- Home
- Modbus register maps
- Siemens
- SICAM P850 / P855 power monitoring and PQ device
Power meter (power quality) · Modbus register map
Siemens SICAM P850 / P855 power monitoring and PQ device Modbus register map
Updated 17 November 2026
SICAM P850 is a panel power monitoring device and P855 a class A power quality device, both with Ethernet Modbus TCP and an optional RS-485 Modbus RTU interface. All data sits in holding registers: measured values as IEEE floats and energy as floats and doubles. This map covers identity, instantaneous values, THD, flicker, load-profile values, total and per-phase energy and the tariff 1 energy values.
This page lists 179 Modbus registers for the Siemens SICAM P850 / P855 power monitoring and PQ device — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.
- Manufacturer
- Siemens
- Model
- SICAM P850 / P855 power monitoring and PQ device
- Equipment type
- Power meter (power quality)
- Registers
- 179 (1 writable)
- Transport
- Modbus TCP, Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- V3.11
- Also known as
- 7KG85, 7KG85X, SICAM P850, SICAM P855
Integration notes: Siemens SICAM P850 / P855 power monitoring and PQ device
Poll holding registers with FC 03: register 0201 (address 200) onward gives voltages, currents, power, power factor and frequency as big-endian floats; read total active energy import as a double at 4773 (address 4772).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 200 | Voltage a-N | FLOAT32 ABCD | Voltage a-N | Read |
| HR 208 | Current a | FLOAT32 ABCD | Current a | Read |
| HR 232 | Active power | FLOAT32 ABCD | Total active power | Read |
| HR 264 | Power factor | FLOAT32 ABCD | Power factor | Read |
| HR 274 | Power frequency | FLOAT32 ABCD | Frequency | Read |
| HR 4772 | Active energy, import (float64) | FLOAT64 ABCD | Active energy import (double) | Read |
| HR 4788 | Active energy, export (float64) | FLOAT64 ABCD | Active energy export (double) | Read |
Enable Modbus control & writes
Modbus TCP is configured in the device parameters (standard port 502 fixed, optional user port 503-65535, access rights full or read-only per port). The RS-485 Modbus RTU interface needs the serial option and its own address, baud and parity settings.
Communication loss & watchdog
Communication supervision time (default 600 x 100 ms = 60 s, 0 = off) for both TCP and RTU; Modbus TCP also has a keep-alive time (default 10 s).
Byte order & addressing
- Register numbers are 1-based; subtract 1 for the address.
- Floats and doubles are high word first.
- Complex values must be read as a whole or the device returns exception 03.
Network setup
- Modbus RTU defaults: address 1, 19200 baud, even parity with 1 stop bit (also odd, none with 1 stop bit, or none with 2 stop bits); baud 1200-115200.
- Modbus TCP: up to 4 connections; with a user port, 2 on port 502 and 2 on the user port.
Watch out for
- A port set to read-only access rejects writes.
- Special NaN/Inf floats mark invalid values; handle them before logging.
Siemens SICAM P850 / P855 power monitoring and PQ device Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0001 | Device type | Up to 16 characters, e.g. SICAM P. | STRING[16] | Read | ||||
| HR | 8doc 0009 | Device ordering code (MLFB) | Up to 32 characters. | STRING[32] | Read | ||||
| HR | 24doc 0025 | Device name from configuration | Up to 32 characters. | STRING[32] | Read | ||||
| HR | 40doc 0041 | Device serial number | Up to 16 characters. | STRING[16] | Read | ||||
