Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) Modbus register map
Updated 17 November 2026
BlueNet BN PRO is a family of intelligent rack PDUs with metering at inlet, phase and outlet level, residual-current monitoring and optional sensors. Modbus TCP exposes everything as read-only holding registers (FC 03) with fixed decimal resolutions. This map covers inlet, phase and outlet measurements, energy counters, MCB and RCM status, residual currents, GPIO and external temperature/humidity sensors.
This page lists 518 Modbus registers for the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Bachmann’s own free documentation (linked below) and checked against it.
- Manufacturer
- Bachmann
- Model
- BlueNet BN PRO intelligent PDU (Modbus TCP)
- Equipment type
- Power meter (metered/switched rack PDU)
- Registers
- 518 (0 writable)
- Transport
- Modbus TCP
- Default unit ID
- 1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- BlueNet BN PRO, BN PRO PDU, BlueNet 2 BN PRO
Integration notes: Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP)
Connect to the PDU's IP address with Modbus TCP, unit ID 1 for a single or main PDU, and read holding registers with FC 03. Inlet values start at address 16; scale each register by its resolution.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 16 | Status Inlet State | INT16 | Inlet status | Read |
| HR 17 | Inlet level - Current | UINT16 | Inlet current | Read |
| HR 19 | Inlet level - Active Power | UINT16 | Inlet active power | Read |
| HR 22 | Inlet level - Active Energy | UINT32 ABCD | Inlet active energy | Read |
| HR 143 | Phase 1 level - Voltage | UINT16 | Phase 1 voltage | Read |
| HR 28 | Inlet level - Frequency | UINT16 | Frequency | Read |
| HR 443 | RCM 1 - RCM AC | UINT16 | RCM 1 AC residual current | Read |
Enable Modbus control & writes
The register list does not say how Modbus TCP is enabled on the PDU or which TCP port it uses; check the BlueNet PDU documentation.
Byte order & addressing
- Register numbers are 1-based; send the decimal address (register - 1).
- Values are integers with fixed resolutions (0.01 A, 0.1 V, 1 W, 0.1 kWh, 0.1 °C).
- Linked PDUs use unit IDs by cluster position.
Network setup
- Use unit ID 1 for single and main PDUs.
- Read-only access with function code 03.
Watch out for
- Status registers return negative codes (e.g. -2 connection lost) for offline outlets or sensors.
- Read each energy pair (high + low register) in one request to avoid a torn value.
Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 16doc 17 | Status Inlet State | INT16 | Read | 0 = On; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 17doc 18 | Inlet level - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 18doc 19 | Inlet level - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 19doc 20 | Inlet level - Active Power | UINT16 | W | Read | ||||
| HR | 20doc 21 | Inlet level - Peak Active Power | UINT16 | W | Read | ||||
| HR | 21doc 22 | Inlet level - Apparent Power | UINT16 | VA | Read | ||||
| HR | 22doc 23 | Inlet level - Active Energy | Registers 23 (high) + 24 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 24doc 25 | Inlet level - Custom Active Energy | Registers 25 (high) + 26 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 26doc 27 | Inlet level - Neutral Current | UINT16 | × 0.01 | A | Read | |||
| HR | 27doc 28 | Inlet level - Peak Neutral Current | UINT16 | × 0.01 | A | Read | |||
| HR | 28doc 29 | Inlet level - Frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 142doc 143 | Status Phase 1 | INT16 | Read | 0 = On; -1 = Offline; -2 = Connection Lost; -3 = Under Voltage; -4 = Over Voltage; -128 = Unknown Error | ||||
| HR | 143doc 144 | Phase 1 level - Voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 144doc 145 | Phase 1 level - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 145doc 146 | Phase 1 level - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 146doc 147 | Phase 1 level - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 147doc 148 | Phase 1 level - Active Power | UINT16 | W | Read | ||||
| HR | 148doc 149 | Phase 1 level - Peak Active Power | UINT16 | W | Read | ||||
| HR | 149doc 150 | Phase 1 level - Apparent Power | UINT16 | VA | Read | ||||
| HR | 150doc 151 | Phase 1 level - Active Energy | Registers 151 (high) + 152 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 152doc 153 | Phase 1 level - Custom Active Energy | Registers 153 (high) + 154 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 154doc 155 | Phase 1 level - Apparent Energy | Registers 155 (high) + 156 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 161doc 162 | Phase 1 level - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 162doc 163 | Status Phase 2 | INT16 | Read | 0 = On; -1 = Offline; -2 = Connection Lost; -3 = Under Voltage; -4 = Over Voltage; -128 = Unknown Error | ||||
| HR | 163doc 164 | Phase 2 level - Voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 164doc 165 | Phase 2 level - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 165doc 166 | Phase 2 level - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 166doc 167 | Phase 2 level - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 167doc 168 | Phase 2 level - Active Power | UINT16 | W | Read | ||||
| HR | 168doc 169 | Phase 2 level - Peak Active Power | UINT16 | W | Read | ||||
| HR | 169doc 170 | Phase 2 level - Apparent Power | UINT16 | VA | Read | ||||
| HR | 170doc 171 | Phase 2 level - Active Energy | Registers 171 (high) + 172 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 172doc 173 | Phase 2 level - Custom Active Energy | Registers 173 (high) + 174 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 174doc 175 | Phase 2 level - Apparent Energy | Registers 175 (high) + 176 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 181doc 182 | Phase 2 level - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 182doc 183 | Status Phase 3 | INT16 | Read | 0 = On; -1 = Offline; -2 = Connection Lost; -3 = Under Voltage; -4 = Over Voltage; -128 = Unknown Error | ||||
| HR | 183doc 184 | Phase 3 level - Voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 184doc 185 | Phase 3 level - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 185doc 186 | Phase 3 level - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 186doc 187 | Phase 3 level - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 187doc 188 | Phase 3 level - Active Power | UINT16 | W | Read | ||||
| HR | 188doc 189 | Phase 3 level - Peak Active Power | UINT16 | W | Read | ||||
| HR | 189doc 190 | Phase 3 level - Apparent Power | UINT16 | VA | Read | ||||
| HR | 190doc 191 | Phase 3 level - Active Energy | Registers 191 (high) + 192 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 192doc 193 | Phase 3 level - Custom Active Energy | Registers 193 (high) + 194 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 194doc 195 | Phase 3 level - Apparent Energy | Registers 195 (high) + 196 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 201doc 202 | Phase 3 level - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 394doc 395 | Status MCB 1 state | INT16 | Read | 0 = On; -1 = Offline; -2 = Connection Lost; -5 = Tripped; -128 = Unknown Error | ||||
