- Home
- Modbus register maps
- Siemens
- SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
Circuit breaker trip unit (power meter) · Modbus register map
Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module Modbus register map
Updated 19 November 2026
SENTRON WL breakers talk Modbus RTU through the COM16 module. Data is grouped in register blocks: the high byte of the register number is the block (data set) number, e.g. block 94 at 0x5E01 holds the live measured values. This map covers the 16-bit and 32-bit measured values of block 94, the min/max blocks 72-76, the counters of block 91 and a few overview values of block 51.
This page lists 100 Modbus registers for the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.
- Manufacturer
- Siemens
- Model
- SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
- Equipment type
- Circuit breaker trip unit (power meter)
- Registers
- 100 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- 126
- Default serial
- 19200 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- SENTRON WL, 3WL, 3WL COM16, COM16
Integration notes: Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
Read the live values of block 94 with function 03 at the printed number minus 1: phase currents L1-L3 are printed 0x5E06-0x5E08 (wire 0x5E05-0x5E07), total active power 0x5E16 and frequency 0x5E36. Min/max values sit in blocks 72-76 and switching/trip counters in block 91.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 24069 | Current in phase L1 | UINT16 | Phase L1 current | Read |
| HR 24072 | Mean current value over the three phases | UINT16 | Average current | Read |
| HR 24082 | Mean value of phase-to-phase voltage | UINT16 | Average L-L voltage | Read |
| HR 24085 | Total active power | INT16 | Total active power | Read |
| HR 24113 | Mean value of the power factor | INT16 | Mean power factor | Read |
| HR 24117 | Frequency | UINT16 | Frequency | Read |
| HR 24105 | Active energy in normal direction | UINT32 ABCD | Active energy, MWh | Read |
Enable Modbus control & writes
Modbus runs through the COM16 module. Its address, baud rate and parity are in block 160 (printed 0xA003 high byte for the address, 0xA019 for baud rate and parity). Without a bridge on the COM16 WriteEnable input, switching, trip reset, parameter changes and counter resets are blocked; setting the system time and resetting min/max values are still allowed.
Byte order & addressing
- Register numbers are block-based: high byte = block number, low byte = 1-based register in the block.
- Several registers pack two 8-bit values; read the whole word and split it.
Network setup
- Factory settings: address 126, 19200 baud, no parity; the module also runs an automatic baud search at start-up.
- Change the Modbus address, baud rate and parity in block 160 if needed.
Watch out for
- Values from the metering function read as unavailable on breakers without it; check the property bytes.
Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 13148doc 13149 (0x335D) | Mean value of the power factor | Data point 168; source: Meter. fct.. | INT16 | × 0.001 | Read | |||
| HR | 13149doc 13150 (0x335E) | Current of phase with maximum load | Data point 374; source: ETU. | UINT16 | A | Read | |||
| HR | 13150doc 13151 (0x335F) | Time until presumed overload trip | Data point 379; source: ETU. | UINT16 | s | Read | |||
| HR | 13151doc 13152 (0x3360) | Current in neutral conductor | Data point 375; source: ETU. | UINT16 | A | Read | |||
| HR | 13152doc 13153 (0x3361) | Current which flows to ground | Data point 376; source: ETU. | UINT16 | A | Read | |||
