- Home
- Modbus register maps
- Janitza
- UMG 605 power quality analyser (Modbus RTU)
Power meter (power analyser) · Modbus register map
Janitza UMG 605 power quality analyser (Modbus RTU) Modbus register map
Updated 17 November 2026
The UMG 605 is Janitza's earlier power quality analyser with four voltage and four current channels and RS485 and Ethernet ports. As a Modbus slave it publishes big-endian 32-bit floats that include the CT/VT ratios. This map covers the 19000-19120 'frequently required readings' block, all-rate energy totals, power factor, digital I/O, pulse counters and the transformer settings.
This page lists 89 Modbus registers for the Janitza UMG 605 power quality analyser (Modbus RTU) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Janitza’s own free documentation (linked below) and checked against it.
- Manufacturer
- Janitza
- Model
- UMG 605 power quality analyser (Modbus RTU)
- Equipment type
- Power meter (power analyser)
- Registers
- 89 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- UMG605, UMG 605, Janitza UMG605
Integration notes: Janitza UMG 605 power quality analyser (Modbus RTU)
Read holding registers (function 03) from 19000: 19000-19121 gives volts, amps, power, CosPhi, frequency, energy and THD as big-endian floats. For all-rate consumed/delivered energy use the energy-table totals.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 19000 | Voltage L1-N | FLOAT32 ABCD | Voltage L1-N | Read |
| HR 19012 | Current L1 | FLOAT32 ABCD | Current L1 | Read |
| HR 19026 | Real power total | FLOAT32 ABCD | Total real power | Read |
| HR 19034 | Apparent power total | FLOAT32 ABCD | Total apparent power | Read |
| HR 19050 | Frequency | FLOAT32 ABCD | Frequency | Read |
| HR 6508 | Real energy L1..L3, consumed (all rates) | FLOAT32 ABCD | Real energy L1..L3, consumed (all rates) | Read |
| HR 6520 | Real energy L1..L3, delivered (all rates) | FLOAT32 ABCD | Real energy L1..L3, delivered (all rates) | Read |
Enable Modbus control & writes
Set the RS485 port to Modbus slave operation with the device address and baud rate in the device configuration; the address list does not give the menu path.
Byte order & addressing
- Addresses are used as printed (0-based).
- Floats are ABCD; add 32768 to an address for little-endian.
- Energy is in Wh/varh/VAh.
- Rotation field (19052) is a float: 1, 0 or -1.
Network setup
- 8 data bits, no parity; the device sends 2 stop bits.
- Baud rates 9.6, 19.2, 38.4, 57.6, 115.2 or 921.6 kbps.
Watch out for
- 19068 is rate 1 only, not the consumed total.
- Short-format copies ignore the CT/VT ratio.
Janitza UMG 605 power quality analyser (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 3893 | Power factor L1 | FLOAT32 | ABCD | Read | ||||
| HR | 3895 | Power factor L2 | FLOAT32 | ABCD | Read | ||||
| HR | 3897 | Power factor L3 | FLOAT32 | ABCD | Read | ||||
| HR | 3899 | Power factor L4 | FLOAT32 | ABCD | Read | ||||
| HR | 6462 | Current rate, real/apparent energy | INT16 | Read | |||||
| HR | 6463 | Current rate, reactive energy | INT16 | Read | |||||
| HR | 6472 | Apparent energy L1..L3 (energy table) | FLOAT32 | ABCD | VAh | Read | |||
| HR | 6484 | Real energy L1..L3 (energy table) | FLOAT32 | ABCD | Wh | Read | |||
| HR | 6496 | Reactive energy L1..L3 (energy table) | FLOAT32 | ABCD | varh | Read | |||
| HR | 6508 | Real energy L1..L3, consumed (all rates) | FLOAT32 | ABCD | Wh | Read | |||
| HR | 6520 | Real energy L1..L3, delivered (all rates) | FLOAT32 | ABCD | Wh | Read | |||
| HR | 6620 | Pulse input 1 counter | Raw pulse count, not scaled (float). | FLOAT32 | ABCD | Read | |||
| HR | 6622 | Pulse input 2 counter | Raw pulse count, not scaled (float). | FLOAT32 | ABCD | Read | |||
| HR | 6624 | Runtime, real/apparent energy metering | FLOAT32 | ABCD | s | Read | |||
| HR | 6626 | Runtime, reactive energy metering | FLOAT32 | ABCD | s | Read | |||
| HR | 6628 | Star point voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 6630 | Digital output 1 status | INT16 | Read | 0 = Not active; 1 = Active | ||||
| HR | 6631 | Digital output 2 status | INT16 | Read | 0 = Not active; 1 = Active | ||||
| HR | 6632 | Digital input 1 status | INT16 | Read | 0 = Not active; 1 = Active | ||||
| HR | 6633 | Digital input 2 status | Listed as 'input 1' in the list; second input by position (_DIGIN_STAT[1]). | INT16 | Read | 0 = Not active; 1 = Active | |||
