Power meter · Modbus register map
Siemens SICAM P power meter (Modbus RTU/ASCII) Modbus register map
Updated 17 November 2026
SICAM P is a panel power meter and power-quality monitor with an RS-485 Modbus slave (RTU or ASCII) on a 9-pin D-sub socket. Every measured value occupies two holding registers and is sent as an IEEE float by default. This map covers device identity, the format switch, time sync, binary I/O and command bits, all measured values, the 5th-19th and 2nd/3rd/21st harmonics, energy values, alarm counters and analog I/O.
This page lists 164 Modbus registers for the Siemens SICAM P power meter (Modbus RTU/ASCII) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.
- Manufacturer
- Siemens
- Model
- SICAM P power meter (Modbus RTU/ASCII)
- Equipment type
- Power meter
- Registers
- 164 (10 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- 7KG7750, 7KG7751, 7KG7755, SICAM P50, SICAM P55, 7KG7610, 7KG7660
Integration notes: Siemens SICAM P power meter (Modbus RTU/ASCII)
Set the Modbus address, baud and parity on the device, then read holding registers (FC 03) from 40201 (wire 200) in float format. Values come as big-endian floats, two registers each; keep 40050 at 0 unless you want scaled integers.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 200 | Voltage UL1-N | FLOAT32 ABCD | Voltage L1-N | Read |
| HR 208 | Current IL1 | FLOAT32 ABCD | Current L1 | Read |
| HR 232 | Active power P total | FLOAT32 ABCD | Total active power | Read |
| HR 264 | Power factor total | FLOAT32 ABCD | Total power factor | Read |
| HR 274 | Frequency | FLOAT32 ABCD | Frequency | Read |
| HR 822 | Active energy total | FLOAT32 ABCD | Total active energy | Read |
| HR 49 | Measured value format | UINT16 | Measured value format (float/integer) | Read/write |
Enable Modbus control & writes
The Modbus serial interface is a hardware variant of the meter. Slave address (1-247), baud, parity and RTU/ASCII mode are set in the device parameters (on the device or with SICAM P PAR).
Byte order & addressing
- Modicon numbering: subtract 40001 for the wire address.
- Floats are high word first (ABCD).
- Register 40050 switches all measured values between float and 16-bit integer; the setting survives power-off.
- Max 125 registers per read in RTU (60 in ASCII).
Network setup
- Slave address 1-247; 300-115200 baud; parity even/odd/none in RTU (even/odd only in ASCII per the technical data); always 1 stop bit.
- RS-485 on a 9-pin D-sub: pin 3 = A, pin 8 = B, pin 5 = GND, pin 6 = +5 V for termination.
- Up to 32 devices per segment without repeaters.
Watch out for
- Writing a read-only register returns exception 03, not 02.
- Switch binary outputs by read-modify-write of 40129; only outputs with no assigned function can be controlled.
- Time sync (40065-40068) must be written with FC 16 as a broadcast.
