Power meter (power analyser) · Modbus register map

Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) Modbus register map

Updated 17 November 2026

Short answer

The UMG 508 is a panel-mount power analyser with four voltage and four current channels, an RS485 port and Ethernet. It is a Modbus RTU slave on RS485 (when that port is set to Modbus Slave) and serves Modbus/TCP on Ethernet. Values are big-endian 32-bit floats that include the CT/VT ratios. This map covers the 19000-19120 'frequently required readings' block, power factor, all-tariff and per-rate energy totals, digital I/O, pulse counters and reset commands.

This page lists 115 Modbus registers for the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Janitza’s own free documentation (linked below) and checked against it.

Manufacturer
Janitza
Model
UMG 508 power analyser (Modbus RTU / Modbus TCP)
Equipment type
Power meter (power analyser)
Registers
115 (16 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
1
Default serial
115200 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
2.x
Also known as
UMG508, UMG 508, Janitza UMG508
Source document
Power Analyser UMG 508 - Modbus-address and Formulary (from firmware release 2.x) · 1.042.008.9.b · rev. 2022-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP)

Integration in brief

Read holding registers (function 03) from 19000: 19000-19121 gives volts, amps, power, CosPhi, frequency, energy and THD as big-endian floats. For all-rate energy totals read 9929 (consumed) and 9941 (delivered).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 19000Voltage L1-NFLOAT32 ABCDVoltage L1-NRead
HR 19012Current L1FLOAT32 ABCDCurrent L1Read
HR 19026Real power totalFLOAT32 ABCDTotal real powerRead
HR 19034Apparent power totalFLOAT32 ABCDTotal apparent powerRead
HR 19050FrequencyFLOAT32 ABCDFrequencyRead
HR 9929Real energy L1..L3, consumedFLOAT32 ABCDConsumed real energy, all ratesRead
HR 9941Real energy L1..L3, deliveredFLOAT32 ABCDDelivered real energy, all ratesRead

Enable Modbus control & writes

For RTU, set the RS485 protocol to Modbus Slave in the device configuration (factory setting is Modbus Master/Gateway), then the device address and baud rate. Modbus/TCP is served on Ethernet; the factory network setting is DHCP.

