Short answer

BlueNet BN PRO is a family of intelligent rack PDUs with metering at inlet, phase and outlet level, residual-current monitoring and optional sensors. Modbus TCP exposes everything as read-only holding registers (FC 03) with fixed decimal resolutions. This map covers inlet, phase and outlet measurements, energy counters, MCB and RCM status, residual currents, GPIO and external temperature/humidity sensors.

This page lists 518 Modbus registers for the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Bachmann’s own free documentation (linked below) and checked against it.

Manufacturer
Bachmann
Model
BlueNet BN PRO intelligent PDU (Modbus TCP)
Equipment type
Power meter (metered/switched rack PDU)
Registers
518 (0 writable)
Transport
Modbus TCP
Default unit ID
1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
BlueNet BN PRO, BN PRO PDU, BlueNet 2 BN PRO
Source document
BlueNet BN PRO Modbus TCP v1.00 Protocol - ModBus Register (Read Holding Register 0x03) · BN_PRO_Modbus-Register v1.00 REV00
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP)

Integration in brief

Connect to the PDU's IP address with Modbus TCP, unit ID 1 for a single or main PDU, and read holding registers with FC 03. Inlet values start at address 16; scale each register by its resolution.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 16Status Inlet StateINT16Inlet statusRead
HR 17Inlet level - CurrentUINT16Inlet currentRead
HR 19Inlet level - Active PowerUINT16Inlet active powerRead
HR 22Inlet level - Active EnergyUINT32 ABCDInlet active energyRead
HR 143Phase 1 level - VoltageUINT16Phase 1 voltageRead
HR 28Inlet level - FrequencyUINT16FrequencyRead
HR 443RCM 1 - RCM ACUINT16RCM 1 AC residual currentRead

Enable Modbus control & writes

The register list does not say how Modbus TCP is enabled on the PDU or which TCP port it uses; check the BlueNet PDU documentation.

Byte order & addressing

Network setup

Watch out for

Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

518 of 518 shown
Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR16doc 17Status Inlet StateINT16Read0 = On; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR17doc 18Inlet level - CurrentUINT16× 0.01ARead
HR18doc 19Inlet level - Peak CurrentUINT16× 0.01ARead
HR19doc 20Inlet level - Active PowerUINT16WRead
HR20doc 21Inlet level - Peak Active PowerUINT16WRead
HR21doc 22Inlet level - Apparent PowerUINT16VARead
HR22doc 23Inlet level - Active EnergyRegisters 23 (high) + 24 (low).UINT32ABCD× 0.1kWhRead
HR24doc 25Inlet level - Custom Active EnergyRegisters 25 (high) + 26 (low).UINT32ABCD× 0.1kWhRead
HR26doc 27Inlet level - Neutral CurrentUINT16× 0.01ARead
HR27doc 28Inlet level - Peak Neutral CurrentUINT16× 0.01ARead
HR28doc 29Inlet level - FrequencyUINT16× 0.1HzRead
HR142doc 143Status Phase 1INT16Read0 = On; -1 = Offline; -2 = Connection Lost; -3 = Under Voltage; -4 = Over Voltage; -128 = Unknown Error
HR143doc 144Phase 1 level - VoltageUINT16× 0.1VRead
HR144doc 145Phase 1 level - CurrentUINT16× 0.01ARead
HR145doc 146Phase 1 level - Peak CurrentUINT16× 0.01ARead
HR146doc 147Phase 1 level - Power FactorUINT16× 0.001Read
HR147doc 148Phase 1 level - Active PowerUINT16WRead
HR148doc 149Phase 1 level - Peak Active PowerUINT16WRead
HR149doc 150Phase 1 level - Apparent PowerUINT16VARead
HR150doc 151Phase 1 level - Active EnergyRegisters 151 (high) + 152 (low).UINT32ABCD× 0.1kWhRead
HR152doc 153Phase 1 level - Custom Active EnergyRegisters 153 (high) + 154 (low).UINT32ABCD× 0.1kWhRead
HR154doc 155Phase 1 level - Apparent EnergyRegisters 155 (high) + 156 (low).UINT32ABCD× 0.1kVAhRead
HR161doc 162Phase 1 level - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR162doc 163Status Phase 2INT16Read0 = On; -1 = Offline; -2 = Connection Lost; -3 = Under Voltage; -4 = Over Voltage; -128 = Unknown Error
