Easy Modbus
  1. Home
  2. Modbus register maps
  3. Siemens
  4. SICAM P850 / P855 power monitoring and PQ device

Power meter (power quality) · Modbus register map

Siemens SICAM P850 / P855 power monitoring and PQ device Modbus register map

Updated 17 November 2026

Short answer

SICAM P850 is a panel power monitoring device and P855 a class A power quality device, both with Ethernet Modbus TCP and an optional RS-485 Modbus RTU interface. All data sits in holding registers: measured values as IEEE floats and energy as floats and doubles. This map covers identity, instantaneous values, THD, flicker, load-profile values, total and per-phase energy and the tariff 1 energy values.

This page lists 179 Modbus registers for the Siemens SICAM P850 / P855 power monitoring and PQ device — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.

Manufacturer
Siemens
Model
SICAM P850 / P855 power monitoring and PQ device
Equipment type
Power meter (power quality)
Registers
179 (1 writable)
Transport
Modbus TCP, Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Firmware
V3.11
Also known as
7KG85, 7KG85X, SICAM P850, SICAM P855
Source document
SICAM Power Monitoring Device and Power Quality Device SICAM P850/P855 7KG85X Communication Manual · E50417-C1040-C482-B1 · rev. 2024-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Siemens SICAM P850 / P855 power monitoring and PQ device

Integration in brief

Poll holding registers with FC 03: register 0201 (address 200) onward gives voltages, currents, power, power factor and frequency as big-endian floats; read total active energy import as a double at 4773 (address 4772).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 200Voltage a-NFLOAT32 ABCDVoltage a-NRead
HR 208Current aFLOAT32 ABCDCurrent aRead
HR 232Active powerFLOAT32 ABCDTotal active powerRead
HR 264Power factorFLOAT32 ABCDPower factorRead
HR 274Power frequencyFLOAT32 ABCDFrequencyRead
HR 4772Active energy, import (float64)FLOAT64 ABCDActive energy import (double)Read
HR 4788Active energy, export (float64)FLOAT64 ABCDActive energy export (double)Read

Enable Modbus control & writes

Modbus TCP is configured in the device parameters (standard port 502 fixed, optional user port 503-65535, access rights full or read-only per port). The RS-485 Modbus RTU interface needs the serial option and its own address, baud and parity settings.

Communication loss & watchdog

Communication supervision time (default 600 x 100 ms = 60 s, 0 = off) for both TCP and RTU; Modbus TCP also has a keep-alive time (default 10 s).

Byte order & addressing

Network setup

Watch out for

Siemens SICAM P850 / P855 power monitoring and PQ device Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

