Power meter (power analyser) · Modbus register map

Janitza UMG 509 power analyser (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The UMG 509 is Janitza's earlier panel power analyser with RS485 and Ethernet ports. As a Modbus slave it publishes big-endian 32-bit floats that include the CT/VT ratios. This map covers the 19000-19120 'frequently required readings' block, all-rate energy totals, power factor, digital I/O, pulse counters and the RS485 address.

This page lists 84 Modbus registers for the Janitza UMG 509 power analyser (Modbus RTU) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Janitza’s own free documentation (linked below) and checked against it.

Manufacturer
Janitza
Model
UMG 509 power analyser (Modbus RTU)
Equipment type
Power meter (power analyser)
Registers
84 (4 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N2
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
UMG509, UMG 509, Janitza UMG509
Source document
Power Analyser UMG 509 - Modbus-address and Formulary · 1.059.004.2.d
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Janitza UMG 509 power analyser (Modbus RTU)

Integration in brief

Read holding registers (function 03) from 19000: 19000-19121 gives volts, amps, power, CosPhi, frequency, energy and THD as big-endian floats. For all-rate consumed/delivered energy use the energy-table totals.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 19000Voltage L1-NFLOAT32 ABCDVoltage L1-NRead
HR 19012Current L1FLOAT32 ABCDCurrent L1Read
HR 19026Real power totalFLOAT32 ABCDTotal real powerRead
HR 19034Apparent power totalFLOAT32 ABCDTotal apparent powerRead
HR 19050FrequencyFLOAT32 ABCDFrequencyRead
HR 13995Real energy L1..L3, consumed (all rates)FLOAT32 ABCDReal energy L1..L3, consumed (all rates)Read
HR 14007Real energy L1..L3, delivered (all rates)FLOAT32 ABCDReal energy L1..L3, delivered (all rates)Read

Enable Modbus control & writes

Set the RS485 port to Modbus slave operation with the device address and baud rate in the device configuration; the address list does not give the menu path.

Byte order & addressing

Network setup

Watch out for

Janitza UMG 509 power analyser (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