| HR | 76doc 0077 | Firmware version | Up to 12 characters, e.g. V03.10.01. | STRING[12] | Read | ||||
| HR | 82doc 0083 | Parameter set version | Up to 12 characters. | STRING[12] | Read | ||||
| HR | 153doc 0154 | Tariff | Read: current tariff; write: tariff from the next measuring period (1-8). | UINT16 | Read/write | ||||
| HR | 200doc 0201 | Voltage a-N | Va | FLOAT32 | ABCD | V | Read | ||
| HR | 202doc 0203 | Voltage b-N | Vb | FLOAT32 | ABCD | V | Read | ||
| HR | 204doc 0205 | Voltage c-N | Vc | FLOAT32 | ABCD | V | Read | ||
| HR | 206doc 0207 | Voltage neutral conductor | VN | FLOAT32 | ABCD | V | Read | ||
| HR | 208doc 0209 | Current a | Ia | FLOAT32 | ABCD | A | Read | ||
| HR | 210doc 0211 | Current b | Ib | FLOAT32 | ABCD | A | Read | ||
| HR | 212doc 0213 | Current c | Ic | FLOAT32 | ABCD | A | Read | ||
| HR | 214doc 0215 | Current neutral conductor | IN | FLOAT32 | ABCD | A | Read | ||
| HR | 216doc 0217 | Voltage a-b | Vab | FLOAT32 | ABCD | V | Read | ||
| HR | 218doc 0219 | Voltage b-c | Vbc | FLOAT32 | ABCD | V | Read | ||
| HR | 220doc 0221 | Voltage c-a | Vca | FLOAT32 | ABCD | V | Read | ||
| HR | 222doc 0223 | Mean value of voltage (P-N) | Vavg | FLOAT32 | ABCD | V | Read | ||
| HR | 224doc 0225 | Mean value of currents | Iavg | FLOAT32 | ABCD | A | Read | ||
| HR | 226doc 0227 | Active power a | Pa | FLOAT32 | ABCD | W | Read | ||
| HR | 228doc 0229 | Active power b | Pb | FLOAT32 | ABCD | W | Read | ||
| HR | 230doc 0231 | Active power c | Pc | FLOAT32 | ABCD | W | Read | ||
| HR | 232doc 0233 | Active power | P | FLOAT32 | ABCD | W | Read | ||
| HR | 234doc 0235 | Reactive power a | Qa | FLOAT32 | ABCD | var | Read | ||
| HR | 236doc 0237 | Reactive power b | Qb | FLOAT32 | ABCD | var | Read | ||
| HR | 238doc 0239 | Reactive power c | Qc | FLOAT32 | ABCD | var | Read | ||
| HR | 240doc 0241 | Reactive power | Q | FLOAT32 | ABCD | var | Read | ||
| HR | 242doc 0243 | Apparent power a | Sa | FLOAT32 | ABCD | VA | Read | ||
| HR | 244doc 0245 | Apparent power b | Sb | FLOAT32 | ABCD | VA | Read | ||
| HR | 246doc 0247 | Apparent power c | Sc | FLOAT32 | ABCD | VA | Read | ||
| HR | 248doc 0249 | Apparent power | S | FLOAT32 | ABCD | VA | Read | ||
| HR | 250doc 0251 | Active power factor a | cos φ (a) | FLOAT32 | ABCD | Read | |||
| HR | 252doc 0253 | Active power factor b | cos φ (b) | FLOAT32 | ABCD | Read | |||
| HR | 254doc 0255 | Active power factor c | cos φ (c) | FLOAT32 | ABCD | Read | |||
| HR | 256doc 0257 | Active power factor | cos φ | FLOAT32 | ABCD | Read | |||
| HR | 258doc 0259 | Power factor a | PFa | FLOAT32 | ABCD | Read | |||
| HR | 260doc 0261 | Power factor b | PFb | FLOAT32 | ABCD | Read | |||
| HR | 262doc 0263 | Power factor c | PFc | FLOAT32 | ABCD | Read | |||
| HR | 264doc 0265 | Power factor | PF | FLOAT32 | ABCD | Read | |||
| HR | 266doc 0267 | Phase angle a | φa | FLOAT32 | ABCD | ° | Read | ||
| HR | 268doc 0269 | Phase angle b | φb | FLOAT32 | ABCD | ° | Read | ||
| HR | 270doc 0271 | Phase angle c | φc | FLOAT32 | ABCD | ° | Read | ||
| HR | 272doc 0273 | Phase angle | φ | FLOAT32 | ABCD | ° | Read | ||
| HR | 274doc 0275 | Power frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 276doc 0277 | Unbalanced voltage | Vunbal | FLOAT32 | ABCD | % | Read | ||
| HR | 278doc 0279 | Unbalanced current | Iunbal | FLOAT32 | ABCD | % | Read | ||
| HR | 292doc 0293 | Frequency calculated every 10 s (internal) | f (10 s) | FLOAT32 | ABCD | Hz | Read | ||
