Energy meter (multifunction) · Modbus register map
SATEC EM133-R residential multifunction meter Modbus register map
Updated 17 November 2026
The EM133 is a SATEC DIN-rail multifunction energy meter with RS-485 and optional Ethernet, WiFi, Profibus or CANopen modules. Its 32-bit register set carries 1-second phase and total values, demands and energy counters as integers, low word first. This map covers volts, amps, power, PF, frequency, unbalance, present demands, energy totals, digital I/O, basic wiring/CT/PT setup, resolution and energy decimal settings, COM1 settings, password and clear commands.
This page lists 104 Modbus registers for the SATEC EM133-R residential multifunction meter — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from SATEC’s own free documentation (linked below) and checked against it.
- Manufacturer
- SATEC
- Model
- EM133-R residential multifunction meter
- Equipment type
- Energy meter (multifunction)
- Registers
- 104 (13 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- EM133, EM133-R, EM133-XM, SATEC EM133
Integration notes: SATEC EM133-R residential multifunction meter
Read 13952 onward (phase values) and 14336 onward (totals) with function 03; decode 32-bit integers low word first. Check the resolution option (2390) and energy decimals (2391) before scaling.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 13952 | V1/V12 Voltage | UINT32 CDAB | V1/V12 voltage | Read |
| HR 13958 | I1 Current | UINT32 CDAB | I1 current | Read |
| HR 14336 | Total kW | INT32 CDAB | Total kW | Read |
| HR 14342 | Total PF | INT32 CDAB | Total PF | Read |
| HR 14468 | Frequency | UINT32 CDAB | Frequency | Read |
| HR 14720 | kWh import | UINT32 CDAB | kWh import | Read |
| HR 2390 | Device resolution | UINT16 | Resolution option (sets units) | Read/write |
Enable Modbus control & writes
COM1 is RS-485 Modbus RTU; set the address, baud and data format at 2346-2348 or from the front panel.
Byte order & addressing
- 32-bit values are low word first (CDAB).
- Unit of V/A/power registers depends on the resolution option.
Network setup
- Set wiring mode, PT ratio and CT primary at 2304-2306.
- Write the password to 2575 if protection is on.
Watch out for
- Switching to high resolution changes every V/A/kW reading by a factor of 10 to 1000.
SATEC EM133-R residential multifunction meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2304 | Wiring mode | UINT16 | Read/write | 0 = 3OP2 - 3-wire open delta, 2 CTs; 1 = 4LN3 - 4-wire wye, 3 PTs, L-N readings; 2 = 3DIR2 - 3-wire direct, 2 CTs; 3 = 4LL3 - 4-wire wye, 3 PTs, L-L readings; 4 = 3OP3 - 3-wire open delta, 3 CTs; 5 = 3LN3 - 4-wire wye, 2 PTs, L-N readings; 6 = 3LL3 - 4-wire wye, 2 PTs, L-L readings; 8 = 3BLN3 - 3-wire broken delta, 2 PTs, L-N readings; 9 = 3BLL3 - 3-wire broken delta, 2 PTs, L-L readings | ||||
| HR | 2305 | PT ratio | 10-65000 = 1.0-6500.0. | UINT16 | × 0.1 | Read/write | |||
| HR | 2306 | CT primary current | 1-50000 A. | UINT16 | A | Read/write | |||
| HR | 2315 | Nominal line frequency | 25, 50, 60 or 400. | UINT16 | Hz | Read/write | |||
| HR | 2346 | COM1 device address | Modbus 1-247. | UINT16 | Read/write | ||||
| HR | 2347 | COM1 baud rate | UINT16 | Read/write | 1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200 | ||||
| HR | 2348 | COM1 data format | UINT16 | Read/write | 0 = 7 bits, even parity; 1 = 8 bits, no parity; 2 = 8 bits, even parity | ||||
| HR | 2390 | Device resolution | Changes the units of voltage, current and power registers. | UINT16 | Read/write | 0 = Low resolution (default); 1 = High resolution | |||
| HR | 2391 | Energy decimal places | 0-4, default 4. | UINT16 | Read/write | ||||