179 of 179 shown
Siemens SICAM P850 / P855 power monitoring and PQ device Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0001Device typeUp to 16 characters, e.g. SICAM P.STRING[16]Read
HR8doc 0009Device ordering code (MLFB)Up to 32 characters.STRING[32]Read
HR24doc 0025Device name from configurationUp to 32 characters.STRING[32]Read
HR40doc 0041Device serial numberUp to 16 characters.STRING[16]Read
HR76doc 0077Firmware versionUp to 12 characters, e.g. V03.10.01.STRING[12]Read
HR82doc 0083Parameter set versionUp to 12 characters.STRING[12]Read
HR153doc 0154TariffRead: current tariff; write: tariff from the next measuring period (1-8).UINT16Read/write
HR200doc 0201Voltage a-NVaFLOAT32ABCDVRead
HR202doc 0203Voltage b-NVbFLOAT32ABCDVRead
HR204doc 0205Voltage c-NVcFLOAT32ABCDVRead
HR206doc 0207Voltage neutral conductorVNFLOAT32ABCDVRead
HR208doc 0209Current aIaFLOAT32ABCDARead
HR210doc 0211Current bIbFLOAT32ABCDARead
HR212doc 0213Current cIcFLOAT32ABCDARead
HR214doc 0215Current neutral conductorINFLOAT32ABCDARead
HR216doc 0217Voltage a-bVabFLOAT32ABCDVRead
HR218doc 0219Voltage b-cVbcFLOAT32ABCDVRead
HR220doc 0221Voltage c-aVcaFLOAT32ABCDVRead
HR222doc 0223Mean value of voltage (P-N)VavgFLOAT32ABCDVRead
HR224doc 0225Mean value of currentsIavgFLOAT32ABCDARead
HR226doc 0227Active power aPaFLOAT32ABCDWRead
HR228doc 0229Active power bPbFLOAT32ABCDWRead
HR230doc 0231Active power cPcFLOAT32ABCDWRead
HR232doc 0233Active powerPFLOAT32ABCDWRead
HR234doc 0235Reactive power aQaFLOAT32ABCDvarRead
HR236doc 0237Reactive power bQbFLOAT32ABCDvarRead
HR238doc 0239Reactive power cQcFLOAT32ABCDvarRead
HR240doc 0241Reactive powerQFLOAT32ABCDvarRead
HR242doc 0243Apparent power aSaFLOAT32ABCDVARead
HR244doc 0245Apparent power bSbFLOAT32ABCDVARead
HR246doc 0247Apparent power cScFLOAT32ABCDVARead
HR248doc 0249Apparent powerSFLOAT32ABCDVARead
HR250doc 0251Active power factor acos φ (a)FLOAT32ABCDRead
HR252doc 0253Active power factor bcos φ (b)FLOAT32ABCDRead
HR254doc 0255Active power factor ccos φ (c)FLOAT32ABCDRead
HR256doc 0257Active power factorcos φFLOAT32ABCDRead
HR258doc 0259Power factor aPFaFLOAT32ABCDRead
HR260doc 0261Power factor bPFbFLOAT32ABCDRead
HR262doc 0263Power factor cPFcFLOAT32ABCDRead
HR264doc 0265Power factorPFFLOAT32ABCDRead
HR266doc 0267Phase angle aφaFLOAT32ABCD°Read
HR268doc 0269Phase angle bφbFLOAT32ABCD°Read
HR270doc 0271Phase angle cφcFLOAT32ABCD°Read
HR272doc 0273Phase angleφFLOAT32ABCD°Read
HR274doc 0275Power frequencyFLOAT32ABCDHzRead
HR276doc 0277Unbalanced voltageVunbalFLOAT32ABCD%Read
HR278doc 0279Unbalanced currentIunbalFLOAT32ABCD%Read
HR292doc 0293Frequency calculated every 10 s (internal)f (10 s)FLOAT32ABCDHzRead
HR294doc 0295Voltage a THDSTHDS (Va)FLOAT32ABCD%Read
HR296doc 0297Voltage b THDSTHDS (Vb)FLOAT32ABCD%Read
HR298doc 0299Voltage c THDSTHDS (Vc)FLOAT32ABCD%Read
HR300doc 0301Current a THDSTHDS (Ia)FLOAT32ABCD%Read
HR302doc 0303Current b THDSTHDS (Ib)FLOAT32ABCD%Read
HR304doc 0305Current c THDSTHDS (Ic)FLOAT32ABCD%Read
HR306doc 0307Angle Vab-VbcVoltage (φ12)FLOAT32ABCD°Read
HR308doc 0309Angle Vab-VcaVoltage (φ13)FLOAT32ABCD°Read
HR310doc 0311Angle Ia-IbCurrent (φ12)FLOAT32ABCD°Read
HR312doc 0313Angle Ia-IcCurrent (φ13)FLOAT32ABCD°Read
HR314doc 0315Reactive power (A)_FundamentalQ1aFLOAT32ABCDvarRead
HR316doc 0317Reactive power (B)_FundamentalQ1bFLOAT32ABCDvarRead
HR318doc 0319Reactive power (C)_FundamentalQ1cFLOAT32ABCDvarRead
HR320doc 0321Reactive power (Σ)_FundamentalQ1FLOAT32ABCDvarRead
HR322doc 0323Flicker instantaneous value voltage VaPinst (a-N)FLOAT32ABCDRead
HR324doc 0325Flicker instantaneous value voltage VbPinst (b-N)FLOAT32ABCDRead
HR326doc 0327Flicker instantaneous value voltage VcPinst (c-N)FLOAT32ABCDRead
HR328doc 0329Short term flicker voltage VaPst (a-N)FLOAT32ABCDRead
HR330doc 0331Short term flicker voltage VbPst (b-N)FLOAT32ABCDRead
HR332doc 0333Short term flicker voltage VcPst (c-N)FLOAT32ABCDRead
HR334doc 0335Long term flicker voltage VaPlt (a-N)FLOAT32ABCDRead
HR336doc 0337Long term flicker voltage VbPlt (b-N)FLOAT32ABCDRead
HR338doc 0339Long term flicker voltage VcPlt (c-N)FLOAT32ABCDRead
HR340doc 0341Flicker instantaneous value voltage Va-bPinst (a-b)FLOAT32ABCDRead
