Power meter (revenue / power quality) · Modbus register map
SATEC EM235 / PM335 PRO advanced power meter Modbus register map
Updated 17 November 2026
The EM235 and PM335 PRO are SATEC revenue and power quality meters with RS-485, Ethernet and optional I/O. Their 32-bit register set carries 1-second phase and total values, demands and energy counters as integers, low word first. This map covers volts, amps, power, PF, THD, frequency, unbalance, present demands, energy totals, digital I/O, basic wiring/CT/PT setup, COM1 settings, password and clear commands.
This page lists 122 Modbus registers for the SATEC EM235 / PM335 PRO advanced power meter — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from SATEC’s own free documentation (linked below) and checked against it.
- Manufacturer
- SATEC
- Model
- EM235 / PM335 PRO advanced power meter
- Equipment type
- Power meter (revenue / power quality)
- Registers
- 122 (13 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- EM235, PM335 PRO, PM335PRO, SATEC EM235, SATEC PM335
Integration notes: SATEC EM235 / PM335 PRO advanced power meter
Read 13952 onward (phase values) and 14336 onward (totals) with function 03; decode 32-bit integers low word first. Energy totals start at 14720; check the energy decimal places setting (46258) before scaling.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 13952 | V1 voltage | UINT32 CDAB | V1 voltage | Read |
| HR 13958 | I1 current | UINT32 CDAB | I1 current | Read |
| HR 14336 | Total kW | INT32 CDAB | Total kW | Read |
| HR 14342 | Total PF | INT32 CDAB | Total PF | Read |
| HR 14468 | Frequency | UINT32 CDAB | Frequency | Read |
| HR 14720 | kWh import | UINT32 CDAB | kWh import | Read |
| HR 14722 | kWh export | UINT32 CDAB | kWh export | Read |
Enable Modbus control & writes
Set the port protocol, address and baud for COM1 at 46448-46452 (or from the front panel/PAS); Modbus/TCP runs on the Ethernet port.
Byte order & addressing
- 32-bit values are low word first (CDAB).
- Voltage and power units change from 0.1 V / 1 W to 1 V / 1 kW when a PT ratio above 1 is set.
- Energy resolution depends on 46258.
Network setup
- Set wiring mode, PT ratio and CT primary at 46208-46213 first.
- Write the 8-digit password to 44378 if protection is on.
Watch out for
- Changing the PT ratio from 1 changes the meaning of every voltage and power register.
SATEC EM235 / PM335 PRO advanced power meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 11906doc 11906-11907 | Phase rotation order | UINT32 | CDAB | Read | 0 = Error; 1 = Positive (ABC); 2 = Negative (CBA) | |||
| HR | 12544doc 12544-12545 | Digital inputs (bitmap) | Bit 0 = DI1, bit 1 = DI2, and so on. | UINT32 | CDAB | Read | |||
| HR | 12800doc 12800-12801 | Relay outputs (bitmap) | Bit 0 = RO1, bit 1 = RO2, and so on. | UINT32 | CDAB | Read | |||
| HR | 13952doc 13952-13953 | V1 voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13954doc 13954-13955 | V2 voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13956doc 13956-13957 | V3 voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13958doc 13958-13959 | I1 current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13960doc 13960-13961 | I2 current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13962doc 13962-13963 | I3 current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13964doc 13964-13965 | kW L1 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13966doc 13966-13967 | kW L2 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13968doc 13968-13969 | kW L3 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13970doc 13970-13971 | kvar L1 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13972doc 13972-13973 | kvar L2 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13974doc 13974-13975 | kvar L3 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13976doc 13976-13977 | kVA L1 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13978doc 13978-13979 | kVA L2 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13980doc 13980-13981 | kVA L3 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13982doc 13982-13983 | Power factor L1 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13984doc 13984-13985 | Power factor L2 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13986doc 13986-13987 | Power factor L3 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13988doc 13988-13989 | V1 voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13990doc 13990-13991 | V2 voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13992doc 13992-13993 | V3 voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13994doc 13994-13995 | I1 current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13996doc 13996-13997 | I2 current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13998doc 13998-13999 | I3 current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14000doc 14000-14001 | I1 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14002doc 14002-14003 | I2 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14004doc 14004-14005 | I3 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14006doc 14006-14007 | I1 current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14008doc 14008-14009 | I2 current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14010doc 14010-14011 | I3 current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14012doc 14012-14013 | V12 voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14014doc 14014-14015 | V23 voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14016doc 14016-14017 | V31 voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14336doc 14336-14337 | Total kW | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14338doc 14338-14339 | Total kvar | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14340doc 14340-14341 | Total kVA | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14342doc 14342-14343 | Total PF | INT32 | CDAB | × 0.001 | Read | |||