HR163doc 164Phase 2 level - VoltageUINT16× 0.1VRead
HR164doc 165Phase 2 level - CurrentUINT16× 0.01ARead
HR165doc 166Phase 2 level - Peak CurrentUINT16× 0.01ARead
HR166doc 167Phase 2 level - Power FactorUINT16× 0.001Read
HR167doc 168Phase 2 level - Active PowerUINT16WRead
HR168doc 169Phase 2 level - Peak Active PowerUINT16WRead
HR169doc 170Phase 2 level - Apparent PowerUINT16VARead
HR170doc 171Phase 2 level - Active EnergyRegisters 171 (high) + 172 (low).UINT32ABCD× 0.1kWhRead
HR172doc 173Phase 2 level - Custom Active EnergyRegisters 173 (high) + 174 (low).UINT32ABCD× 0.1kWhRead
HR174doc 175Phase 2 level - Apparent EnergyRegisters 175 (high) + 176 (low).UINT32ABCD× 0.1kVAhRead
HR181doc 182Phase 2 level - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR182doc 183Status Phase 3INT16Read0 = On; -1 = Offline; -2 = Connection Lost; -3 = Under Voltage; -4 = Over Voltage; -128 = Unknown Error
HR183doc 184Phase 3 level - VoltageUINT16× 0.1VRead
HR184doc 185Phase 3 level - CurrentUINT16× 0.01ARead
HR185doc 186Phase 3 level - Peak CurrentUINT16× 0.01ARead
HR186doc 187Phase 3 level - Power FactorUINT16× 0.001Read
HR187doc 188Phase 3 level - Active PowerUINT16WRead
HR188doc 189Phase 3 level - Peak Active PowerUINT16WRead
HR189doc 190Phase 3 level - Apparent PowerUINT16VARead
HR190doc 191Phase 3 level - Active EnergyRegisters 191 (high) + 192 (low).UINT32ABCD× 0.1kWhRead
HR192doc 193Phase 3 level - Custom Active EnergyRegisters 193 (high) + 194 (low).UINT32ABCD× 0.1kWhRead
HR194doc 195Phase 3 level - Apparent EnergyRegisters 195 (high) + 196 (low).UINT32ABCD× 0.1kVAhRead
HR201doc 202Phase 3 level - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR394doc 395Status MCB 1 stateINT16Read0 = On; -1 = Offline; -2 = Connection Lost; -5 = Tripped; -128 = Unknown Error
HR398doc 399Status MCB 2 stateINT16Read0 = On; -1 = Offline; -2 = Connection Lost; -5 = Tripped; -128 = Unknown Error
HR402doc 403Status MCB 3 stateINT16Read0 = On; -1 = Offline; -2 = Connection Lost; -5 = Tripped; -128 = Unknown Error
HR406doc 407Status MCB 4 stateINT16Read0 = On; -1 = Offline; -2 = Connection Lost; -5 = Tripped; -128 = Unknown Error
HR410doc 411Status MCB 5 stateINT16Read0 = On; -1 = Offline; -2 = Connection Lost; -5 = Tripped; -128 = Unknown Error
HR414doc 415Status MCB 6 stateINT16Read0 = On; -1 = Offline; -2 = Connection Lost; -5 = Tripped; -128 = Unknown Error
HR442doc 443Status RCM 1 stateINT16Read0 = On; -1 = Offline; -2 = Connection Lost; -9 = RCM defect; -128 = Unknown Error
HR443doc 444RCM 1 - RCM ACUINT16× 0.1mARead
HR444doc 445RCM 1 - Peak RCM ACUINT16× 0.1mARead
HR445doc 446RCM 1 - RCM DCUINT16× 0.1mARead
HR446doc 447RCM 1 - Peak RCM DCUINT16× 0.1mARead
HR448doc 449Status RCM 2 stateINT16Read0 = On; -1 = Offline; -2 = Connection Lost; -9 = RCM defect; -128 = Unknown Error
HR449doc 450RCM 2 - RCM ACUINT16× 0.1mARead
HR450doc 451RCM 2 - Peak RCM ACUINT16× 0.1mARead
HR451doc 452RCM 2 - RCM DCUINT16× 0.1mARead
HR452doc 453RCM 2 - Peak RCM DCUINT16× 0.1mARead
HR455doc 456Status RCM 3 stateINT16Read0 = On; -1 = Offline; -2 = Connection Lost; -9 = RCM defect; -128 = Unknown Error
HR456doc 457RCM 3 - RCM ACUINT16× 0.1mARead
HR457doc 458RCM 3 - Peak RCM ACUINT16× 0.1mARead
HR458doc 459RCM 3 - RCM DCUINT16× 0.1mARead
HR459doc 460RCM 3 - Peak RCM DCUINT16× 0.1mARead
HR526doc 527Status Outlet 1INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR527doc 528Outlet 1 - CurrentUINT16× 0.01ARead
HR528doc 529Outlet 1 - Peak CurrentUINT16× 0.01ARead
HR529doc 530Outlet 1 - Power FactorUINT16× 0.001Read
HR530doc 531Outlet 1 - Active PowerUINT16WRead
HR531doc 532Outlet 1 - Peak Active PowerUINT16WRead
HR532doc 533Outlet 1 - Apparent PowerUINT16VARead
HR533doc 534Outlet 1 - Active EnergyRegisters 534 (high) + 535 (low).UINT32ABCD× 0.1kWhRead