84 of 84 shown
Janitza UMG 509 power analyser (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR13949Current rate, real/apparent energyINT16Read
HR13950Current rate, reactive energyINT16Read
HR13959Apparent energy L1..L3 (energy table)FLOAT32ABCDVAhRead
HR13971Real energy L1..L3 (energy table)FLOAT32ABCDWhRead
HR13983Reactive energy L1..L3 (energy table)FLOAT32ABCDvarhRead
HR13995Real energy L1..L3, consumed (all rates)FLOAT32ABCDWhRead
HR14007Real energy L1..L3, delivered (all rates)FLOAT32ABCDWhRead
HR14067Reactive energy L1..L3, inductive (energy table)FLOAT32ABCDvarhRead
HR14079Reactive energy L1..L3, capacitive (energy table)FLOAT32ABCDvarhRead
HR14107Pulse counter 1Raw count, not scaled (float).FLOAT32ABCDRead
HR14109Pulse counter 2Raw count, not scaled (float).FLOAT32ABCDRead
HR14111Runtime, real/apparent energy meteringFLOAT32ABCDsRead
HR14113Runtime, reactive energy meteringFLOAT32ABCDsRead
HR14115Star point voltageFLOAT32ABCDVRead
HR14117Digital output 1 statusINT16Read/write0 = Not active; 1 = Active
HR14118Digital output 2 statusINT16Read/write0 = Not active; 1 = Active
HR14119Digital input 1 statusINT16Read0 = Not active; 1 = Active
HR14120Digital input 2 statusINT16Read0 = Not active; 1 = Active
HR14326RS485 Modbus addressINT32ABCDRead/write
HR14338DHCP modeINT32ABCDRead/write0 = DHCP off; 1 = DHCP on
HR18864Power factor L1FLOAT32ABCDRead
HR18866Power factor L2FLOAT32ABCDRead
HR18868Power factor L3FLOAT32ABCDRead
HR19000Voltage L1-NFLOAT32ABCDVRead
HR19002Voltage L2-NFLOAT32ABCDVRead
HR19004Voltage L3-NFLOAT32ABCDVRead
HR19006Voltage L1-L2FLOAT32ABCDVRead
HR19008Voltage L2-L3FLOAT32ABCDVRead
HR19010Voltage L3-L1FLOAT32ABCDVRead
HR19012Current L1FLOAT32ABCDARead
HR19014Current L2FLOAT32ABCDARead
HR19016Current L3FLOAT32ABCDARead
HR19018Neutral current (vector sum)FLOAT32ABCDARead
HR19020Real power L1FLOAT32ABCDWRead
HR19022Real power L2FLOAT32ABCDWRead
HR19024Real power L3FLOAT32ABCDWRead
HR19026Real power totalFLOAT32ABCDWRead
HR19028Apparent power L1FLOAT32ABCDVARead
HR19030Apparent power L2FLOAT32ABCDVARead
HR19032Apparent power L3FLOAT32ABCDVARead
HR19034Apparent power totalFLOAT32ABCDVARead
HR19036Reactive power L1 (fundamental)FLOAT32ABCDvarRead
HR19038Reactive power L2 (fundamental)FLOAT32ABCDvarRead
HR19040Reactive power L3 (fundamental)FLOAT32ABCDvarRead
HR19042Reactive power total (fundamental)FLOAT32ABCDvarRead
HR19044CosPhi L1 (fundamental)FLOAT32ABCDRead
HR19046CosPhi L2 (fundamental)FLOAT32ABCDRead
HR19048CosPhi L3 (fundamental)FLOAT32ABCDRead
HR19050FrequencyFLOAT32ABCDHzRead
HR19052Rotation fieldPhase sequence as a float: 1 = right, 0 = none, -1 = left.FLOAT32ABCDRead
HR19054Real energy L1FLOAT32ABCDWhRead
HR19056Real energy L2FLOAT32ABCDWhRead
HR19058Real energy L3FLOAT32ABCDWhRead
HR19060Real energy L1..L3Three-phase total, not split into consumed/delivered.FLOAT32ABCDWhRead
HR19062Real energy L1, consumedFLOAT32ABCDWhRead
HR19064Real energy L2, consumedFLOAT32ABCDWhRead
HR19066Real energy L3, consumedFLOAT32ABCDWhRead
HR19068Real energy L1..L3, consumed, rate 1Rate (tariff) 1 only; use the energy-table total for all rates.FLOAT32ABCDWhRead
HR19070Real energy L1, deliveredFLOAT32ABCDWhRead
HR19072Real energy L2, deliveredFLOAT32ABCDWhRead
HR19074Real energy L3, deliveredFLOAT32ABCDWhRead
HR19076Real energy L1..L3, deliveredFLOAT32ABCDWhRead
HR19078Apparent energy L1FLOAT32ABCDVAhRead
HR19080Apparent energy L2FLOAT32ABCDVAhRead
HR19082Apparent energy L3FLOAT32ABCDVAhRead
HR19084Apparent energy L1..L3FLOAT32ABCDVAhRead
HR19086Reactive energy L1 (fundamental)FLOAT32ABCDvarhRead
HR19088Reactive energy L2 (fundamental)FLOAT32ABCDvarhRead
HR19090Reactive energy L3 (fundamental)FLOAT32ABCDvarhRead
HR19092Reactive energy L1..L3 (fundamental)FLOAT32ABCDvarhRead
HR19094Reactive energy inductive L1FLOAT32ABCDvarhRead
HR19096Reactive energy inductive L2FLOAT32ABCDvarhRead
HR19098Reactive energy inductive L3FLOAT32ABCDvarhRead
HR19100Reactive energy inductive L1..L3FLOAT32ABCDvarhRead
HR19102Reactive energy capacitive L1FLOAT32ABCDvarhRead
HR19104Reactive energy capacitive L2FLOAT32ABCDvarhRead
HR19106Reactive energy capacitive L3FLOAT32ABCDvarhRead
HR19108Reactive energy capacitive L1..L3FLOAT32ABCDvarhRead
HR19110THD voltage L1-NFLOAT32ABCD%Read
HR19112THD voltage L2-NFLOAT32ABCD%Read
HR19114THD voltage L3-NFLOAT32ABCD%Read
HR19116THD current L1FLOAT32ABCD%Read
HR19118THD current L2FLOAT32ABCD%Read
HR19120THD current L3FLOAT32ABCD%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Janitza UMG 509 power analyser (Modbus RTU)

What Modbus registers does the Janitza UMG 509 power analyser (Modbus RTU) have?

This map lists 84 registers: 84 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Janitza UMG 509 power analyser (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as protocol addresses and sent unchanged: 19000 is requested as 19000. The list starts at address 0 (real-time clock), which only fits 0-based numbering. In a 1-based or Modicon tool enter 19001 / 419001.

What byte order does the Janitza UMG 509 power analyser (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Janitza UMG 509 power analyser (Modbus RTU)?

Start with HR 19000 Voltage L1-N (Voltage L1-N); HR 19012 Current L1 (Current L1); HR 19026 Real power total (Total real power); HR 19034 Apparent power total (Total apparent power); HR 19050 Frequency (Frequency); HR 13995 Real energy L1..L3, consumed (all rates) (Real energy L1..L3, consumed (all rates)); HR 14007 Real energy L1..L3, delivered (all rates) (Real energy L1..L3, delivered (all rates)).

How do I enable Modbus control of the Janitza UMG 509 power analyser (Modbus RTU)?

Set the RS485 port to Modbus slave operation with the device address and baud rate in the device configuration; the address list does not give the menu path.

Where is the official Janitza UMG 509 power analyser (Modbus RTU) Modbus documentation?

The source is Power Analyser UMG 509 - Modbus-address and Formulary (1.059.004.2.d), published free by Janitza at https://www.janitza.com/files/download/manuals/current/UMG509/janitza-mal-umg509-en.pdf.

More Janitza Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Power Analyser UMG 509 - Modbus-address and Formulary · 1.059.004.2.d. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.