| HR | 294doc 0295 | Voltage a THDS | THDS (Va) | FLOAT32 | ABCD | % | Read | ||
| HR | 296doc 0297 | Voltage b THDS | THDS (Vb) | FLOAT32 | ABCD | % | Read | ||
| HR | 298doc 0299 | Voltage c THDS | THDS (Vc) | FLOAT32 | ABCD | % | Read | ||
| HR | 300doc 0301 | Current a THDS | THDS (Ia) | FLOAT32 | ABCD | % | Read | ||
| HR | 302doc 0303 | Current b THDS | THDS (Ib) | FLOAT32 | ABCD | % | Read | ||
| HR | 304doc 0305 | Current c THDS | THDS (Ic) | FLOAT32 | ABCD | % | Read | ||
| HR | 306doc 0307 | Angle Vab-Vbc | Voltage (φ12) | FLOAT32 | ABCD | ° | Read | ||
| HR | 308doc 0309 | Angle Vab-Vca | Voltage (φ13) | FLOAT32 | ABCD | ° | Read | ||
| HR | 310doc 0311 | Angle Ia-Ib | Current (φ12) | FLOAT32 | ABCD | ° | Read | ||
| HR | 312doc 0313 | Angle Ia-Ic | Current (φ13) | FLOAT32 | ABCD | ° | Read | ||
| HR | 314doc 0315 | Reactive power (A)_Fundamental | Q1a | FLOAT32 | ABCD | var | Read | ||
| HR | 316doc 0317 | Reactive power (B)_Fundamental | Q1b | FLOAT32 | ABCD | var | Read | ||
| HR | 318doc 0319 | Reactive power (C)_Fundamental | Q1c | FLOAT32 | ABCD | var | Read | ||
| HR | 320doc 0321 | Reactive power (Σ)_Fundamental | Q1 | FLOAT32 | ABCD | var | Read | ||
| HR | 322doc 0323 | Flicker instantaneous value voltage Va | Pinst (a-N) | FLOAT32 | ABCD | Read | |||
| HR | 324doc 0325 | Flicker instantaneous value voltage Vb | Pinst (b-N) | FLOAT32 | ABCD | Read | |||
| HR | 326doc 0327 | Flicker instantaneous value voltage Vc | Pinst (c-N) | FLOAT32 | ABCD | Read | |||
| HR | 328doc 0329 | Short term flicker voltage Va | Pst (a-N) | FLOAT32 | ABCD | Read | |||
| HR | 330doc 0331 | Short term flicker voltage Vb | Pst (b-N) | FLOAT32 | ABCD | Read | |||
| HR | 332doc 0333 | Short term flicker voltage Vc | Pst (c-N) | FLOAT32 | ABCD | Read | |||
| HR | 334doc 0335 | Long term flicker voltage Va | Plt (a-N) | FLOAT32 | ABCD | Read | |||
| HR | 336doc 0337 | Long term flicker voltage Vb | Plt (b-N) | FLOAT32 | ABCD | Read | |||
| HR | 338doc 0339 | Long term flicker voltage Vc | Plt (c-N) | FLOAT32 | ABCD | Read | |||
| HR | 340doc 0341 | Flicker instantaneous value voltage Va-b | Pinst (a-b) | FLOAT32 | ABCD | Read | |||
| HR | 342doc 0343 | Flicker instantaneous value voltage Vb-c | Pinst (b-c) | FLOAT32 | ABCD | Read | |||
| HR | 344doc 0345 | Flicker instantaneous value voltage Vc-a | Pinst (c-a) | FLOAT32 | ABCD | Read | |||
| HR | 346doc 0347 | Short term flicker voltage Va-b | Pst (a-b) | FLOAT32 | ABCD | Read | |||
| HR | 348doc 0349 | Short term flicker voltage Vb-c | Pst (b-c) | FLOAT32 | ABCD | Read | |||
| HR | 350doc 0351 | Short term flicker voltage Vc-a | Pst (c-a) | FLOAT32 | ABCD | Read | |||
| HR | 352doc 0353 | Long term flicker voltage Va-b | Plt (a-b) | FLOAT32 | ABCD | Read | |||
| HR | 354doc 0355 | Long term flicker voltage Vb-c | Plt (b-c) | FLOAT32 | ABCD | Read | |||
| HR | 356doc 0357 | Long term flicker voltage Vc-a | Plt (c-a) | FLOAT32 | ABCD | Read | |||
| HR | 4760doc 4761 | Active energy, import, Phase A (float64) | WPa_imp | FLOAT64 | ABCD | Wh | Read | ||
| HR | 4764doc 4765 | Active energy, import, Phase B (float64) | WPb_imp | FLOAT64 | ABCD | Wh | Read | ||
| HR | 4768doc 4769 | Active energy, import, Phase C (float64) | WPc_imp | FLOAT64 | ABCD | Wh | Read | ||
| HR | 4772doc 4773 | Active energy, import (float64) | WP_imp | FLOAT64 | ABCD | Wh | Read | ||