Siemens SICAM P power meter (Modbus RTU/ASCII) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | MLFB (order number) | Order number as ASCII text, up to 32 characters. | STRING[32] | Read | ||||
| HR | 39doc 40040 | Firmware version, part 1 | First field of the firmware version (e.g. 1 of V1.1.2). | UINT16 | Read | ||||
| HR | 40doc 40041 | Firmware version, part 2 | UINT16 | Read | |||||
| HR | 41doc 40042 | Firmware version, part 3 | UINT16 | Read | |||||
| HR | 44doc 40045 | Date of calibration | ASCII DDMMYYYY, e.g. 07032001 = 2001-03-07. | STRING[8] | Read | ||||
| HR | 49doc 40050 | Measured value format | Selects float or 16-bit integer transfer for measured values; kept after power-off. | UINT16 | Read/write | 0 = Float; 1 = Integer | |||
| HR | 64doc 40065 | Time sync: milliseconds | 0-59999. Write 40065-40068 together with FC16 (broadcast) to set the clock. | UINT16 | ms | Write | |||
| HR | 65doc 40066 | Time sync: hours / minutes | High byte hours 0-23, low byte minutes 0-59. | UINT16 | Write | ||||
| HR | 66doc 40067 | Time sync: month / day | High byte month 1-12, low byte day 1-31. | UINT16 | Write | ||||
| HR | 67doc 40068 | Time sync: year | Low byte year counted from 1900 (0 = 1900); high byte unused. | UINT16 | Write | ||||
| HR | 128doc 40129 | Binary outputs and device status | Read-modify-write to switch outputs that have no assigned function. | BITMAP16 | Read/write | bit 0 = BO1 (terminal G3); bit 1 = BO2 (terminal G2); bit 2 = BO3-BO6 depend on fitted RO/BO modules (bits 2-5); bit 15 = Battery failure (1 = failure) | |||
| HR | 129doc 40130 | Binary input status | Inputs on BI modules in slots A-D. | BITMAP16 | Read | bit 0 = BI_A12; bit 1 = BI_A34; bit 2 = BI_B12; bit 3 = BI_B34; bit 4 = BI_C12; bit 5 = BI_C34; bit 6 = BI_D12; bit 7 = BI_D34 | |||
| HR | 132doc 40133 | Commands | Set a bit to 1 to run the reset. | BITMAP16 | Write | bit 0 = Reset min/max values; bit 1 = Reset energy values; bit 2 = Reset alarm counter | |||
| HR | 199doc 40200 | Measuring overflow status | Set when an input exceeds 120 % of nominal. From device version V4.10. | BITMAP16 | Read | bit 0 = Overflow voltage L1-N; bit 1 = Overflow voltage L2-N; bit 2 = Overflow voltage L3-N; bit 3 = Overflow current L1; bit 4 = Overflow current L2; bit 5 = Overflow current L3 | |||
| HR | 200doc 40201 | Voltage UL1-N | FLOAT32 | ABCD | V | Read | |||
| HR | 202doc 40203 | Voltage UL2-N | FLOAT32 | ABCD | V | Read | |||
| HR | 204doc 40205 | Voltage UL3-N | FLOAT32 | ABCD | V | Read | |||
| HR | 206doc 40207 | Voltage UNE | Sum of the phase-to-neutral voltages (calculated). | FLOAT32 | ABCD | V | Read | ||
| HR | 208doc 40209 | Current IL1 | FLOAT32 | ABCD | A | Read | |||
| HR | 210doc 40211 | Current IL2 | FLOAT32 | ABCD | A | Read | |||
| HR | 212doc 40213 | Current IL3 | FLOAT32 | ABCD | A | Read | |||
| HR | 214doc 40215 | Current INE | Neutral current. | FLOAT32 | ABCD | A | Read | ||
| HR | 216doc 40217 | Voltage UL12 | FLOAT32 | ABCD | V | Read | |||
| HR | 218doc 40219 | Voltage UL23 | FLOAT32 | ABCD | V | Read | |||
| HR | 220doc 40221 | Voltage UL31 | FLOAT32 | ABCD | V | Read | |||
| HR | 222doc 40223 | Voltage sum | FLOAT32 | ABCD | V | Read | |||
| HR | 224doc 40225 | Current sum | FLOAT32 | ABCD | A | Read | |||