| HR | 2560 | Warm restart | Write 0xFFFF to restart; reads 0. | UINT16 | Read/write | ||||
| HR | 2565 | Firmware version number | Two high decimal digits = major version, two low = minor. | UINT16 | Read | ||||
| HR | 2575 | Device authorization (password) | Write the 4-digit password before setup writes; reads 0 = allowed, -1 = needed. | INT16 | Read/write | ||||
| HR | 3404 | Clear total energy registers | Write 0. | UINT16 | Write | ||||
| HR | 3405 | Clear maximum demands | UINT16 | Write | 0 = Clear all maximum demands; 1 = Clear power demands; 2 = Clear volt and ampere demands | ||||
| HR | 11904doc 11904-11905 | Phase rotation order | UINT32 | CDAB | Read | 0 = Error; 1 = Positive (ABC); 2 = Negative (CBA) | |||
| HR | 12544doc 12544-12545 | Digital inputs (bitmap) | 0 = open, 1 = closed; bit 0 = DI1. | UINT32 | CDAB | Read | |||
| HR | 12800doc 12800-12801 | Relay outputs (bitmap) | 0 = open, 1 = closed; bit 0 = RO1. | UINT32 | CDAB | Read | |||
| HR | 13952doc 13952-13953 | V1/V12 Voltage | Low-resolution default; high resolution gives 0.1 V (PT=1). | UINT32 | CDAB | V | Read | ||
| HR | 13954doc 13954-13955 | V2/V23 Voltage | Low-resolution default; high resolution gives 0.1 V (PT=1). | UINT32 | CDAB | V | Read | ||
| HR | 13956doc 13956-13957 | V3/V31 Voltage | Low-resolution default; high resolution gives 0.1 V (PT=1). | UINT32 | CDAB | V | Read | ||
| HR | 13958doc 13958-13959 | I1 Current | Low-resolution default; high resolution gives 0.01 A. | UINT32 | CDAB | A | Read | ||
| HR | 13960doc 13960-13961 | I2 Current | Low-resolution default; high resolution gives 0.01 A. | UINT32 | CDAB | A | Read | ||
| HR | 13962doc 13962-13963 | I3 Current | Low-resolution default; high resolution gives 0.01 A. | UINT32 | CDAB | A | Read | ||
| HR | 13964doc 13964-13965 | kW L1 | Low-resolution default; high resolution gives 0.001 kW (PT=1). | INT32 | CDAB | kW | Read | ||
| HR | 13966doc 13966-13967 | kW L2 | Low-resolution default; high resolution gives 0.001 kW (PT=1). | INT32 | CDAB | kW | Read | ||
| HR | 13968doc 13968-13969 | kW L3 | Low-resolution default; high resolution gives 0.001 kW (PT=1). | INT32 | CDAB | kW | Read | ||
| HR | 13970doc 13970-13971 | kvar L1 | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | INT32 | CDAB | kvar | Read | ||
| HR | 13972doc 13972-13973 | kvar L2 | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | INT32 | CDAB | kvar | Read | ||
| HR | 13974doc 13974-13975 | kvar L3 | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | INT32 | CDAB | kvar | Read | ||
| HR | 13976doc 13976-13977 | kVA L1 | Low-resolution default; high resolution gives 0.001 kVA (PT=1). | UINT32 | CDAB | kVA | Read | ||
| HR | 13978doc 13978-13979 | kVA L2 | Low-resolution default; high resolution gives 0.001 kVA (PT=1). | UINT32 | CDAB | kVA | Read | ||
| HR | 13980doc 13980-13981 | kVA L3 | Low-resolution default; high resolution gives 0.001 kVA (PT=1). | UINT32 | CDAB | kVA | Read | ||
| HR | 13982doc 13982-13983 | Power factor L1 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13984doc 13984-13985 | Power factor L2 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13986doc 13986-13987 | Power factor L3 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13988doc 13988-13989 | V1/V12 Voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13990doc 13990-13991 | V2/V23 Voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13992doc 13992-13993 | V3/V31 Voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13994doc 13994-13995 | I1 Current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13996doc 13996-13997 | I2 