| HR | 4776doc 4777 | Active energy, export, Phase A (float64) | WPa_exp | FLOAT64 | ABCD | Wh | Read | ||
| HR | 4780doc 4781 | Active energy, export, Phase B (float64) | WPb_exp | FLOAT64 | ABCD | Wh | Read | ||
| HR | 4784doc 4785 | Active energy, export, Phase C (float64) | WPc_exp | FLOAT64 | ABCD | Wh | Read | ||
| HR | 4788doc 4789 | Active energy, export (float64) | WP_exp | FLOAT64 | ABCD | Wh | Read | ||
| HR | 4792doc 4793 | Reactive energy, import, Phase A (float64) | WQa_imp | FLOAT64 | ABCD | varh | Read | ||
| HR | 4796doc 4797 | Reactive energy, import, Phase B (float64) | WQb_imp | FLOAT64 | ABCD | varh | Read | ||
| HR | 4800doc 4801 | Reactive energy, import, Phase C (float64) | WQc_imp | FLOAT64 | ABCD | varh | Read | ||
| HR | 4804doc 4805 | Reactive energy, import (float64) | WQ_imp | FLOAT64 | ABCD | varh | Read | ||
| HR | 4808doc 4809 | Reactive energy, export, Phase A (float64) | WQa_exp | FLOAT64 | ABCD | varh | Read | ||
| HR | 4812doc 4813 | Reactive energy, export, Phase B (float64) | WQb_exp | FLOAT64 | ABCD | varh | Read | ||
| HR | 4816doc 4817 | Reactive energy, export, Phase C (float64) | WQc_exp | FLOAT64 | ABCD | varh | Read | ||
| HR | 4820doc 4821 | Reactive energy, export (float64) | WQ_exp | FLOAT64 | ABCD | varh | Read | ||
| HR | 4824doc 4825 | Reactive energy, inductive, Phase A (float64) | WQa_ind | FLOAT64 | ABCD | varh | Read | ||
| HR | 4828doc 4829 | Reactive energy, inductive, Phase B (float64) | WQb_ind | FLOAT64 | ABCD | varh | Read | ||
| HR | 4832doc 4833 | Reactive energy, inductive, Phase C (float64) | WQc_ind | FLOAT64 | ABCD | varh | Read | ||
| HR | 4836doc 4837 | Reactive energy, inductive (float64) | WQ_ind | FLOAT64 | ABCD | varh | Read | ||
| HR | 4840doc 4841 | Reactive energy, capacitive, Phase A (float64) | WQa_cap | FLOAT64 | ABCD | varh | Read | ||
| HR | 4844doc 4845 | Reactive energy, capacitive, Phase B (float64) | WQb_cap | FLOAT64 | ABCD | varh | Read | ||
| HR | 4848doc 4849 | Reactive energy, capacitive, Phase C (float64) | WQc_cap | FLOAT64 | ABCD | varh | Read | ||
| HR | 4852doc 4853 | Reactive energy, capacitive (float64) | WQ_cap | FLOAT64 | ABCD | varh | Read | ||
| HR | 4856doc 4857 | Apparent energy, Phase A (float64) | WSa | FLOAT64 | ABCD | VAh | Read | ||
| HR | 4860doc 4861 | Apparent energy, Phase B (float64) | WSb | FLOAT64 | ABCD | VAh | Read | ||
| HR | 4864doc 4865 | Apparent energy, Phase C (float64) | WSc | FLOAT64 | ABCD | VAh | Read | ||
| HR | 4868doc 4869 | Apparent energy (float64) | WS | FLOAT64 | ABCD | VAh | Read | ||
| HR | 6100doc 6101 | Total power factor import (previous period) | FLOAT32 | ABCD | Read | ||||
| HR | 6102doc 6103 | Total power factor export (previous period) | FLOAT32 | ABCD | Read | ||||
| HR | 6104doc 6105 | Average active power import (previous period) | FLOAT32 | ABCD | W | Read | |||
| HR | 6106doc 6107 | Average active power export (previous period) | FLOAT32 | ABCD | W | Read | |||
| HR | 6108doc 6109 | Average reactive power import (previous period) | FLOAT32 | ABCD | var | Read | |||
| HR | 6110doc 6111 | Average reactive power export (previous period) | FLOAT32 | ABCD | var | Read | |||
| HR | 6112doc 6113 | Average apparent power (previous period) | FLOAT32 | ABCD | VA | Read | |||
| HR | 6114doc 6115 | Cumulated active power import (previous period) | FLOAT32 | ABCD | W | Read | |||
| HR | 6116doc 6117 | Cumulated active power export (previous period) | FLOAT32 | ABCD | W | Read | |||
