Power meter (power analyser) · Modbus register map
Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) Modbus register map
Updated 17 November 2026
The UMG 508 is a panel-mount power analyser with four voltage and four current channels, an RS485 port and Ethernet. It is a Modbus RTU slave on RS485 (when that port is set to Modbus Slave) and serves Modbus/TCP on Ethernet. Values are big-endian 32-bit floats that include the CT/VT ratios. This map covers the 19000-19120 'frequently required readings' block, power factor, all-tariff and per-rate energy totals, digital I/O, pulse counters and reset commands.
This page lists 115 Modbus registers for the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Janitza’s own free documentation (linked below) and checked against it.
- Manufacturer
- Janitza
- Model
- UMG 508 power analyser (Modbus RTU / Modbus TCP)
- Equipment type
- Power meter (power analyser)
- Registers
- 115 (16 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 1
- Default serial
- 115200 baud, 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- 2.x
- Also known as
- UMG508, UMG 508, Janitza UMG508
Integration notes: Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP)
Read holding registers (function 03) from 19000: 19000-19121 gives volts, amps, power, CosPhi, frequency, energy and THD as big-endian floats. For all-rate energy totals read 9929 (consumed) and 9941 (delivered).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 19000 | Voltage L1-N | FLOAT32 ABCD | Voltage L1-N | Read |
| HR 19012 | Current L1 | FLOAT32 ABCD | Current L1 | Read |
| HR 19026 | Real power total | FLOAT32 ABCD | Total real power | Read |
| HR 19034 | Apparent power total | FLOAT32 ABCD | Total apparent power | Read |
| HR 19050 | Frequency | FLOAT32 ABCD | Frequency | Read |
| HR 9929 | Real energy L1..L3, consumed | FLOAT32 ABCD | Consumed real energy, all rates | Read |
| HR 9941 | Real energy L1..L3, delivered | FLOAT32 ABCD | Delivered real energy, all rates | Read |
Enable Modbus control & writes
For RTU, set the RS485 protocol to Modbus Slave in the device configuration (factory setting is Modbus Master/Gateway), then the device address and baud rate. Modbus/TCP is served on Ethernet; the factory network setting is DHCP.
Byte order & addressing
- Addresses are used as printed (0-based).
- Floats are ABCD; add 32768 to an address for little-endian.
- Energy is in Wh/varh/VAh.
- Rotation field (19052) is a float: 1, 0 or -1.
Network setup
- RS485: 8 data bits, no parity; the device sends 2 stop bits.
- Factory RS485 settings: address 1, 115.2 kbps.
- Write 1 to 10096 / 10097 to clear the real / reactive energy counters.
Watch out for
- Out of the box the RS485 port is a Modbus master/gateway and will not answer as a slave.
- 19068 is rate 1 only, not the consumed total.
Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 4 | System time (UTC) | Seconds, UTC. | INT32 | ABCD | s | Read/write | ||
| HR | 9883 | Current rate, real/apparent energy | INT16 | Read/write | |||||
| HR | 9884 | Current rate, reactive energy | INT16 | Read/write | |||||
| HR | 9893 | Apparent energy L1..L3 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 9895 | Apparent energy L1..L4 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 9905 | Real energy L1..L3 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 9907 | Real energy L1..L4 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 9917 | Reactive energy L1..L3 | FLOAT32 | ABCD | varh | Read | |||
| HR | 9919 | Reactive energy L1..L4 | FLOAT32 | ABCD | varh | Read | |||
| HR | 9929 | Real energy L1..L3, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 9931 | Real energy L1..L4, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 9941 | Real energy L1..L3, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 9943 | Real energy L1..L4, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 9965 | Real energy L1..L3, consumed, rate 2 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 9977 | Real energy L1..L3, delivered, rate 1 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 9989 | Real energy L1..L3, delivered, rate 2 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 10001 | Reactive energy L1..L3, inductive | FLOAT32 | ABCD | varh | Read | |||
