Circuit breaker trip unit (power meter) · Modbus register map

Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module Modbus register map

Updated 19 November 2026

Short answer

SENTRON WL breakers talk Modbus RTU through the COM16 module. Data is grouped in register blocks: the high byte of the register number is the block (data set) number, e.g. block 94 at 0x5E01 holds the live measured values. This map covers the 16-bit and 32-bit measured values of block 94, the min/max blocks 72-76, the counters of block 91 and a few overview values of block 51.

This page lists 100 Modbus registers for the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.

Manufacturer
Siemens
Model
SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
Equipment type
Circuit breaker trip unit (power meter)
Registers
100 (0 writable)
Transport
Modbus RTU
Default unit ID
126
Default serial
19200 baud, 8N1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
SENTRON WL, 3WL, 3WL COM16, COM16
Source document
SENTRON 3WL/3VL circuit breakers with communication capability - Modbus, System Manual · A5E02126891-02 · rev. 2011-07
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module

Integration in brief

Read the live values of block 94 with function 03 at the printed number minus 1: phase currents L1-L3 are printed 0x5E06-0x5E08 (wire 0x5E05-0x5E07), total active power 0x5E16 and frequency 0x5E36. Min/max values sit in blocks 72-76 and switching/trip counters in block 91.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 24069Current in phase L1UINT16Phase L1 currentRead
HR 24072Mean current value over the three phasesUINT16Average currentRead
HR 24082Mean value of phase-to-phase voltageUINT16Average L-L voltageRead
HR 24085Total active powerINT16Total active powerRead
HR 24113Mean value of the power factorINT16Mean power factorRead
HR 24117FrequencyUINT16FrequencyRead
HR 24105Active energy in normal directionUINT32 ABCDActive energy, MWhRead

Enable Modbus control & writes

Modbus runs through the COM16 module. Its address, baud rate and parity are in block 160 (printed 0xA003 high byte for the address, 0xA019 for baud rate and parity). Without a bridge on the COM16 WriteEnable input, switching, trip reset, parameter changes and counter resets are blocked; setting the system time and resetting min/max values are still allowed.