| HR | 6118doc 6119 | Cumulated reactive power import (previous period) | FLOAT32 | ABCD | var | Read | |||
| HR | 6120doc 6121 | Cumulated reactive power export (previous period) | FLOAT32 | ABCD | var | Read | |||
| HR | 6122doc 6123 | Cumulated apparent power (previous period) | FLOAT32 | ABCD | VA | Read | |||
| HR | 6124doc 6125 | Maximum active power (previous period) | FLOAT32 | ABCD | W | Read | |||
| HR | 6126doc 6127 | Minimum active power (previous period) | FLOAT32 | ABCD | W | Read | |||
| HR | 6128doc 6129 | Maximum reactive power (previous period) | FLOAT32 | ABCD | var | Read | |||
| HR | 6130doc 6131 | Minimum reactive power (previous period) | FLOAT32 | ABCD | var | Read | |||
| HR | 6132doc 6133 | Maximum apparent power (previous period) | FLOAT32 | ABCD | VA | Read | |||
| HR | 6134doc 6135 | Minimum apparent power (previous period) | FLOAT32 | ABCD | VA | Read | |||
| HR | 6136doc 6137 | Cumulated active power import (current period) | FLOAT32 | ABCD | W | Read | |||
| HR | 6138doc 6139 | Cumulated active power export (current period) | FLOAT32 | ABCD | W | Read | |||
| HR | 6140doc 6141 | Cumulated reactive power import (current period) | FLOAT32 | ABCD | var | Read | |||
| HR | 6142doc 6143 | Cumulated reactive power export (current period) | FLOAT32 | ABCD | var | Read | |||
| HR | 6144doc 6145 | Cumulated apparent power (current period) | FLOAT32 | ABCD | VA | Read | |||
| HR | 6146doc 6147 | Maximum active power (current period) | FLOAT32 | ABCD | W | Read | |||
| HR | 6148doc 6149 | Minimum active power (current period) | FLOAT32 | ABCD | W | Read | |||
| HR | 6150doc 6151 | Maximum reactive power (current period) | FLOAT32 | ABCD | var | Read | |||
| HR | 6152doc 6153 | Minimum reactive power (current period) | FLOAT32 | ABCD | var | Read | |||
| HR | 6154doc 6155 | Maximum apparent power (current period) | FLOAT32 | ABCD | VA | Read | |||
| HR | 6156doc 6157 | Minimum apparent power (current period) | FLOAT32 | ABCD | VA | Read | |||
| HR | 6400doc 6401 | Voltage ab THDS | THDS (Vab) | FLOAT32 | ABCD | % | Read | ||
| HR | 6402doc 6403 | Voltage bc THDS | THDS (Vbc) | FLOAT32 | ABCD | % | Read | ||
| HR | 6404doc 6405 | Voltage ca THDS | THDS (Vca) | FLOAT32 | ABCD | % | Read | ||
| HR | 8600doc 8601 | Active energy, import, Phase A (float32) | WPa_imp | FLOAT32 | ABCD | Wh | Read | ||
| HR | 8602doc 8603 | Active energy, import, Phase B (float32) | WPb_imp | FLOAT32 | ABCD | Wh | Read | ||
| HR | 8604doc 8605 | Active energy, import, Phase C (float32) | WPc_imp | FLOAT32 | ABCD | Wh | Read | ||
| HR | 8606doc 8607 | Active energy, import (float32) | WP_imp | FLOAT32 | ABCD | Wh | Read | ||
| HR | 8608doc 8609 | Active energy, export, Phase A (float32) | WPa_exp | FLOAT32 | ABCD | Wh | Read | ||
| HR | 8610doc 8611 | Active energy, export, Phase B (float32) | WPb_exp | FLOAT32 | ABCD | Wh | Read | ||
| HR | 8612doc 8613 | Active energy, export, Phase C (float32) | WPc_exp | FLOAT32 | ABCD | Wh | Read | ||
| HR | 8614doc 8615 | Active energy, export (float32) | WP_exp | FLOAT32 | ABCD | Wh | Read | ||