| HR | 6689 | CT primary L1-L3 | FLOAT32 | ABCD | A | Read | |||
| HR | 6691 | CT primary L4 | FLOAT32 | ABCD | A | Read | |||
| HR | 6693 | CT secondary L1-L3 | FLOAT32 | ABCD | A | Read | |||
| HR | 6695 | CT secondary L4 | FLOAT32 | ABCD | A | Read | |||
| HR | 6697 | VT primary L1-L3 | FLOAT32 | ABCD | V | Read | |||
| HR | 6699 | VT primary L4 | FLOAT32 | ABCD | V | Read | |||
| HR | 6701 | VT secondary L1-L3 | FLOAT32 | ABCD | V | Read | |||
| HR | 6703 | VT secondary L4 | FLOAT32 | ABCD | V | Read | |||
| HR | 19000 | Voltage L1-N | FLOAT32 | ABCD | V | Read | |||
| HR | 19002 | Voltage L2-N | FLOAT32 | ABCD | V | Read | |||
| HR | 19004 | Voltage L3-N | FLOAT32 | ABCD | V | Read | |||
| HR | 19006 | Voltage L1-L2 | FLOAT32 | ABCD | V | Read | |||
| HR | 19008 | Voltage L2-L3 | FLOAT32 | ABCD | V | Read | |||
| HR | 19010 | Voltage L3-L1 | FLOAT32 | ABCD | V | Read | |||
| HR | 19012 | Current L1 | FLOAT32 | ABCD | A | Read | |||
| HR | 19014 | Current L2 | FLOAT32 | ABCD | A | Read | |||
| HR | 19016 | Current L3 | FLOAT32 | ABCD | A | Read | |||
| HR | 19018 | Neutral current (vector sum) | FLOAT32 | ABCD | A | Read | |||
| HR | 19020 | Real power L1 | FLOAT32 | ABCD | W | Read | |||
| HR | 19022 | Real power L2 | FLOAT32 | ABCD | W | Read | |||
| HR | 19024 | Real power L3 | FLOAT32 | ABCD | W | Read | |||
| HR | 19026 | Real power total | FLOAT32 | ABCD | W | Read | |||
| HR | 19028 | Apparent power L1 | FLOAT32 | ABCD | VA | Read | |||
| HR | 19030 | Apparent power L2 | FLOAT32 | ABCD | VA | Read | |||
| HR | 19032 | Apparent power L3 | FLOAT32 | ABCD | VA | Read | |||
| HR | 19034 | Apparent power total | FLOAT32 | ABCD | VA | Read | |||
| HR | 19036 | Reactive power L1 (fundamental) | FLOAT32 | ABCD | var | Read | |||
| HR | 19038 | Reactive power L2 (fundamental) | FLOAT32 | ABCD | var | Read | |||
| HR | 19040 | Reactive power L3 (fundamental) | FLOAT32 | ABCD | var | Read | |||
| HR | 19042 | Reactive power total (fundamental) | FLOAT32 | ABCD | var | Read | |||
| HR | 19044 | CosPhi L1 (fundamental) | FLOAT32 | ABCD | Read | ||||
| HR | 19046 | CosPhi L2 (fundamental) | FLOAT32 | ABCD | Read | ||||
| HR | 19048 | CosPhi L3 (fundamental) | FLOAT32 | ABCD | Read | ||||
| HR | 19050 | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 19052 | Rotation field | Phase sequence as a float: 1 = right, 0 = none, -1 = left. | FLOAT32 | ABCD | Read | |||
| HR | 19054 | Real energy L1 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19056 | Real energy L2 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19058 | Real energy L3 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19060 | Real energy L1..L3 | Three-phase total, not split into consumed/delivered. | FLOAT32 | ABCD | Wh | Read | ||
| HR | 19062 | Real energy L1, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19064 | Real energy L2, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19066 | Real energy L3, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19068 | Real energy L1..L3, consumed, rate 1 | Rate (tariff) 1 only; use the energy-table total for all rates. | FLOAT32 | ABCD | Wh | Read | ||
| HR | 19070 | Real energy L1, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19072 | Real energy L2, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19074 | Real energy L3, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19076 | Real energy L1..L3, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19078 | Apparent energy L1 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 19080 | Apparent energy L2 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 19082 | Apparent energy L3 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 19084 | Apparent energy L1..L3 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 19086 | Reactive energy L1 (fundamental) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19088 | Reactive energy L2 (fundamental) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19090 | Reactive energy L3 (fundamental) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19092 | Reactive energy L1..L3 (fundamental) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19094 | Reactive energy inductive L1 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19096 | Reactive energy inductive L2 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19098 | Reactive energy inductive L3 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19100 | Reactive energy inductive L1..L3 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19102 | Reactive energy capacitive L1 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19104 | Reactive energy capacitive L2 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19106 | Reactive energy capacitive L3 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19108 | Reactive energy capacitive L1..L3 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19110 | THD voltage L1-N | FLOAT32 | ABCD | % | Read | |||