| HR | 13158doc 13159 (0x3367) | Overload parameter IR parameter set A (PS A) | Data point 333; source: ETU. | UINT16 | Read | ||||
| HR | 13159doc 13160 (0x3368) | Overload parameter IR parameter set B (PS B) | Data point 349; source: ETU. | UINT16 | Read | ||||
| HR | 13160doc 13161 (0x3369) | Rating plug | Data point 377; source: ETU. | UINT16 | Read | ||||
| HR | 18432doc 18433 (0x4801) | Minimum current in phase 1 | Stored min/max value (data point 384). | UINT16 | A | Read | |||
| HR | 18433doc 18434 (0x4802) | Maximum current in phase 1 | Stored min/max value (data point 385). | UINT16 | A | Read | |||
| HR | 18434doc 18435 (0x4803) | Minimum current in phase 2 | Stored min/max value (data point 386). | UINT16 | A | Read | |||
| HR | 18435doc 18436 (0x4804) | Maximum current in phase 2 | Stored min/max value (data point 387). | UINT16 | A | Read | |||
| HR | 18436doc 18437 (0x4805) | Minimum current in phase 3 | Stored min/max value (data point 388). | UINT16 | A | Read | |||
| HR | 18437doc 18438 (0x4806) | Maximum current in phase 3 | Stored min/max value (data point 389). | UINT16 | A | Read | |||
| HR | 18438doc 18439 (0x4807) | Minimum current in neutral conductor | Stored min/max value (data point 390). | UINT16 | A | Read | |||
| HR | 18439doc 18440 (0x4808) | Maximum current in neutral conductor | Stored min/max value (data point 391). | UINT16 | A | Read | |||
| HR | 18440doc 18441 (0x4809) | Minimum current which flows to ground | Stored min/max value (data point 392). | UINT16 | A | Read | |||
| HR | 18441doc 18442 (0x480A) | Maximum current which flows to ground | Stored min/max value (data point 393). | UINT16 | A | Read | |||
| HR | 18442doc 18443 (0x480B) | Minimum mean value over the three phases | Stored min/max value (data point 394). | UINT16 | A | Read | |||
| HR | 18443doc 18444 (0x480C) | Maximum mean value over the three phases | Stored min/max value (data point 395). | UINT16 | A | Read | |||
| HR | 18444doc 18445 (0x480D) | Minimum long-time mean value for current | Stored min/max value (data point 244). | UINT16 | A | Read | |||
| HR | 18445doc 18446 (0x480E) | Maximum long-time mean value for current | Stored min/max value (data point 245). | UINT16 | A | Read | |||
| HR | 18688doc 18689 (0x4901) | Minimum phase-to-phase voltage between phase L1 and L2 | Stored min/max value (data point 205). | UINT16 | V | Read | |||
| HR | 18689doc 18690 (0x4902) | Maximum phase-to-phase voltage between phase L1 and L2 | Stored min/max value (data point 206). | UINT16 | V | Read | |||
| HR | 18690doc 18691 (0x4903) | Minimum phase-to-phase voltage between phase L2 and L3 | Stored min/max value (data point 207). | UINT16 | V | Read | |||
| HR | 18691doc 18692 (0x4904) | Maximum phase-to-phase voltage between phase L2 and L3 | Stored min/max value (data point 208). | UINT16 | V | Read | |||
| HR | 18692doc 18693 (0x4905) | Minimum phase-to-phase voltage between phase L3 and L1 | Stored min/max value (data point 209). | UINT16 | V | Read | |||
| HR | 18693doc 18694 (0x4906) | Maximum phase-to-phase voltage between phase L3 and L1 | Stored min/max value (data point 210). | UINT16 | V | Read | |||
| HR | 18694doc 18695 (0x4907) | Minimum of the neutral point voltage phase L1 | Stored min/max value (data point 211). | UINT16 | V | Read | |||
| HR | 18695doc 18696 (0x4908) | Maximum of the neutral point voltage phase L1 | Stored min/max value (data point 212). | UINT16 | V | Read | |||