| HR | 398doc 399 | Status MCB 2 state | INT16 | Read | 0 = On; -1 = Offline; -2 = Connection Lost; -5 = Tripped; -128 = Unknown Error | ||||
| HR | 402doc 403 | Status MCB 3 state | INT16 | Read | 0 = On; -1 = Offline; -2 = Connection Lost; -5 = Tripped; -128 = Unknown Error | ||||
| HR | 406doc 407 | Status MCB 4 state | INT16 | Read | 0 = On; -1 = Offline; -2 = Connection Lost; -5 = Tripped; -128 = Unknown Error | ||||
| HR | 410doc 411 | Status MCB 5 state | INT16 | Read | 0 = On; -1 = Offline; -2 = Connection Lost; -5 = Tripped; -128 = Unknown Error | ||||
| HR | 414doc 415 | Status MCB 6 state | INT16 | Read | 0 = On; -1 = Offline; -2 = Connection Lost; -5 = Tripped; -128 = Unknown Error | ||||
| HR | 442doc 443 | Status RCM 1 state | INT16 | Read | 0 = On; -1 = Offline; -2 = Connection Lost; -9 = RCM defect; -128 = Unknown Error | ||||
| HR | 443doc 444 | RCM 1 - RCM AC | UINT16 | × 0.1 | mA | Read | |||
| HR | 444doc 445 | RCM 1 - Peak RCM AC | UINT16 | × 0.1 | mA | Read | |||
| HR | 445doc 446 | RCM 1 - RCM DC | UINT16 | × 0.1 | mA | Read | |||
| HR | 446doc 447 | RCM 1 - Peak RCM DC | UINT16 | × 0.1 | mA | Read | |||
| HR | 448doc 449 | Status RCM 2 state | INT16 | Read | 0 = On; -1 = Offline; -2 = Connection Lost; -9 = RCM defect; -128 = Unknown Error | ||||
| HR | 449doc 450 | RCM 2 - RCM AC | UINT16 | × 0.1 | mA | Read | |||
| HR | 450doc 451 | RCM 2 - Peak RCM AC | UINT16 | × 0.1 | mA | Read | |||
| HR | 451doc 452 | RCM 2 - RCM DC | UINT16 | × 0.1 | mA | Read | |||
| HR | 452doc 453 | RCM 2 - Peak RCM DC | UINT16 | × 0.1 | mA | Read | |||
| HR | 455doc 456 | Status RCM 3 state | INT16 | Read | 0 = On; -1 = Offline; -2 = Connection Lost; -9 = RCM defect; -128 = Unknown Error | ||||
| HR | 456doc 457 | RCM 3 - RCM AC | UINT16 | × 0.1 | mA | Read | |||
| HR | 457doc 458 | RCM 3 - Peak RCM AC | UINT16 | × 0.1 | mA | Read | |||
| HR | 458doc 459 | RCM 3 - RCM DC | UINT16 | × 0.1 | mA | Read | |||
| HR | 459doc 460 | RCM 3 - Peak RCM DC | UINT16 | × 0.1 | mA | Read | |||
| HR | 526doc 527 | Status Outlet 1 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 527doc 528 | Outlet 1 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 528doc 529 | Outlet 1 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 529doc 530 | Outlet 1 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 530doc 531 | Outlet 1 - Active Power | UINT16 | W | Read | ||||
| HR | 531doc 532 | Outlet 1 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 532doc 533 | Outlet 1 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 533doc 534 | Outlet 1 - Active Energy | Registers 534 (high) + 535 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 535doc 536 | Outlet 1 - Custom Active Energy | Registers 536 (high) + 537 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 537doc 538 | Outlet 1 - Apparent Energy | Registers 538 (high) + 539 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 539doc 540 | Outlet 1 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 541doc 542 | Status Outlet 2 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 542doc 543 | Outlet 2 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 543doc 544 | Outlet 2 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 544doc 545 | Outlet 2 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 545doc 546 | Outlet 2 - Active Power | UINT16 | W | Read | ||||
| HR | 546doc 547 | Outlet 2 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 547doc 548 | Outlet 2 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 548doc 549 | Outlet 2 - Active Energy | Registers 549 (high) + 550 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 550doc 551 | Outlet 2 - Custom Active Energy | Registers 551 (high) + 552 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 552doc 553 | Outlet 2 - Apparent Energy | Registers 553 (high) + 554 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 554doc 555 | Outlet 2 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 556doc 557 | Status Outlet 3 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 557doc 558 | Outlet 3 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 558doc 559 | Outlet 3 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 559doc 560 | Outlet 3 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 560doc 561 | Outlet 3 - Active Power | UINT16 | W | Read | ||||
| HR | 561doc 562 | Outlet 3 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 562doc 563 | Outlet 3 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 563doc 564 | Outlet 3 - Active Energy | Registers 564 (high) + 565 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 565doc 566 | Outlet 3 - Custom Active Energy | Registers 566 (high) + 567 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 567doc 568 | Outlet 3 - Apparent Energy | Registers 568 (high) + 569 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 569doc 570 | Outlet 3 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 571doc 572 | Status Outlet 4 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 572doc 573 | Outlet 4 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 573doc 574 | Outlet 4 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 574doc 575 | Outlet 4 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 575doc 576 | Outlet 4 - Active Power | UINT16 | W | Read | ||||
| HR | 576doc 577 | Outlet 4 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 577doc 578 | Outlet 4 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 578doc 579 | Outlet 4 - Active Energy | Registers 579 (high) + 580 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 580doc 581 | Outlet 4 - Custom Active Energy | Registers 581 (high) + 582 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 582doc 583 | Outlet 4 - Apparent Energy | Registers 583 (high) + 584 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 584doc 585 | Outlet 4 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 586doc 587 | Status Outlet 5 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 587doc 588 | Outlet 5 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 588doc 589 | Outlet 5 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 589doc 590 | Outlet 5 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 590doc 591 | Outlet 5 - Active Power | UINT16 | W | Read | ||||
| HR | 591doc 592 | Outlet 5 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 592doc 593 | Outlet 5 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 593doc 594 | Outlet 5 - Active Energy | Registers 594 (high) + 595 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 595doc 596 | Outlet 5 - Custom Active Energy | Registers 596 (high) + 597 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 597doc 598 | Outlet 5 - Apparent Energy | Registers 598 (high) + 599 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 599doc 600 | Outlet 5 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 601doc 602 | Status Outlet 6 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 602doc 603 | Outlet 6 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 603doc 604 | Outlet 6 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 604doc 605 | Outlet 6 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 605doc 606 | Outlet 6 - Active Power | UINT16 | W | Read | ||||