| HR | 10013 | Reactive energy L1..L3, capacitive | FLOAT32 | ABCD | varh | Read | |||
| HR | 10041 | Pulse input 1 counter | Raw pulse count, not scaled (float). | FLOAT32 | ABCD | Read | |||
| HR | 10043 | Pulse input 2 counter | Raw pulse count, not scaled (float). | FLOAT32 | ABCD | Read | |||
| HR | 10045 | Pulse input 3 counter | Raw pulse count, not scaled (float). | FLOAT32 | ABCD | Read | |||
| HR | 10047 | Pulse input 4 counter | Raw pulse count, not scaled (float). | FLOAT32 | ABCD | Read | |||
| HR | 10049 | Pulse input 5 counter | Raw pulse count, not scaled (float). | FLOAT32 | ABCD | Read | |||
| HR | 10051 | Pulse input 6 counter | Raw pulse count, not scaled (float). | FLOAT32 | ABCD | Read | |||
| HR | 10053 | Pulse input 7 counter | Raw pulse count, not scaled (float). | FLOAT32 | ABCD | Read | |||
| HR | 10055 | Pulse input 8 counter | Raw pulse count, not scaled (float). | FLOAT32 | ABCD | Read | |||
| HR | 10057 | Runtime, real/apparent energy metering | FLOAT32 | ABCD | s | Read | |||
| HR | 10059 | Runtime, reactive energy metering | FLOAT32 | ABCD | s | Read | |||
| HR | 10061 | Star point voltage | Voltage of the star connection point. | FLOAT32 | ABCD | V | Read | ||
| HR | 10063 | Digital output 1 status | INT16 | Read/write | 0 = Not active; 1 = Active | ||||
| HR | 10064 | Digital output 2 status | INT16 | Read/write | 0 = Not active; 1 = Active | ||||
| HR | 10065 | Digital output 3 status | INT16 | Read/write | 0 = Not active; 1 = Active | ||||
| HR | 10066 | Digital output 4 status | INT16 | Read/write | 0 = Not active; 1 = Active | ||||
| HR | 10067 | Digital output 5 status | INT16 | Read/write | 0 = Not active; 1 = Active | ||||
| HR | 10068 | Digital input 1 status | INT16 | Read | 0 = Not active; 1 = Active | ||||
| HR | 10069 | Digital input 2 status | INT16 | Read | 0 = Not active; 1 = Active | ||||
| HR | 10070 | Digital input 3 status | INT16 | Read | 0 = Not active; 1 = Active | ||||
| HR | 10071 | Digital input 4 status | INT16 | Read | 0 = Not active; 1 = Active | ||||
| HR | 10072 | Digital input 5 status | INT16 | Read | 0 = Not active; 1 = Active | ||||
| HR | 10073 | Digital input 6 status | INT16 | Read | 0 = Not active; 1 = Active | ||||
| HR | 10074 | Digital input 7 status | INT16 | Read | 0 = Not active; 1 = Active | ||||
| HR | 10075 | Digital input 8 status | INT16 | Read | 0 = Not active; 1 = Active | ||||
| HR | 10076 | Event counter | UINT32 | ABCD | Read/write | ||||
| HR | 10090 | RS485 receive error counter | UINT32 | ABCD | Read/write | ||||
| HR | 10094 | RS485 error counter | UINT32 | ABCD | Read/write | ||||
| HR | 10096 | Delete real energy counters | Write 1 to clear all real energy counters. | INT16 | Read/write | ||||
| HR | 10097 | Delete reactive energy counters | Write 1 to clear all reactive energy counters. | INT16 | Read/write | ||||
| HR | 10281 | RS485 Modbus address | Device address on the RS485 port. | INT32 | ABCD | Read/write | |||
| HR | 10293 | DHCP mode | INT32 | ABCD | Read/write | 0 = Off; 1 = BootP; 2 = DHCP | |||
| HR | 10361 | Nominal frequency | FLOAT32 | ABCD | Hz | Read/write | |||
| HR | 17383 | Power factor L1 | FLOAT32 | ABCD | Read | ||||
| HR | 17385 | Power factor L2 | FLOAT32 | ABCD | Read | ||||
| HR | 17387 | Power factor L3 | FLOAT32 | ABCD | Read | ||||
| HR | 17389 | Power factor L4 | FLOAT32 | ABCD | Read | ||||
| HR | 19000 | Voltage L1-N | FLOAT32 | ABCD | V | Read | |||
| HR | 19002 | Voltage L2-N | FLOAT32 | ABCD | V | Read | |||
| HR | 19004 | Voltage L3-N | FLOAT32 | ABCD | V | Read | |||
| HR | 19006 | Voltage L1-L2 | FLOAT32 | ABCD | V | Read | |||
| HR | 19008 | Voltage L2-L3 | FLOAT32 | ABCD | V | Read | |||
| HR | 19010 | Voltage L3-L1 | FLOAT32 | ABCD | V | Read | |||
| HR | 19012 | Current L1 | FLOAT32 | ABCD | A | Read | |||
| HR | 19014 | Current L2 | FLOAT32 | ABCD | A | Read | |||
| HR | 19016 | Current L3 | FLOAT32 | ABCD | A | Read | |||
| HR | 19018 | Neutral current (vector sum) | FLOAT32 | ABCD | A | Read | |||
| HR | 19020 | Real power L1 | FLOAT32 | ABCD | W | Read | |||
| HR | 19022 | Real power L2 | FLOAT32 | ABCD | W | Read | |||