HR535doc 536Outlet 1 - Custom Active EnergyRegisters 536 (high) + 537 (low).UINT32ABCD× 0.1kWhRead
HR537doc 538Outlet 1 - Apparent EnergyRegisters 538 (high) + 539 (low).UINT32ABCD× 0.1kVAhRead
HR539doc 540Outlet 1 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR541doc 542Status Outlet 2INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR542doc 543Outlet 2 - CurrentUINT16× 0.01ARead
HR543doc 544Outlet 2 - Peak CurrentUINT16× 0.01ARead
HR544doc 545Outlet 2 - Power FactorUINT16× 0.001Read
HR545doc 546Outlet 2 - Active PowerUINT16WRead
HR546doc 547Outlet 2 - Peak Active PowerUINT16WRead
HR547doc 548Outlet 2 - Apparent PowerUINT16VARead
HR548doc 549Outlet 2 - Active EnergyRegisters 549 (high) + 550 (low).UINT32ABCD× 0.1kWhRead
HR550doc 551Outlet 2 - Custom Active EnergyRegisters 551 (high) + 552 (low).UINT32ABCD× 0.1kWhRead
HR552doc 553Outlet 2 - Apparent EnergyRegisters 553 (high) + 554 (low).UINT32ABCD× 0.1kVAhRead
HR554doc 555Outlet 2 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR556doc 557Status Outlet 3INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR557doc 558Outlet 3 - CurrentUINT16× 0.01ARead
HR558doc 559Outlet 3 - Peak CurrentUINT16× 0.01ARead
HR559doc 560Outlet 3 - Power FactorUINT16× 0.001Read
HR560doc 561Outlet 3 - Active PowerUINT16WRead
HR561doc 562Outlet 3 - Peak Active PowerUINT16WRead
HR562doc 563Outlet 3 - Apparent PowerUINT16VARead
HR563doc 564Outlet 3 - Active EnergyRegisters 564 (high) + 565 (low).UINT32ABCD× 0.1kWhRead
HR565doc 566Outlet 3 - Custom Active EnergyRegisters 566 (high) + 567 (low).UINT32ABCD× 0.1kWhRead
HR567doc 568Outlet 3 - Apparent EnergyRegisters 568 (high) + 569 (low).UINT32ABCD× 0.1kVAhRead
HR569doc 570Outlet 3 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR571doc 572Status Outlet 4INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR572doc 573Outlet 4 - CurrentUINT16× 0.01ARead
HR573doc 574Outlet 4 - Peak CurrentUINT16× 0.01ARead
HR574doc 575Outlet 4 - Power FactorUINT16× 0.001Read
HR575doc 576Outlet 4 - Active PowerUINT16WRead
HR576doc 577Outlet 4 - Peak Active PowerUINT16WRead
HR577doc 578Outlet 4 - Apparent PowerUINT16VARead
HR578doc 579Outlet 4 - Active EnergyRegisters 579 (high) + 580 (low).UINT32ABCD× 0.1kWhRead
HR580doc 581Outlet 4 - Custom Active EnergyRegisters 581 (high) + 582 (low).UINT32ABCD× 0.1kWhRead
HR582doc 583Outlet 4 - Apparent EnergyRegisters 583 (high) + 584 (low).UINT32ABCD× 0.1kVAhRead
HR584doc 585Outlet 4 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR586doc 587Status Outlet 5INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR587doc 588Outlet 5 - CurrentUINT16× 0.01ARead
HR588doc 589Outlet 5 - Peak CurrentUINT16× 0.01ARead
HR589doc 590Outlet 5 - Power FactorUINT16× 0.001Read
HR590doc 591Outlet 5 - Active PowerUINT16WRead
HR591doc 592Outlet 5 - Peak Active PowerUINT16WRead
HR592doc 593Outlet 5 - Apparent PowerUINT16VARead
HR593doc 594Outlet 5 - Active EnergyRegisters 594 (high) + 595 (low).UINT32ABCD× 0.1kWhRead
HR595doc 596Outlet 5 - Custom Active EnergyRegisters 596 (high) + 597 (low).UINT32ABCD× 0.1kWhRead
HR597doc 598Outlet 5 - Apparent EnergyRegisters 598 (high) + 599 (low).UINT32ABCD× 0.1kVAhRead
HR599doc 600Outlet 5 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR601doc 602Status Outlet 6INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR602doc 603Outlet 6 - CurrentUINT16× 0.01ARead
HR603doc 604Outlet 6 - Peak CurrentUINT16× 0.01ARead
HR604doc 605Outlet 6 - Power FactorUINT16× 0.001Read
HR605doc 606Outlet 6 - Active PowerUINT16WRead
HR606doc 607Outlet 6 - Peak Active PowerUINT16WRead
HR607doc 608Outlet 6 - Apparent PowerUINT16VARead
HR608doc 609Outlet 6 - Active EnergyRegisters 609 (high) + 610 (low).UINT32ABCD× 0.1kWhRead
HR610doc 611Outlet 6 - Custom Active EnergyRegisters 611 (high) + 612 (low).UINT32ABCD× 0.1kWhRead