| HR | 18696doc 18697 (0x4909) | Minimum of the neutral point voltage phase L2 | Stored min/max value (data point 213). | UINT16 | V | Read | |||
| HR | 18697doc 18698 (0x490A) | Maximum of the neutral point voltage phase L2 | Stored min/max value (data point 214). | UINT16 | V | Read | |||
| HR | 18698doc 18699 (0x490B) | Minimum of the neutral point voltage phase L3 | Stored min/max value (data point 215). | UINT16 | V | Read | |||
| HR | 18699doc 18700 (0x490C) | Maximum of the neutral point voltage phase L3 | Stored min/max value (data point 216). | UINT16 | V | Read | |||
| HR | 18944doc 18945 (0x4A01) | Minimum of the mean value of the power factor | Stored min/max value (data point 242). | INT16 | × 0.001 | Read | |||
| HR | 18945doc 18946 (0x4A02) | Maximum of the mean value of the power factor | Stored min/max value (data point 243). | INT16 | × 0.001 | Read | |||
| HR | 18946doc 18947 (0x4A03) | Minimum of the mean value of the apparent power | Stored min/max value (data point 246). | UINT16 | kVA | Read | |||
| HR | 18947doc 18948 (0x4A04) | Maximum of the mean value of the apparent power | Stored min/max value (data point 247). | UINT16 | kVA | Read | |||
| HR | 18948doc 18949 (0x4A05) | Minimum of the mean value of the active power | Stored min/max value (data point 250). | INT16 | kW | Read | |||
| HR | 18949doc 18950 (0x4A06) | Maximum of the mean value of the active power | Stored min/max value (data point 251). | INT16 | kW | Read | |||
| HR | 18950doc 18951 (0x4A07) | Minimum of the mean value of the reactive power | Stored min/max value (data point 248). | INT16 | kvar | Read | |||
| HR | 18951doc 18952 (0x4A08) | Maximum of the mean value of the reactive power | Stored min/max value (data point 249). | INT16 | kvar | Read | |||
| HR | 19456doc 19457 (0x4C01) | Maximum frequency | Stored min/max value (data point 253). | UINT16 | × 0.01 | Hz | Read | ||
| HR | 19457doc 19458 (0x4C02) | Minimum frequency | Stored min/max value (data point 252). | UINT16 | × 0.01 | Hz | Read | ||
| HR | 23296doc 23297 (0x5B01) | Number of switching operations under load | Data point 80; source: COM16. | UINT16 | Read | ||||
| HR | 23297doc 23298 (0x5B02) | Number of switching operations caused by trips | Data point 81; source: COM16. | UINT16 | Read | ||||
| HR | 23298doc 23299 (0x5B03) | Switching cycle counter (for switching cycle on/off) | Data point 82; source: COM16. | UINT16 | Read | ||||
| HR | 23299doc 23300 (0x5B04) | Runtime meter (when On + current > 0) | Data point 83; counts while closed with current flowing. Unit not stated. | UINT32 | ABCD | Read | |||
| HR | 23305doc 23306 (0x5B0A) | Number of short-circuit trips (SI) | Data point 104; source: ETU. | UINT16 | Read | ||||
| HR | 23306doc 23307 (0x5B0B) | Number of overload trips (L) | Data point 105; source: ETU. | UINT16 | Read | ||||
| HR | 23307doc 23308 (0x5B0C) | Number of ground-fault tripping operations (G) | Data point 106; source: ETU. | UINT16 | Read | ||||
| HR | 23569doc 23570 (0x5C12) | Current at the moment of shutdown | Data point 403; source: ETU. | UINT16 | × 10 | A | Read | ||
| HR | 24065doc 24066 (0x5E02) | Long-time mean value of 3-phase current | Data point 193; source: Meter. fct.. | UINT16 | A | Read | |||
| HR | 24066doc 24067 (0x5E03) | Long-time mean value of current L1 | Data point 194; source: Meter. fct.. | UINT16 | A | Read | |||
| HR | 24067doc 24068 (0x5E04) | Long-time mean value of current L2 | Data point 195; source: Meter. fct.. | UINT16 | A | Read | |||
| HR | 24068doc 24069 (0x5E05) | Long-time mean value of current L3 | Data point 196; source: Meter. fct.. | UINT16 | A | Read | |||