Byte order & addressing

Network setup

Watch out for

Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

100 of 100 shown
Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR13148doc 13149 (0x335D)Mean value of the power factorData point 168; source: Meter. fct..INT16× 0.001Read
HR13149doc 13150 (0x335E)Current of phase with maximum loadData point 374; source: ETU.UINT16ARead
HR13150doc 13151 (0x335F)Time until presumed overload tripData point 379; source: ETU.UINT16sRead
HR13151doc 13152 (0x3360)Current in neutral conductorData point 375; source: ETU.UINT16ARead
HR13152doc 13153 (0x3361)Current which flows to groundData point 376; source: ETU.UINT16ARead
HR13158doc 13159 (0x3367)Overload parameter IR parameter set A (PS A)Data point 333; source: ETU.UINT16Read
HR13159doc 13160 (0x3368)Overload parameter IR parameter set B (PS B)Data point 349; source: ETU.UINT16Read
HR13160doc 13161 (0x3369)Rating plugData point 377; source: ETU.UINT16Read
HR18432doc 18433 (0x4801)Minimum current in phase 1Stored min/max value (data point 384).UINT16ARead
HR18433doc 18434 (0x4802)Maximum current in phase 1Stored min/max value (data point 385).UINT16ARead
HR18434doc 18435 (0x4803)Minimum current in phase 2Stored min/max value (data point 386).UINT16ARead
HR18435doc 18436 (0x4804)Maximum current in phase 2Stored min/max value (data point 387).UINT16ARead
HR18436doc 18437 (0x4805)Minimum current in phase 3Stored min/max value (data point 388).UINT16ARead
HR18437doc 18438 (0x4806)Maximum current in phase 3Stored min/max value (data point 389).UINT16ARead
HR18438doc 18439 (0x4807)Minimum current in neutral conductorStored min/max value (data point 390).UINT16ARead
HR18439doc 18440 (0x4808)Maximum current in neutral conductorStored min/max value (data point 391).UINT16ARead
HR18440doc 18441 (0x4809)Minimum current which flows to groundStored min/max value (data point 392).UINT16ARead
HR18441doc 18442 (0x480A)Maximum current which flows to groundStored min/max value (data point 393).UINT16ARead
HR18442doc 18443 (0x480B)Minimum mean value over the three phasesStored min/max value (data point 394).UINT16ARead
HR18443doc 18444 (0x480C)Maximum mean value over the three phasesStored min/max value (data point 395).UINT16ARead
HR18444doc 18445 (0x480D)Minimum long-time mean value for currentStored min/max value (data point 244).UINT16ARead
HR18445doc 18446 (0x480E)Maximum long-time mean value for currentStored min/max value (data point 245).UINT16ARead
HR18688doc 18689 (0x4901)Minimum phase-to-phase voltage between phase L1 and L2Stored min/max value (data point 205).UINT16VRead
HR18689doc 18690 (0x4902)Maximum phase-to-phase voltage between phase L1 and L2Stored min/max value (data point 206).UINT16VRead
HR18690doc 18691 (0x4903)Minimum phase-to-phase voltage between phase L2 and L3Stored min/max value (data point 207).UINT16VRead
HR18691doc 18692 (0x4904)Maximum phase-to-phase voltage between phase L2 and L3Stored min/max value (data point 208).UINT16VRead
HR18692doc 18693 (0x4905)Minimum phase-to-phase voltage between phase L3 and L1Stored min/max value (data point 209).UINT16VRead
HR18693doc 18694 (0x4906)Maximum phase-to-phase voltage between phase L3 and L1Stored min/max value (data point 210).UINT16VRead
HR18694doc 18695 (0x4907)Minimum of the neutral point voltage phase L1Stored min/max value (data point 211).UINT16VRead
HR18695doc 18696 (0x4908)Maximum of the neutral point voltage phase L1Stored min/max value (data point 212).UINT16VRead
HR18696doc 18697 (0x4909)Minimum of the neutral point voltage phase L2Stored min/max value (data point 213).UINT16VRead
HR18697doc 18698 (0x490A)Maximum of the neutral point voltage phase L2Stored min/max value (data point 214).UINT16VRead
HR18698doc 18699 (0x490B)Minimum of the neutral point voltage phase L3Stored min/max value (data point 215).UINT16VRead
HR18699doc 18700 (0x490C)Maximum of the neutral point voltage phase L3Stored min/max value (data point 216).UINT16VRead
HR18944doc 18945 (0x4A01)Minimum of the mean value of the power factorStored min/max value (data point 242).INT16× 0.001Read
HR18945doc 18946 (0x4A02)Maximum of the mean value of the power factorStored min/max value (data point 243).INT16× 0.001Read
HR18946doc 18947 (0x4A03)Minimum of the mean value of the apparent powerStored min/max value (data point 246).UINT16kVARead
HR18947doc 18948 (0x4A04)Maximum of the mean value of the apparent powerStored min/max value (data point 247).UINT16kVARead
HR18948doc 18949 (0x4A05)Minimum of the mean value of the active powerStored min/max value (data point 250).INT16kWRead
HR18949doc 18950 (0x4A06)Maximum of the mean value of the active powerStored min/max value (data point 251).INT16kWRead
HR18950doc 18951 (0x4A07)Minimum of the mean value of the reactive powerStored min/max value (data point 248).INT16kvarRead
HR18951doc 18952 (0x4A08)Maximum of the mean value of the reactive powerStored min/max value (data point 249).INT16kvarRead
HR19456doc 19457 (0x4C01)Maximum frequencyStored min/max value (data point 253).UINT16× 0.01HzRead
HR19457doc 19458 (0x4C02)Minimum frequencyStored min/max value (data point 252).UINT16× 0.01HzRead
HR23296doc 23297 (0x5B01)Number of switching operations under loadData point 80; source: COM16.UINT16Read
HR23297doc 23298 (0x5B02)Number of switching operations caused by tripsData point 81; source: COM16.UINT16Read
HR23298doc 23299 (0x5B03)Switching cycle counter (for switching cycle on/off)Data point 82; source: COM16.UINT16Read
HR23299doc 23300 (0x5B04)Runtime meter (when On + current > 0)Data point 83; counts while closed with current flowing. Unit not stated.UINT32ABCDRead