| HR | 19024 | Real power L3 | FLOAT32 | ABCD | W | Read | |||
| HR | 19026 | Real power total | FLOAT32 | ABCD | W | Read | |||
| HR | 19028 | Apparent power L1 | FLOAT32 | ABCD | VA | Read | |||
| HR | 19030 | Apparent power L2 | FLOAT32 | ABCD | VA | Read | |||
| HR | 19032 | Apparent power L3 | FLOAT32 | ABCD | VA | Read | |||
| HR | 19034 | Apparent power total | FLOAT32 | ABCD | VA | Read | |||
| HR | 19036 | Reactive power L1 (fundamental) | FLOAT32 | ABCD | var | Read | |||
| HR | 19038 | Reactive power L2 (fundamental) | FLOAT32 | ABCD | var | Read | |||
| HR | 19040 | Reactive power L3 (fundamental) | FLOAT32 | ABCD | var | Read | |||
| HR | 19042 | Reactive power total (fundamental) | FLOAT32 | ABCD | var | Read | |||
| HR | 19044 | CosPhi L1 (fundamental) | FLOAT32 | ABCD | Read | ||||
| HR | 19046 | CosPhi L2 (fundamental) | FLOAT32 | ABCD | Read | ||||
| HR | 19048 | CosPhi L3 (fundamental) | FLOAT32 | ABCD | Read | ||||
| HR | 19050 | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 19052 | Rotation field | Phase sequence as a float: 1 = right, 0 = none, -1 = left. | FLOAT32 | ABCD | Read | |||
| HR | 19054 | Real energy L1 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19056 | Real energy L2 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19058 | Real energy L3 | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19060 | Real energy L1..L3 | Three-phase total, not split into consumed/delivered. | FLOAT32 | ABCD | Wh | Read | ||
| HR | 19062 | Real energy L1, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19064 | Real energy L2, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19066 | Real energy L3, consumed | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19068 | Real energy L1..L3, consumed, rate 1 | Tariff 1 only (designation _G_WH_V_HT_SUML13); use 9929 for the all-tariff total. | FLOAT32 | ABCD | Wh | Read | ||
| HR | 19070 | Real energy L1, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19072 | Real energy L2, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19074 | Real energy L3, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19076 | Real energy L1..L3, delivered | FLOAT32 | ABCD | Wh | Read | |||
| HR | 19078 | Apparent energy L1 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 19080 | Apparent energy L2 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 19082 | Apparent energy L3 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 19084 | Apparent energy L1..L3 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 19086 | Reactive energy L1 (fundamental) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19088 | Reactive energy L2 (fundamental) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19090 | Reactive energy L3 (fundamental) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19092 | Reactive energy L1..L3 (fundamental) | FLOAT32 | ABCD | varh | Read | |||
| HR | 19094 | Reactive energy inductive L1 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19096 | Reactive energy inductive L2 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19098 | Reactive energy inductive L3 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19100 | Reactive energy inductive L1..L3 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19102 | Reactive energy capacitive L1 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19104 | Reactive energy capacitive L2 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19106 | Reactive energy capacitive L3 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19108 | Reactive energy capacitive L1..L3 | FLOAT32 | ABCD | varh | Read | |||
| HR | 19110 | THD voltage L1-N | FLOAT32 | ABCD | % | Read | |||
| HR | 19112 | THD voltage L2-N | FLOAT32 | ABCD | % | Read | |||
| HR | 19114 | THD voltage L3-N | FLOAT32 | ABCD | % | Read | |||
| HR | 19116 | THD current L1 | FLOAT32 | ABCD | % | Read | |||
| HR | 19118 | THD current L2 | FLOAT32 | ABCD | % | Read | |||
| HR | 19120 | THD current L3 | FLOAT32 | ABCD | % | Read |
Notes on this map
- Byte order: the list says its addresses return data big-endian (ABCD for floats and 32-bit integers). Adding 32768 to an address returns the same value little-endian; that block is not listed.