| HR | 24069doc 24070 (0x5E06) | Current in phase L1 | Data point 380; source: ETU. | UINT16 | A | Read | |||
| HR | 24070doc 24071 (0x5E07) | Current in phase L2 | Data point 381; source: ETU. | UINT16 | A | Read | |||
| HR | 24071doc 24072 (0x5E08) | Current in phase L3 | Data point 382; source: ETU. | UINT16 | A | Read | |||
| HR | 24072doc 24073 (0x5E09) | Mean current value over the three phases | Data point 383; source: ETU. | UINT16 | A | Read | |||
| HR | 24073doc 24074 (0x5E0A) | Current in neutral conductor | Data point 375; source: ETU. | UINT16 | A | Read | |||
| HR | 24074doc 24075 (0x5E0B) | Current which flows to ground | Data point 376; source: ETU. | UINT16 | A | Read | |||
| HR | 24076doc 24077 (0x5E0D) | Phase-to-phase voltage between phase L1 and L2 | Data point 197; source: Meter. fct.. | UINT16 | V | Read | |||
| HR | 24077doc 24078 (0x5E0E) | Phase-to-phase voltage between phase L2 and L3 | Data point 198; source: Meter. fct.. | UINT16 | V | Read | |||
| HR | 24078doc 24079 (0x5E0F) | Phase-to-phase voltage between phase L3 and L1 | Data point 199; source: Meter. fct.. | UINT16 | V | Read | |||
| HR | 24079doc 24080 (0x5E10) | Neutral point voltage phase L1 | Data point 200; source: Meter. fct.. | UINT16 | V | Read | |||
| HR | 24080doc 24081 (0x5E11) | Neutral point voltage phase L2 | Data point 201; source: Meter. fct.. | UINT16 | V | Read | |||
| HR | 24081doc 24082 (0x5E12) | Neutral point voltage phase L3 | Data point 202; source: Meter. fct.. | UINT16 | V | Read | |||
| HR | 24082doc 24083 (0x5E13) | Mean value of phase-to-phase voltage | Data point 203; source: Meter. fct.. | UINT16 | V | Read | |||
| HR | 24083doc 24084 (0x5E14) | Mean value of neutral-point star voltage | Data point 204; source: Meter. fct.. | UINT16 | V | Read | |||
| HR | 24084doc 24085 (0x5E15) | Total apparent power | Data point 217; source: Meter. fct.. | UINT16 | kVA | Read | |||
| HR | 24085doc 24086 (0x5E16) | Total active power | Data point 221; source: Meter. fct.. | INT16 | kW | Read | |||
| HR | 24086doc 24087 (0x5E17) | Active power in phase L1 | Data point 222; source: Meter. fct.. | INT16 | kW | Read | |||
| HR | 24087doc 24088 (0x5E18) | Active power in phase L2 | Data point 223; source: Meter. fct.. | INT16 | kW | Read | |||
| HR | 24088doc 24089 (0x5E19) | Active power in phase L3 | Data point 224; source: Meter. fct.. | INT16 | kW | Read | |||
| HR | 24089doc 24090 (0x5E1A) | Total reactive power | Data point 225; source: Meter. fct.. | INT16 | kvar | Read | |||
| HR | 24090doc 24091 (0x5E1B) | Long-time mean value of 3-phase active power | Data point 229; source: Meter. fct.. | INT16 | kW | Read | |||
| HR | 24091doc 24092 (0x5E1C) | Long-time mean value of active power in phase L1 | Data point 230; source: Meter. fct.. | INT16 | kW | Read | |||
| HR | 24092doc 24093 (0x5E1D) | Long-time mean value of active power in phase L2 | Data point 231; source: Meter. fct.. | INT16 | kW | Read | |||
| HR | 24093doc 24094 (0x5E1E) | Long-time mean value of active power in phase L3 | Data point 232; source: Meter. fct.. | INT16 | kW | Read | |||
| HR | 24094doc 24095 (0x5E1F) | Long-time mean value of 3-phase apparent power | Data point 233; source: Meter. fct.. | UINT16 | kVA | Read | |||
| HR | 24095doc 24096 (0x5E20) | Apparent power in phase L1 | Data point 218; source: Meter. fct.. | UINT16 | kVA | Read | |||
| HR | 24096doc 24097 (0x5E21) | Apparent power in phase L2 | Data point 219; source: Meter. fct.. | UINT16 | kVA | Read | |||