| HR | 226doc 40227 | Active power PL1 | FLOAT32 | ABCD | W | Read | |||
| HR | 228doc 40229 | Active power PL2 | FLOAT32 | ABCD | W | Read | |||
| HR | 230doc 40231 | Active power PL3 | FLOAT32 | ABCD | W | Read | |||
| HR | 232doc 40233 | Active power P total | FLOAT32 | ABCD | W | Read | |||
| HR | 234doc 40235 | Reactive power QL1 | FLOAT32 | ABCD | var | Read | |||
| HR | 236doc 40237 | Reactive power QL2 | FLOAT32 | ABCD | var | Read | |||
| HR | 238doc 40239 | Reactive power QL3 | FLOAT32 | ABCD | var | Read | |||
| HR | 240doc 40241 | Reactive power Q total | FLOAT32 | ABCD | var | Read | |||
| HR | 242doc 40243 | Apparent power SL1 | FLOAT32 | ABCD | VA | Read | |||
| HR | 244doc 40245 | Apparent power SL2 | FLOAT32 | ABCD | VA | Read | |||
| HR | 246doc 40247 | Apparent power SL3 | FLOAT32 | ABCD | VA | Read | |||
| HR | 248doc 40249 | Apparent power S total | FLOAT32 | ABCD | VA | Read | |||
| HR | 250doc 40251 | Cos phi L1 | FLOAT32 | ABCD | Read | ||||
| HR | 252doc 40253 | Cos phi L2 | FLOAT32 | ABCD | Read | ||||
| HR | 254doc 40255 | Cos phi L3 | FLOAT32 | ABCD | Read | ||||
| HR | 256doc 40257 | Cos phi total | FLOAT32 | ABCD | Read | ||||
| HR | 258doc 40259 | Power factor L1 | FLOAT32 | ABCD | Read | ||||
| HR | 260doc 40261 | Power factor L2 | FLOAT32 | ABCD | Read | ||||
| HR | 262doc 40263 | Power factor L3 | FLOAT32 | ABCD | Read | ||||
| HR | 264doc 40265 | Power factor total | FLOAT32 | ABCD | Read | ||||
| HR | 266doc 40267 | Phase angle L1 | FLOAT32 | ABCD | ° | Read | |||
| HR | 268doc 40269 | Phase angle L2 | FLOAT32 | ABCD | ° | Read | |||
| HR | 270doc 40271 | Phase angle L3 | FLOAT32 | ABCD | ° | Read | |||
| HR | 272doc 40273 | Phase angle sum | FLOAT32 | ABCD | ° | Read | |||
| HR | 274doc 40275 | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 276doc 40277 | Voltage unbalance | FLOAT32 | ABCD | % | Read | |||
| HR | 278doc 40279 | Current unbalance | FLOAT32 | ABCD | % | Read | |||
| HR | 280doc 40281 | THD voltage L1 | FLOAT32 | ABCD | % | Read | |||
| HR | 282doc 40283 | THD voltage L2 | FLOAT32 | ABCD | % | Read | |||
| HR | 284doc 40285 | THD voltage L3 | FLOAT32 | ABCD | % | Read | |||
| HR | 286doc 40287 | THD current L1 | FLOAT32 | ABCD | % | Read | |||
| HR | 288doc 40289 | THD current L2 | FLOAT32 | ABCD | % | Read | |||
| HR | 290doc 40291 | THD current L3 | FLOAT32 | ABCD | % | Read | |||
| HR | 292doc 40293 | Harmonic voltage L1, 5th | FLOAT32 | ABCD | % | Read | |||
| HR | 294doc 40295 | Harmonic voltage L2, 5th | FLOAT32 | ABCD | % | Read | |||
| HR | 296doc 40297 | Harmonic voltage L3, 5th | FLOAT32 | ABCD | % | Read | |||
| HR | 298doc 40299 | Harmonic voltage L1, 7th | FLOAT32 | ABCD | % | Read | |||
| HR | 300doc 40301 | Harmonic voltage L2, 7th | FLOAT32 | ABCD | % | Read | |||
| HR | 302doc 40303 | Harmonic voltage L3, 7th | FLOAT32 | ABCD | % | Read | |||
| HR | 304doc 40305 | Harmonic voltage L1, 11th | FLOAT32 | ABCD | % | Read | |||
| HR | 306doc 40307 | Harmonic voltage L2, 11th | FLOAT32 | ABCD | % | Read | |||
| HR | 308doc 40309 | Harmonic voltage L3, 11th | FLOAT32 | ABCD | % | Read | |||
| HR | 310doc 40311 | Harmonic voltage L1, 13th | FLOAT32 | ABCD | % | Read | |||
| HR | 312doc 40313 | Harmonic voltage L2, 13th | FLOAT32 | ABCD | % | Read | |||