- Transfer parameters (p. 5): 9.6-921.6 kbps, 8 data bits, no parity, the UMG 508 sends 2 stop bits (the master may use 1 or 2).
- Defaults for the RS485 port come from the UMG 508 user manual (https://www.janitza.com/files/download/manuals/current/UMG508/janitza-bhb-umg508-en.pdf, RS485 settings): device address 1, 115.2 kbps, and the protocol is factory-set to Modbus Master/Gateway, not Modbus Slave.
- The Modbus/TCP port number is not given in the address list or user manual; 502 is the Modbus default but is left blank here.
- Data types: short = signed 16-bit, int = signed 32-bit, uint = unsigned 32-bit, float = IEEE 754 32-bit.
- 19068 is consumed energy of rate 1 only (its designation says HT = rate 1). For the all-rate consumed and delivered totals use 9929 and 9941.
- Left out: the CT/VT ratio arrays 10131-10161 (each element is labelled 'L1, L2, L3', so which element maps to which input is not clear), RS485 mode and baud (10283/10285, no value coding given), IP address/mask/gateway as packed integers, string settings, internal-use registers, harmonics and min/max/mean blocks.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP)
What Modbus registers does the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) have?
This map lists 115 registers: 115 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as protocol addresses and sent unchanged: 19000 is requested as 19000. The list starts at address 0 (real-time clock), which only fits 0-based numbering. In a 1-based or Modicon tool enter 19001 / 419001.
What byte order does the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP)?
Start with HR 19000 Voltage L1-N (Voltage L1-N); HR 19012 Current L1 (Current L1); HR 19026 Real power total (Total real power); HR 19034 Apparent power total (Total apparent power); HR 19050 Frequency (Frequency); HR 9929 Real energy L1..L3, consumed (Consumed real energy, all rates); HR 9941 Real energy L1..L3, delivered (Delivered real energy, all rates).
How do I enable Modbus control of the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP)?
For RTU, set the RS485 protocol to Modbus Slave in the device configuration (factory setting is Modbus Master/Gateway), then the device address and baud rate. Modbus/TCP is served on Ethernet; the factory network setting is DHCP.
Where is the official Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) Modbus documentation?
The source is Power Analyser UMG 508 - Modbus-address and Formulary (from firmware release 2.x) (1.042.008.9.b), revision 2022-08, published free by Janitza at https://www.janitza.com/files/download/manuals/current/UMG508/janitza-mal-umg508-en.pdf.
More Janitza Modbus register maps
- Power meter (power analyser)
Janitza UMG 104 power analyser (RS-485 Modbus RTU)
UMG 104 DIN-rail power analyser, firmware 1.268, per address list 1.041.006.1.e (01/2023).
Also known as: UMG104, UMG 104, Janitza UMG104 - Power meter (power analyser)
Janitza UMG 509 power analyser (Modbus RTU)
UMG 509 (the original, non-PRO model), per Modbus address list 1.059.004.2.d. For the UMG 509-PRO use its own map.
Also known as: UMG509, UMG 509, Janitza UMG509 - Power meter (power quality analyser)
Janitza UMG 509-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 509-PRO per Modbus address list 1.059.004.2.n (06/2024).
Also known as: UMG509-PRO, UMG 509PRO, UMG509PRO, Janitza UMG 509 - Power meter (power quality analyser)
Janitza UMG 511 power quality analyser (Modbus RTU)
UMG 511 per Modbus address list 1.037.021.9.g (05/2021).
Also known as: UMG511, UMG 511, Janitza UMG511 - Power meter (power quality analyser)
Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 512-PRO power quality analyser, per address list 1.054.016.3.k (08/2023).