| HR | 24097doc 24098 (0x5E22) | Apparent power in phase L3 | Data point 220; source: Meter. fct.. | UINT16 | kVA | Read | |||
| HR | 24098doc 24099 (0x5E23) | Long-time mean value of apparent power in phase L1 | Data point 234; source: Meter. fct.. | UINT16 | kVA | Read | |||
| HR | 24099doc 24100 (0x5E24) | Long-time mean value of apparent power in phase L2 | Data point 235; source: Meter. fct.. | UINT16 | kVA | Read | |||
| HR | 24100doc 24101 (0x5E25) | Long-time mean value of apparent power in phase L3 | Data point 236; source: Meter. fct.. | UINT16 | kVA | Read | |||
| HR | 24101doc 24102 (0x5E26) | Long-time mean value of 3-phase reactive power | Data point 237; source: Meter. fct.. | INT16 | kvar | Read | |||
| HR | 24102doc 24103 (0x5E27) | Reactive power in phase L1 | Data point 226; source: Meter. fct.. | INT16 | kvar | Read | |||
| HR | 24103doc 24104 (0x5E28) | Reactive power in phase L2 | Data point 227; source: Meter. fct.. | INT16 | kvar | Read | |||
| HR | 24104doc 24105 (0x5E29) | Reactive power in phase L3 | Data point 228; source: Meter. fct.. | INT16 | kvar | Read | |||
| HR | 24105doc 24106 (0x5E2A) | Active energy in normal direction | Data point 238; source: Meter. fct.. | UINT32 | ABCD | MWh | Read | ||
| HR | 24107doc 24108 (0x5E2C) | Active energy in reverse direction | Data point 239; source: Meter. fct.. | UINT32 | ABCD | MWh | Read | ||
| HR | 24109doc 24110 (0x5E2E) | Reactive energy in normal direction | Data point 240; source: Meter. fct.. | UINT32 | ABCD | Mvarh | Read | ||
| HR | 24111doc 24112 (0x5E30) | Reactive energy in reverse direction | Data point 241; source: Meter. fct.. | UINT32 | ABCD | Mvarh | Read | ||
| HR | 24113doc 24114 (0x5E32) | Mean value of the power factor | Data point 168; source: Meter. fct.. | INT16 | × 0.001 | Read | |||
| HR | 24114doc 24115 (0x5E33) | Power factor in phase L1 | Data point 169; source: Meter. fct.. | INT16 | × 0.001 | Read | |||
| HR | 24115doc 24116 (0x5E34) | Power factor in phase L2 | Data point 170; source: Meter. fct.. | INT16 | × 0.001 | Read | |||
| HR | 24116doc 24117 (0x5E35) | Power factor in phase L3 | Data point 171; source: Meter. fct.. | INT16 | × 0.001 | Read | |||
| HR | 24117doc 24118 (0x5E36) | Frequency | Data point 262; source: Meter. fct.. | UINT16 | × 0.01 | Hz | Read |
Notes on this map
- Scaling in the tables is a power-of-ten exponent applied at the master (e.g. frequency -2 means x 0.01); it is converted to a plain multiplier here.
- The data-format chapter says all Modbus RTU data is sent in Motorola (big-endian) format; 32-bit 'unsigned long' values (energies, runtime meter) are mapped high word first.
- Units follow the manual's default unit table (A, V, kW, kVA, kvar, Hz, s); energies carry the unit printed in their name.
- Left out: byte-packed values (one register holding two 8-bit items, e.g. unbalance %, THD, form/peak factor, temperatures), 64-bit time stamps, logs, harmonics, format-coded status words and all property bytes.
- Voltage, power, energy, power factor and frequency need the breaker's metering function or metering function PLUS; currents come from the electronic trip unit (ETU).
- The value buffer area is read with function 03 and written with 16; basic type data, control bytes and status bits use functions 04, 01/05/15 and 02.
- SENTRON 3VL moulded-case breakers use different data areas (section 8.8) and are not covered by this map.
- The kWh/kvarh energy registers of block 94 (0x5E3B-0x5E41) have no scaling entry in the table and are left out; the MWh/Mvarh versions are included.