| HR | 8616doc 8617 | Reactive energy, import, Phase A (float32) | WQa_imp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8618doc 8619 | Reactive energy, import, Phase B (float32) | WQb_imp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8620doc 8621 | Reactive energy, import, Phase C (float32) | WQc_imp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8622doc 8623 | Reactive energy, import (float32) | WQ_imp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8624doc 8625 | Reactive energy, export, Phase A (float32) | WQa_exp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8626doc 8627 | Reactive energy, export, Phase B (float32) | WQb_exp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8628doc 8629 | Reactive energy, export, Phase C (float32) | WQc_exp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8630doc 8631 | Reactive energy, export (float32) | WQ_exp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8632doc 8633 | Reactive energy, inductive, Phase A (float32) | WQa_ind | FLOAT32 | ABCD | varh | Read | ||
| HR | 8634doc 8635 | Reactive energy, inductive, Phase B (float32) | WQb_ind | FLOAT32 | ABCD | varh | Read | ||
| HR | 8636doc 8637 | Reactive energy, inductive, Phase C (float32) | WQc_ind | FLOAT32 | ABCD | varh | Read | ||
| HR | 8638doc 8639 | Reactive energy, inductive (float32) | WQ_ind | FLOAT32 | ABCD | varh | Read | ||
| HR | 8640doc 8641 | Reactive energy, capacitive, Phase A (float32) | WQa_cap | FLOAT32 | ABCD | varh | Read | ||
| HR | 8642doc 8643 | Reactive energy, capacitive, Phase B (float32) | WQb_cap | FLOAT32 | ABCD | varh | Read | ||
| HR | 8644doc 8645 | Reactive energy, capacitive, Phase C (float32) | WQc_cap | FLOAT32 | ABCD | varh | Read | ||
| HR | 8646doc 8647 | Reactive energy, capacitive (float32) | WQ_cap | FLOAT32 | ABCD | varh | Read | ||
| HR | 8648doc 8649 | Apparent energy, Phase A (float32) | WSa | FLOAT32 | ABCD | VAh | Read | ||
| HR | 8650doc 8651 | Apparent energy, Phase B (float32) | WSb | FLOAT32 | ABCD | VAh | Read | ||
| HR | 8652doc 8653 | Apparent energy, Phase C (float32) | WSc | FLOAT32 | ABCD | VAh | Read | ||
| HR | 8654doc 8655 | Apparent energy (float32) | WS | FLOAT32 | ABCD | VAh | Read | ||
| HR | 8800doc 8801 | Active energy, import, tariff 1 | WP_imp | FLOAT32 | ABCD | Wh | Read | ||
| HR | 8802doc 8803 | Active energy, export, tariff 1 | WP_exp | FLOAT32 | ABCD | Wh | Read | ||
| HR | 8804doc 8805 | Reactive energy, inductive, import, tariff 1 | WQ_ind_imp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8806doc 8807 | Reactive energy, capacitive, export, tariff 1 | WQ_cap_exp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8808doc 8809 | Reactive energy, inductive, export, tariff 1 | WQ_ind_exp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8810doc 8811 | Reactive energy, capacitive, import, tariff 1 | WQ_cap_imp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8812doc 8813 | Reactive energy, inductive, tariff 1 | WQ_ind | FLOAT32 | ABCD | varh | Read | ||
| HR | 8814doc 8815 | Reactive energy, capacitive, tariff 1 | WQ_cap | FLOAT32 | ABCD | varh | Read | ||
| HR | 8816doc 8817 | Reactive energy, import, tariff 1 | WQ_imp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8818doc 8819 | Reactive energy, export, tariff 1 | WQ_exp | FLOAT32 | ABCD | varh | Read | ||
| HR | 8820doc 8821 | Apparent energy, tariff 1 | WS | FLOAT32 | ABCD | VAh | Read |
Notes on this map
- Word order: the manual states that for values larger than one register the lowest register holds the most significant byte (and Modbus TCP data is big-endian), so floats and doubles are high word first (ABCD).
- Invalid or overflowed measured values are reported as special floats: 7F800000h = overflow/invalid, 7F800001h = not calculated (e.g. voltage below 15 % of rated), 7F800002h = value does not exist for the network type.