Current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13998doc 13998-13999 | I3 Current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14000doc 14000-14001 | I1 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14002doc 14002-14003 | I2 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14004doc 14004-14005 | I3 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14006doc 14006-14007 | I1 Current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14008doc 14008-14009 | I2 Current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14010doc 14010-14011 | I3 Current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14012doc 14012-14013 | V12 Voltage | Low-resolution default; high resolution gives 0.1 V (PT=1). | UINT32 | CDAB | V | Read | ||
| HR | 14014doc 14014-14015 | V23 Voltage | Low-resolution default; high resolution gives 0.1 V (PT=1). | UINT32 | CDAB | V | Read | ||
| HR | 14016doc 14016-14017 | V31 Voltage | Low-resolution default; high resolution gives 0.1 V (PT=1). | UINT32 | CDAB | V | Read | ||
| HR | 14336doc 14336-14337 | Total kW | Low-resolution default; high resolution gives 0.001 kW (PT=1). | INT32 | CDAB | kW | Read | ||
| HR | 14338doc 14338-14339 | Total kvar | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | INT32 | CDAB | kvar | Read | ||
| HR | 14340doc 14340-14341 | Total kVA | Low-resolution default; high resolution gives 0.001 kVA (PT=1). | UINT32 | CDAB | kVA | Read | ||
| HR | 14342doc 14342-14343 | Total PF | INT32 | CDAB | × 0.001 | Read | |||
| HR | 14348doc 14348-14349 | Total kW import | Low-resolution default; high resolution gives 0.001 kW (PT=1). | UINT32 | CDAB | kW | Read | ||
| HR | 14350doc 14350-14351 | Total kW export | Low-resolution default; high resolution gives 0.001 kW (PT=1). | UINT32 | CDAB | kW | Read | ||
| HR | 14352doc 14352-14353 | Total kvar import | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | UINT32 | CDAB | kvar | Read | ||
| HR | 14354doc 14354-14355 | Total kvar export | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | UINT32 | CDAB | kvar | Read | ||
| HR | 14356doc 14356-14357 | 3-phase average L-N/L-L voltage | Low-resolution default; high resolution gives 0.1 V (PT=1). | UINT32 | CDAB | V | Read | ||
| HR | 14358doc 14358-14359 | 3-phase average L-L voltage | Low-resolution default; high resolution gives 0.1 V (PT=1). | UINT32 | CDAB | V | Read | ||
| HR | 14360doc 14360-14361 | 3-phase average current | Low-resolution default; high resolution gives 0.01 A. | UINT32 | CDAB | A | Read | ||
| HR | 14466doc 14466-14467 | In (neutral) Current | Low-resolution default; high resolution gives 0.01 A. | UINT32 | CDAB | A | Read | ||
| HR | 14468doc 14468-14469 | Frequency | UINT32 | CDAB | × 0.01 | Hz | Read | ||
| HR | 14592doc 14592-14593 | V1/V12 Volt demand | Low-resolution default; high resolution gives 0.1 V (PT=1). | UINT32 | CDAB | V | Read | ||
| HR | 14594doc 14594-14595 | V2/V23 Volt demand | Low-resolution default; high resolution gives 0.1 V (PT=1). | UINT32 | CDAB | V | Read | ||
| HR | 14596doc 14596-14597 | V3/V31 Volt demand | Low-resolution default; high resolution gives 0.1 V (PT=1). | UINT32 | CDAB | V | Read | ||
| HR | 14598doc 14598-14599 | I1 Ampere demand | Low-resolution default; high resolution gives 0.01 A. | UINT32 | CDAB | A | Read | ||
| HR | 14600doc 14600-14601 | I2 Ampere demand | Low-resolution default; high resolution gives 0.01 A. | UINT32 | CDAB | A | Read | ||
| HR | 14602doc 14602-14603 | I3 Ampere demand | Low-resolution default; high resolution gives 0.01 A. | UINT32 | CDAB | A | Read | ||