HR612doc 613Outlet 6 - Apparent EnergyRegisters 613 (high) + 614 (low).UINT32ABCD× 0.1kVAhRead
HR614doc 615Outlet 6 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR616doc 617Status Outlet 7INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR617doc 618Outlet 7 - CurrentUINT16× 0.01ARead
HR618doc 619Outlet 7 - Peak CurrentUINT16× 0.01ARead
HR619doc 620Outlet 7 - Power FactorUINT16× 0.001Read
HR620doc 621Outlet 7 - Active PowerUINT16WRead
HR621doc 622Outlet 7 - Peak Active PowerUINT16WRead
HR622doc 623Outlet 7 - Apparent PowerUINT16VARead
HR623doc 624Outlet 7 - Active EnergyRegisters 624 (high) + 625 (low).UINT32ABCD× 0.1kWhRead
HR625doc 626Outlet 7 - Custom Active EnergyRegisters 626 (high) + 627 (low).UINT32ABCD× 0.1kWhRead
HR627doc 628Outlet 7 - Apparent EnergyRegisters 628 (high) + 629 (low).UINT32ABCD× 0.1kVAhRead
HR629doc 630Outlet 7 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR631doc 632Status Outlet 8INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR632doc 633Outlet 8 - CurrentUINT16× 0.01ARead
HR633doc 634Outlet 8 - Peak CurrentUINT16× 0.01ARead
HR634doc 635Outlet 8 - Power FactorUINT16× 0.001Read
HR635doc 636Outlet 8 - Active PowerUINT16WRead
HR636doc 637Outlet 8 - Peak Active PowerUINT16WRead
HR637doc 638Outlet 8 - Apparent PowerUINT16VARead
HR638doc 639Outlet 8 - Active EnergyRegisters 639 (high) + 640 (low).UINT32ABCD× 0.1kWhRead
HR640doc 641Outlet 8 - Custom Active EnergyRegisters 641 (high) + 642 (low).UINT32ABCD× 0.1kWhRead
HR642doc 643Outlet 8 - Apparent EnergyRegisters 643 (high) + 644 (low).UINT32ABCD× 0.1kVAhRead
HR644doc 645Outlet 8 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR646doc 647Status Outlet 9INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR647doc 648Outlet 9 - CurrentUINT16× 0.01ARead
HR648doc 649Outlet 9 - Peak CurrentUINT16× 0.01ARead
HR649doc 650Outlet 9 - Power FactorUINT16× 0.001Read
HR650doc 651Outlet 9 - Active PowerUINT16WRead
HR651doc 652Outlet 9 - Peak Active PowerUINT16WRead
HR652doc 653Outlet 9 - Apparent PowerUINT16VARead
HR653doc 654Outlet 9 - Active EnergyRegisters 654 (high) + 655 (low).UINT32ABCD× 0.1kWhRead
HR655doc 656Outlet 9 - Custom Active EnergyRegisters 656 (high) + 657 (low).UINT32ABCD× 0.1kWhRead
HR657doc 658Outlet 9 - Apparent EnergyRegisters 658 (high) + 659 (low).UINT32ABCD× 0.1kVAhRead
HR659doc 660Outlet 9 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR661doc 662Status Outlet 10INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR662doc 663Outlet 10 - CurrentUINT16× 0.01ARead
HR663doc 664Outlet 10 - Peak CurrentUINT16× 0.01ARead
HR664doc 665Outlet 10 - Power FactorUINT16× 0.001Read
HR665doc 666Outlet 10 - Active PowerUINT16WRead
HR666doc 667Outlet 10 - Peak Active PowerUINT16WRead
HR667doc 668Outlet 10 - Apparent PowerUINT16VARead
HR668doc 669Outlet 10 - Active EnergyRegisters 669 (high) + 670 (low).UINT32ABCD× 0.1kWhRead
HR670doc 671Outlet 10 - Custom Active EnergyRegisters 671 (high) + 672 (low).UINT32ABCD× 0.1kWhRead
HR672doc 673Outlet 10 - Apparent EnergyRegisters 673 (high) + 674 (low).UINT32ABCD× 0.1kVAhRead
HR674doc 675Outlet 10 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR676doc 677Status Outlet 11INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR677doc 678Outlet 11 - CurrentUINT16× 0.01ARead
HR678doc 679Outlet 11 - Peak CurrentUINT16× 0.01ARead
HR679doc 680Outlet 11 - Power FactorUINT16× 0.001Read
HR680doc 681Outlet 11 - Active PowerUINT16WRead
HR681doc 682Outlet 11 - Peak Active PowerUINT16WRead
HR682doc 683Outlet 11 - Apparent PowerUINT16VARead
HR683doc 684Outlet 11 - Active EnergyRegisters 684 (high) + 685 (low).UINT32ABCD× 0.1kWhRead
HR685doc 686Outlet 11 - Custom Active EnergyRegisters 686 (high) + 687 (low).UINT32ABCD× 0.1kWhRead
HR687doc 688Outlet 11 - Apparent EnergyRegisters 688 (high) + 689 (low).UINT32ABCD× 0.1kVAhRead