| HR | 606doc 607 | Outlet 6 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 607doc 608 | Outlet 6 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 608doc 609 | Outlet 6 - Active Energy | Registers 609 (high) + 610 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 610doc 611 | Outlet 6 - Custom Active Energy | Registers 611 (high) + 612 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 612doc 613 | Outlet 6 - Apparent Energy | Registers 613 (high) + 614 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 614doc 615 | Outlet 6 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 616doc 617 | Status Outlet 7 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 617doc 618 | Outlet 7 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 618doc 619 | Outlet 7 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 619doc 620 | Outlet 7 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 620doc 621 | Outlet 7 - Active Power | UINT16 | W | Read | ||||
| HR | 621doc 622 | Outlet 7 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 622doc 623 | Outlet 7 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 623doc 624 | Outlet 7 - Active Energy | Registers 624 (high) + 625 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 625doc 626 | Outlet 7 - Custom Active Energy | Registers 626 (high) + 627 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 627doc 628 | Outlet 7 - Apparent Energy | Registers 628 (high) + 629 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 629doc 630 | Outlet 7 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 631doc 632 | Status Outlet 8 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 632doc 633 | Outlet 8 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 633doc 634 | Outlet 8 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 634doc 635 | Outlet 8 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 635doc 636 | Outlet 8 - Active Power | UINT16 | W | Read | ||||
| HR | 636doc 637 | Outlet 8 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 637doc 638 | Outlet 8 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 638doc 639 | Outlet 8 - Active Energy | Registers 639 (high) + 640 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 640doc 641 | Outlet 8 - Custom Active Energy | Registers 641 (high) + 642 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 642doc 643 | Outlet 8 - Apparent Energy | Registers 643 (high) + 644 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 644doc 645 | Outlet 8 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 646doc 647 | Status Outlet 9 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 647doc 648 | Outlet 9 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 648doc 649 | Outlet 9 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 649doc 650 | Outlet 9 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 650doc 651 | Outlet 9 - Active Power | UINT16 | W | Read | ||||
| HR | 651doc 652 | Outlet 9 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 652doc 653 | Outlet 9 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 653doc 654 | Outlet 9 - Active Energy | Registers 654 (high) + 655 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 655doc 656 | Outlet 9 - Custom Active Energy | Registers 656 (high) + 657 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 657doc 658 | Outlet 9 - Apparent Energy | Registers 658 (high) + 659 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 659doc 660 | Outlet 9 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 661doc 662 | Status Outlet 10 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 662doc 663 | Outlet 10 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 663doc 664 | Outlet 10 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 664doc 665 | Outlet 10 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 665doc 666 | Outlet 10 - Active Power | UINT16 | W | Read | ||||
| HR | 666doc 667 | Outlet 10 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 667doc 668 | Outlet 10 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 668doc 669 | Outlet 10 - Active Energy | Registers 669 (high) + 670 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 670doc 671 | Outlet 10 - Custom Active Energy | Registers 671 (high) + 672 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 672doc 673 | Outlet 10 - Apparent Energy | Registers 673 (high) + 674 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 674doc 675 | Outlet 10 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 676doc 677 | Status Outlet 11 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 677doc 678 | Outlet 11 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 678doc 679 | Outlet 11 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 679doc 680 | Outlet 11 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 680doc 681 | Outlet 11 - Active Power | UINT16 | W | Read | ||||
| HR | 681doc 682 | Outlet 11 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 682doc 683 | Outlet 11 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 683doc 684 | Outlet 11 - Active Energy | Registers 684 (high) + 685 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 685doc 686 | Outlet 11 - Custom Active Energy | Registers 686 (high) + 687 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 687doc 688 | Outlet 11 - Apparent Energy | Registers 688 (high) + 689 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 689doc 690 | Outlet 11 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 691doc 692 | Status Outlet 12 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 692doc 693 | Outlet 12 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 693doc 694 | Outlet 12 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 694doc 695 | Outlet 12 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 695doc 696 | Outlet 12 - Active Power | UINT16 | W | Read | ||||
| HR | 696doc 697 | Outlet 12 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 697doc 698 | Outlet 12 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 698doc 699 | Outlet 12 - Active Energy | Registers 699 (high) + 700 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 700doc 701 | Outlet 12 - Custom Active Energy | Registers 701 (high) + 702 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 702doc 703 | Outlet 12 - Apparent Energy | Registers 703 (high) + 704 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 704doc 705 | Outlet 12 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 706doc 707 | Status Outlet 13 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 707doc 708 | Outlet 13 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 708doc 709 | Outlet 13 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 709doc 710 | Outlet 13 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 710doc 711 | Outlet 13 - Active Power | UINT16 | W | Read | ||||