| HR | 19112 | THD voltage L2-N | FLOAT32 | ABCD | % | Read | |||
| HR | 19114 | THD voltage L3-N | FLOAT32 | ABCD | % | Read | |||
| HR | 19116 | THD current L1 | FLOAT32 | ABCD | % | Read | |||
| HR | 19118 | THD current L2 | FLOAT32 | ABCD | % | Read | |||
| HR | 19120 | THD current L3 | FLOAT32 | ABCD | % | Read |
Notes on this map
- Byte order: the list says its addresses return data big-endian (ABCD for floats and 32-bit integers). Adding 32768 to an address returns the same value little-endian; that block is not listed.
- Transfer parameters (p. 5): 9.6-921.6 kbps, 8 data bits, no parity, the device sends 2 stop bits (the master may use 1 or 2). The list gives no default address or baud rate.
- Float and integer values include the CT/VT ratios; short values do not.
- Data types: short = signed 16-bit, int = signed 32-bit, uint = unsigned 32-bit, float = IEEE 754 32-bit.
- 19068 is consumed energy of rate 1 only (designation HT = rate 1); use the energy-table total for all rates.
- Outside the frequently-required block the list has no RD/WR column; the CT/VT settings and status registers are listed here as read-only because the list does not say they are writable.
- Left out: the delete-energy commands (6654/6655), whose access is not stated, the RS485/IP parameters (6860-6876, marked internal or packed), harmonics, min/max/mean blocks, monthly energy and per-rate counters.
- The UMG 605 has an Ethernet port (the list carries IP address and DHCP registers) but the address list does not describe Modbus/TCP, so only RTU is listed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Janitza UMG 605 power quality analyser (Modbus RTU)
What Modbus registers does the Janitza UMG 605 power quality analyser (Modbus RTU) have?
This map lists 89 registers: 89 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Janitza UMG 605 power quality analyser (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as protocol addresses and sent unchanged: 19000 is requested as 19000. The list starts at address 0 (real-time clock), which only fits 0-based numbering. In a 1-based or Modicon tool enter 19001 / 419001.
What byte order does the Janitza UMG 605 power quality analyser (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Janitza UMG 605 power quality analyser (Modbus RTU)?
Start with HR 19000 Voltage L1-N (Voltage L1-N); HR 19012 Current L1 (Current L1); HR 19026 Real power total (Total real power); HR 19034 Apparent power total (Total apparent power); HR 19050 Frequency (Frequency); HR 6508 Real energy L1..L3, consumed (all rates) (Real energy L1..L3, consumed (all rates)); HR 6520 Real energy L1..L3, delivered (all rates) (Real energy L1..L3, delivered (all rates)).
How do I enable Modbus control of the Janitza UMG 605 power quality analyser (Modbus RTU)?
Set the RS485 port to Modbus slave operation with the device address and baud rate in the device configuration; the address list does not give the menu path.
Where is the official Janitza UMG 605 power quality analyser (Modbus RTU) Modbus documentation?
The source is Power Quality Analyser UMG 605 - Modbus-address list and Formulary (1.038.009.7.a), published free by Janitza at https://www.janitza.com/files/download/manuals/current/UMG605/janitza-mal-umg605-en.pdf.
More Janitza Modbus register maps
- Power meter (power analyser)
Janitza UMG 104 power analyser (RS-485 Modbus RTU)
UMG 104 DIN-rail power analyser, firmware 1.268, per address list 1.041.006.1.e (01/2023).
Also known as: UMG104, UMG 104, Janitza UMG104 - Power meter (power analyser)
Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP)
UMG 508 power analyser from firmware release 2.x, per Modbus address list 1.042.008.9.b (08/2022).
Also known as: UMG508, UMG 508, Janitza UMG508 - Power meter (power analyser)
Janitza UMG 509 power analyser (Modbus RTU)
UMG 509 (the original, non-PRO model), per Modbus address list 1.059.004.2.d. For the UMG 509-PRO use its own map.