| HR | 14344doc 14344-14345 | Total PF lag | UINT32 | CDAB | × 0.001 | Read | |||
| HR | 14346doc 14346-14347 | Total PF lead | UINT32 | CDAB | × 0.001 | Read | |||
| HR | 14348doc 14348-14349 | Total kW import | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14350doc 14350-14351 | Total kW export | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14352doc 14352-14353 | Total kvar import | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14354doc 14354-14355 | Total kvar export | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14356doc 14356-14357 | 3-phase average L-N voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14358doc 14358-14359 | 3-phase average L-L voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14360doc 14360-14361 | 3-phase average current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14464doc 14464-14465 | I4 current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14466doc 14466-14467 | In current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14468doc 14468-14469 | Frequency | UINT32 | CDAB | × 0.01 | Hz | Read | ||
| HR | 14470doc 14470-14471 | Voltage unbalance | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14472doc 14472-14473 | Current unbalance | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14482doc 14482-14483 | Internal temperature | INT32 | CDAB | × 0.1 | ºC | Read | ||
| HR | 14484doc 14484-14485 | Frequency (3 decimals) | UINT32 | CDAB | × 0.001 | Hz | Read | ||
| HR | 14486doc 14486-14487 | Vbatt | UINT32 | CDAB | × 0.001 | V | Read | ||
| HR | 14488doc 14488-14489 | Internal temperature | INT32 | CDAB | × 0.1 | ºC | Read | ||
| HR | 14490doc 14490-14491 | Frequency (4 decimals) | UINT32 | CDAB | × 0.0001 | Hz | Read | ||
| HR | 14492doc 14492-14493 | I leakage current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14494doc 14494-14495 | V3xI4kW | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14592doc 14592-14593 | V1 volt demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14594doc 14594-14595 | V2 volt demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14596doc 14596-14597 | V3 volt demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14598doc 14598-14599 | I1 ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14600doc 14600-14601 | I2 ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14602doc 14602-14603 | I3 ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14604doc 14604-14605 | kW import block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14606doc 14606-14607 | kvar import block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14608doc 14608-14609 | kVA block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14610doc 14610-14611 | kW import sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14612doc 14612-14613 | kvar import sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14614doc 14614-14615 | kVA sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14622doc 14622-14623 | kW import accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14624doc 14624-14625 | kvar import accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14626doc 14626-14627 | kVA accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14628doc 14628-14629 | kW import predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14630doc 14630-14631 | kvar import predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14632doc 14632-14633 | kVA predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14634doc 14634-14635 | PF (import) at Max. kVA sliding window demand | UINT32 | CDAB | × 0.001 | Read | |||
| HR | 14636doc 14636-14637 | kW export block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14638doc 14638-14639 | kvar export block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14640doc 14640-14641 | kW export sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14642doc 14642-14643 | kvar export sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14644doc 14644-14645 | kW export accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14646doc 14646-14647 | kvar export accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14648doc 14648-14649 | kW export predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14650doc 14650-14651 | kvar export predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14658doc 14658-14659 | I4 ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14660doc 14660-14661 | In ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14720doc 14720-14721 | kWh import | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kWh | Read | ||
| HR | 14722doc 14722-14723 | kWh export | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kWh | Read | ||
