map covers the internal instantaneous values (0-145), the 64-bit energy counters (512-791) and the identification block (8192-8249).

This page lists 69 Modbus registers for the KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KOSTAL’s own free documentation (linked below) and checked against it.

Manufacturer
KOSTAL
Model
KOSTAL Smart Energy Meter (KSEM G1 / G2)
Equipment type
Energy meter
Registers
69 (0 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
KSEM software 2.6.0
Also known as
KSEM, KSEM G1, KSEM G2, KOSTAL Smart Energy Meter
Source document
KSEM G1/G2 KOSTAL Smart Energy Meter - Interface Description MODBUS · DOC02348405-0007 · rev. 2025-03-13
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2)

Integration in brief

Turn on the Modbus TCP slave in the KSEM web UI and poll the listed blocks of holding registers 0-145 for live values and 512-791 for 64-bit energy counters, high word first, splitting reads at the gaps. Net grid power is Active power+ minus Active power-.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Active power+UINT32 ABCDActive power import (0.1 W)Read
HR 2Active power-UINT32 ABCDActive power export (0.1 W)Read
HR 26Supply frequencyUINT32 ABCDGrid frequencyRead
HR 62Voltage (L1)UINT32 ABCDVoltage L1Read
HR 60Current (L1)UINT32 ABCDCurrent L1Read
HR 512Active energy+UINT64 ABCDImported active energy (0.1 Wh)Read
HR 516Active energy-UINT64 ABCDExported active energy (0.1 Wh)Read
HR 8228SerialNumberSTRING[32]Serial number for identificationRead

Enable Modbus control & writes

In the KSEM web interface open the Modbus settings and activate the TCP slave (and optionally TLS), or set RS485 A or B to Modbus RTU slave; save the settings before polling.