Byte order & addressing

Network setup

Watch out for

Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

115 of 115 shown
Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR4System time (UTC)Seconds, UTC.INT32ABCDsRead/write
HR9883Current rate, real/apparent energyINT16Read/write
HR9884Current rate, reactive energyINT16Read/write
HR9893Apparent energy L1..L3FLOAT32ABCDVAhRead
HR9895Apparent energy L1..L4FLOAT32ABCDVAhRead
HR9905Real energy L1..L3FLOAT32ABCDWhRead
HR9907Real energy L1..L4FLOAT32ABCDWhRead
HR9917Reactive energy L1..L3FLOAT32ABCDvarhRead
HR9919Reactive energy L1..L4FLOAT32ABCDvarhRead
HR9929Real energy L1..L3, consumedFLOAT32ABCDWhRead
HR9931Real energy L1..L4, consumedFLOAT32ABCDWhRead
HR9941Real energy L1..L3, deliveredFLOAT32ABCDWhRead
HR9943Real energy L1..L4, deliveredFLOAT32ABCDWhRead
HR9965Real energy L1..L3, consumed, rate 2FLOAT32ABCDWhRead
HR9977Real energy L1..L3, delivered, rate 1FLOAT32ABCDWhRead
HR9989Real energy L1..L3, delivered, rate 2FLOAT32ABCDWhRead
HR10001Reactive energy L1..L3, inductiveFLOAT32ABCDvarhRead
HR10013Reactive energy L1..L3, capacitiveFLOAT32ABCDvarhRead
HR10041Pulse input 1 counterRaw pulse count, not scaled (float).FLOAT32ABCDRead
HR10043Pulse input 2 counterRaw pulse count, not scaled (float).FLOAT32ABCDRead
HR10045Pulse input 3 counterRaw pulse count, not scaled (float).FLOAT32ABCDRead
HR10047Pulse input 4 counterRaw pulse count, not scaled (float).FLOAT32ABCDRead
HR10049Pulse input 5 counterRaw pulse count, not scaled (float).FLOAT32ABCDRead
HR10051Pulse input 6 counterRaw pulse count, not scaled (float).FLOAT32ABCDRead
HR10053Pulse input 7 counterRaw pulse count, not scaled (float).FLOAT32ABCDRead
HR10055Pulse input 8 counterRaw pulse count, not scaled (float).FLOAT32ABCDRead
HR10057Runtime, real/apparent energy meteringFLOAT32ABCDsRead
HR10059Runtime, reactive energy meteringFLOAT32ABCDsRead
HR10061Star point voltageVoltage of the star connection point.FLOAT32ABCDVRead
HR10063Digital output 1 statusINT16Read/write0 = Not active; 1 = Active
HR10064Digital output 2 statusINT16Read/write0 = Not active; 1 = Active
HR10065Digital output 3 statusINT16Read/write0 = Not active; 1 = Active
HR10066Digital output 4 statusINT16Read/write0 = Not active; 1 = Active
HR10067Digital output 5 statusINT16Read/write0 = Not active; 1 = Active
HR10068Digital input 1 statusINT16Read0 = Not active; 1 = Active
HR10069Digital input 2 statusINT16Read0 = Not active; 1 = Active
HR10070Digital input 3 statusINT16Read0 = Not active; 1 = Active
HR10071Digital input 4 statusINT16Read0 = Not active; 1 = Active
HR10072Digital input 5 statusINT16Read0 = Not active; 1 = Active
HR10073Digital input 6 statusINT16Read0 = Not active; 1 = Active
HR10074Digital input 7 statusINT16Read0 = Not active; 1 = Active
HR10075Digital input 8 statusINT16Read0 = Not active; 1 = Active
HR10076Event counterUINT32ABCDRead/write
HR10090RS485 receive error counterUINT32ABCDRead/write
HR10094RS485 error counterUINT32ABCDRead/write
HR10096Delete real energy countersWrite 1 to clear all real energy counters.INT16Read/write
HR10097Delete reactive energy countersWrite 1 to clear all reactive energy counters.INT16Read/write
HR10281RS485 Modbus addressDevice address on the RS485 port.INT32ABCDRead/write
HR10293DHCP modeINT32ABCDRead/write0 = Off; 1 = BootP; 2 = DHCP
HR10361Nominal frequencyFLOAT32ABCDHzRead/write
HR17383Power factor L1FLOAT32ABCDRead
HR17385Power factor L2FLOAT32ABCDRead
HR17387Power factor L3FLOAT32ABCDRead
HR17389Power factor L4FLOAT32ABCDRead
HR19000Voltage L1-NFLOAT32ABCDVRead
HR19002Voltage L2-NFLOAT32ABCDVRead
HR19004Voltage L3-NFLOAT32ABCDVRead
HR19006Voltage L1-L2FLOAT32ABCDVRead
HR19008Voltage L2-L3FLOAT32ABCDVRead
HR19010Voltage L3-L1FLOAT32ABCDVRead
HR19012Current L1FLOAT32ABCDARead
HR19014Current L2FLOAT32ABCDARead
HR19016Current L3FLOAT32ABCDARead
HR19018Neutral current (vector sum)FLOAT32ABCDARead
HR19020Real power L1FLOAT32ABCDWRead
HR19022Real power L2FLOAT32ABCDWRead
HR19024Real power L3FLOAT32ABCDWRead
HR19026Real power totalFLOAT32ABCDWRead
HR19028Apparent power L1FLOAT32ABCDVARead
HR19030Apparent power L2FLOAT32ABCDVARead
HR19032Apparent power L3FLOAT32ABCDVARead
HR19034Apparent power totalFLOAT32ABCDVARead
HR19036Reactive power L1 (fundamental)FLOAT32ABCDvarRead
HR19038Reactive power L2 (fundamental)FLOAT32ABCDvarRead
HR19040Reactive power L3 (fundamental)FLOAT32ABCDvarRead
HR19042Reactive power total (fundamental)FLOAT32ABCDvarRead
HR19044CosPhi L1 (fundamental)FLOAT32ABCDRead
HR19046CosPhi L2 (fundamental)FLOAT32ABCDRead
HR19048CosPhi L3 (fundamental)FLOAT32ABCDRead
HR19050FrequencyFLOAT32ABCDHzRead
HR19052Rotation fieldPhase sequence as a float: 1 = right, 0 = none, -1 = left.FLOAT32ABCDRead
HR19054Real energy L1FLOAT32ABCDWhRead
HR19056Real energy L2FLOAT32ABCDWhRead
HR19058Real energy L3FLOAT32ABCDWhRead
HR19060Real energy L1..L3Three-phase total, not split into consumed/delivered.FLOAT32ABCDWhRead
HR19062Real energy L1, consumedFLOAT32ABCDWhRead
HR19064Real energy L2, consumedFLOAT32ABCDWhRead
HR19066Real energy L3, consumedFLOAT32ABCDWhRead
HR19068Real energy L1..L3, consumed, rate 1Tariff 1 only (designation _G_WH_V_HT_SUML13); use 9929 for the all-tariff total.FLOAT32ABCDWhRead
HR19070Real energy L1, deliveredFLOAT32ABCDWhRead
HR19072Real energy L2, deliveredFLOAT32ABCDWhRead
HR19074Real energy L3, deliveredFLOAT32ABCDWhRead
HR19076Real energy L1..L3, deliveredFLOAT32ABCDWhRead
HR19078Apparent energy L1FLOAT32ABCDVAhRead
HR19080Apparent energy L2FLOAT32ABCDVAhRead
HR19082Apparent energy L3FLOAT32ABCDVAhRead
HR19084Apparent energy L1..L3FLOAT32ABCDVAhRead
HR19086Reactive energy L1 (fundamental)FLOAT32ABCDvarhRead
HR19088Reactive energy L2 (fundamental)FLOAT32ABCDvarhRead
HR19090Reactive energy L3 (fundamental)FLOAT32ABCDvarhRead
HR19092Reactive energy L1..L3 (fundamental)FLOAT32ABCDvarhRead
HR19094Reactive energy inductive L1FLOAT32ABCDvarhRead
HR19096Reactive energy inductive L2FLOAT32ABCDvarhRead
HR19098Reactive energy inductive L3FLOAT32ABCDvarhRead
HR19100Reactive energy inductive L1..L3FLOAT32ABCDvarhRead
HR19102Reactive energy capacitive L1FLOAT32ABCDvarhRead
HR19104Reactive energy capacitive L2FLOAT32ABCDvarhRead
HR19106Reactive energy capacitive L3FLOAT32ABCDvarhRead
HR19108Reactive energy capacitive L1..L3FLOAT32ABCDvarhRead
HR19110THD voltage L1-NFLOAT32ABCD%Read
HR19112THD voltage L2-NFLOAT32ABCD%Read
HR19114THD voltage L3-NFLOAT32ABCD%Read
HR19116THD current L1FLOAT32ABCD%Read
HR19118THD current L2FLOAT32ABCD%Read
HR19120THD current L3FLOAT32ABCD%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP)