| HR | 711doc 712 | Outlet 13 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 712doc 713 | Outlet 13 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 713doc 714 | Outlet 13 - Active Energy | Registers 714 (high) + 715 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 715doc 716 | Outlet 13 - Custom Active Energy | Registers 716 (high) + 717 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 717doc 718 | Outlet 13 - Apparent Energy | Registers 718 (high) + 719 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 719doc 720 | Outlet 13 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 721doc 722 | Status Outlet 14 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 722doc 723 | Outlet 14 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 723doc 724 | Outlet 14 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 724doc 725 | Outlet 14 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 725doc 726 | Outlet 14 - Active Power | UINT16 | W | Read | ||||
| HR | 726doc 727 | Outlet 14 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 727doc 728 | Outlet 14 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 728doc 729 | Outlet 14 - Active Energy | Registers 729 (high) + 730 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 730doc 731 | Outlet 14 - Custom Active Energy | Registers 731 (high) + 732 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 732doc 733 | Outlet 14 - Apparent Energy | Registers 733 (high) + 734 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 734doc 735 | Outlet 14 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 736doc 737 | Status Outlet 15 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 737doc 738 | Outlet 15 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 738doc 739 | Outlet 15 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 739doc 740 | Outlet 15 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 740doc 741 | Outlet 15 - Active Power | UINT16 | W | Read | ||||
| HR | 741doc 742 | Outlet 15 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 742doc 743 | Outlet 15 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 743doc 744 | Outlet 15 - Active Energy | Registers 744 (high) + 745 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 745doc 746 | Outlet 15 - Custom Active Energy | Registers 746 (high) + 747 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 747doc 748 | Outlet 15 - Apparent Energy | Registers 748 (high) + 749 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 749doc 750 | Outlet 15 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 751doc 752 | Status Outlet 16 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 752doc 753 | Outlet 16 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 753doc 754 | Outlet 16 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 754doc 755 | Outlet 16 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 755doc 756 | Outlet 16 - Active Power | UINT16 | W | Read | ||||
| HR | 756doc 757 | Outlet 16 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 757doc 758 | Outlet 16 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 758doc 759 | Outlet 16 - Active Energy | Registers 759 (high) + 760 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 760doc 761 | Outlet 16 - Custom Active Energy | Registers 761 (high) + 762 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 762doc 763 | Outlet 16 - Apparent Energy | Registers 763 (high) + 764 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 764doc 765 | Outlet 16 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 766doc 767 | Status Outlet 17 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 767doc 768 | Outlet 17 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 768doc 769 | Outlet 17 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 769doc 770 | Outlet 17 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 770doc 771 | Outlet 17 - Active Power | UINT16 | W | Read | ||||
| HR | 771doc 772 | Outlet 17 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 772doc 773 | Outlet 17 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 773doc 774 | Outlet 17 - Active Energy | Registers 774 (high) + 775 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 775doc 776 | Outlet 17 - Custom Active Energy | Registers 776 (high) + 777 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 777doc 778 | Outlet 17 - Apparent Energy | Registers 778 (high) + 779 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 779doc 780 | Outlet 17 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 781doc 782 | Status Outlet 18 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 782doc 783 | Outlet 18 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 783doc 784 | Outlet 18 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 784doc 785 | Outlet 18 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 785doc 786 | Outlet 18 - Active Power | UINT16 | W | Read | ||||
| HR | 786doc 787 | Outlet 18 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 787doc 788 | Outlet 18 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 788doc 789 | Outlet 18 - Active Energy | Registers 789 (high) + 790 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 790doc 791 | Outlet 18 - Custom Active Energy | Registers 791 (high) + 792 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 792doc 793 | Outlet 18 - Apparent Energy | Registers 793 (high) + 794 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 794doc 795 | Outlet 18 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 796doc 797 | Status Outlet 19 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 797doc 798 | Outlet 19 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 798doc 799 | Outlet 19 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 799doc 800 | Outlet 19 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 800doc 801 | Outlet 19 - Active Power | UINT16 | W | Read | ||||
| HR | 801doc 802 | Outlet 19 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 802doc 803 | Outlet 19 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 803doc 804 | Outlet 19 - Active Energy | Registers 804 (high) + 805 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 805doc 806 | Outlet 19 - Custom Active Energy | Registers 806 (high) + 807 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 807doc 808 | Outlet 19 - Apparent Energy | Registers 808 (high) + 809 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 809doc 810 | Outlet 19 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 811doc 812 | Status Outlet 20 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 812doc 813 | Outlet 20 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 813doc 814 | Outlet 20 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 814doc 815 | Outlet 20 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 815doc 816 | Outlet 20 - Active Power | UINT16 | W | Read | ||||