- Byte order inside a register is high byte first in the function 03/04 examples; the function 16 system-time example labels its bytes differently, but that only concerns byte-packed values, which are left out here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
What Modbus registers does the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module have?
This map lists 100 registers: 100 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register-block tables print 1-based register numbers in decimal and hex, where the high byte is the block number (block 94 starts at 0x5E01). The manual's write example for block 68 sends start address 0x4402 for the system time, which the block 68 table lists at 0x4403, so the wire address is the printed number minus 1.
What byte order does the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module?
Start with HR 24069 Current in phase L1 (Phase L1 current); HR 24072 Mean current value over the three phases (Average current); HR 24082 Mean value of phase-to-phase voltage (Average L-L voltage); HR 24085 Total active power (Total active power); HR 24113 Mean value of the power factor (Mean power factor); HR 24117 Frequency (Frequency); HR 24105 Active energy in normal direction (Active energy, MWh).
How do I enable Modbus control of the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module?
Modbus runs through the COM16 module. Its address, baud rate and parity are in block 160 (printed 0xA003 high byte for the address, 0xA019 for baud rate and parity). Without a bridge on the COM16 WriteEnable input, switching, trip reset, parameter changes and counter resets are blocked; setting the system time and resetting min/max values are still allowed.
Where is the official Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module Modbus documentation?
The source is SENTRON 3WL/3VL circuit breakers with communication capability - Modbus, System Manual (A5E02126891-02), revision 2011-07, published free by Siemens at https://assets.new.siemens.com/siemens/assets/api/uuid:2216d539-488d-4320-b10a-d79f984e4a75/manual-modbus-sentron-3wl-3vl-en.pdf.
More Siemens Modbus register maps
- Sensor (room humidity / temperature)
Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)
Siemens QFA3150/MO room relative humidity and temperature sensor, basic documentation edition a (2021-01).
Also known as: QFA3150/MO, S55720-S535 - Sensor (duct humidity / temperature / CO2 / VOC)
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Siemens QFM9150/MO duct humidity/temperature sensor and QPM9152/MO duct air quality (CO2, VOC, humidity, temperature) sensor, basic documentation edition a (2022-12).
Also known as: QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585 - Protection relay
Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)
Reyrolle 7SR10 overcurrent / earth-fault relays, default Modbus RTU point list per Communication Protocols manual C53000-L7040-C002-7 (edition 11.2025, V01.00).
Also known as: 7SR10 Argus, Reyrolle 7SR10, 7SR1003, 7SR1004 - Protection relay
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Reyrolle 7SR11 (non-directional) and 7SR12 (directional) Argus overcurrent relays, default Modbus RTU point list in the 7SR11 & 7SR12 Complete Technical Manual (Chapter 4, Data Communications, 2015).
Also known as: 7SR11 Argus, 7SR12 Argus, Reyrolle 7SR11, Reyrolle 7SR12, 7SR120 - Energy meter
Siemens SENTRON PAC2200
SENTRON 7KM PAC2200 Modbus TCP and Modbus RTU variants (5 A and 65 A), per Equipment Manual 12/2022.
Also known as: 7KM PAC2200 - Power meter
Siemens SENTRON PAC3200
SENTRON PAC3200 (7KM2111/7KM2112), Ethernet port and optional PAC RS485 expansion module, per manual edition 02/2008.
Also known as: 7KM2112-0BA00-2AA0, 7KM2112-0BA00-3AA0, 7KM2111-1BA00-3AA0, 7KM PAC3200 - Power meter
Siemens SICAM P power meter (Modbus RTU/ASCII)
SICAM P (7KG7xxx) power meters with the Modbus serial interface, per manual E50417-B1076-C241-A5 (release 11.2012).
Also known as: 7KG7750, 7KG7751, 7KG7755, SICAM P50, SICAM P55, 7KG7610, 7KG7660 - Power meter (power quality)
Siemens SICAM P850 / P855 power monitoring and PQ device
SICAM P850 / P855 (7KG85x) with Modbus TCP or Modbus RTU, firmware V3.11, per communication manual E50417-C1040-C482-B1 (05.2024).