HR23305doc 23306 (0x5B0A)Number of short-circuit trips (SI)Data point 104; source: ETU.UINT16Read
HR23306doc 23307 (0x5B0B)Number of overload trips (L)Data point 105; source: ETU.UINT16Read
HR23307doc 23308 (0x5B0C)Number of ground-fault tripping operations (G)Data point 106; source: ETU.UINT16Read
HR23569doc 23570 (0x5C12)Current at the moment of shutdownData point 403; source: ETU.UINT16× 10ARead
HR24065doc 24066 (0x5E02)Long-time mean value of 3-phase currentData point 193; source: Meter. fct..UINT16ARead
HR24066doc 24067 (0x5E03)Long-time mean value of current L1Data point 194; source: Meter. fct..UINT16ARead
HR24067doc 24068 (0x5E04)Long-time mean value of current L2Data point 195; source: Meter. fct..UINT16ARead
HR24068doc 24069 (0x5E05)Long-time mean value of current L3Data point 196; source: Meter. fct..UINT16ARead
HR24069doc 24070 (0x5E06)Current in phase L1Data point 380; source: ETU.UINT16ARead
HR24070doc 24071 (0x5E07)Current in phase L2Data point 381; source: ETU.UINT16ARead
HR24071doc 24072 (0x5E08)Current in phase L3Data point 382; source: ETU.UINT16ARead
HR24072doc 24073 (0x5E09)Mean current value over the three phasesData point 383; source: ETU.UINT16ARead
HR24073doc 24074 (0x5E0A)Current in neutral conductorData point 375; source: ETU.UINT16ARead
HR24074doc 24075 (0x5E0B)Current which flows to groundData point 376; source: ETU.UINT16ARead
HR24076doc 24077 (0x5E0D)Phase-to-phase voltage between phase L1 and L2Data point 197; source: Meter. fct..UINT16VRead
HR24077doc 24078 (0x5E0E)Phase-to-phase voltage between phase L2 and L3Data point 198; source: Meter. fct..UINT16VRead
HR24078doc 24079 (0x5E0F)Phase-to-phase voltage between phase L3 and L1Data point 199; source: Meter. fct..UINT16VRead
HR24079doc 24080 (0x5E10)Neutral point voltage phase L1Data point 200; source: Meter. fct..UINT16VRead
HR24080doc 24081 (0x5E11)Neutral point voltage phase L2Data point 201; source: Meter. fct..UINT16VRead
HR24081doc 24082 (0x5E12)Neutral point voltage phase L3Data point 202; source: Meter. fct..UINT16VRead
HR24082doc 24083 (0x5E13)Mean value of phase-to-phase voltageData point 203; source: Meter. fct..UINT16VRead
HR24083doc 24084 (0x5E14)Mean value of neutral-point star voltageData point 204; source: Meter. fct..UINT16VRead
HR24084doc 24085 (0x5E15)Total apparent powerData point 217; source: Meter. fct..UINT16kVARead
HR24085doc 24086 (0x5E16)Total active powerData point 221; source: Meter. fct..INT16kWRead
HR24086doc 24087 (0x5E17)Active power in phase L1Data point 222; source: Meter. fct..INT16kWRead
HR24087doc 24088 (0x5E18)Active power in phase L2Data point 223; source: Meter. fct..INT16kWRead
HR24088doc 24089 (0x5E19)Active power in phase L3Data point 224; source: Meter. fct..INT16kWRead
HR24089doc 24090 (0x5E1A)Total reactive powerData point 225; source: Meter. fct..INT16kvarRead
HR24090doc 24091 (0x5E1B)Long-time mean value of 3-phase active powerData point 229; source: Meter. fct..INT16kWRead
HR24091doc 24092 (0x5E1C)Long-time mean value of active power in phase L1Data point 230; source: Meter. fct..INT16kWRead
HR24092doc 24093 (0x5E1D)Long-time mean value of active power in phase L2Data point 231; source: Meter. fct..INT16kWRead
HR24093doc 24094 (0x5E1E)Long-time mean value of active power in phase L3Data point 232; source: Meter. fct..INT16kWRead
HR24094doc 24095 (0x5E1F)Long-time mean value of 3-phase apparent powerData point 233; source: Meter. fct..UINT16kVARead
HR24095doc 24096 (0x5E20)Apparent power in phase L1Data point 218; source: Meter. fct..UINT16kVARead
HR24096doc 24097 (0x5E21)Apparent power in phase L2Data point 219; source: Meter. fct..UINT16kVARead
HR24097doc 24098 (0x5E22)Apparent power in phase L3Data point 220; source: Meter. fct..UINT16kVARead
HR24098doc 24099 (0x5E23)Long-time mean value of apparent power in phase L1Data point 234; source: Meter. fct..UINT16kVARead
HR24099doc 24100 (0x5E24)Long-time mean value of apparent power in phase L2Data point 235; source: Meter. fct..UINT16kVARead
HR24100doc 24101 (0x5E25)Long-time mean value of apparent power in phase L3Data point 236; source: Meter. fct..UINT16kVARead
HR24101doc 24102 (0x5E26)Long-time mean value of 3-phase reactive powerData point 237; source: Meter. fct..INT16kvarRead
HR24102doc 24103 (0x5E27)Reactive power in phase L1Data point 226; source: Meter. fct..INT16kvarRead
HR24103doc 24104 (0x5E28)Reactive power in phase L2Data point 227; source: Meter. fct..INT16kvarRead
HR24104doc 24105 (0x5E29)Reactive power in phase L3Data point 228; source: Meter. fct..INT16kvarRead
HR24105doc 24106 (0x5E2A)Active energy in normal directionData point 238; source: Meter. fct..UINT32ABCDMWhRead
HR24107doc 24108 (0x5E2C)Active energy in reverse directionData point 239; source: Meter. fct..UINT32ABCDMWhRead
HR24109doc 24110 (0x5E2E)Reactive energy in normal directionData point 240; source: Meter. fct..UINT32ABCDMvarhRead
HR24111doc 24112 (0x5E30)Reactive energy in reverse directionData point 241; source: Meter. fct..UINT32ABCDMvarhRead
HR24113doc 24114 (0x5E32)Mean value of the power factorData point 168; source: Meter. fct..INT16× 0.001Read
HR24114doc 24115 (0x5E33)Power factor in phase L1Data point 169; source: Meter. fct..INT16× 0.001Read
HR24115doc 24116 (0x5E34)Power factor in phase L2Data point 170; source: Meter. fct..INT16× 0.001Read
HR24116doc 24117 (0x5E35)Power factor in phase L3Data point 171; source: Meter. fct..INT16× 0.001Read
HR24117doc 24118 (0x5E36)FrequencyData point 262; source: Meter. fct..UINT16× 0.01HzRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module