| HR | 314doc 40315 | Harmonic voltage L3, 13th | FLOAT32 | ABCD | % | Read | |||
| HR | 316doc 40317 | Harmonic voltage L1, 17th | FLOAT32 | ABCD | % | Read | |||
| HR | 318doc 40319 | Harmonic voltage L2, 17th | FLOAT32 | ABCD | % | Read | |||
| HR | 320doc 40321 | Harmonic voltage L3, 17th | FLOAT32 | ABCD | % | Read | |||
| HR | 322doc 40323 | Harmonic voltage L1, 19th | FLOAT32 | ABCD | % | Read | |||
| HR | 324doc 40325 | Harmonic voltage L2, 19th | FLOAT32 | ABCD | % | Read | |||
| HR | 326doc 40327 | Harmonic voltage L3, 19th | FLOAT32 | ABCD | % | Read | |||
| HR | 328doc 40329 | Harmonic current L1, 5th | FLOAT32 | ABCD | A | Read | |||
| HR | 330doc 40331 | Harmonic current L2, 5th | FLOAT32 | ABCD | A | Read | |||
| HR | 332doc 40333 | Harmonic current L3, 5th | FLOAT32 | ABCD | A | Read | |||
| HR | 334doc 40335 | Harmonic current L1, 7th | FLOAT32 | ABCD | A | Read | |||
| HR | 336doc 40337 | Harmonic current L2, 7th | FLOAT32 | ABCD | A | Read | |||
| HR | 338doc 40339 | Harmonic current L3, 7th | FLOAT32 | ABCD | A | Read | |||
| HR | 340doc 40341 | Harmonic current L1, 11th | FLOAT32 | ABCD | A | Read | |||
| HR | 342doc 40343 | Harmonic current L2, 11th | FLOAT32 | ABCD | A | Read | |||
| HR | 344doc 40345 | Harmonic current L3, 11th | FLOAT32 | ABCD | A | Read | |||
| HR | 346doc 40347 | Harmonic current L1, 13th | FLOAT32 | ABCD | A | Read | |||
| HR | 348doc 40349 | Harmonic current L2, 13th | FLOAT32 | ABCD | A | Read | |||
| HR | 350doc 40351 | Harmonic current L3, 13th | FLOAT32 | ABCD | A | Read | |||
| HR | 352doc 40353 | Harmonic current L1, 17th | FLOAT32 | ABCD | A | Read | |||
| HR | 354doc 40355 | Harmonic current L2, 17th | FLOAT32 | ABCD | A | Read | |||
| HR | 356doc 40357 | Harmonic current L3, 17th | FLOAT32 | ABCD | A | Read | |||
| HR | 358doc 40359 | Harmonic current L1, 19th | FLOAT32 | ABCD | A | Read | |||
| HR | 360doc 40361 | Harmonic current L2, 19th | FLOAT32 | ABCD | A | Read | |||
| HR | 362doc 40363 | Harmonic current L3, 19th | FLOAT32 | ABCD | A | Read | |||
| HR | 499doc 40500 | Harmonic voltage L1, 2nd | FLOAT32 | ABCD | % | Read | |||
| HR | 501doc 40502 | Harmonic voltage L2, 2nd | FLOAT32 | ABCD | % | Read | |||
| HR | 503doc 40504 | Harmonic voltage L3, 2nd | FLOAT32 | ABCD | % | Read | |||
| HR | 505doc 40506 | Harmonic voltage L1, 3rd | FLOAT32 | ABCD | % | Read | |||
| HR | 507doc 40508 | Harmonic voltage L2, 3rd | FLOAT32 | ABCD | % | Read | |||
| HR | 509doc 40510 | Harmonic voltage L3, 3rd | FLOAT32 | ABCD | % | Read | |||
| HR | 613doc 40614 | Harmonic voltage L1, 21st | FLOAT32 | ABCD | % | Read | |||
| HR | 615doc 40616 | Harmonic voltage L2, 21st | FLOAT32 | ABCD | % | Read | |||
| HR | 617doc 40618 | Harmonic voltage L3, 21st | FLOAT32 | ABCD | % | Read | |||
| HR | 619doc 40620 | Harmonic current L1, 2nd | FLOAT32 | ABCD | % | Read | |||
| HR | 621doc 40622 | Harmonic current L2, 2nd | FLOAT32 | ABCD | % | Read | |||
| HR | 623doc 40624 | Harmonic current L3, 2nd | FLOAT32 | ABCD | % | Read | |||
| HR | 625doc 40626 | Harmonic current L1, 3rd | FLOAT32 | ABCD | % | Read | |||
| HR | 627doc 40628 | Harmonic current L2, 3rd | FLOAT32 | ABCD | % | Read | |||
| HR | 629doc 40630 | Harmonic current L3, 3rd | FLOAT32 | ABCD | % | Read | |||
| HR | 733doc 40734 | Harmonic current L1, 21st | FLOAT32 | ABCD | % | Read | |||