Also known as: UMG509, UMG 509, Janitza UMG509 - Power meter (power quality analyser)
Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 509-PRO per Modbus address list 1.059.004.2.n (06/2024).
Also known as: UMG509-PRO, UMG 509PRO, UMG509PRO, Janitza UMG 509 - Power meter (power quality analyser)
Janitza UMG 511 power quality analyser (Modbus RTU)
UMG 511 per Modbus address list 1.037.021.9.g (05/2021).
Also known as: UMG511, UMG 511, Janitza UMG511 - Power meter (power quality analyser)
Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 512-PRO power quality analyser, per address list 1.054.016.3.k (08/2023).
Also known as: UMG512-PRO, UMG 512, UMG512, UMG 512 PRO, Janitza UMG512-PRO - Power meter (power quality analyser)
Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP)
UMG 604 (non-PRO) from firmware release 2.x, per address list 1.033.033.g.
Also known as: UMG604, UMG 604-E, UMG 604-EP, Janitza UMG 604 (non-PRO) - Power meter (power quality analyser)
Janitza UMG 604-PRO power analyser (Modbus RTU / Modbus TCP)
UMG 604-PRO from firmware release 5.028, per address list 1.033.034.e (08/2023).
Also known as: UMG604-PRO, UMG 604PRO, UMG604PRO, UMG 604-EP PRO, Janitza UMG 604 - Power meter (power quality analyser)
Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 605-PRO from firmware release 5.028, per address list 1.038.009.7.h (09/2022).
Also known as: UMG605-PRO, UMG 605PRO, UMG605PRO, Janitza UMG 605 - Power meter (energy analyser)
Janitza UMG 96-S2 energy analyser (serial Modbus)
UMG 96-S2 energy analyser, per address list 2.062.026.1.b (10/2019).
Also known as: UMG96-S2, UMG 96 S2, UMG96S2, Janitza UMG96-S2 - Power meter (power analyser)
Janitza UMG 96RM power analyser (basic device, RS-485 Modbus RTU)
UMG 96RM basic device from firmware release 1.14, per address list 1.040.034.t; the same list covers the shared registers of the -P, -CBM and -PN extensions. Other UMG 96RM variants (e.g. the Ethernet -E / -EL) are not covered by this list.
Also known as: UMG96RM, UMG 96 RM, UMG 96RM-P, UMG 96RM-CBM, UMG 96RM-PN, Janitza UMG96RM - Power meter (power analyser)
Janitza UMG 96RM-E power analyser (Ethernet, Modbus TCP / RTU)
UMG 96RM-E from firmware 3.01 / hardware release 104, per address list 1.040.085.8.n (06/2024).
Also known as: UMG96RM-E, UMG 96 RM-E, UMG96RME, Janitza UMG96RM-E
Other power & energy meters register maps
- Energy meter
KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2)
KOSTAL Smart Energy Meter generation 1 and 2, firmware 2.6.0 (interface description dated 13.03.2025); OBIS-coded internal registers only.
Also known as: KSEM, KSEM G1, KSEM G2, KOSTAL Smart Energy Meter - Power meter (power factor controller)
Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers
DCRL3, DCRL5 and DCRL8 automatic power factor controllers with optical port or EXP10xx modules (Modbus TCP on DCRL8 only), per protocol document I427 GB 05 20.
Also known as: DCRL3, DCRL5, DCRL8, DCRL 3, DCRL 5, DCRL 8 - Energy meter (DIN-rail, three-phase, MID)
Lumel NMID31 / NMID32 three-phase energy meter
Lumel NMID31 and NMID32 DIN-rail single/three-phase energy meters with RS-485 Modbus RTU, per their interface manual.
Also known as: NMID31, NMID32 - Power meter (modular multi-circuit energy meter)
Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU)
Each SM352 slave meter in a multicube system with the RTU485 Modbus module, per comms manual Rev Beta 1.02 (March 2011).
Also known as: MultiCube, ND multicube, SM352, RTU485 - Sensor / multi-parameter controller
ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)
diaLog DACa controllers with the Modbus RTU interface option, per software manual BA DM 212 12/15.
Also known as: DACa, diaLog DACa, DULCOMETER DACa - Power meter
Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter
Rishabh RISH Delta VAF NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0118 Rev. F.
Also known as: RISH Delta VAF NX, Delta VAF NX, RISH Delta VAF
All power & energy meters Modbus register maps →
Source: Power Quality Analyser UMG 605 - Modbus-address list and Formulary · 1.038.009.7.a. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.