Energy meter (multifunction) · Modbus register map

SATEC EM133-R residential multifunction meter Modbus register map

Updated 17 November 2026

Short answer

The EM133 is a SATEC DIN-rail multifunction energy meter with RS-485 and optional Ethernet, WiFi, Profibus or CANopen modules. Its 32-bit register set carries 1-second phase and total values, demands and energy counters as integers, low word first. This map covers volts, amps, power, PF, frequency, unbalance, present demands, energy totals, digital I/O, basic wiring/CT/PT setup, resolution and energy decimal settings, COM1 settings, password and clear commands.

This page lists 104 Modbus registers for the SATEC EM133-R residential multifunction meter — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from SATEC’s own free documentation (linked below) and checked against it.

Manufacturer
SATEC
Model
EM133-R residential multifunction meter
Equipment type
Energy meter (multifunction)
Registers
104 (13 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
CDAB low word first (word-swapped)
Also known as
EM133, EM133-R, EM133-XM, SATEC EM133
Source document
EM133-R Residential Multifunction Meter - Modbus Communications Protocol Reference Guide · BG0520 Rev. A6 · rev. 2018-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: SATEC EM133-R residential multifunction meter

Integration in brief

Read 13952 onward (phase values) and 14336 onward (totals) with function 03; decode 32-bit integers low word first. Check the resolution option (2390) and energy decimals (2391) before scaling.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 13952V1/V12 VoltageUINT32 CDABV1/V12 voltageRead
HR 13958I1 CurrentUINT32 CDABI1 currentRead
HR 14336Total kWINT32 CDABTotal kWRead
HR 14342Total PFINT32 CDABTotal PFRead
HR 14468FrequencyUINT32 CDABFrequencyRead
HR 14720kWh importUINT32 CDABkWh importRead
HR 2390Device resolutionUINT16Resolution option (sets units)Read/write

Enable Modbus control & writes

COM1 is RS-485 Modbus RTU; set the address, baud and data format at 2346-2348 or from the front panel.

Byte order & addressing

Network setup

Watch out for

SATEC EM133-R residential multifunction meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