HR689doc 690Outlet 11 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR691doc 692Status Outlet 12INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR692doc 693Outlet 12 - CurrentUINT16× 0.01ARead
HR693doc 694Outlet 12 - Peak CurrentUINT16× 0.01ARead
HR694doc 695Outlet 12 - Power FactorUINT16× 0.001Read
HR695doc 696Outlet 12 - Active PowerUINT16WRead
HR696doc 697Outlet 12 - Peak Active PowerUINT16WRead
HR697doc 698Outlet 12 - Apparent PowerUINT16VARead
HR698doc 699Outlet 12 - Active EnergyRegisters 699 (high) + 700 (low).UINT32ABCD× 0.1kWhRead
HR700doc 701Outlet 12 - Custom Active EnergyRegisters 701 (high) + 702 (low).UINT32ABCD× 0.1kWhRead
HR702doc 703Outlet 12 - Apparent EnergyRegisters 703 (high) + 704 (low).UINT32ABCD× 0.1kVAhRead
HR704doc 705Outlet 12 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR706doc 707Status Outlet 13INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR707doc 708Outlet 13 - CurrentUINT16× 0.01ARead
HR708doc 709Outlet 13 - Peak CurrentUINT16× 0.01ARead
HR709doc 710Outlet 13 - Power FactorUINT16× 0.001Read
HR710doc 711Outlet 13 - Active PowerUINT16WRead
HR711doc 712Outlet 13 - Peak Active PowerUINT16WRead
HR712doc 713Outlet 13 - Apparent PowerUINT16VARead
HR713doc 714Outlet 13 - Active EnergyRegisters 714 (high) + 715 (low).UINT32ABCD× 0.1kWhRead
HR715doc 716Outlet 13 - Custom Active EnergyRegisters 716 (high) + 717 (low).UINT32ABCD× 0.1kWhRead
HR717doc 718Outlet 13 - Apparent EnergyRegisters 718 (high) + 719 (low).UINT32ABCD× 0.1kVAhRead
HR719doc 720Outlet 13 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR721doc 722Status Outlet 14INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR722doc 723Outlet 14 - CurrentUINT16× 0.01ARead
HR723doc 724Outlet 14 - Peak CurrentUINT16× 0.01ARead
HR724doc 725Outlet 14 - Power FactorUINT16× 0.001Read
HR725doc 726Outlet 14 - Active PowerUINT16WRead
HR726doc 727Outlet 14 - Peak Active PowerUINT16WRead
HR727doc 728Outlet 14 - Apparent PowerUINT16VARead
HR728doc 729Outlet 14 - Active EnergyRegisters 729 (high) + 730 (low).UINT32ABCD× 0.1kWhRead
HR730doc 731Outlet 14 - Custom Active EnergyRegisters 731 (high) + 732 (low).UINT32ABCD× 0.1kWhRead
HR732doc 733Outlet 14 - Apparent EnergyRegisters 733 (high) + 734 (low).UINT32ABCD× 0.1kVAhRead
HR734doc 735Outlet 14 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR736doc 737Status Outlet 15INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR737doc 738Outlet 15 - CurrentUINT16× 0.01ARead
HR738doc 739Outlet 15 - Peak CurrentUINT16× 0.01ARead
HR739doc 740Outlet 15 - Power FactorUINT16× 0.001Read
HR740doc 741Outlet 15 - Active PowerUINT16WRead
HR741doc 742Outlet 15 - Peak Active PowerUINT16WRead
HR742doc 743Outlet 15 - Apparent PowerUINT16VARead
HR743doc 744Outlet 15 - Active EnergyRegisters 744 (high) + 745 (low).UINT32ABCD× 0.1kWhRead
HR745doc 746Outlet 15 - Custom Active EnergyRegisters 746 (high) + 747 (low).UINT32ABCD× 0.1kWhRead
HR747doc 748Outlet 15 - Apparent EnergyRegisters 748 (high) + 749 (low).UINT32ABCD× 0.1kVAhRead
HR749doc 750Outlet 15 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR751doc 752Status Outlet 16INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR752doc 753Outlet 16 - CurrentUINT16× 0.01ARead
HR753doc 754Outlet 16 - Peak CurrentUINT16× 0.01ARead
HR754doc 755Outlet 16 - Power FactorUINT16× 0.001Read
HR755doc 756Outlet 16 - Active PowerUINT16WRead
HR756doc 757Outlet 16 - Peak Active PowerUINT16WRead
HR757doc 758Outlet 16 - Apparent PowerUINT16VARead
HR758doc 759Outlet 16 - Active EnergyRegisters 759 (high) + 760 (low).UINT32ABCD× 0.1kWhRead
HR760doc 761Outlet 16 - Custom Active EnergyRegisters 761 (high) + 762 (low).UINT32ABCD× 0.1kWhRead
HR762doc 763Outlet 16 - Apparent EnergyRegisters 763 (high) + 764 (low).UINT32ABCD× 0.1kVAhRead