What Modbus registers does the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module have?

This map lists 100 registers: 100 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register-block tables print 1-based register numbers in decimal and hex, where the high byte is the block number (block 94 starts at 0x5E01). The manual's write example for block 68 sends start address 0x4402 for the system time, which the block 68 table lists at 0x4403, so the wire address is the printed number minus 1.

What byte order does the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module?

Start with HR 24069 Current in phase L1 (Phase L1 current); HR 24072 Mean current value over the three phases (Average current); HR 24082 Mean value of phase-to-phase voltage (Average L-L voltage); HR 24085 Total active power (Total active power); HR 24113 Mean value of the power factor (Mean power factor); HR 24117 Frequency (Frequency); HR 24105 Active energy in normal direction (Active energy, MWh).

How do I enable Modbus control of the Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module?

Modbus runs through the COM16 module. Its address, baud rate and parity are in block 160 (printed 0xA003 high byte for the address, 0xA019 for baud rate and parity). Without a bridge on the COM16 WriteEnable input, switching, trip reset, parameter changes and counter resets are blocked; setting the system time and resetting min/max values are still allowed.

Where is the official Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module Modbus documentation?

The source is SENTRON 3WL/3VL circuit breakers with communication capability - Modbus, System Manual (A5E02126891-02), revision 2011-07, published free by Siemens at https://assets.new.siemens.com/siemens/assets/api/uuid:2216d539-488d-4320-b10a-d79f984e4a75/manual-modbus-sentron-3wl-3vl-en.pdf.

More Siemens Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: SENTRON 3WL/3VL circuit breakers with communication capability - Modbus, System Manual · A5E02126891-02 · rev. 2011-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.