| HR | 816doc 817 | Outlet 20 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 817doc 818 | Outlet 20 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 818doc 819 | Outlet 20 - Active Energy | Registers 819 (high) + 820 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 820doc 821 | Outlet 20 - Custom Active Energy | Registers 821 (high) + 822 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 822doc 823 | Outlet 20 - Apparent Energy | Registers 823 (high) + 824 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 824doc 825 | Outlet 20 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 826doc 827 | Status Outlet 21 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 827doc 828 | Outlet 21 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 828doc 829 | Outlet 21 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 829doc 830 | Outlet 21 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 830doc 831 | Outlet 21 - Active Power | UINT16 | W | Read | ||||
| HR | 831doc 832 | Outlet 21 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 832doc 833 | Outlet 21 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 833doc 834 | Outlet 21 - Active Energy | Registers 834 (high) + 835 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 835doc 836 | Outlet 21 - Custom Active Energy | Registers 836 (high) + 837 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 837doc 838 | Outlet 21 - Apparent Energy | Registers 838 (high) + 839 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 839doc 840 | Outlet 21 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 841doc 842 | Status Outlet 22 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 842doc 843 | Outlet 22 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 843doc 844 | Outlet 22 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 844doc 845 | Outlet 22 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 845doc 846 | Outlet 22 - Active Power | UINT16 | W | Read | ||||
| HR | 846doc 847 | Outlet 22 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 847doc 848 | Outlet 22 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 848doc 849 | Outlet 22 - Active Energy | Registers 849 (high) + 850 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 850doc 851 | Outlet 22 - Custom Active Energy | Registers 851 (high) + 852 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 852doc 853 | Outlet 22 - Apparent Energy | Registers 853 (high) + 854 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 854doc 855 | Outlet 22 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 856doc 857 | Status Outlet 23 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 857doc 858 | Outlet 23 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 858doc 859 | Outlet 23 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 859doc 860 | Outlet 23 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 860doc 861 | Outlet 23 - Active Power | UINT16 | W | Read | ||||
| HR | 861doc 862 | Outlet 23 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 862doc 863 | Outlet 23 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 863doc 864 | Outlet 23 - Active Energy | Registers 864 (high) + 865 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 865doc 866 | Outlet 23 - Custom Active Energy | Registers 866 (high) + 867 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 867doc 868 | Outlet 23 - Apparent Energy | Registers 868 (high) + 869 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 869doc 870 | Outlet 23 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 871doc 872 | Status Outlet 24 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 872doc 873 | Outlet 24 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 873doc 874 | Outlet 24 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 874doc 875 | Outlet 24 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 875doc 876 | Outlet 24 - Active Power | UINT16 | W | Read | ||||
| HR | 876doc 877 | Outlet 24 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 877doc 878 | Outlet 24 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 878doc 879 | Outlet 24 - Active Energy | Registers 879 (high) + 880 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 880doc 881 | Outlet 24 - Custom Active Energy | Registers 881 (high) + 882 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 882doc 883 | Outlet 24 - Apparent Energy | Registers 883 (high) + 884 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 884doc 885 | Outlet 24 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 886doc 887 | Status Outlet 25 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 887doc 888 | Outlet 25 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 888doc 889 | Outlet 25 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 889doc 890 | Outlet 25 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 890doc 891 | Outlet 25 - Active Power | UINT16 | W | Read | ||||
| HR | 891doc 892 | Outlet 25 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 892doc 893 | Outlet 25 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 893doc 894 | Outlet 25 - Active Energy | Registers 894 (high) + 895 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 895doc 896 | Outlet 25 - Custom Active Energy | Registers 896 (high) + 897 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 897doc 898 | Outlet 25 - Apparent Energy | Registers 898 (high) + 899 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 899doc 900 | Outlet 25 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 901doc 902 | Status Outlet 26 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 902doc 903 | Outlet 26 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 903doc 904 | Outlet 26 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 904doc 905 | Outlet 26 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 905doc 906 | Outlet 26 - Active Power | UINT16 | W | Read | ||||
| HR | 906doc 907 | Outlet 26 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 907doc 908 | Outlet 26 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 908doc 909 | Outlet 26 - Active Energy | Registers 909 (high) + 910 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 910doc 911 | Outlet 26 - Custom Active Energy | Registers 911 (high) + 912 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 912doc 913 | Outlet 26 - Apparent Energy | Registers 913 (high) + 914 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 914doc 915 | Outlet 26 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 916doc 917 | Status Outlet 27 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 917doc 918 | Outlet 27 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 918doc 919 | Outlet 27 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 919doc 920 | Outlet 27 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 920doc 921 | Outlet 27 - Active Power | UINT16 | W | Read | ||||