HR764doc 765Outlet 16 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR766doc 767Status Outlet 17INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR767doc 768Outlet 17 - CurrentUINT16× 0.01ARead
HR768doc 769Outlet 17 - Peak CurrentUINT16× 0.01ARead
HR769doc 770Outlet 17 - Power FactorUINT16× 0.001Read
HR770doc 771Outlet 17 - Active PowerUINT16WRead
HR771doc 772Outlet 17 - Peak Active PowerUINT16WRead
HR772doc 773Outlet 17 - Apparent PowerUINT16VARead
HR773doc 774Outlet 17 - Active EnergyRegisters 774 (high) + 775 (low).UINT32ABCD× 0.1kWhRead
HR775doc 776Outlet 17 - Custom Active EnergyRegisters 776 (high) + 777 (low).UINT32ABCD× 0.1kWhRead
HR777doc 778Outlet 17 - Apparent EnergyRegisters 778 (high) + 779 (low).UINT32ABCD× 0.1kVAhRead
HR779doc 780Outlet 17 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR781doc 782Status Outlet 18INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR782doc 783Outlet 18 - CurrentUINT16× 0.01ARead
HR783doc 784Outlet 18 - Peak CurrentUINT16× 0.01ARead
HR784doc 785Outlet 18 - Power FactorUINT16× 0.001Read
HR785doc 786Outlet 18 - Active PowerUINT16WRead
HR786doc 787Outlet 18 - Peak Active PowerUINT16WRead
HR787doc 788Outlet 18 - Apparent PowerUINT16VARead
HR788doc 789Outlet 18 - Active EnergyRegisters 789 (high) + 790 (low).UINT32ABCD× 0.1kWhRead
HR790doc 791Outlet 18 - Custom Active EnergyRegisters 791 (high) + 792 (low).UINT32ABCD× 0.1kWhRead
HR792doc 793Outlet 18 - Apparent EnergyRegisters 793 (high) + 794 (low).UINT32ABCD× 0.1kVAhRead
HR794doc 795Outlet 18 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR796doc 797Status Outlet 19INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR797doc 798Outlet 19 - CurrentUINT16× 0.01ARead
HR798doc 799Outlet 19 - Peak CurrentUINT16× 0.01ARead
HR799doc 800Outlet 19 - Power FactorUINT16× 0.001Read
HR800doc 801Outlet 19 - Active PowerUINT16WRead
HR801doc 802Outlet 19 - Peak Active PowerUINT16WRead
HR802doc 803Outlet 19 - Apparent PowerUINT16VARead
HR803doc 804Outlet 19 - Active EnergyRegisters 804 (high) + 805 (low).UINT32ABCD× 0.1kWhRead
HR805doc 806Outlet 19 - Custom Active EnergyRegisters 806 (high) + 807 (low).UINT32ABCD× 0.1kWhRead
HR807doc 808Outlet 19 - Apparent EnergyRegisters 808 (high) + 809 (low).UINT32ABCD× 0.1kVAhRead
HR809doc 810Outlet 19 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR811doc 812Status Outlet 20INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR812doc 813Outlet 20 - CurrentUINT16× 0.01ARead
HR813doc 814Outlet 20 - Peak CurrentUINT16× 0.01ARead
HR814doc 815Outlet 20 - Power FactorUINT16× 0.001Read
HR815doc 816Outlet 20 - Active PowerUINT16WRead
HR816doc 817Outlet 20 - Peak Active PowerUINT16WRead
HR817doc 818Outlet 20 - Apparent PowerUINT16VARead
HR818doc 819Outlet 20 - Active EnergyRegisters 819 (high) + 820 (low).UINT32ABCD× 0.1kWhRead
HR820doc 821Outlet 20 - Custom Active EnergyRegisters 821 (high) + 822 (low).UINT32ABCD× 0.1kWhRead
HR822doc 823Outlet 20 - Apparent EnergyRegisters 823 (high) + 824 (low).UINT32ABCD× 0.1kVAhRead
HR824doc 825Outlet 20 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR826doc 827Status Outlet 21INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR827doc 828Outlet 21 - CurrentUINT16× 0.01ARead
HR828doc 829Outlet 21 - Peak CurrentUINT16× 0.01ARead
HR829doc 830Outlet 21 - Power FactorUINT16× 0.001Read
HR830doc 831Outlet 21 - Active PowerUINT16WRead
HR831doc 832Outlet 21 - Peak Active PowerUINT16WRead
HR832doc 833Outlet 21 - Apparent PowerUINT16VARead
HR833doc 834Outlet 21 - Active EnergyRegisters 834 (high) + 835 (low).UINT32ABCD× 0.1kWhRead
HR835doc 836Outlet 21 - Custom Active EnergyRegisters 836 (high) + 837 (low).UINT32ABCD× 0.1kWhRead
HR837doc 838Outlet 21 - Apparent EnergyRegisters 838 (high) + 839 (low).UINT32ABCD× 0.1kVAhRead