HR342doc 0343Flicker instantaneous value voltage Vb-cPinst (b-c)FLOAT32ABCDRead
HR344doc 0345Flicker instantaneous value voltage Vc-aPinst (c-a)FLOAT32ABCDRead
HR346doc 0347Short term flicker voltage Va-bPst (a-b)FLOAT32ABCDRead
HR348doc 0349Short term flicker voltage Vb-cPst (b-c)FLOAT32ABCDRead
HR350doc 0351Short term flicker voltage Vc-aPst (c-a)FLOAT32ABCDRead
HR352doc 0353Long term flicker voltage Va-bPlt (a-b)FLOAT32ABCDRead
HR354doc 0355Long term flicker voltage Vb-cPlt (b-c)FLOAT32ABCDRead
HR356doc 0357Long term flicker voltage Vc-aPlt (c-a)FLOAT32ABCDRead
HR4760doc 4761Active energy, import, Phase A (float64)WPa_impFLOAT64ABCDWhRead
HR4764doc 4765Active energy, import, Phase B (float64)WPb_impFLOAT64ABCDWhRead
HR4768doc 4769Active energy, import, Phase C (float64)WPc_impFLOAT64ABCDWhRead
HR4772doc 4773Active energy, import (float64)WP_impFLOAT64ABCDWhRead
HR4776doc 4777Active energy, export, Phase A (float64)WPa_expFLOAT64ABCDWhRead
HR4780doc 4781Active energy, export, Phase B (float64)WPb_expFLOAT64ABCDWhRead
HR4784doc 4785Active energy, export, Phase C (float64)WPc_expFLOAT64ABCDWhRead
HR4788doc 4789Active energy, export (float64)WP_expFLOAT64ABCDWhRead
HR4792doc 4793Reactive energy, import, Phase A (float64)WQa_impFLOAT64ABCDvarhRead
HR4796doc 4797Reactive energy, import, Phase B (float64)WQb_impFLOAT64ABCDvarhRead
HR4800doc 4801Reactive energy, import, Phase C (float64)WQc_impFLOAT64ABCDvarhRead
HR4804doc 4805Reactive energy, import (float64)WQ_impFLOAT64ABCDvarhRead
HR4808doc 4809Reactive energy, export, Phase A (float64)WQa_expFLOAT64ABCDvarhRead
HR4812doc 4813Reactive energy, export, Phase B (float64)WQb_expFLOAT64ABCDvarhRead
HR4816doc 4817Reactive energy, export, Phase C (float64)WQc_expFLOAT64ABCDvarhRead
HR4820doc 4821Reactive energy, export (float64)WQ_expFLOAT64ABCDvarhRead
HR4824doc 4825Reactive energy, inductive, Phase A (float64)WQa_indFLOAT64ABCDvarhRead
HR4828doc 4829Reactive energy, inductive, Phase B (float64)WQb_indFLOAT64ABCDvarhRead
HR4832doc 4833Reactive energy, inductive, Phase C (float64)WQc_indFLOAT64ABCDvarhRead
HR4836doc 4837Reactive energy, inductive (float64)WQ_indFLOAT64ABCDvarhRead
HR4840doc 4841Reactive energy, capacitive, Phase A (float64)WQa_capFLOAT64ABCDvarhRead
HR4844doc 4845Reactive energy, capacitive, Phase B (float64)WQb_capFLOAT64ABCDvarhRead
HR4848doc 4849Reactive energy, capacitive, Phase C (float64)WQc_capFLOAT64ABCDvarhRead
HR4852doc 4853Reactive energy, capacitive (float64)WQ_capFLOAT64ABCDvarhRead
HR4856doc 4857Apparent energy, Phase A (float64)WSaFLOAT64ABCDVAhRead
HR4860doc 4861Apparent energy, Phase B (float64)WSbFLOAT64ABCDVAhRead
HR4864doc 4865Apparent energy, Phase C (float64)WScFLOAT64ABCDVAhRead
HR4868doc 4869Apparent energy (float64)WSFLOAT64ABCDVAhRead
HR6100doc 6101Total power factor import (previous period)FLOAT32ABCDRead
HR6102doc 6103Total power factor export (previous period)FLOAT32ABCDRead
HR6104doc 6105Average active power import (previous period)FLOAT32ABCDWRead
HR6106doc 6107Average active power export (previous period)FLOAT32ABCDWRead
HR6108doc 6109Average reactive power import (previous period)FLOAT32ABCDvarRead
HR6110doc 6111Average reactive power export (previous period)FLOAT32ABCDvarRead
HR6112doc 6113Average apparent power (previous period)FLOAT32ABCDVARead
HR6114doc 6115Cumulated active power import (previous period)FLOAT32ABCDWRead
HR6116doc 6117Cumulated active power export (previous period)FLOAT32ABCDWRead
HR6118doc 6119Cumulated reactive power import (previous period)FLOAT32ABCDvarRead
HR6120doc 6121Cumulated reactive power export (previous period)FLOAT32ABCDvarRead
HR6122doc 6123Cumulated apparent power (previous period)FLOAT32ABCDVARead
HR6124doc 6125Maximum active power (previous period)FLOAT32ABCDWRead
HR6126doc 6127Minimum active power (previous period)FLOAT32ABCDWRead
HR6128doc 6129Maximum reactive power (previous period)FLOAT32ABCDvarRead
HR6130doc 6131Minimum reactive power (previous period)FLOAT32ABCDvarRead
HR6132doc 6133Maximum apparent power (previous period)FLOAT32ABCDVARead
HR6134doc 6135Minimum apparent power (previous period)FLOAT32ABCDVARead