| HR | 735doc 40736 | Harmonic current L2, 21st | FLOAT32 | ABCD | % | Read | |||
| HR | 737doc 40738 | Harmonic current L3, 21st | FLOAT32 | ABCD | % | Read | |||
| HR | 800doc 40801 | Active energy L1 demand | FLOAT32 | ABCD | Wh | Read | |||
| HR | 802doc 40803 | Active energy L2 demand | FLOAT32 | ABCD | Wh | Read | |||
| HR | 804doc 40805 | Active energy L3 demand | FLOAT32 | ABCD | Wh | Read | |||
| HR | 806doc 40807 | Active energy demand | FLOAT32 | ABCD | Wh | Read | |||
| HR | 808doc 40809 | Active energy L1 supply | FLOAT32 | ABCD | Wh | Read | |||
| HR | 810doc 40811 | Active energy L2 supply | FLOAT32 | ABCD | Wh | Read | |||
| HR | 812doc 40813 | Active energy L3 supply | FLOAT32 | ABCD | Wh | Read | |||
| HR | 814doc 40815 | Active energy supply | FLOAT32 | ABCD | Wh | Read | |||
| HR | 816doc 40817 | Active energy L1 total | FLOAT32 | ABCD | Wh | Read | |||
| HR | 818doc 40819 | Active energy L2 total | FLOAT32 | ABCD | Wh | Read | |||
| HR | 820doc 40821 | Active energy L3 total | FLOAT32 | ABCD | Wh | Read | |||
| HR | 822doc 40823 | Active energy total | FLOAT32 | ABCD | Wh | Read | |||
| HR | 824doc 40825 | Reactive energy L1 total | FLOAT32 | ABCD | varh | Read | |||
| HR | 826doc 40827 | Reactive energy L2 total | FLOAT32 | ABCD | varh | Read | |||
| HR | 828doc 40829 | Reactive energy L3 total | FLOAT32 | ABCD | varh | Read | |||
| HR | 830doc 40831 | Reactive energy total | FLOAT32 | ABCD | varh | Read | |||
| HR | 832doc 40833 | Reactive energy L1 inductive | FLOAT32 | ABCD | varh | Read | |||
| HR | 834doc 40835 | Reactive energy L2 inductive | FLOAT32 | ABCD | varh | Read | |||
| HR | 836doc 40837 | Reactive energy L3 inductive | FLOAT32 | ABCD | varh | Read | |||
| HR | 838doc 40839 | Reactive energy inductive | FLOAT32 | ABCD | varh | Read | |||
| HR | 840doc 40841 | Reactive energy L1 capacitive | FLOAT32 | ABCD | varh | Read | |||
| HR | 842doc 40843 | Reactive energy L2 capacitive | FLOAT32 | ABCD | varh | Read | |||
| HR | 844doc 40845 | Reactive energy L3 capacitive | FLOAT32 | ABCD | varh | Read | |||
| HR | 846doc 40847 | Reactive energy capacitive | FLOAT32 | ABCD | varh | Read | |||
| HR | 848doc 40849 | Apparent energy L1 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 850doc 40851 | Apparent energy L2 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 852doc 40853 | Apparent energy L3 | FLOAT32 | ABCD | VAh | Read | |||
| HR | 854doc 40855 | Apparent energy | FLOAT32 | ABCD | VAh | Read | |||
| HR | 856doc 40857 | Active energy (3L) demand net | FLOAT32 | ABCD | Wh | Read | |||
| HR | 900doc 40901 | Limit value counter 1 | Alarm counter for limit value 1. | UINT32 | ABCD | Read | |||
| HR | 902doc 40903 | Limit value counter 2 | Alarm counter for limit value 2. | UINT32 | ABCD | Read | |||
| HR | 904doc 40905 | Limit value counter 3 | Alarm counter for limit value 3. | UINT32 | ABCD | Read | |||
| HR | 906doc 40907 | Limit value counter 4 | Alarm counter for limit value 4. | UINT32 | ABCD | Read | |||
| HR | 950doc 40951 | Analog input AI_A12 | Analog input on AI module in slot A. | FLOAT32 | ABCD | mA | Read | ||
| HR | 952doc 40953 | Analog input AI_A34 | Analog input on AI module in slot A. | FLOAT32 | ABCD | mA | Read | ||