| HR | 14604doc 14604-14605 | kW import block demand | Low-resolution default; high resolution gives 0.001 kW (PT=1). | UINT32 | CDAB | kW | Read | ||
| HR | 14606doc 14606-14607 | kvar import block demand | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | UINT32 | CDAB | kvar | Read | ||
| HR | 14608doc 14608-14609 | kVA block demand | Low-resolution default; high resolution gives 0.001 kVA (PT=1). | UINT32 | CDAB | kVA | Read | ||
| HR | 14610doc 14610-14611 | kW import sliding window demand | Low-resolution default; high resolution gives 0.001 kW (PT=1). | UINT32 | CDAB | kW | Read | ||
| HR | 14612doc 14612-14613 | kvar import sliding window demand | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | UINT32 | CDAB | kvar | Read | ||
| HR | 14614doc 14614-14615 | kVA sliding window demand | Low-resolution default; high resolution gives 0.001 kVA (PT=1). | UINT32 | CDAB | kVA | Read | ||
| HR | 14622doc 14622-14623 | kW import accumulated demand | Low-resolution default; high resolution gives 0.001 kW (PT=1). | UINT32 | CDAB | kW | Read | ||
| HR | 14624doc 14624-14625 | kvar import accumulated demand | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | UINT32 | CDAB | kvar | Read | ||
| HR | 14626doc 14626-14627 | kVA accumulated demand | Low-resolution default; high resolution gives 0.001 kVA (PT=1). | UINT32 | CDAB | kVA | Read | ||
| HR | 14628doc 14628-14629 | kW import predicted sliding window demand | Low-resolution default; high resolution gives 0.001 kW (PT=1). | UINT32 | CDAB | kW | Read | ||
| HR | 14630doc 14630-14631 | kvar import predicted sliding window demand | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | UINT32 | CDAB | kvar | Read | ||
| HR | 14632doc 14632-14633 | kVA predicted sliding window demand | Low-resolution default; high resolution gives 0.001 kVA (PT=1). | UINT32 | CDAB | kVA | Read | ||
| HR | 14634doc 14634-14635 | PF (import) at Max. kVA sliding window demand | UINT32 | CDAB | × 0.001 | Read | |||
| HR | 14636doc 14636-14637 | kW export block demand | Low-resolution default; high resolution gives 0.001 kW (PT=1). | UINT32 | CDAB | kW | Read | ||
| HR | 14638doc 14638-14639 | kvar export block demand | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | UINT32 | CDAB | kvar | Read | ||
| HR | 14640doc 14640-14641 | kW export sliding window demand | Low-resolution default; high resolution gives 0.001 kW (PT=1). | UINT32 | CDAB | kW | Read | ||
| HR | 14642doc 14642-14643 | kvar export sliding window demand | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | UINT32 | CDAB | kvar | Read | ||
| HR | 14644doc 14644-14645 | kW export accumulated demand | Low-resolution default; high resolution gives 0.001 kW (PT=1). | UINT32 | CDAB | kW | Read | ||
| HR | 14646doc 14646-14647 | kvar export accumulated demand | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | UINT32 | CDAB | kvar | Read | ||
| HR | 14648doc 14648-14649 | kW export predicted sliding window demand | Low-resolution default; high resolution gives 0.001 kW (PT=1). | UINT32 | CDAB | kW | Read | ||
| HR | 14650doc 14650-14651 | kvar export predicted sliding window demand | Low-resolution default; high resolution gives 0.001 kvar (PT=1). | UINT32 | CDAB | kvar | Read | ||
| HR | 14660doc 14660-14661 | In Ampere demand | Low-resolution default; high resolution gives 0.01 A. | UINT32 | CDAB | A | Read | ||
| HR | 14720doc 14720-14721 | kWh import | At the default 4 energy decimal places (2391). | UINT32 | CDAB | × 0.0001 | kWh | Read | |
| HR | 14722doc 14722-14723 | kWh export | At the default 4 energy decimal places (2391). | UINT32 | CDAB | × 0.0001 | kWh | Read | |
| HR | 14728doc 14728-14729 | kvarh import | At the default 4 energy decimal places (2391). | UINT32 | CDAB | × 0.0001 | kvarh | Read | |
