Power meter (multi-circuit power monitor) · Modbus register map

Omron KM-N2-FLK multi-circuit power monitor Modbus register map

Updated 17 November 2026

Short answer

The KM-N2-FLK is a compact power monitor that meters up to four 1-phase 2-wire circuits (or two 1P3W/3P3W circuits), each circuit answering on its own Modbus RTU address. Every value is a 32-bit integer in two holding registers, high word first, with fixed scaling (voltage x10, current x1000, power x10). The map covers the measured values, energy counters, key settings and the command register.

This page lists 62 Modbus registers for the Omron KM-N2-FLK multi-circuit power monitor — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Omron’s own free documentation (linked below) and checked against it.

Manufacturer
Omron
Model
KM-N2-FLK multi-circuit power monitor
Equipment type
Power meter (multi-circuit power monitor)
Registers
62 (10 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8E1
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
KM-N2-FLK, KM-N2
Source document
Power Monitor model KM-N2-FLK Users Manual · N200-E1-04 · rev. 2023-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Omron KM-N2-FLK multi-circuit power monitor

Integration in brief

Read holding registers from 0x0000 with FC03 (even counts): voltage, current, PF, frequency and power as high-word-first 32-bit integers, then energy from 0x0200. Address each circuit by its own slave address.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Voltage 1UINT32 ABCDVoltage 1 (x0.1 V)Read
HR 6Current 1UINT32 ABCDCurrent 1 (x0.001 A)Read
HR 16Active powerINT32 ABCDActive power (x0.1 W)Read
HR 12Power factorINT32 ABCDPower factorRead
HR 14FrequencyUINT32 ABCDFrequencyRead
HR 544Active energy import (not resettable)UINT32 ABCDActive energy import, kWhRead

Enable Modbus control & writes

Modbus is the default protocol (MENU 00 = MODBS). Set circuit A's communication address on the rotary switch; circuits B-D follow in order.

Byte order & addressing

Network setup

Watch out for

Omron KM-N2-FLK multi-circuit power monitor Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