- Left out: the indication registers (0101-0152), whose 2-bit value/quality layout is shown only in figures; the date/time registers; PQ aggregation, harmonics, PQ event and tariff counter blocks; the counter-pulse energy registers 0801-0846; tariffs 2-8 float32 and all float64 tariff values; the internal 1-cycle values 0281-0292.
- The same register map applies to Modbus TCP and Modbus RTU.
- Flicker values (0323-0357) have no unit.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Siemens SICAM P850 / P855 power monitoring and PQ device
What Modbus registers does the Siemens SICAM P850 / P855 power monitoring and PQ device have?
This map lists 179 registers: 179 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Siemens SICAM P850 / P855 power monitoring and PQ device Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 1-based register numbers (0201, 4761...) and states that the address in the message is register number - 1. Register 0201 (voltage a-N) is requested as address 200.
What byte order does the Siemens SICAM P850 / P855 power monitoring and PQ device use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Siemens SICAM P850 / P855 power monitoring and PQ device?
Start with HR 200 Voltage a-N (Voltage a-N); HR 208 Current a (Current a); HR 232 Active power (Total active power); HR 264 Power factor (Power factor); HR 274 Power frequency (Frequency); HR 4772 Active energy, import (float64) (Active energy import (double)); HR 4788 Active energy, export (float64) (Active energy export (double)).
How do I enable Modbus control of the Siemens SICAM P850 / P855 power monitoring and PQ device?
Modbus TCP is configured in the device parameters (standard port 502 fixed, optional user port 503-65535, access rights full or read-only per port). The RS-485 Modbus RTU interface needs the serial option and its own address, baud and parity settings.
What happens when the Siemens SICAM P850 / P855 power monitoring and PQ device loses Modbus communication?
Communication supervision time (default 600 x 100 ms = 60 s, 0 = off) for both TCP and RTU; Modbus TCP also has a keep-alive time (default 10 s).
Where is the official Siemens SICAM P850 / P855 power monitoring and PQ device Modbus documentation?
The source is SICAM Power Monitoring Device and Power Quality Device SICAM P850/P855 7KG85X Communication Manual (E50417-C1040-C482-B1), revision 2024-05, published free by Siemens at https://cache.industry.siemens.com/dl/files/152/109752152/att_1289026/v1/SICAM_P85x_7KG85_CM_US.pdf.
More Siemens Modbus register maps
- Sensor (room humidity / temperature)
Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)
Siemens QFA3150/MO room relative humidity and temperature sensor, basic documentation edition a (2021-01).
Also known as: QFA3150/MO, S55720-S535 - Sensor (duct humidity / temperature / CO2 / VOC)
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Siemens QFM9150/MO duct humidity/temperature sensor and QPM9152/MO duct air quality (CO2, VOC, humidity, temperature) sensor, basic documentation edition a (2022-12).
Also known as: QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585 - Protection relay
Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)
Reyrolle 7SR10 overcurrent / earth-fault relays, default Modbus RTU point list per Communication Protocols manual C53000-L7040-C002-7 (edition 11.2025, V01.00).
Also known as: 7SR10 Argus, Reyrolle 7SR10, 7SR1003, 7SR1004 - Protection relay
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Reyrolle 7SR11 (non-directional) and 7SR12 (directional) Argus overcurrent relays, default Modbus RTU point list in the 7SR11 & 7SR12 Complete Technical Manual (Chapter 4, Data Communications, 2015).
Also known as: 7SR11 Argus, 7SR12 Argus, Reyrolle 7SR11, Reyrolle 7SR12, 7SR120 - Energy meter
Siemens SENTRON PAC2200
SENTRON 7KM PAC2200 Modbus TCP and Modbus RTU variants (5 A and 65 A), per Equipment Manual 12/2022.
Also known as: 7KM PAC2200 - Power meter
Siemens SENTRON PAC3200
SENTRON PAC3200 (7KM2111/7KM2112), Ethernet port and optional PAC RS485 expansion module, per manual edition 02/2008.
Also known as: 7KM2112-0BA00-2AA0, 7KM2112-0BA00-3AA0, 7KM2111-1BA00-3AA0, 7KM PAC3200 - Circuit breaker trip unit (power meter)
Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
Siemens SENTRON 3WL air circuit breakers with a COM16 Modbus RTU communication module and, for voltage/power/energy values, the metering function (PLUS), per system manual A5E02126891-02.