| HR | 921doc 922 | Outlet 27 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 922doc 923 | Outlet 27 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 923doc 924 | Outlet 27 - Active Energy | Registers 924 (high) + 925 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 925doc 926 | Outlet 27 - Custom Active Energy | Registers 926 (high) + 927 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 927doc 928 | Outlet 27 - Apparent Energy | Registers 928 (high) + 929 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 929doc 930 | Outlet 27 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 931doc 932 | Status Outlet 28 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 932doc 933 | Outlet 28 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 933doc 934 | Outlet 28 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 934doc 935 | Outlet 28 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 935doc 936 | Outlet 28 - Active Power | UINT16 | W | Read | ||||
| HR | 936doc 937 | Outlet 28 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 937doc 938 | Outlet 28 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 938doc 939 | Outlet 28 - Active Energy | Registers 939 (high) + 940 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 940doc 941 | Outlet 28 - Custom Active Energy | Registers 941 (high) + 942 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 942doc 943 | Outlet 28 - Apparent Energy | Registers 943 (high) + 944 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 944doc 945 | Outlet 28 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 946doc 947 | Status Outlet 29 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 947doc 948 | Outlet 29 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 948doc 949 | Outlet 29 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 949doc 950 | Outlet 29 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 950doc 951 | Outlet 29 - Active Power | UINT16 | W | Read | ||||
| HR | 951doc 952 | Outlet 29 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 952doc 953 | Outlet 29 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 953doc 954 | Outlet 29 - Active Energy | Registers 954 (high) + 955 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 955doc 956 | Outlet 29 - Custom Active Energy | Registers 956 (high) + 957 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 957doc 958 | Outlet 29 - Apparent Energy | Registers 958 (high) + 959 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 959doc 960 | Outlet 29 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 961doc 962 | Status Outlet 30 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 962doc 963 | Outlet 30 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 963doc 964 | Outlet 30 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 964doc 965 | Outlet 30 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 965doc 966 | Outlet 30 - Active Power | UINT16 | W | Read | ||||
| HR | 966doc 967 | Outlet 30 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 967doc 968 | Outlet 30 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 968doc 969 | Outlet 30 - Active Energy | Registers 969 (high) + 970 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 970doc 971 | Outlet 30 - Custom Active Energy | Registers 971 (high) + 972 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 972doc 973 | Outlet 30 - Apparent Energy | Registers 973 (high) + 974 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 974doc 975 | Outlet 30 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 976doc 977 | Status Outlet 31 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 977doc 978 | Outlet 31 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 978doc 979 | Outlet 31 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 979doc 980 | Outlet 31 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 980doc 981 | Outlet 31 - Active Power | UINT16 | W | Read | ||||
| HR | 981doc 982 | Outlet 31 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 982doc 983 | Outlet 31 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 983doc 984 | Outlet 31 - Active Energy | Registers 984 (high) + 985 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 985doc 986 | Outlet 31 - Custom Active Energy | Registers 986 (high) + 987 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 987doc 988 | Outlet 31 - Apparent Energy | Registers 988 (high) + 989 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 989doc 990 | Outlet 31 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 991doc 992 | Status Outlet 32 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 992doc 993 | Outlet 32 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 993doc 994 | Outlet 32 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 994doc 995 | Outlet 32 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 995doc 996 | Outlet 32 - Active Power | UINT16 | W | Read | ||||
| HR | 996doc 997 | Outlet 32 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 997doc 998 | Outlet 32 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 998doc 999 | Outlet 32 - Active Energy | Registers 999 (high) + 1000 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 1000doc 1001 | Outlet 32 - Custom Active Energy | Registers 1001 (high) + 1002 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 1002doc 1003 | Outlet 32 - Apparent Energy | Registers 1003 (high) + 1004 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 1004doc 1005 | Outlet 32 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 1006doc 1007 | Status Outlet 33 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 1007doc 1008 | Outlet 33 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 1008doc 1009 | Outlet 33 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 1009doc 1010 | Outlet 33 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 1010doc 1011 | Outlet 33 - Active Power | UINT16 | W | Read | ||||
| HR | 1011doc 1012 | Outlet 33 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 1012doc 1013 | Outlet 33 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 1013doc 1014 | Outlet 33 - Active Energy | Registers 1014 (high) + 1015 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 1015doc 1016 | Outlet 33 - Custom Active Energy | Registers 1016 (high) + 1017 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 1017doc 1018 | Outlet 33 - Apparent Energy | Registers 1018 (high) + 1019 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 1019doc 1020 | Outlet 33 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 1021doc 1022 | Status Outlet 34 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 1022doc 1023 | Outlet 34 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 1023doc 1024 | Outlet 34 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 1024doc 1025 | Outlet 34 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 1025doc 1026 | Outlet 34 - Active Power | UINT16 | W | Read | ||||
| HR | 1026doc 1027 | Outlet 34 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 1027doc 1028 | Outlet 34 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 1028doc 1029 | Outlet 34 - Active Energy | Registers 1029 (high) + 1030 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 1030doc 1031 | Outlet 34 - Custom Active Energy | Registers 1031 (high) + 1032 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 1032doc 1033 | Outlet 34 - Apparent Energy | Registers 1033 (high) + 1034 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 1034doc 1035 | Outlet 34 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 1036doc 1037 | Status Outlet 35 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 1037doc 1038 | Outlet 35 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 1038doc 1039 | Outlet 35 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 1039doc 1040 | Outlet 35 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 1040doc 1041 | Outlet 35 - Active Power | UINT16 | W | Read | ||||