HR839doc 840Outlet 21 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR841doc 842Status Outlet 22INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR842doc 843Outlet 22 - CurrentUINT16× 0.01ARead
HR843doc 844Outlet 22 - Peak CurrentUINT16× 0.01ARead
HR844doc 845Outlet 22 - Power FactorUINT16× 0.001Read
HR845doc 846Outlet 22 - Active PowerUINT16WRead
HR846doc 847Outlet 22 - Peak Active PowerUINT16WRead
HR847doc 848Outlet 22 - Apparent PowerUINT16VARead
HR848doc 849Outlet 22 - Active EnergyRegisters 849 (high) + 850 (low).UINT32ABCD× 0.1kWhRead
HR850doc 851Outlet 22 - Custom Active EnergyRegisters 851 (high) + 852 (low).UINT32ABCD× 0.1kWhRead
HR852doc 853Outlet 22 - Apparent EnergyRegisters 853 (high) + 854 (low).UINT32ABCD× 0.1kVAhRead
HR854doc 855Outlet 22 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR856doc 857Status Outlet 23INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR857doc 858Outlet 23 - CurrentUINT16× 0.01ARead
HR858doc 859Outlet 23 - Peak CurrentUINT16× 0.01ARead
HR859doc 860Outlet 23 - Power FactorUINT16× 0.001Read
HR860doc 861Outlet 23 - Active PowerUINT16WRead
HR861doc 862Outlet 23 - Peak Active PowerUINT16WRead
HR862doc 863Outlet 23 - Apparent PowerUINT16VARead
HR863doc 864Outlet 23 - Active EnergyRegisters 864 (high) + 865 (low).UINT32ABCD× 0.1kWhRead
HR865doc 866Outlet 23 - Custom Active EnergyRegisters 866 (high) + 867 (low).UINT32ABCD× 0.1kWhRead
HR867doc 868Outlet 23 - Apparent EnergyRegisters 868 (high) + 869 (low).UINT32ABCD× 0.1kVAhRead
HR869doc 870Outlet 23 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR871doc 872Status Outlet 24INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR872doc 873Outlet 24 - CurrentUINT16× 0.01ARead
HR873doc 874Outlet 24 - Peak CurrentUINT16× 0.01ARead
HR874doc 875Outlet 24 - Power FactorUINT16× 0.001Read
HR875doc 876Outlet 24 - Active PowerUINT16WRead
HR876doc 877Outlet 24 - Peak Active PowerUINT16WRead
HR877doc 878Outlet 24 - Apparent PowerUINT16VARead
HR878doc 879Outlet 24 - Active EnergyRegisters 879 (high) + 880 (low).UINT32ABCD× 0.1kWhRead
HR880doc 881Outlet 24 - Custom Active EnergyRegisters 881 (high) + 882 (low).UINT32ABCD× 0.1kWhRead
HR882doc 883Outlet 24 - Apparent EnergyRegisters 883 (high) + 884 (low).UINT32ABCD× 0.1kVAhRead
HR884doc 885Outlet 24 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR886doc 887Status Outlet 25INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR887doc 888Outlet 25 - CurrentUINT16× 0.01ARead
HR888doc 889Outlet 25 - Peak CurrentUINT16× 0.01ARead
HR889doc 890Outlet 25 - Power FactorUINT16× 0.001Read
HR890doc 891Outlet 25 - Active PowerUINT16WRead
HR891doc 892Outlet 25 - Peak Active PowerUINT16WRead
HR892doc 893Outlet 25 - Apparent PowerUINT16VARead
HR893doc 894Outlet 25 - Active EnergyRegisters 894 (high) + 895 (low).UINT32ABCD× 0.1kWhRead
HR895doc 896Outlet 25 - Custom Active EnergyRegisters 896 (high) + 897 (low).UINT32ABCD× 0.1kWhRead
HR897doc 898Outlet 25 - Apparent EnergyRegisters 898 (high) + 899 (low).UINT32ABCD× 0.1kVAhRead
HR899doc 900Outlet 25 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR901doc 902Status Outlet 26INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR902doc 903Outlet 26 - CurrentUINT16× 0.01ARead
HR903doc 904Outlet 26 - Peak CurrentUINT16× 0.01ARead
HR904doc 905Outlet 26 - Power FactorUINT16× 0.001Read
HR905doc 906Outlet 26 - Active PowerUINT16WRead
HR906doc 907Outlet 26 - Peak Active PowerUINT16WRead
HR907doc 908Outlet 26 - Apparent PowerUINT16VARead
HR908doc 909Outlet 26 - Active EnergyRegisters 909 (high) + 910 (low).UINT32ABCD× 0.1kWhRead
HR910doc 911Outlet 26 - Custom Active EnergyRegisters 911 (high) + 912 (low).UINT32ABCD× 0.1kWhRead
HR912doc 913Outlet 26 - Apparent EnergyRegisters 913 (high) + 914 (low).UINT32ABCD× 0.1kVAhRead