Also known as: SENTRON WL, 3WL, 3WL COM16, COM16 - Power meter
Siemens SICAM P power meter (Modbus RTU/ASCII)
SICAM P (7KG7xxx) power meters with the Modbus serial interface, per manual E50417-B1076-C241-A5 (release 11.2012).
Also known as: 7KG7750, 7KG7751, 7KG7755, SICAM P50, SICAM P55, 7KG7610, 7KG7660 - Motor management and protection relay
Siemens SIMOCODE pro V Modbus RTU basic unit
SIMOCODE pro V Modbus RTU basic units, per Configuration Manual 04/2015 (A5E33498234002A/RS-AA/001).
Also known as: SIMOCODE pro V Modbus, SIMOCODE pro V Modbus RTU - Variable frequency drive
Siemens SINAMICS G120 / G120C (Modbus RTU)
SINAMICS G120 with an RS485 Control Unit (CU230P-2 HVAC/BT, CU240B-2, CU240E-2 / -2 F, CU250S-2), G120C USS/MB and G110M CU240M USS, firmware V4.7, per Fieldbuses function manual A5E34229197B AA. Not SINAMICS G120X, which has its own documentation.
Also known as: G120C USS/MB, CU230P-2 HVAC, CU230P-2 BT, CU240B-2, CU240E-2, CU240E-2 F, CU250S-2, G110M CU240M USS, G120P - Variable frequency drive
Siemens SINAMICS V20 inverter (Modbus RTU)
SINAMICS V20 basic inverters (1AC 230 V 6SL3210-5BB.. and 3AC 400 V 6SL3210-5BE..) using the built-in RS485 port with P2023 = 2 (Modbus), per operating instructions A5E34559884-006 (11/2016).
Also known as: V20, 6SL3210-5BB, 6SL3210-5BE - Sensor (flow transmitter)
Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module
SITRANS F C MASS 6000 Coriolis flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MASS 6000, SITRANS FC MASS 6000 - Sensor (flow transmitter)
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
SITRANS F M MAG 6000 / MAG 6000 I electromagnetic flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MAG 6000, MAG 6000 I, SITRANS FM MAG 6000 - EV charger
Siemens VersiCharge AC series wallbox (Modbus map)
VersiCharge AC series chargers with firmware V2.135 or later (per-register minimum firmware is given in the source).
Also known as: VersiCharge, VersiCharge AC
Other power & energy meters register maps
- Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Energy meter (thermal / BTU meter)
Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP)
Belimo Thermal Energy Meter DN 15...50 version 4 (22PE..-1U.., 22PF-..U..), interface description V4.2.0 edition 2025-11.
Also known as: 22PE-1U, 22PEM-1UC, 22PE..-1U.., 22PF, Belimo Thermal Energy Meter, Belimo TEM - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN (PFA, PFB and X models)
EM24-DIN three-phase energy analyzers, PFA/PFB (MID) and X models with the RS485 Modbus RTU port (IS option), protocol version 4 revision 0.
Also known as: EM24, EM24DIN, EM24DINAV93XISPFA, EM24DINAV93XISPFB, EM24DINAV93XISX, EM24DINAV53XISX, EM24DINAV23XISX, EM24 DIN AV9, EM24 DIN AV5 - Energy meter
Carlo Gavazzi EM530 / EM540 three-phase energy meters (RS485 Modbus)
EM530 (CT-connected) and EM540 (direct-connected) with the S1 RS485 port, X and MID (PFA/PFB/PFC) versions, protocol document version 1.3.
Also known as: EM530, EM540, EM530DINAV53XS1X, EM530DINAV53XS1PFA, EM530DINAV53XS1PFB, EM530DINAV53XS1PFC, EM540DINAV23XS1X, EM540DINAV23XS1PFA, EM540DINAV23XS1PFB, EM540DINAV23XS1PFC, EM500 series - Power meter (static reactive energy regulator)
Circutor Computer SMART III FAST
Circutor Computer SMART III FAST static reactive power regulators (6 and 12 stage), manual M021B01-03-21A.
Also known as: Computer SMART III FAST 6, Computer SMART III FAST 12
All power & energy meters Modbus register maps →
Source: SICAM Power Monitoring Device and Power Quality Device SICAM P850/P855 7KG85X Communication Manual · E50417-C1040-C482-B1 · rev. 2024-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.