104 of 104 shown
SATEC EM133-R residential multifunction meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2304Wiring modeUINT16Read/write0 = 3OP2 - 3-wire open delta, 2 CTs; 1 = 4LN3 - 4-wire wye, 3 PTs, L-N readings; 2 = 3DIR2 - 3-wire direct, 2 CTs; 3 = 4LL3 - 4-wire wye, 3 PTs, L-L readings; 4 = 3OP3 - 3-wire open delta, 3 CTs; 5 = 3LN3 - 4-wire wye, 2 PTs, L-N readings; 6 = 3LL3 - 4-wire wye, 2 PTs, L-L readings; 8 = 3BLN3 - 3-wire broken delta, 2 PTs, L-N readings; 9 = 3BLL3 - 3-wire broken delta, 2 PTs, L-L readings
HR2305PT ratio10-65000 = 1.0-6500.0.UINT16× 0.1Read/write
HR2306CT primary current1-50000 A.UINT16ARead/write
HR2315Nominal line frequency25, 50, 60 or 400.UINT16HzRead/write
HR2346COM1 device addressModbus 1-247.UINT16Read/write
HR2347COM1 baud rateUINT16Read/write1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200
HR2348COM1 data formatUINT16Read/write0 = 7 bits, even parity; 1 = 8 bits, no parity; 2 = 8 bits, even parity
HR2390Device resolutionChanges the units of voltage, current and power registers.UINT16Read/write0 = Low resolution (default); 1 = High resolution
HR2391Energy decimal places0-4, default 4.UINT16Read/write
HR2560Warm restartWrite 0xFFFF to restart; reads 0.UINT16Read/write
HR2565Firmware version numberTwo high decimal digits = major version, two low = minor.UINT16Read
HR2575Device authorization (password)Write the 4-digit password before setup writes; reads 0 = allowed, -1 = needed.INT16Read/write
HR3404Clear total energy registersWrite 0.UINT16Write
HR3405Clear maximum demandsUINT16Write0 = Clear all maximum demands; 1 = Clear power demands; 2 = Clear volt and ampere demands
HR11904doc 11904-11905Phase rotation orderUINT32CDABRead0 = Error; 1 = Positive (ABC); 2 = Negative (CBA)
HR12544doc 12544-12545Digital inputs (bitmap)0 = open, 1 = closed; bit 0 = DI1.UINT32CDABRead
HR12800doc 12800-12801Relay outputs (bitmap)0 = open, 1 = closed; bit 0 = RO1.UINT32CDABRead
HR13952doc 13952-13953V1/V12 VoltageLow-resolution default; high resolution gives 0.1 V (PT=1).UINT32CDABVRead
HR13954doc 13954-13955V2/V23 VoltageLow-resolution default; high resolution gives 0.1 V (PT=1).UINT32CDABVRead
HR13956doc 13956-13957V3/V31 VoltageLow-resolution default; high resolution gives 0.1 V (PT=1).UINT32CDABVRead
HR13958doc 13958-13959I1 CurrentLow-resolution default; high resolution gives 0.01 A.UINT32CDABARead
HR13960doc 13960-13961I2 CurrentLow-resolution default; high resolution gives 0.01 A.UINT32CDABARead
HR13962doc 13962-13963I3 CurrentLow-resolution default; high resolution gives 0.01 A.UINT32CDABARead
HR13964doc 13964-13965kW L1Low-resolution default; high resolution gives 0.001 kW (PT=1).INT32CDABkWRead
HR13966doc 13966-13967kW L2Low-resolution default; high resolution gives 0.001 kW (PT=1).INT32CDABkWRead
HR13968doc 13968-13969kW L3Low-resolution default; high resolution gives 0.001 kW (PT=1).INT32CDABkWRead
HR13970doc 13970-13971kvar L1Low-resolution default; high resolution gives 0.001 kvar (PT=1).INT32CDABkvarRead
HR13972doc 13972-13973kvar L2Low-resolution default; high resolution gives 0.001 kvar (PT=1).INT32CDABkvarRead
HR13974doc 13974-13975kvar L3Low-resolution default; high resolution gives 0.001 kvar (PT=1).INT32CDABkvarRead
HR13976doc 13976-13977kVA L1Low-resolution default; high resolution gives 0.001 kVA (PT=1).UINT32CDABkVARead
HR13978doc 13978-13979kVA L2Low-resolution default; high resolution gives 0.001 kVA (PT=1).UINT32CDABkVARead
HR13980doc 13980-13981kVA L3Low-resolution default; high resolution gives 0.001 kVA (PT=1).UINT32CDABkVARead
HR13982doc 13982-13983Power factor L1INT32CDAB× 0.001Read
HR13984doc 13984-13985Power factor L2INT32CDAB× 0.001Read
HR13986doc 13986-13987Power factor L3INT32CDAB× 0.001Read
HR13988doc 13988-13989V1/V12 Voltage THDUINT32CDAB× 0.1%Read
HR13990doc 13990-13991V2/V23 Voltage THDUINT32CDAB× 0.1%Read
HR13992doc 13992-13993V3/V31 Voltage THDUINT32CDAB× 0.1%Read
HR13994doc 13994-13995I1 Current THDUINT32CDAB× 0.1%Read
HR13996doc 13996-13997I2 Current THDUINT32CDAB× 0.1%Read
HR13998doc 13998-13999I3 Current THDUINT32CDAB× 0.1%Read
HR14000doc 14000-14001I1 K-FactorUINT32CDAB× 0.1Read
HR14002doc 14002-14003I2 K-FactorUINT32CDAB× 0.1Read
HR14004doc 14004-14005I3 K-FactorUINT32CDAB× 0.1Read
HR14006doc 14006-14007I1 Current TDDUINT32CDAB× 0.1%Read
HR14008doc 14008-14009I2 Current TDDUINT32CDAB× 0.1%Read
HR14010doc 14010-14011I3 Current TDDUINT32CDAB× 0.1%Read
HR14012doc 14012-14013V12 VoltageLow-resolution default; high resolution gives 0.1 V (PT=1).UINT32CDABVRead
HR14014doc 14014-14015V23 VoltageLow-resolution default; high resolution gives 0.1 V (PT=1).UINT32CDABVRead
HR14016doc 14016-14017V31 VoltageLow-resolution default; high resolution gives 0.1 V (PT=1).UINT32CDABVRead
HR14336doc 14336-14337Total kWLow-resolution default; high resolution gives 0.001 kW (PT=1).INT32CDABkWRead
HR14338doc 14338-14339Total kvarLow-resolution default; high resolution gives 0.001 kvar (PT=1).INT32CDABkvarRead
HR14340doc 14340-14341Total kVALow-resolution default; high resolution gives 0.001 kVA (PT=1).UINT32CDABkVARead
HR14342doc 14342-14343Total PFINT32CDAB× 0.001Read
HR14348doc 14348-14349Total kW importLow-resolution default; high resolution gives 0.001 kW (PT=1).UINT32CDABkWRead
HR14350doc 14350-14351Total kW exportLow-resolution default; high resolution gives 0.001 kW (PT=1).UINT32CDABkWRead
HR14352doc 14352-14353Total kvar importLow-resolution default; high resolution gives 0.001 kvar (PT=1).UINT32CDABkvarRead