What Modbus registers does the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) have?

This map lists 115 registers: 115 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as protocol addresses and sent unchanged: 19000 is requested as 19000. The list starts at address 0 (real-time clock), which only fits 0-based numbering. In a 1-based or Modicon tool enter 19001 / 419001.

What byte order does the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP)?

Start with HR 19000 Voltage L1-N (Voltage L1-N); HR 19012 Current L1 (Current L1); HR 19026 Real power total (Total real power); HR 19034 Apparent power total (Total apparent power); HR 19050 Frequency (Frequency); HR 9929 Real energy L1..L3, consumed (Consumed real energy, all rates); HR 9941 Real energy L1..L3, delivered (Delivered real energy, all rates).

How do I enable Modbus control of the Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP)?

For RTU, set the RS485 protocol to Modbus Slave in the device configuration (factory setting is Modbus Master/Gateway), then the device address and baud rate. Modbus/TCP is served on Ethernet; the factory network setting is DHCP.

Where is the official Janitza UMG 508 power analyser (Modbus RTU / Modbus TCP) Modbus documentation?

The source is Power Analyser UMG 508 - Modbus-address and Formulary (from firmware release 2.x) (1.042.008.9.b), revision 2022-08, published free by Janitza at https://www.janitza.com/files/download/manuals/current/UMG508/janitza-mal-umg508-en.pdf.

More Janitza Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Power Analyser UMG 508 - Modbus-address and Formulary (from firmware release 2.x) · 1.042.008.9.b · rev. 2022-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.