| HR | 14724doc 14724-14725 | kWh net | Whole units at the default 0 energy decimal places (46258). | INT32 | CDAB | kWh | Read | ||
| HR | 14726doc 14726-14727 | kWh total | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kWh | Read | ||
| HR | 14728doc 14728-14729 | kvarh import | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 14730doc 14730-14731 | kvarh export | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 14732doc 14732-14733 | kvarh net | Whole units at the default 0 energy decimal places (46258). | INT32 | CDAB | kvarh | Read | ||
| HR | 14734doc 14734-14735 | kvarh total | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 14736doc 14736-14737 | kVAh total | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kVAh | Read | ||
| HR | 14738doc 14738-14739 | Vh total | UINT32 | CDAB | Vh | Read | |||
| HR | 14740doc 14740-14741 | Ah total | UINT32 | CDAB | Ah | Read | |||
| HR | 14742doc 14742-14743 | kVAh import | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kVAh | Read | ||
| HR | 14744doc 14744-14745 | kVAh export | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kVAh | Read | ||
| HR | 14756doc 14756-14757 | kvarh Q1 | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 14758doc 14758-14759 | kvarh Q2 | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 14760doc 14760-14761 | kvarh Q3 | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 14762doc 14762-14763 | kvarh Q4 | Whole units at the default 0 energy decimal places (46258). | UINT32 | CDAB | kvarh | Read | ||
| HR | 44102 | Clear energies | Write 0. | UINT16 | Write | ||||
| HR | 44107 | Clear min/max log | Write 0. | UINT16 | Write | ||||
| HR | 44378doc 44378-44379 | Device authorization (8-digit password) | Write the password before setup writes; reads 0 = allowed, -1 = needed. | INT32 | CDAB | Read/write | |||
| HR | 46080doc 46080-46081 | Device serial number | UINT32 | CDAB | Read | ||||
| HR | 46082doc 46082-46083 | Device model ID | 13250 or 13550 (EM235 / PM335 PRO). | UINT32 | CDAB | Read | |||
| HR | 46208 | Wiring mode | UINT16 | Read/write | 0 = 3OP2 - 3-wire open delta, 2 CTs; 1 = 4LN3 - 4-wire wye, 3 PTs, L-N readings; 2 = 3DIR2 - 3-wire direct, 2 CTs; 3 = 4LL3 - 4-wire wye, 3 PTs, L-L readings; 4 = 3OP3 - 3-wire open delta, 3 CTs; 5 = 3LN3 - 4-wire wye, 2 PTs, L-N readings; 6 = 3LL3 - 4-wire wye, 2 PTs, L-L readings; 8 = 3BLN3 - 3-wire broken delta, 2 PTs, L-N readings; 9 = 3BLL3 - 3-wire broken delta, 2 PTs, L-L readings | ||||
| HR | 46209 | PT ratio | 10-65000 = 1.0-6500.0. | UINT16 | × 0.1 | Read/write | |||
| HR | 46213 | CT primary current | 1-30000 A. | UINT16 | A | Read/write | |||
| HR | 46225 | Nominal line frequency | 50 or 60. | UINT16 | Hz | Read/write | |||
| HR | 46226 | Phase order | UINT16 | Read/write | 0 = ABC; 1 = CBA | ||||
| HR | 46258 | Number of energy decimal places | 0-3, default 0. Sets the resolution of the energy registers. | UINT16 | Read/write | ||||
| HR | 46448 | COM1 protocol | UINT16 | Read/write | 0 = Modbus RTU; 1 = Modbus ASCII; 2 = DNP3.0; 7 = IEC 60870-5 | ||||
| HR | 46450 | COM1 device address | Modbus 1-247. | UINT16 | Read/write | ||||
| HR | 46451 | COM1 baud rate | UINT16 | Read/write | 1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200 | ||||
| HR | 46452 | COM1 data format | UINT16 | Read/write | 0 = 7 bits, even parity; 1 = 8 bits, no parity; 2 = 8 bits, even parity |
Notes on this map
- Addressing: the guide says to add 40001 to a register address to get the Modicon holding-register number (400001 above 9999), so printed addresses are 0-based wire addresses.
- Word order: 32-bit values are sent with the low-order word in the first (even) register and the high-order word in the second, so they are CDAB here.
- Units U1 (voltage) and U3 (power) depend on the PT ratio: with PT ratio = 1 they are 0.1 V and 0.001 kW/kvar/kVA (the scales used here); with PT ratio > 1 they become 1 V and 1 kW/kvar/kVA. U2 (current) is always 0.01 A.
- Function 04 can be used the same way as function 03.
- Energy registers use unit U5, set by 'number of energy decimal places' (46258, 0-3, default 0). The scale here (1 kWh/kvarh/kVAh) is for the default; with 1, 2 or 3 decimals use 0.1, 0.01 or 0.001.
- Rows marked DC-applicable in the guide also read on DC models.
- Left out: 16-bit scaled registers, 1/2-cycle, 0.2-second and 3-second values, low/high phase values, harmonics and interharmonics, IEEE 519 statistics, min/max logs, billing/TOU, setpoints, files and COM2-COM5 settings.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the SATEC EM235 / PM335 PRO advanced power meter
What Modbus registers does the SATEC EM235 / PM335 PRO advanced power meter have?
This map lists 122 registers: 122 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the SATEC EM235 / PM335 PRO advanced power meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers from 0 and says to add 40001 (or 400001 above 9999) to get Modicon holding-register numbers, so the printed address is the wire address: 13952 is requested as 13952 (Modicon 413953).
What byte order does the SATEC EM235 / PM335 PRO advanced power meter use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the SATEC EM235 / PM335 PRO advanced power meter?