HR14354doc 14354-14355Total kvar exportLow-resolution default; high resolution gives 0.001 kvar (PT=1).UINT32CDABkvarRead
HR14356doc 14356-143573-phase average L-N/L-L voltageLow-resolution default; high resolution gives 0.1 V (PT=1).UINT32CDABVRead
HR14358doc 14358-143593-phase average L-L voltageLow-resolution default; high resolution gives 0.1 V (PT=1).UINT32CDABVRead
HR14360doc 14360-143613-phase average currentLow-resolution default; high resolution gives 0.01 A.UINT32CDABARead
HR14466doc 14466-14467In (neutral) CurrentLow-resolution default; high resolution gives 0.01 A.UINT32CDABARead
HR14468doc 14468-14469FrequencyUINT32CDAB× 0.01HzRead
HR14592doc 14592-14593V1/V12 Volt demandLow-resolution default; high resolution gives 0.1 V (PT=1).UINT32CDABVRead
HR14594doc 14594-14595V2/V23 Volt demandLow-resolution default; high resolution gives 0.1 V (PT=1).UINT32CDABVRead
HR14596doc 14596-14597V3/V31 Volt demandLow-resolution default; high resolution gives 0.1 V (PT=1).UINT32CDABVRead
HR14598doc 14598-14599I1 Ampere demandLow-resolution default; high resolution gives 0.01 A.UINT32CDABARead
HR14600doc 14600-14601I2 Ampere demandLow-resolution default; high resolution gives 0.01 A.UINT32CDABARead
HR14602doc 14602-14603I3 Ampere demandLow-resolution default; high resolution gives 0.01 A.UINT32CDABARead
HR14604doc 14604-14605kW import block demandLow-resolution default; high resolution gives 0.001 kW (PT=1).UINT32CDABkWRead
HR14606doc 14606-14607kvar import block demandLow-resolution default; high resolution gives 0.001 kvar (PT=1).UINT32CDABkvarRead
HR14608doc 14608-14609kVA block demandLow-resolution default; high resolution gives 0.001 kVA (PT=1).UINT32CDABkVARead
HR14610doc 14610-14611kW import sliding window demandLow-resolution default; high resolution gives 0.001 kW (PT=1).UINT32CDABkWRead
HR14612doc 14612-14613kvar import sliding window demandLow-resolution default; high resolution gives 0.001 kvar (PT=1).UINT32CDABkvarRead
HR14614doc 14614-14615kVA sliding window demandLow-resolution default; high resolution gives 0.001 kVA (PT=1).UINT32CDABkVARead
HR14622doc 14622-14623kW import accumulated demandLow-resolution default; high resolution gives 0.001 kW (PT=1).UINT32CDABkWRead
HR14624doc 14624-14625kvar import accumulated demandLow-resolution default; high resolution gives 0.001 kvar (PT=1).UINT32CDABkvarRead
HR14626doc 14626-14627kVA accumulated demandLow-resolution default; high resolution gives 0.001 kVA (PT=1).UINT32CDABkVARead
HR14628doc 14628-14629kW import predicted sliding window demandLow-resolution default; high resolution gives 0.001 kW (PT=1).UINT32CDABkWRead
HR14630doc 14630-14631kvar import predicted sliding window demandLow-resolution default; high resolution gives 0.001 kvar (PT=1).UINT32CDABkvarRead
HR14632doc 14632-14633kVA predicted sliding window demandLow-resolution default; high resolution gives 0.001 kVA (PT=1).UINT32CDABkVARead
HR14634doc 14634-14635PF (import) at Max. kVA sliding window demandUINT32CDAB× 0.001Read
HR14636doc 14636-14637kW export block demandLow-resolution default; high resolution gives 0.001 kW (PT=1).UINT32CDABkWRead
HR14638doc 14638-14639kvar export block demandLow-resolution default; high resolution gives 0.001 kvar (PT=1).UINT32CDABkvarRead
HR14640doc 14640-14641kW export sliding window demandLow-resolution default; high resolution gives 0.001 kW (PT=1).UINT32CDABkWRead
HR14642doc 14642-14643kvar export sliding window demandLow-resolution default; high resolution gives 0.001 kvar (PT=1).UINT32CDABkvarRead
HR14644doc 14644-14645kW export accumulated demandLow-resolution default; high resolution gives 0.001 kW (PT=1).UINT32CDABkWRead
HR14646doc 14646-14647kvar export accumulated demandLow-resolution default; high resolution gives 0.001 kvar (PT=1).UINT32CDABkvarRead
HR14648doc 14648-14649kW export predicted sliding window demandLow-resolution default; high resolution gives 0.001 kW (PT=1).UINT32CDABkWRead
HR14650doc 14650-14651kvar export predicted sliding window demandLow-resolution default; high resolution gives 0.001 kvar (PT=1).UINT32CDABkvarRead
HR14660doc 14660-14661In Ampere demandLow-resolution default; high resolution gives 0.01 A.UINT32CDABARead
HR14720doc 14720-14721kWh importAt the default 4 energy decimal places (2391).UINT32CDAB× 0.0001kWhRead
HR14722doc 14722-14723kWh exportAt the default 4 energy decimal places (2391).UINT32CDAB× 0.0001kWhRead
HR14728doc 14728-14729kvarh importAt the default 4 energy decimal places (2391).UINT32CDAB× 0.0001kvarhRead
HR14730doc 14730-14731kvarh exportAt the default 4 energy decimal places (2391).UINT32CDAB× 0.0001kvarhRead
HR14736doc 14736-14737kVAh totalAt the default 4 energy decimal places (2391).UINT32CDAB× 0.0001kVAhRead
HR14742doc 14742-14743kVAh importAt the default 4 energy decimal places (2391).UINT32CDAB× 0.0001kVAhRead
HR14744doc 14744-14745kVAh exportAt the default 4 energy decimal places (2391).UINT32CDAB× 0.0001kVAhRead
HR14746doc 14746-14747kvarh Q1At the default 4 energy decimal places (2391).UINT32CDAB× 0.0001kvarhRead
HR14748doc 14748-14749kvarh Q2At the default 4 energy decimal places (2391).UINT32CDAB× 0.0001kvarhRead
HR14750doc 14750-14751kvarh Q3At the default 4 energy decimal places (2391).UINT32CDAB× 0.0001kvarhRead
HR14752doc 14752-14753kvarh Q4At the default 4 energy decimal places (2391).UINT32CDAB× 0.0001kvarhRead
HR46080doc 46080-46081Device serial numberUINT32CDABRead
HR46082doc 46082-46083Device model ID13340 for EM133.UINT32CDABRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the SATEC EM133-R residential multifunction meter