Byte order & addressing

Network setup

Watch out for

KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

69 of 69 shown
KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0Active power+OBIS 1-0:1.4.0*255UINT32ABCD× 0.1WRead
HR2Active power-OBIS 1-0:2.4.0*255UINT32ABCD× 0.1WRead
HR4Reactive power+OBIS 1-0:3.4.0*255UINT32ABCD× 0.1varRead
HR6Reactive power-OBIS 1-0:4.4.0*255UINT32ABCD× 0.1varRead
HR16Apparent power+OBIS 1-0:9.4.0*255UINT32ABCD× 0.1VARead
HR18Apparent power-OBIS 1-0:10.4.0*255UINT32ABCD× 0.1VARead
HR24Power factorOBIS 1-0:13.4.0*255INT32ABCD× 0.001Read
HR26Supply frequencyOBIS 1-0:14.4.0*255UINT32ABCD× 0.001HzRead
HR40Active power+ (L1)OBIS 1-0:21.4.0*255UINT32ABCD× 0.1WRead
HR42Active power- (L1)OBIS 1-0:22.4.0*255UINT32ABCD× 0.1WRead
HR44Reactive power+ (L1)OBIS 1-0:23.4.0*255UINT32ABCD× 0.1varRead
HR46Reactive power- (L1)OBIS 1-0:24.4.0*255UINT32ABCD× 0.1varRead
HR56Apparent power+ (L1)OBIS 1-0:29.4.0*255UINT32ABCD× 0.1VARead
HR58Apparent power- (L1)OBIS 1-0:30.4.0*255UINT32ABCD× 0.1VARead
HR60Current (L1)OBIS 1-0:31.4.0*255UINT32ABCD× 0.001ARead
HR62Voltage (L1)OBIS 1-0:32.4.0*255UINT32ABCD× 0.001VRead
HR64Power factor (L1)OBIS 1-0:33.4.0*255INT32ABCD× 0.001Read
HR80Active power+ (L2)OBIS 1-0:41.4.0*255UINT32ABCD× 0.1WRead
HR82Active power- (L2)OBIS 1-0:42.4.0*255UINT32ABCD× 0.1WRead
HR84Reactive power+ (L2)OBIS 1-0:43.4.0*255UINT32ABCD× 0.1varRead
HR86Reactive power- (L2)OBIS 1-0:44.4.0*255UINT32ABCD× 0.1varRead
HR96Apparent power+ (L2)OBIS 1-0:49.4.0*255UINT32ABCD× 0.1VARead
HR98Apparent power- (L2)OBIS 1-0:50.4.0*255UINT32ABCD× 0.1VARead
HR100Current (L2)OBIS 1-0:51.4.0*255UINT32ABCD× 0.001ARead
HR102Voltage (L2)OBIS 1-0:52.4.0*255UINT32ABCD× 0.001VRead
HR104Power factor (L2)OBIS 1-0:53.4.0*255INT32ABCD× 0.001Read
HR120Active power+ (L3)OBIS 1-0:61.4.0*255UINT32ABCD× 0.1WRead
HR122Active power- (L3)OBIS 1-0:62.4.0*255UINT32ABCD× 0.1WRead
HR124Reactive power+ (L3)OBIS 1-0:63.4.0*255UINT32ABCD× 0.1varRead
HR126Reactive power- (L3)OBIS 1-0:64.4.0*255UINT32ABCD× 0.1varRead
HR136Apparent power+ (L3)OBIS 1-0:69.4.0*255UINT32ABCD× 0.1VARead
HR138Apparent power- (L3)OBIS 1-0:70.4.0*255UINT32ABCD× 0.1VARead
HR140Current (L3)OBIS 1-0:71.4.0*255UINT32ABCD× 0.001ARead
HR142Voltage (L3)OBIS 1-0:72.4.0*255UINT32ABCD× 0.001VRead
HR144Power factor (L3)OBIS 1-0:73.4.0*255INT32ABCD× 0.001Read
HR512Active energy+OBIS 1-0:1.8.0*255UINT64ABCD× 0.1WhRead
HR516Active energy-OBIS 1-0:2.8.0*255UINT64ABCD× 0.1WhRead
HR520Reactive energy+OBIS 1-0:3.8.0*255UINT64ABCD× 0.1varhRead
HR524Reactive energy-OBIS 1-0:4.8.0*255UINT64ABCD× 0.1varhRead
HR544Apparent energy+OBIS 1-0:9.8.0*255UINT64ABCD× 0.1VAhRead
HR548Apparent energy-OBIS 1-0:10.8.0*255UINT64ABCD× 0.1VAhRead
HR592Active energy+ (L1)OBIS 1-0:21.8.0*255UINT64ABCD× 0.1WhRead
HR596Active energy- (L1)OBIS 1-0:22.8.0*255UINT64ABCD× 0.1WhRead
HR600Reactive energy+ (L1)OBIS 1-0:23.8.0*255UINT64ABCD× 0.1varhRead
HR604Reactive energy- (L1)OBIS 1-0:24.8.0*255UINT64ABCD× 0.1varhRead
HR624Apparent energy+ (L1)OBIS 1-0:29.8.0*255UINT64ABCD× 0.1VAhRead
HR628Apparent energy- (L1)OBIS 1-0:30.8.0*255UINT64ABCD× 0.1VAhRead
HR672Active energy+ (L2)OBIS 1-0:41.8.0*255UINT64ABCD× 0.1WhRead
HR676Active energy- (L2)OBIS 1-0:42.8.0*255UINT64ABCD× 0.1WhRead
HR680Reactive energy+ (L2)OBIS 1-0:43.8.0*255UINT64ABCD× 0.1varhRead
HR684Reactive energy- (L2)OBIS 1-0:44.8.0*255UINT64ABCD× 0.1varhRead
HR704Apparent energy+ (L2)OBIS 1-0:49.8.0*255UINT64ABCD× 0.1VAhRead
HR708Apparent energy- (L2)OBIS 1-0:50.8.0*255UINT64ABCD× 0.1VAhRead
HR752Active energy+ (L3)OBIS 1-0:61.8.0*255UINT64ABCD× 0.1WhRead
HR756Active energy- (L3)OBIS 1-0:62.8.0*255UINT64ABCD× 0.1WhRead
HR760Reactive energy+ (L3)OBIS 1-0:63.8.0*255UINT64ABCD× 0.1varhRead
HR764Reactive energy- (L3)OBIS 1-0:64.8.0*255UINT64ABCD× 0.1varhRead
HR784Apparent energy+ (L3)OBIS 1-0:69.8.0*255UINT64ABCD× 0.1VAhRead
HR788Apparent energy- (L3)OBIS 1-0:70.8.0*255UINT64ABCD× 0.1VAhRead
HR8192ManufacturerIDFixed TQ maker ID, reads 0x5233.UINT16Read
HR8193ProductIDHardware type of the meter.UINT16Read18498 = HW v1 (0x4842); 18514 = HW v2 (0x4852); 18530 = HW v3 (0x4862)
HR8194ProductVersionHardware revision of the processor board.UINT16Read
HR8195FirmwareVersionFirmware revision, e.g. 0x0103 = 1.3.x.UINT16Read
HR8196VendorNameVendor name, NUL padded.STRING[32]Read
HR8212ProductNameProduct name, NUL padded.STRING[32]Read
HR8228SerialNumberSerial number, NUL padded.STRING[32]Read
HR8244MeasuringIntervalMeasuring interval of the metering chip.UINT16msRead
HR8245UNIXTimestampCurrent UNIX time in milliseconds.UINT64ABCDmsRead
HR8249ModbusSpecVersionVersion of the Modbus specification in use.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2)

What Modbus registers does the KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2) have?

This map lists 69 registers: 69 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register tables give decimal and hex addresses that are used directly on the wire: the manual's own example reads active power+ from holding registers 0 and 1 and energy from registers 512-515.

What byte order does the KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2)?

Start with HR 0 Active power+ (Active power import (0.1 W)); HR 2 Active power- (Active power export (0.1 W)); HR 26 Supply frequency (Grid frequency); HR 62 Voltage (L1) (Voltage L1); HR 60 Current (L1) (Current L1); HR 512 Active energy+ (Imported active energy (0.1 Wh)); HR 516 Active energy- (Exported active energy (0.1 Wh)); HR 8228 SerialNumber (Serial number for identification).

How do I enable Modbus control of the KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2)?

In the KSEM web interface open the Modbus settings and activate the TCP slave (and optionally TLS), or set RS485 A or B to Modbus RTU slave; save the settings before polling.

Where is the official KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2) Modbus documentation?

The source is KSEM G1/G2 KOSTAL Smart Energy Meter - Interface Description MODBUS (DOC02348405-0007), revision 2025-03-13, published free by KOSTAL at https://www.kostal-solar-electric.com/fileadmin/downloadcenter/kse/BA_KOSTAL_Interface_KSEM_EN.pdf.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: KSEM G1/G2 KOSTAL Smart Energy Meter - Interface Description MODBUS · DOC02348405-0007 · rev. 2025-03-13. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.