| HR | 954doc 40955 | Analog input AI_B12 | Analog input on AI module in slot B. | FLOAT32 | ABCD | mA | Read | ||
| HR | 956doc 40957 | Analog input AI_B34 | Analog input on AI module in slot B. | FLOAT32 | ABCD | mA | Read | ||
| HR | 958doc 40959 | Analog input AI_C12 | Analog input on AI module in slot C. | FLOAT32 | ABCD | mA | Read | ||
| HR | 960doc 40961 | Analog input AI_C34 | Analog input on AI module in slot C. | FLOAT32 | ABCD | mA | Read | ||
| HR | 962doc 40963 | Analog input AI_D12 | Analog input on AI module in slot D. | FLOAT32 | ABCD | mA | Read | ||
| HR | 964doc 40965 | Analog input AI_D34 | Analog input on AI module in slot D. | FLOAT32 | ABCD | mA | Read | ||
| HR | 966doc 40967 | Analog output AO_A12 | Analog output on AO module in slot A; writable. | FLOAT32 | ABCD | mA | Read/write | ||
| HR | 968doc 40969 | Analog output AO_A34 | Analog output on AO module in slot A; writable. | FLOAT32 | ABCD | mA | Read/write | ||
| HR | 970doc 40971 | Analog output AO_B12 | Analog output on AO module in slot B. | FLOAT32 | ABCD | mA | Read | ||
| HR | 972doc 40973 | Analog output AO_B34 | Analog output on AO module in slot B. | FLOAT32 | ABCD | mA | Read | ||
| HR | 974doc 40975 | Analog output AO_C12 | Analog output on AO module in slot C. | FLOAT32 | ABCD | mA | Read | ||
| HR | 976doc 40977 | Analog output AO_C34 | Analog output on AO module in slot C. | FLOAT32 | ABCD | mA | Read | ||
| HR | 978doc 40979 | Analog output AO_D12 | Analog output on AO module in slot D. | FLOAT32 | ABCD | mA | Read | ||
| HR | 980doc 40981 | Analog output AO_D34 | Analog output on AO module in slot D. | FLOAT32 | ABCD | mA | Read | ||
| HR | 1209doc 41210 | Direction of current and power | From device version V4.10. | BITMAP16 | Read/write | bit 0 = Current direction (0 = inverse, 1 = standard); bit 1 = Power direction (0 = generator, 1 = load) |
Notes on this map
- Word order: the manual says the lower register of a multi-register value holds the most significant byte, so floats and the unsigned-long alarm counters are high word first (ABCD).
- All float registers assume the default float format (40050 = 0). In integer format only the first register of each pair is used and the value must be multiplied by a range-dependent factor (table 5-1, which depends on the measuring ranges and CT/VT setup); that mode is not mapped.
- Energy values are listed with data type 'measured value', so in float mode they are floats in Wh/varh/VAh.
- Bits 2-5 of 40129 are BO3-BO6, but which output each bit drives depends on which RO/BO modules are fitted in slots A and B (four layouts in the manual); check the table on pp. 24-25 for your hardware.
- Only rows printed individually are listed for harmonic block 2. The 4th-20th harmonic voltages (40512-40612) and currents (40632-40732) are printed only as ranges, so they are left out.
- The harmonic currents of block 1 (5th-19th) are in A; the harmonic currents of block 2 (2nd, 3rd, 21st) are printed in %.
- Left out: serial number 40020-40030 (the printed range is 11 registers for a 20-character string), and the limit-value group parameters 41000-41209 (packed byte fields; needs the full table on pp. 36-42).
- Analog inputs AI_A12 to AI_D34 depend on fitted AI modules; on 7KG775x only slot A. Only AO_A12/AO_A34 (40967/40969) are writable.