Also known as: UMG512-PRO, UMG 512, UMG512, UMG 512 PRO, Janitza UMG512-PRO - Power meter (power quality analyser)
Janitza UMG 604 power analyser, firmware 2.x (Modbus RTU / Modbus TCP)
UMG 604 (non-PRO) from firmware release 2.x, per address list 1.033.033.g.
Also known as: UMG604, UMG 604-E, UMG 604-EP, Janitza UMG 604 (non-PRO) - Power meter (power quality analyser)
Janitza UMG 604-PRO power analyser (Modbus RTU / Modbus TCP)
UMG 604-PRO from firmware release 5.028, per address list 1.033.034.e (08/2023).
Also known as: UMG604-PRO, UMG 604PRO, UMG604PRO, UMG 604-EP PRO, Janitza UMG 604 - Power meter (power analyser)
Janitza UMG 605 power quality analyser (Modbus RTU)
UMG 605 (the original, non-PRO model), per Modbus address list 1.038.009.7.a. For the UMG 605-PRO use its own map.
Also known as: UMG605, UMG 605, Janitza UMG605 - Power meter (power quality analyser)
Janitza UMG 605-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 605-PRO from firmware release 5.028, per address list 1.038.009.7.h (09/2022).
Also known as: UMG605-PRO, UMG 605PRO, UMG605PRO, Janitza UMG 605 - Power meter (energy analyser)
Janitza UMG 96-S2 energy analyser (serial Modbus)
UMG 96-S2 energy analyser, per address list 2.062.026.1.b (10/2019).
Also known as: UMG96-S2, UMG 96 S2, UMG96S2, Janitza UMG96-S2 - Power meter (power analyser)
Janitza UMG 96RM power analyser (basic device, RS-485 Modbus RTU)
UMG 96RM basic device from firmware release 1.14, per address list 1.040.034.t; the same list covers the shared registers of the -P, -CBM and -PN extensions. Other UMG 96RM variants (e.g. the Ethernet -E / -EL) are not covered by this list.
Also known as: UMG96RM, UMG 96 RM, UMG 96RM-P, UMG 96RM-CBM, UMG 96RM-PN, Janitza UMG96RM - Power meter (power analyser)
Janitza UMG 96RM-E power analyser (Ethernet, Modbus TCP / RTU)
UMG 96RM-E from firmware 3.01 / hardware release 104, per address list 1.040.085.8.n (06/2024).
Also known as: UMG96RM-E, UMG 96 RM-E, UMG96RME, Janitza UMG96RM-E
Other power & energy meters register maps
- Energy meter
KOSTAL KOSTAL Smart Energy Meter (KSEM G1 / G2)
KOSTAL Smart Energy Meter generation 1 and 2, firmware 2.6.0 (interface description dated 13.03.2025); OBIS-coded internal registers only.
Also known as: KSEM, KSEM G1, KSEM G2, KOSTAL Smart Energy Meter - Power meter (power factor controller)
Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers
DCRL3, DCRL5 and DCRL8 automatic power factor controllers with optical port or EXP10xx modules (Modbus TCP on DCRL8 only), per protocol document I427 GB 05 20.
Also known as: DCRL3, DCRL5, DCRL8, DCRL 3, DCRL 5, DCRL 8 - Energy meter (DIN-rail, three-phase, MID)
Lumel NMID31 / NMID32 three-phase energy meter
Lumel NMID31 and NMID32 DIN-rail single/three-phase energy meters with RS-485 Modbus RTU, per their interface manual.
Also known as: NMID31, NMID32 - Power meter (modular multi-circuit energy meter)
Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU)
Each SM352 slave meter in a multicube system with the RTU485 Modbus module, per comms manual Rev Beta 1.02 (March 2011).
Also known as: MultiCube, ND multicube, SM352, RTU485 - Sensor / multi-parameter controller
ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)
diaLog DACa controllers with the Modbus RTU interface option, per software manual BA DM 212 12/15.
Also known as: DACa, diaLog DACa, DULCOMETER DACa - Power meter
Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter
Rishabh RISH Delta VAF NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0118 Rev. F.
Also known as: RISH Delta VAF NX, Delta VAF NX, RISH Delta VAF
All power & energy meters Modbus register maps →
Source: Power Analyser UMG 508 - Modbus-address and Formulary (from firmware release 2.x) · 1.042.008.9.b · rev. 2022-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.