HR6136doc 6137Cumulated active power import (current period)FLOAT32ABCDWRead
HR6138doc 6139Cumulated active power export (current period)FLOAT32ABCDWRead
HR6140doc 6141Cumulated reactive power import (current period)FLOAT32ABCDvarRead
HR6142doc 6143Cumulated reactive power export (current period)FLOAT32ABCDvarRead
HR6144doc 6145Cumulated apparent power (current period)FLOAT32ABCDVARead
HR6146doc 6147Maximum active power (current period)FLOAT32ABCDWRead
HR6148doc 6149Minimum active power (current period)FLOAT32ABCDWRead
HR6150doc 6151Maximum reactive power (current period)FLOAT32ABCDvarRead
HR6152doc 6153Minimum reactive power (current period)FLOAT32ABCDvarRead
HR6154doc 6155Maximum apparent power (current period)FLOAT32ABCDVARead
HR6156doc 6157Minimum apparent power (current period)FLOAT32ABCDVARead
HR6400doc 6401Voltage ab THDSTHDS (Vab)FLOAT32ABCD%Read
HR6402doc 6403Voltage bc THDSTHDS (Vbc)FLOAT32ABCD%Read
HR6404doc 6405Voltage ca THDSTHDS (Vca)FLOAT32ABCD%Read
HR8600doc 8601Active energy, import, Phase A (float32)WPa_impFLOAT32ABCDWhRead
HR8602doc 8603Active energy, import, Phase B (float32)WPb_impFLOAT32ABCDWhRead
HR8604doc 8605Active energy, import, Phase C (float32)WPc_impFLOAT32ABCDWhRead
HR8606doc 8607Active energy, import (float32)WP_impFLOAT32ABCDWhRead
HR8608doc 8609Active energy, export, Phase A (float32)WPa_expFLOAT32ABCDWhRead
HR8610doc 8611Active energy, export, Phase B (float32)WPb_expFLOAT32ABCDWhRead
HR8612doc 8613Active energy, export, Phase C (float32)WPc_expFLOAT32ABCDWhRead
HR8614doc 8615Active energy, export (float32)WP_expFLOAT32ABCDWhRead
HR8616doc 8617Reactive energy, import, Phase A (float32)WQa_impFLOAT32ABCDvarhRead
HR8618doc 8619Reactive energy, import, Phase B (float32)WQb_impFLOAT32ABCDvarhRead
HR8620doc 8621Reactive energy, import, Phase C (float32)WQc_impFLOAT32ABCDvarhRead
HR8622doc 8623Reactive energy, import (float32)WQ_impFLOAT32ABCDvarhRead
HR8624doc 8625Reactive energy, export, Phase A (float32)WQa_expFLOAT32ABCDvarhRead
HR8626doc 8627Reactive energy, export, Phase B (float32)WQb_expFLOAT32ABCDvarhRead
HR8628doc 8629Reactive energy, export, Phase C (float32)WQc_expFLOAT32ABCDvarhRead
HR8630doc 8631Reactive energy, export (float32)WQ_expFLOAT32ABCDvarhRead
HR8632doc 8633Reactive energy, inductive, Phase A (float32)WQa_indFLOAT32ABCDvarhRead
HR8634doc 8635Reactive energy, inductive, Phase B (float32)WQb_indFLOAT32ABCDvarhRead
HR8636doc 8637Reactive energy, inductive, Phase C (float32)WQc_indFLOAT32ABCDvarhRead
HR8638doc 8639Reactive energy, inductive (float32)WQ_indFLOAT32ABCDvarhRead
HR8640doc 8641Reactive energy, capacitive, Phase A (float32)WQa_capFLOAT32ABCDvarhRead
HR8642doc 8643Reactive energy, capacitive, Phase B (float32)WQb_capFLOAT32ABCDvarhRead
HR8644doc 8645Reactive energy, capacitive, Phase C (float32)WQc_capFLOAT32ABCDvarhRead
HR8646doc 8647Reactive energy, capacitive (float32)WQ_capFLOAT32ABCDvarhRead
HR8648doc 8649Apparent energy, Phase A (float32)WSaFLOAT32ABCDVAhRead
HR8650doc 8651Apparent energy, Phase B (float32)WSbFLOAT32ABCDVAhRead
HR8652doc 8653Apparent energy, Phase C (float32)WScFLOAT32ABCDVAhRead
HR8654doc 8655Apparent energy (float32)WSFLOAT32ABCDVAhRead
HR8800doc 8801Active energy, import, tariff 1WP_impFLOAT32ABCDWhRead
HR8802doc 8803Active energy, export, tariff 1WP_expFLOAT32ABCDWhRead
HR8804doc 8805Reactive energy, inductive, import, tariff 1WQ_ind_impFLOAT32ABCDvarhRead
HR8806doc 8807Reactive energy, capacitive, export, tariff 1WQ_cap_expFLOAT32ABCDvarhRead
HR8808doc 8809Reactive energy, inductive, export, tariff 1WQ_ind_expFLOAT32ABCDvarhRead
HR8810doc 8811Reactive energy, capacitive, import, tariff 1WQ_cap_impFLOAT32ABCDvarhRead
HR8812doc 8813Reactive energy, inductive, tariff 1WQ_indFLOAT32ABCDvarhRead
HR8814doc 8815Reactive energy, capacitive, tariff 1WQ_capFLOAT32ABCDvarhRead
HR8816doc 8817Reactive energy, import, tariff 1WQ_impFLOAT32ABCDvarhRead
HR8818doc 8819Reactive energy, export, tariff 1WQ_expFLOAT32ABCDvarhRead
HR8820doc 8821Apparent energy, tariff 1WSFLOAT32ABCDVAhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Siemens SICAM P850 / P855 power monitoring and PQ device