| HR | 14730doc 14730-14731 | kvarh export | At the default 4 energy decimal places (2391). | UINT32 | CDAB | × 0.0001 | kvarh | Read | |
| HR | 14736doc 14736-14737 | kVAh total | At the default 4 energy decimal places (2391). | UINT32 | CDAB | × 0.0001 | kVAh | Read | |
| HR | 14742doc 14742-14743 | kVAh import | At the default 4 energy decimal places (2391). | UINT32 | CDAB | × 0.0001 | kVAh | Read | |
| HR | 14744doc 14744-14745 | kVAh export | At the default 4 energy decimal places (2391). | UINT32 | CDAB | × 0.0001 | kVAh | Read | |
| HR | 14746doc 14746-14747 | kvarh Q1 | At the default 4 energy decimal places (2391). | UINT32 | CDAB | × 0.0001 | kvarh | Read | |
| HR | 14748doc 14748-14749 | kvarh Q2 | At the default 4 energy decimal places (2391). | UINT32 | CDAB | × 0.0001 | kvarh | Read | |
| HR | 14750doc 14750-14751 | kvarh Q3 | At the default 4 energy decimal places (2391). | UINT32 | CDAB | × 0.0001 | kvarh | Read | |
| HR | 14752doc 14752-14753 | kvarh Q4 | At the default 4 energy decimal places (2391). | UINT32 | CDAB | × 0.0001 | kvarh | Read | |
| HR | 46080doc 46080-46081 | Device serial number | UINT32 | CDAB | Read | ||||
| HR | 46082doc 46082-46083 | Device model ID | 13340 for EM133. | UINT32 | CDAB | Read |
Notes on this map
- Addressing: the guide says to add 40001 to a register address to get the Modicon holding-register number (400001 above 9999), so printed addresses are 0-based wire addresses.
- Word order: 32-bit values are sent with the low-order word in the first (even) register and the high-order word in the second, so they are CDAB here.
- Function 04 can be used the same way as function 03.
- Units depend on the device resolution option (2390). Scales here are for the default low resolution: U1 = 1 V, U2 = 1 A, U3 = 1 kW/kvar/kVA. With high resolution they become 0.1 V and 0.001 kW at PT ratio 1 (1 V and 1 kW above PT 1) and 0.01 A.
- Energy registers use U4, set by energy decimal places (2391, 0-4, default 4). The scale here (0.0001) is for the default.
- Phase rotation sits at 11904 on this model (not 11906 as on some other SATEC meters).
- Left out: 16-bit scaled registers, harmonics, min/max logs, billing/TOU, data logs, the total PF lag/lead rows (printed UINT16 in a two-register slot), and COM2/COM3 settings.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the SATEC EM133-R residential multifunction meter
What Modbus registers does the SATEC EM133-R residential multifunction meter have?
This map lists 104 registers: 104 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the SATEC EM133-R residential multifunction meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide says to add 40001 (or 400001 above 9999) to a register address for Modicon holding-register numbers, so printed addresses go straight into the frame: 13952 is requested as 13952 (Modicon 413953).
What byte order does the SATEC EM133-R residential multifunction meter use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the SATEC EM133-R residential multifunction meter?
Start with HR 13952 V1/V12 Voltage (V1/V12 voltage); HR 13958 I1 Current (I1 current); HR 14336 Total kW (Total kW); HR 14342 Total PF (Total PF); HR 14468 Frequency (Frequency); HR 14720 kWh import (kWh import); HR 2390 Device resolution (Resolution option (sets units)).
How do I enable Modbus control of the SATEC EM133-R residential multifunction meter?
COM1 is RS-485 Modbus RTU; set the address, baud and data format at 2346-2348 or from the front panel.
Where is the official SATEC EM133-R residential multifunction meter Modbus documentation?