- Broadcast (address 0) is accepted for FC 06 and FC 16 writes, not for reads.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Siemens SICAM P power meter (Modbus RTU/ASCII)
What Modbus registers does the Siemens SICAM P power meter (Modbus RTU/ASCII) have?
This map lists 164 registers: 164 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Siemens SICAM P power meter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints Modicon holding-register numbers (40001, 40201...). Subtract 40001 for the wire address: 40201 (voltage L1-N) is requested as address 200. Bit-coded registers are printed as 'register / 2^n', meaning bit n of that register.
What byte order does the Siemens SICAM P power meter (Modbus RTU/ASCII) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Siemens SICAM P power meter (Modbus RTU/ASCII)?
Start with HR 200 Voltage UL1-N (Voltage L1-N); HR 208 Current IL1 (Current L1); HR 232 Active power P total (Total active power); HR 264 Power factor total (Total power factor); HR 274 Frequency (Frequency); HR 822 Active energy total (Total active energy); HR 49 Measured value format (Measured value format (float/integer)).
How do I enable Modbus control of the Siemens SICAM P power meter (Modbus RTU/ASCII)?
The Modbus serial interface is a hardware variant of the meter. Slave address (1-247), baud, parity and RTU/ASCII mode are set in the device parameters (on the device or with SICAM P PAR).
Where is the official Siemens SICAM P power meter (Modbus RTU/ASCII) Modbus documentation?
The source is Power Meter SICAM P Modbus Manual (E50417-B1076-C241-A5 (document version V01.12.02)), revision 2012-11, published free by Siemens at https://cache.industry.siemens.com/dl/files/374/109752374/att_934502/v1/MAN_SICAM_P_7KG775x_MODBUS_EN.pdf.
More Siemens Modbus register maps
- Sensor (room humidity / temperature)
Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)
Siemens QFA3150/MO room relative humidity and temperature sensor, basic documentation edition a (2021-01).
Also known as: QFA3150/MO, S55720-S535 - Sensor (duct humidity / temperature / CO2 / VOC)
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Siemens QFM9150/MO duct humidity/temperature sensor and QPM9152/MO duct air quality (CO2, VOC, humidity, temperature) sensor, basic documentation edition a (2022-12).
Also known as: QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585 - Protection relay
Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)
Reyrolle 7SR10 overcurrent / earth-fault relays, default Modbus RTU point list per Communication Protocols manual C53000-L7040-C002-7 (edition 11.2025, V01.00).
Also known as: 7SR10 Argus, Reyrolle 7SR10, 7SR1003, 7SR1004 - Protection relay
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Reyrolle 7SR11 (non-directional) and 7SR12 (directional) Argus overcurrent relays, default Modbus RTU point list in the 7SR11 & 7SR12 Complete Technical Manual (Chapter 4, Data Communications, 2015).
Also known as: 7SR11 Argus, 7SR12 Argus, Reyrolle 7SR11, Reyrolle 7SR12, 7SR120 - Energy meter
Siemens SENTRON PAC2200
SENTRON 7KM PAC2200 Modbus TCP and Modbus RTU variants (5 A and 65 A), per Equipment Manual 12/2022.
Also known as: 7KM PAC2200 - Power meter
Siemens SENTRON PAC3200
SENTRON PAC3200 (7KM2111/7KM2112), Ethernet port and optional PAC RS485 expansion module, per manual edition 02/2008.
Also known as: 7KM2112-0BA00-2AA0, 7KM2112-0BA00-3AA0, 7KM2111-1BA00-3AA0, 7KM PAC3200 - Circuit breaker trip unit (power meter)
Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
Siemens SENTRON 3WL air circuit breakers with a COM16 Modbus RTU communication module and, for voltage/power/energy values, the metering function (PLUS), per system manual A5E02126891-02.
Also known as: SENTRON WL, 3WL, 3WL COM16, COM16 - Power meter (power quality)
Siemens SICAM P850 / P855 power monitoring and PQ device
SICAM P850 / P855 (7KG85x) with Modbus TCP or Modbus RTU, firmware V3.11, per communication manual E50417-C1040-C482-B1 (05.2024).