62 of 62 shown
Omron KM-N2-FLK multi-circuit power monitor Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0000Voltage 1Phase voltage; meaning depends on phase/wire type.UINT32ABCD× 0.1VRead
HR2doc 0002Voltage 2UINT32ABCD× 0.1VRead
HR4doc 0004Voltage 3UINT32ABCD× 0.1VRead
HR6doc 0006Current 1UINT32ABCD× 0.001ARead
HR8doc 0008Current 2UINT32ABCD× 0.001ARead
HR10doc 000ACurrent 3UINT32ABCD× 0.001ARead
HR12doc 000CPower factorINT32ABCD× 0.01Read
HR14doc 000EFrequencyUINT32ABCD× 0.1HzRead
HR16doc 0010Active powerINT32ABCD× 0.1WRead
HR18doc 0012Reactive powerINT32ABCD× 0.1varRead
HR20doc 0014Voltage V1-V2UINT32ABCD× 0.1VRead
HR22doc 0016Voltage V1-V3UINT32ABCD× 0.1VRead
HR24doc 0018Voltage V2-V3UINT32ABCD× 0.1VRead
HR512doc 0200Active energy import (not resettable)UINT32ABCDWhRead
HR514doc 0202Active energy export (regenerative) (not resettable)UINT32ABCDWhRead
HR516doc 0204Reactive energy import (not resettable)UINT32ABCDvarhRead
HR518doc 0206Reactive energy export (not resettable)UINT32ABCDvarhRead
HR520doc 0208Total reactive energy (not resettable)UINT32ABCDvarhRead
HR522doc 020ATariff T1 active energy (not resettable)UINT32ABCDWhRead
HR524doc 020CTariff T2 active energy (not resettable)UINT32ABCDWhRead
HR526doc 020ETariff T3 active energy (not resettable)UINT32ABCDWhRead
HR528doc 0210Tariff T4 active energy (not resettable)UINT32ABCDWhRead
HR544doc 0220Active energy import (not resettable)UINT32ABCDkWhRead
HR546doc 0222Active energy export (regenerative) (not resettable)UINT32ABCDkWhRead
HR548doc 0224Reactive energy import (not resettable)UINT32ABCDkvarhRead
HR550doc 0226Reactive energy export (not resettable)UINT32ABCDkvarhRead
HR552doc 0228Total reactive energy (not resettable)UINT32ABCDkvarhRead
HR554doc 022ATariff T1 active energy (not resettable)UINT32ABCDkWhRead
HR556doc 022CTariff T2 active energy (not resettable)UINT32ABCDkWhRead
HR558doc 022ETariff T3 active energy (not resettable)UINT32ABCDkWhRead
HR560doc 0230Tariff T4 active energy (not resettable)UINT32ABCDkWhRead
HR576doc 0240Active energy import (resettable)UINT32ABCDWhRead
HR578doc 0242Active energy export (regenerative) (resettable)UINT32ABCDWhRead
HR580doc 0244Reactive energy import (resettable)UINT32ABCDvarhRead
HR582doc 0246Reactive energy export (resettable)UINT32ABCDvarhRead
HR584doc 0248Total reactive energy (resettable)UINT32ABCDvarhRead
HR586doc 024ATariff T1 active energy (resettable)UINT32ABCDWhRead
HR588doc 024CTariff T2 active energy (resettable)UINT32ABCDWhRead
HR590doc 024ETariff T3 active energy (resettable)UINT32ABCDWhRead
HR592doc 0250Tariff T4 active energy (resettable)UINT32ABCDWhRead
HR608doc 0260Active energy import (resettable)UINT32ABCDkWhRead
HR610doc 0262Active energy export (regenerative) (resettable)UINT32ABCDkWhRead
HR612doc 0264Reactive energy import (resettable)UINT32ABCDkvarhRead
HR614doc 0266Reactive energy export (resettable)UINT32ABCDkvarhRead
HR616doc 0268Total reactive energy (resettable)UINT32ABCDkvarhRead
HR618doc 026ATariff T1 active energy (resettable)UINT32ABCDkWhRead
HR620doc 026CTariff T2 active energy (resettable)UINT32ABCDkWhRead
HR622doc 026ETariff T3 active energy (resettable)UINT32ABCDkWhRead
HR624doc 0270Tariff T4 active energy (resettable)UINT32ABCDkWhRead
HR768doc 0300Converted value x1000Conversion value, raw is 1000x the value.UINT32ABCD× 0.001Read
HR770doc 0302Converted value x0.001Raw is 0.001x the value, for large totals.UINT32ABCD× 1000Read
HR8192doc 2000Phase and wire typeUINT32ABCDRead/write0 = 1P2W; 1 = 1P3W; 2 = 3P3W; 3 = 1P2W2; 4 = 1P3W2; 5 = 3P4W
HR8194doc 2002Communication address1-99 for Modbus; one per circuit.UINT32ABCDRead
HR8212doc 2014CT secondary currentUINT32ABCDRead/write0 = 1 A; 1 = 5 A
HR8214doc 2016CT primary currentPrimary amps, x1.UINT32ABCDRead/write
HR8704doc 2200ProtocolUINT32ABCDRead/write0 = CompoWay/F; 1 = Modbus
HR8706doc 2202Communication speedUINT32ABCDRead/write0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps
HR8710doc 2206Stop bitUINT32ABCDRead/write0 = 1 bit; 1 = 2 bits
HR8712doc 2208ParityUINT32ABCDRead/write0 = None; 1 = Odd; 2 = Even
HR8714doc 220ATransmission wait time0-99 ms.UINT32ABCDRead/write
HR8718doc 220EVT ratioStored x100.UINT32ABCD× 0.01Read/write
HR65535doc FFFFCommandWrite with FC06 only: command code in the high byte, 00 in the low byte.UINT16Write768 = 0x0300: reset resettable energy; 1024 = 0x0400: move to measuring mode; 1792 = 0x0700: move to setting mode; 2304 = 0x0900: initialise resettable energy and settings

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Omron KM-N2-FLK multi-circuit power monitor

What Modbus registers does the Omron KM-N2-FLK multi-circuit power monitor have?

This map lists 62 registers: 62 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Omron KM-N2-FLK multi-circuit power monitor Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The address map prints Modbus addresses in hex and they go on the wire unchanged; the manual's example reads voltage 1 with start address 0000 and 2 registers. Each value takes two registers, so read an even count.

What byte order does the Omron KM-N2-FLK multi-circuit power monitor use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Omron KM-N2-FLK multi-circuit power monitor?

Start with HR 0 Voltage 1 (Voltage 1 (x0.1 V)); HR 6 Current 1 (Current 1 (x0.001 A)); HR 16 Active power (Active power (x0.1 W)); HR 12 Power factor (Power factor); HR 14 Frequency (Frequency); HR 544 Active energy import (not resettable) (Active energy import, kWh).

How do I enable Modbus control of the Omron KM-N2-FLK multi-circuit power monitor?

Modbus is the default protocol (MENU 00 = MODBS). Set circuit A's communication address on the rotary switch; circuits B-D follow in order.

Where is the official Omron KM-N2-FLK multi-circuit power monitor Modbus documentation?

The source is Power Monitor model KM-N2-FLK Users Manual (N200-E1-04), revision 2023-05, published free by Omron at https://files.omron.eu/downloads/latest/manual/en/n200_km-n2_users_manual_en.pdf.

More Omron Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Power Monitor model KM-N2-FLK Users Manual · N200-E1-04 · rev. 2023-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.