Start with HR 13952 V1 voltage (V1 voltage); HR 13958 I1 current (I1 current); HR 14336 Total kW (Total kW); HR 14342 Total PF (Total PF); HR 14468 Frequency (Frequency); HR 14720 kWh import (kWh import); HR 14722 kWh export (kWh export).
How do I enable Modbus control of the SATEC EM235 / PM335 PRO advanced power meter?
Set the port protocol, address and baud for COM1 at 46448-46452 (or from the front panel/PAS); Modbus/TCP runs on the Ethernet port.
Where is the official SATEC EM235 / PM335 PRO advanced power meter Modbus documentation?
The source is EM235/PM335 PRO Advanced Power Meter - Modbus Communications Protocol Reference Guide (BG0613 Rev. A8), revision 2025-09, published free by SATEC at https://www.satec-global.com/wp-content/uploads/2025/09/EM235-PM335-PRO-Modbus-Guide.pdf.
More SATEC Modbus register maps
- Power meter (multi-circuit branch feeder monitor)
SATEC BFM-II branch feeder monitor
SATEC BFM-II multi-circuit meter per Modbus reference guide BG0589 Rev. A12 (May 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM II, BFM2, SATEC BFM-II - Power meter (multi-circuit branch feeder monitor)
SATEC BFM136/036 branch feeder monitor
SATEC BFM136 and BFM036 multi-circuit meters per Modbus reference guide BG0395 Rev. A8 (July 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM136, BFM036, BFM 136, SATEC BFM136 - Energy meter (multifunction)
SATEC EM133-R residential multifunction meter
SATEC EM133-R (and EM133-XM) multifunction meters, per Modbus reference guide BG0520 Rev. A6 (Oct 2018).
Also known as: EM133, EM133-R, EM133-XM, SATEC EM133 - Power meter (power quality analyzer)
SATEC PM174 powermeter and power quality analyzer
SATEC PM174 from firmware 24.3.1, per Modbus reference guide BG0414 Rev. A7 (April 2013).
Also known as: PM174, SATEC PM174, PM 174 - Power meter (power quality analyzer)
SATEC PM175 powermeter and power quality analyzer
SATEC PM175 from firmware 25.2.6, per Modbus reference guide BG0416 Rev. A7 (Nov 2009).
Also known as: PM175, SATEC PM175, PM 175 - Power meter (power quality analyzer)
SATEC PM180 expertmeter high performance analyzer
SATEC PM180 expertmeter, per Modbus reference guide BG0527 Rev. A11 (Sep 2024).
Also known as: PM180, expertmeter PM180, SATEC PM180
Other power & energy meters register maps
- Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203 - Power meter
Siemens SICAM P power meter (Modbus RTU/ASCII)
SICAM P (7KG7xxx) power meters with the Modbus serial interface, per manual E50417-B1076-C241-A5 (release 11.2012).
Also known as: 7KG7750, 7KG7751, 7KG7755, SICAM P50, SICAM P55, 7KG7610, 7KG7660 - Power meter
Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU)
Enercept H8035 (energy only) and H8036 (enhanced data stream) split-core three-phase power transducers, 100-2400 A, installation guide Z201686-0K.
Also known as: Enercept H8035, Enercept H8036, H8035-0100-2, H8035-0300-2, H8035-0400-3, H8035-0800-3, H8035-0800-4, H8035-1600-4, H8035-2400-4, H8036-0100-2, H8036-0300-2, H8036-0400-3, H8036-0800-3, H8036-0800-4, H8036-1600-4, H8036-2400-4 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Actuator / valve (pressure-independent control valve with energy metering)
Belimo Energy Valve DN 15-50 (Version 4) Modbus RTU / TCP
Belimo Energy Valve Version 4, DN 15-50 (EV..R2+(K)BAC, EV..R2+MID, EV..R3+BAC), per Energy Valve Modbus interface description en-gb 2023-08.
Also known as: EV..R2+BAC, EV..R2+KBAC, EV..R2+MID, EV..R3+BAC, Energy Valve 4 - Energy meter (energy analyzer)
Carlo Gavazzi EM210 (AV versions)
EM210 three-phase energy analyzers, AV input versions with the RS485 Modbus RTU option, protocol version 4 revision 3 (newest variables need firmware A.5/A.6).
Also known as: EM210, EM210-72D, EM210 AV
All power & energy meters Modbus register maps →
Source: EM235/PM335 PRO Advanced Power Meter - Modbus Communications Protocol Reference Guide · BG0613 Rev. A8 · rev. 2025-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.