Also known as: 7KG85, 7KG85X, SICAM P850, SICAM P855 - Motor management and protection relay
Siemens SIMOCODE pro V Modbus RTU basic unit
SIMOCODE pro V Modbus RTU basic units, per Configuration Manual 04/2015 (A5E33498234002A/RS-AA/001).
Also known as: SIMOCODE pro V Modbus, SIMOCODE pro V Modbus RTU - Variable frequency drive
Siemens SINAMICS G120 / G120C (Modbus RTU)
SINAMICS G120 with an RS485 Control Unit (CU230P-2 HVAC/BT, CU240B-2, CU240E-2 / -2 F, CU250S-2), G120C USS/MB and G110M CU240M USS, firmware V4.7, per Fieldbuses function manual A5E34229197B AA. Not SINAMICS G120X, which has its own documentation.
Also known as: G120C USS/MB, CU230P-2 HVAC, CU230P-2 BT, CU240B-2, CU240E-2, CU240E-2 F, CU250S-2, G110M CU240M USS, G120P - Variable frequency drive
Siemens SINAMICS V20 inverter (Modbus RTU)
SINAMICS V20 basic inverters (1AC 230 V 6SL3210-5BB.. and 3AC 400 V 6SL3210-5BE..) using the built-in RS485 port with P2023 = 2 (Modbus), per operating instructions A5E34559884-006 (11/2016).
Also known as: V20, 6SL3210-5BB, 6SL3210-5BE - Sensor (flow transmitter)
Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module
SITRANS F C MASS 6000 Coriolis flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MASS 6000, SITRANS FC MASS 6000 - Sensor (flow transmitter)
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
SITRANS F M MAG 6000 / MAG 6000 I electromagnetic flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MAG 6000, MAG 6000 I, SITRANS FM MAG 6000 - EV charger
Siemens VersiCharge AC series wallbox (Modbus map)
VersiCharge AC series chargers with firmware V2.135 or later (per-register minimum firmware is given in the source).
Also known as: VersiCharge, VersiCharge AC
Other power & energy meters register maps
- Power meter
Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU)
Enercept H8035 (energy only) and H8036 (enhanced data stream) split-core three-phase power transducers, 100-2400 A, installation guide Z201686-0K.
Also known as: Enercept H8035, Enercept H8036, H8035-0100-2, H8035-0300-2, H8035-0400-3, H8035-0800-3, H8035-0800-4, H8035-1600-4, H8035-2400-4, H8036-0100-2, H8036-0300-2, H8036-0400-3, H8036-0800-3, H8036-0800-4, H8036-1600-4, H8036-2400-4 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Actuator / valve (pressure-independent control valve with energy metering)
Belimo Energy Valve DN 15-50 (Version 4) Modbus RTU / TCP
Belimo Energy Valve Version 4, DN 15-50 (EV..R2+(K)BAC, EV..R2+MID, EV..R3+BAC), per Energy Valve Modbus interface description en-gb 2023-08.
Also known as: EV..R2+BAC, EV..R2+KBAC, EV..R2+MID, EV..R3+BAC, Energy Valve 4 - Energy meter (energy analyzer)
Carlo Gavazzi EM210 (AV versions)
EM210 three-phase energy analyzers, AV input versions with the RS485 Modbus RTU option, protocol version 4 revision 3 (newest variables need firmware A.5/A.6).
Also known as: EM210, EM210-72D, EM210 AV - Energy meter
Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)
EM511 direct-connected single-phase DIN meters with RS485 and digital input (X, PFA, PFB, SFA versions), protocol rev. 1.8.
Also known as: EM511-IS, EM511DINAV81XS1X, EM511DINAV81XS1PFA, EM511DINAV81XS1PFB, EM511DINAV81XS1SFA - Power meter (power factor regulator with network analyzer)
Circutor Computer SMART III
Circutor Computer SMART III reactive energy regulators (6 and 12 step models), RS-485 Modbus RTU, manual M015B01-03-25B.
Also known as: Computer SMART III 6, Computer SMART III 12, SMART III
All power & energy meters Modbus register maps →
Source: Power Meter SICAM P Modbus Manual · E50417-B1076-C241-A5 (document version V01.12.02) · rev. 2012-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.