| HR | 1041doc 1042 | Outlet 35 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 1042doc 1043 | Outlet 35 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 1043doc 1044 | Outlet 35 - Active Energy | Registers 1044 (high) + 1045 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 1045doc 1046 | Outlet 35 - Custom Active Energy | Registers 1046 (high) + 1047 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 1047doc 1048 | Outlet 35 - Apparent Energy | Registers 1048 (high) + 1049 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 1049doc 1050 | Outlet 35 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 1051doc 1052 | Status Outlet 36 | INT16 | Read | 0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error | ||||
| HR | 1052doc 1053 | Outlet 36 - Current | UINT16 | × 0.01 | A | Read | |||
| HR | 1053doc 1054 | Outlet 36 - Peak Current | UINT16 | × 0.01 | A | Read | |||
| HR | 1054doc 1055 | Outlet 36 - Power Factor | UINT16 | × 0.001 | Read | ||||
| HR | 1055doc 1056 | Outlet 36 - Active Power | UINT16 | W | Read | ||||
| HR | 1056doc 1057 | Outlet 36 - Peak Active Power | UINT16 | W | Read | ||||
| HR | 1057doc 1058 | Outlet 36 - Apparent Power | UINT16 | VA | Read | ||||
| HR | 1058doc 1059 | Outlet 36 - Active Energy | Registers 1059 (high) + 1060 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 1060doc 1061 | Outlet 36 - Custom Active Energy | Registers 1061 (high) + 1062 (low). | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 1062doc 1063 | Outlet 36 - Apparent Energy | Registers 1063 (high) + 1064 (low). | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 1064doc 1065 | Outlet 36 - Power Factor Suffix | INT16 | Read | 1 = LA - inductive load; -1 = LE - capacitive load | ||||
| HR | 1261doc 1262 | GPIO Sensor Digital Output 1 | INT16 | Read | 0 = On; 1 = Off | ||||
| HR | 1281doc 1282 | GPIO Sensor Digital Output 2 | INT16 | Read | 0 = On; 1 = Off | ||||
| HR | 1301doc 1302 | GPIO Sensor Digital Input 1 | INT16 | Read | 0 = High; 1 = Low | ||||
| HR | 1321doc 1322 | GPIO Sensor Digital Input 2 | INT16 | Read | 0 = High; 1 = Low | ||||
| HR | 1341doc 1342 | Status Ext Sensor 1 | INT16 | Read | 0 = Okay (active); -1 = Offline; -2 = Connection Lost | ||||
| HR | 1342doc 1343 | Ext. Sensor 1 - Humidity | UINT16 | % | Read | ||||
| HR | 1343doc 1344 | Ext. Sensor 1 - Peak Humidity | UINT16 | % | Read | ||||
| HR | 1344doc 1345 | Ext. Sensor 1 - Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1345doc 1346 | Ext. Sensor 1 - Peak Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1361doc 1362 | Status Ext Sensor 2 | INT16 | Read | 0 = Okay (active); -1 = Offline; -2 = Connection Lost | ||||
| HR | 1362doc 1363 | Ext. Sensor 2 - Humidity | UINT16 | % | Read | ||||
| HR | 1363doc 1364 | Ext. Sensor 2 - Peak Humidity | UINT16 | % | Read | ||||
| HR | 1364doc 1365 | Ext. Sensor 2 - Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1365doc 1366 | Ext. Sensor 2 - Peak Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1381doc 1382 | Status Ext Sensor 3 | INT16 | Read | 0 = Okay (active); -1 = Offline; -2 = Connection Lost | ||||
| HR | 1382doc 1383 | Ext. Sensor 3 - Humidity | UINT16 | % | Read | ||||
| HR | 1383doc 1384 | Ext. Sensor 3 - Peak Humidity | UINT16 | % | Read | ||||
| HR | 1384doc 1385 | Ext. Sensor 3 - Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1385doc 1386 | Ext. Sensor 3 - Peak Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1401doc 1402 | Status Ext Sensor 4 | INT16 | Read | 0 = Okay (active); -1 = Offline; -2 = Connection Lost | ||||
| HR | 1402doc 1403 | Ext. Sensor 4 - Humidity | UINT16 | % | Read | ||||
| HR | 1403doc 1404 | Ext. Sensor 4 - Peak Humidity | UINT16 | % | Read | ||||
| HR | 1404doc 1405 | Ext. Sensor 4 - Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1405doc 1406 | Ext. Sensor 4 - Peak Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1421doc 1422 | Status Ext Sensor 5 | INT16 | Read | 0 = Okay (active); -1 = Offline; -2 = Connection Lost | ||||
| HR | 1422doc 1423 | Ext. Sensor 5 - Humidity | UINT16 | % | Read | ||||
| HR | 1423doc 1424 | Ext. Sensor 5 - Peak Humidity | UINT16 | % | Read | ||||
| HR | 1424doc 1425 | Ext. Sensor 5 - Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1425doc 1426 | Ext. Sensor 5 - Peak Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1441doc 1442 | Status Ext Sensor 6 | INT16 | Read | 0 = Okay (active); -1 = Offline; -2 = Connection Lost | ||||
| HR | 1442doc 1443 | Ext. Sensor 6 - Humidity | UINT16 | % | Read | ||||
| HR | 1443doc 1444 | Ext. Sensor 6 - Peak Humidity | UINT16 | % | Read | ||||
| HR | 1444doc 1445 | Ext. Sensor 6 - Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1445doc 1446 | Ext. Sensor 6 - Peak Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1461doc 1462 | Status Ext Sensor 7 | INT16 | Read | 0 = Okay (active); -1 = Offline; -2 = Connection Lost | ||||
| HR | 1462doc 1463 | Ext. Sensor 7 - Humidity | UINT16 | % | Read | ||||
| HR | 1463doc 1464 | Ext. Sensor 7 - Peak Humidity | UINT16 | % | Read | ||||
| HR | 1464doc 1465 | Ext. Sensor 7 - Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1465doc 1466 | Ext. Sensor 7 - Peak Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1481doc 1482 | Status Ext Sensor 8 | INT16 | Read | 0 = Okay (active); -1 = Offline; -2 = Connection Lost | ||||
| HR | 1482doc 1483 | Ext. Sensor 8 - Humidity | UINT16 | % | Read | ||||
| HR | 1483doc 1484 | Ext. Sensor 8 - Peak Humidity | UINT16 | % | Read | ||||
| HR | 1484doc 1485 | Ext. Sensor 8 - Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1485doc 1486 | Ext. Sensor 8 - Peak Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1501doc 1502 | Status Ext Sensor 9 | INT16 | Read | 0 = Okay (active); -1 = Offline; -2 = Connection Lost | ||||
| HR | 1502doc 1503 | Ext. Sensor 9 - Humidity | UINT16 | % | Read | ||||
| HR | 1503doc 1504 | Ext. Sensor 9 - Peak Humidity | UINT16 | % | Read | ||||
| HR | 1504doc 1505 | Ext. Sensor 9 - Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1505doc 1506 | Ext. Sensor 9 - Peak Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1521doc 1522 | Status Ext Sensor 10 | INT16 | Read | 0 = Okay (active); -1 = Offline; -2 = Connection Lost | ||||
| HR | 1522doc 1523 | Ext. Sensor 10 - Humidity | UINT16 | % | Read | ||||
| HR | 1523doc 1524 | Ext. Sensor 10 - Peak Humidity | UINT16 | % | Read | ||||
| HR | 1524doc 1525 | Ext. Sensor 10 - Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1525doc 1526 | Ext. Sensor 10 - Peak Temperature | INT16 | × 0.1 | °C | Read |
Notes on this map
- Energy counters are split into a register named 'High Byte' followed by one named 'Low Byte'. Each pair is listed as one 32-bit value at the 'High' register, high word first (ABCD), as the names indicate.