Also known as: 7KG85, 7KG85X, SICAM P850, SICAM P855 - Motor management and protection relay
Siemens SIMOCODE pro V Modbus RTU basic unit
SIMOCODE pro V Modbus RTU basic units, per Configuration Manual 04/2015 (A5E33498234002A/RS-AA/001).
Also known as: SIMOCODE pro V Modbus, SIMOCODE pro V Modbus RTU - Variable frequency drive
Siemens SINAMICS G120 / G120C (Modbus RTU)
SINAMICS G120 with an RS485 Control Unit (CU230P-2 HVAC/BT, CU240B-2, CU240E-2 / -2 F, CU250S-2), G120C USS/MB and G110M CU240M USS, firmware V4.7, per Fieldbuses function manual A5E34229197B AA. Not SINAMICS G120X, which has its own documentation.
Also known as: G120C USS/MB, CU230P-2 HVAC, CU230P-2 BT, CU240B-2, CU240E-2, CU240E-2 F, CU250S-2, G110M CU240M USS, G120P - Variable frequency drive
Siemens SINAMICS V20 inverter (Modbus RTU)
SINAMICS V20 basic inverters (1AC 230 V 6SL3210-5BB.. and 3AC 400 V 6SL3210-5BE..) using the built-in RS485 port with P2023 = 2 (Modbus), per operating instructions A5E34559884-006 (11/2016).
Also known as: V20, 6SL3210-5BB, 6SL3210-5BE - Sensor (flow transmitter)
Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module
SITRANS F C MASS 6000 Coriolis flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MASS 6000, SITRANS FC MASS 6000 - Sensor (flow transmitter)
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
SITRANS F M MAG 6000 / MAG 6000 I electromagnetic flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MAG 6000, MAG 6000 I, SITRANS FM MAG 6000 - EV charger
Siemens VersiCharge AC series wallbox (Modbus map)
VersiCharge AC series chargers with firmware V2.135 or later (per-register minimum firmware is given in the source).
Also known as: VersiCharge, VersiCharge AC
Other power & energy meters register maps
- Power meter (panel meter)
Trumeter APM Power meter (APM-PWR) Modbus map
Trumeter APM-PWR panel power meters with Modbus, per the Trumeter knowledge-base register map.
Also known as: APM-PWR, APM Power, Trumeter APM Power meter - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Power meter (metered/switched rack PDU)
Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP)
Bachmann BlueNet BN PRO rack PDUs with Modbus TCP, protocol v1.00 REV00 register list.
Also known as: BlueNet BN PRO, BN PRO PDU, BlueNet 2 BN PRO - Energy meter
Carlo Gavazzi EM100 / ET100 series (EM111, EM112, ET112)
Single-phase EM111, EM112 energy meters and ET112 bidirectional meter with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 14.
Also known as: EM111, EM112, ET112, EM110, EM111-DIN, EM112-DIN, ET112-DIN, EM111DINAV81XS1X, EM112DINAV01XS1X, ET112DINAV01XS1X - Energy meter
Carlo Gavazzi EM300 / ET300 series (EM330, EM340, ET330, ET340)
EM330, EM331, EM340, EM341 energy meters and ET330/ET340 bidirectional meters with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 17.
Also known as: EM330, EM340, ET330, ET340, EM331, EM341, EM330-DIN, EM340-DIN, ET340-DIN, EM340DINAV23XS1X, EM340DINAV23XS1PFA, EM340DINAV23XS1PFB - Power meter (power analyzer)
Carlo Gavazzi WM50 power analyzer with TCD branch channels
WM50 base unit (firmware X0, i.e. all A and B versions) with an MC485232 or MCETH communication module, plus TCD branch channels, per communication protocol user version rev. 1.0.0 (2017-09-27).
Also known as: WM50, WM50AV5, WM50-96, WM50 AV5
All power & energy meters Modbus register maps →
Source: SENTRON 3WL/3VL circuit breakers with communication capability - Modbus, System Manual · A5E02126891-02 · rev. 2011-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.