What Modbus registers does the Siemens SICAM P850 / P855 power monitoring and PQ device have?

This map lists 179 registers: 179 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Siemens SICAM P850 / P855 power monitoring and PQ device Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 1-based register numbers (0201, 4761...) and states that the address in the message is register number - 1. Register 0201 (voltage a-N) is requested as address 200.

What byte order does the Siemens SICAM P850 / P855 power monitoring and PQ device use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Siemens SICAM P850 / P855 power monitoring and PQ device?

Start with HR 200 Voltage a-N (Voltage a-N); HR 208 Current a (Current a); HR 232 Active power (Total active power); HR 264 Power factor (Power factor); HR 274 Power frequency (Frequency); HR 4772 Active energy, import (float64) (Active energy import (double)); HR 4788 Active energy, export (float64) (Active energy export (double)).

How do I enable Modbus control of the Siemens SICAM P850 / P855 power monitoring and PQ device?

Modbus TCP is configured in the device parameters (standard port 502 fixed, optional user port 503-65535, access rights full or read-only per port). The RS-485 Modbus RTU interface needs the serial option and its own address, baud and parity settings.

What happens when the Siemens SICAM P850 / P855 power monitoring and PQ device loses Modbus communication?

Communication supervision time (default 600 x 100 ms = 60 s, 0 = off) for both TCP and RTU; Modbus TCP also has a keep-alive time (default 10 s).

Where is the official Siemens SICAM P850 / P855 power monitoring and PQ device Modbus documentation?

The source is SICAM Power Monitoring Device and Power Quality Device SICAM P850/P855 7KG85X Communication Manual (E50417-C1040-C482-B1), revision 2024-05, published free by Siemens at https://cache.industry.siemens.com/dl/files/152/109752152/att_1289026/v1/SICAM_P85x_7KG85_CM_US.pdf.

More Siemens Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: SICAM Power Monitoring Device and Power Quality Device SICAM P850/P855 7KG85X Communication Manual · E50417-C1040-C482-B1 · rev. 2024-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.