- The list gives a resolution for each value but no data type. Status and power-factor-suffix codes include negative numbers, so they are INT16; temperatures are listed as INT16, other measurements as UINT16. Check signedness on site if a value can go negative.
- Single and main PDUs answer to unit ID 1. Linked PDUs in a cluster answer to the unit ID of their position in the cluster.
- Power factor is unsigned (resolution 0.001); the separate 'Power Factor Suffix' register says whether the load is inductive (1, LA) or capacitive (-1, LE).
- MCB current registers are left out: the list prints no resolution or unit for them.
- Several hex addresses in the list do not match the decimal column (e.g. phase 2 suffix: register 182 printed as 0x00B1 but decimal 181); the decimal column, which always equals register - 1, is used.
- The list is read-only (FC 03 only); there are no switching or reset registers.
- Outlet blocks are listed for outlets 1-36.
- Humidity rows print only '%' as resolution; they are listed with scale 1.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP)
What Modbus registers does the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) have?
This map lists 518 registers: 518 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints a 1-based register number plus the 0-based wire address in hex and decimal. The 'documented' column here is the register number; the address is the printed decimal address (register - 1). Register 18 (inlet current) is requested as address 17 (0x0011).
What byte order does the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP)?
Start with HR 16 Status Inlet State (Inlet status); HR 17 Inlet level - Current (Inlet current); HR 19 Inlet level - Active Power (Inlet active power); HR 22 Inlet level - Active Energy (Inlet active energy); HR 143 Phase 1 level - Voltage (Phase 1 voltage); HR 28 Inlet level - Frequency (Frequency); HR 443 RCM 1 - RCM AC (RCM 1 AC residual current).
How do I enable Modbus control of the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP)?
The register list does not say how Modbus TCP is enabled on the PDU or which TCP port it uses; check the BlueNet PDU documentation.
Where is the official Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) Modbus documentation?
The source is BlueNet BN PRO Modbus TCP v1.00 Protocol - ModBus Register (Read Holding Register 0x03) (BN_PRO_Modbus-Register v1.00 REV00), published free by Bachmann at https://www.bachmann.com/fileadmin/05a_Downloads/BlueNet/BN_PRO/BN_PRO_Modbus-Register_v1.00_REV00.pdf.
Other power & energy meters register maps
- Energy meter
Carlo Gavazzi EM100 / ET100 series (EM111, EM112, ET112)
Single-phase EM111, EM112 energy meters and ET112 bidirectional meter with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 14.
Also known as: EM111, EM112, ET112, EM110, EM111-DIN, EM112-DIN, ET112-DIN, EM111DINAV81XS1X, EM112DINAV01XS1X, ET112DINAV01XS1X - Energy meter
Carlo Gavazzi EM300 / ET300 series (EM330, EM340, ET330, ET340)
EM330, EM331, EM340, EM341 energy meters and ET330/ET340 bidirectional meters with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 17.
Also known as: EM330, EM340, ET330, ET340, EM331, EM341, EM330-DIN, EM340-DIN, ET340-DIN, EM340DINAV23XS1X, EM340DINAV23XS1PFA, EM340DINAV23XS1PFB - Power meter (power analyzer)
Carlo Gavazzi WM50 power analyzer with TCD branch channels
WM50 base unit (firmware X0, i.e. all A and B versions) with an MC485232 or MCETH communication module, plus TCD branch channels, per communication protocol user version rev. 1.0.0 (2017-09-27).
Also known as: WM50, WM50AV5, WM50-96, WM50 AV5 - Energy meter
Continental Control Systems WattNode Modbus (WNC) energy meter
WattNode Modbus WNC and revenue RWNC models, firmware 18-24, per manual WNC-MB-1.18c (2015-11-03).
Also known as: WNC-3Y-208-MB, WNC-3Y-400-MB, WNC-3Y-480-MB, WNC-3Y-600-MB, WNC-3D-240-MB, WNC-3D-400-MB, WNC-3D-480-MB, RWNC-3Y-208-MB, RWNC-3Y-400-MB, RWNC-3Y-480-MB, RWNC-3Y-600-MB, RWNC-3D-240-MB, RWNC-3D-400-MB, RWNC-3D-480-MB, WattNode Revenue Modbus - Energy meter
Eastron SDM120CT-M
Eastron SDM120CTM single-phase CT-operated DIN-rail meter (1 A / 5 A CT secondary), protocol implementation V1.3. Not the SDM120CT-40mA.
Also known as: SDM120CTM, SDM120CT Modbus, SDM120CT-MV - Power meter
Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
Eaton PXM 1000 series meters on the built-in RS-485 Modbus RTU port, per user manual MN150009EN (October 2018).
Also known as: PXM 1000, PXM 1100, PXM 1200, PXM 1300, PXM1000, PXM1100, PXM1200, PXM1300, Power Xpert Meter 1000
All power & energy meters Modbus register maps →
Source: BlueNet BN PRO Modbus TCP v1.00 Protocol - ModBus Register (Read Holding Register 0x03) · BN_PRO_Modbus-Register v1.00 REV00. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.