The source is EM133-R Residential Multifunction Meter - Modbus Communications Protocol Reference Guide (BG0520 Rev. A6), revision 2018-10, published free by SATEC at https://www.satec-global.com/wp-content/uploads/2022/11/EM133-R-Modbus.pdf.
More SATEC Modbus register maps
- Power meter (multi-circuit branch feeder monitor)
SATEC BFM-II branch feeder monitor
SATEC BFM-II multi-circuit meter per Modbus reference guide BG0589 Rev. A12 (May 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM II, BFM2, SATEC BFM-II - Power meter (multi-circuit branch feeder monitor)
SATEC BFM136/036 branch feeder monitor
SATEC BFM136 and BFM036 multi-circuit meters per Modbus reference guide BG0395 Rev. A8 (July 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM136, BFM036, BFM 136, SATEC BFM136 - Power meter (revenue / power quality)
SATEC EM235 / PM335 PRO advanced power meter
SATEC EM235 and PM335 PRO advanced power meters, per Modbus reference guide BG0613 Rev. A8 (Sept 2025).
Also known as: EM235, PM335 PRO, PM335PRO, SATEC EM235, SATEC PM335 - Power meter (power quality analyzer)
SATEC PM174 powermeter and power quality analyzer
SATEC PM174 from firmware 24.3.1, per Modbus reference guide BG0414 Rev. A7 (April 2013).
Also known as: PM174, SATEC PM174, PM 174 - Power meter (power quality analyzer)
SATEC PM175 powermeter and power quality analyzer
SATEC PM175 from firmware 25.2.6, per Modbus reference guide BG0416 Rev. A7 (Nov 2009).
Also known as: PM175, SATEC PM175, PM 175 - Power meter (power quality analyzer)
SATEC PM180 expertmeter high performance analyzer
SATEC PM180 expertmeter, per Modbus reference guide BG0527 Rev. A11 (Sep 2024).
Also known as: PM180, expertmeter PM180, SATEC PM180
Other power & energy meters register maps
- Energy meter (wireless sensors through an Ethernet gateway)
Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)
PowerTag Energy 63, M250/M630, F160 and Rope sensors read through a PowerTag Link or PowerTag Link HD gateway, per DOCA0157EN-09 (10/2025).
Also known as: PowerTag Link, PowerTag Link HD, A9XMWD20, A9XMWD100, PowerTag Energy 63, A9MEM1520, A9MEM1540, A9MEM1560, A9MEM1570, PowerTag M250, PowerTag M630, LV434020, PowerTag F160, A9MEM1580, PowerTag Rope, A9MEM1590 - Circuit breaker trip unit (power meter)
Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
Siemens SENTRON 3WL air circuit breakers with a COM16 Modbus RTU communication module and, for voltage/power/energy values, the metering function (PLUS), per system manual A5E02126891-02.
Also known as: SENTRON WL, 3WL, 3WL COM16, COM16 - Power meter (panel meter)
Trumeter APM Power meter (APM-PWR) Modbus map
Trumeter APM-PWR panel power meters with Modbus, per the Trumeter knowledge-base register map.
Also known as: APM-PWR, APM Power, Trumeter APM Power meter - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Power meter (metered/switched rack PDU)
Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP)
Bachmann BlueNet BN PRO rack PDUs with Modbus TCP, protocol v1.00 REV00 register list.
Also known as: BlueNet BN PRO, BN PRO PDU, BlueNet 2 BN PRO - Energy meter
Carlo Gavazzi EM100 / ET100 series (EM111, EM112, ET112)
Single-phase EM111, EM112 energy meters and ET112 bidirectional meter with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 14.
Also known as: EM111, EM112, ET112, EM110, EM111-DIN, EM112-DIN, ET112-DIN, EM111DINAV81XS1X, EM112DINAV01XS1X, ET112DINAV01XS1X
All power & energy meters Modbus register maps →
Source: EM133-R Residential Multifunction Meter - Modbus Communications Protocol Reference Guide · BG0520 Rev. A6 · rev. 2018-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.