What Modbus registers does the SATEC EM133-R residential multifunction meter have?

This map lists 104 registers: 104 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the SATEC EM133-R residential multifunction meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide says to add 40001 (or 400001 above 9999) to a register address for Modicon holding-register numbers, so printed addresses go straight into the frame: 13952 is requested as 13952 (Modicon 413953).

What byte order does the SATEC EM133-R residential multifunction meter use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the SATEC EM133-R residential multifunction meter?

Start with HR 13952 V1/V12 Voltage (V1/V12 voltage); HR 13958 I1 Current (I1 current); HR 14336 Total kW (Total kW); HR 14342 Total PF (Total PF); HR 14468 Frequency (Frequency); HR 14720 kWh import (kWh import); HR 2390 Device resolution (Resolution option (sets units)).

How do I enable Modbus control of the SATEC EM133-R residential multifunction meter?

COM1 is RS-485 Modbus RTU; set the address, baud and data format at 2346-2348 or from the front panel.

Where is the official SATEC EM133-R residential multifunction meter Modbus documentation?

The source is EM133-R Residential Multifunction Meter - Modbus Communications Protocol Reference Guide (BG0520 Rev. A6), revision 2018-10, published free by SATEC at https://www.satec-global.com/wp-content/uploads/2022/11/EM133-R-Modbus.pdf.

More SATEC Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: EM133-R Residential Multifunction Meter - Modbus Communications Protocol Reference Guide · BG0520 Rev. A6 · rev. 2018-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.