HR914doc 915Outlet 26 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR916doc 917Status Outlet 27INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR917doc 918Outlet 27 - CurrentUINT16× 0.01ARead
HR918doc 919Outlet 27 - Peak CurrentUINT16× 0.01ARead
HR919doc 920Outlet 27 - Power FactorUINT16× 0.001Read
HR920doc 921Outlet 27 - Active PowerUINT16WRead
HR921doc 922Outlet 27 - Peak Active PowerUINT16WRead
HR922doc 923Outlet 27 - Apparent PowerUINT16VARead
HR923doc 924Outlet 27 - Active EnergyRegisters 924 (high) + 925 (low).UINT32ABCD× 0.1kWhRead
HR925doc 926Outlet 27 - Custom Active EnergyRegisters 926 (high) + 927 (low).UINT32ABCD× 0.1kWhRead
HR927doc 928Outlet 27 - Apparent EnergyRegisters 928 (high) + 929 (low).UINT32ABCD× 0.1kVAhRead
HR929doc 930Outlet 27 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR931doc 932Status Outlet 28INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR932doc 933Outlet 28 - CurrentUINT16× 0.01ARead
HR933doc 934Outlet 28 - Peak CurrentUINT16× 0.01ARead
HR934doc 935Outlet 28 - Power FactorUINT16× 0.001Read
HR935doc 936Outlet 28 - Active PowerUINT16WRead
HR936doc 937Outlet 28 - Peak Active PowerUINT16WRead
HR937doc 938Outlet 28 - Apparent PowerUINT16VARead
HR938doc 939Outlet 28 - Active EnergyRegisters 939 (high) + 940 (low).UINT32ABCD× 0.1kWhRead
HR940doc 941Outlet 28 - Custom Active EnergyRegisters 941 (high) + 942 (low).UINT32ABCD× 0.1kWhRead
HR942doc 943Outlet 28 - Apparent EnergyRegisters 943 (high) + 944 (low).UINT32ABCD× 0.1kVAhRead
HR944doc 945Outlet 28 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR946doc 947Status Outlet 29INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR947doc 948Outlet 29 - CurrentUINT16× 0.01ARead
HR948doc 949Outlet 29 - Peak CurrentUINT16× 0.01ARead
HR949doc 950Outlet 29 - Power FactorUINT16× 0.001Read
HR950doc 951Outlet 29 - Active PowerUINT16WRead
HR951doc 952Outlet 29 - Peak Active PowerUINT16WRead
HR952doc 953Outlet 29 - Apparent PowerUINT16VARead
HR953doc 954Outlet 29 - Active EnergyRegisters 954 (high) + 955 (low).UINT32ABCD× 0.1kWhRead
HR955doc 956Outlet 29 - Custom Active EnergyRegisters 956 (high) + 957 (low).UINT32ABCD× 0.1kWhRead
HR957doc 958Outlet 29 - Apparent EnergyRegisters 958 (high) + 959 (low).UINT32ABCD× 0.1kVAhRead
HR959doc 960Outlet 29 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR961doc 962Status Outlet 30INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR962doc 963Outlet 30 - CurrentUINT16× 0.01ARead
HR963doc 964Outlet 30 - Peak CurrentUINT16× 0.01ARead
HR964doc 965Outlet 30 - Power FactorUINT16× 0.001Read
HR965doc 966Outlet 30 - Active PowerUINT16WRead
HR966doc 967Outlet 30 - Peak Active PowerUINT16WRead
HR967doc 968Outlet 30 - Apparent PowerUINT16VARead
HR968doc 969Outlet 30 - Active EnergyRegisters 969 (high) + 970 (low).UINT32ABCD× 0.1kWhRead
HR970doc 971Outlet 30 - Custom Active EnergyRegisters 971 (high) + 972 (low).UINT32ABCD× 0.1kWhRead
HR972doc 973Outlet 30 - Apparent EnergyRegisters 973 (high) + 974 (low).UINT32ABCD× 0.1kVAhRead
HR974doc 975Outlet 30 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR976doc 977Status Outlet 31INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR977doc 978Outlet 31 - CurrentUINT16× 0.01ARead
HR978doc 979Outlet 31 - Peak CurrentUINT16× 0.01ARead
HR979doc 980Outlet 31 - Power FactorUINT16× 0.001Read
HR980doc 981Outlet 31 - Active PowerUINT16WRead
HR981doc 982Outlet 31 - Peak Active PowerUINT16WRead
HR982doc 983Outlet 31 - Apparent PowerUINT16VARead
HR983doc 984Outlet 31 - Active EnergyRegisters 984 (high) + 985 (low).UINT32ABCD× 0.1kWhRead
HR985doc 986Outlet 31 - Custom Active EnergyRegisters 986 (high) + 987 (low).UINT32ABCD× 0.1kWhRead
HR987doc 988Outlet 31 - Apparent EnergyRegisters 988 (high) + 989 (low).UINT32ABCD× 0.1kVAhRead
HR989doc 990Outlet 31 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR991doc 992Status Outlet 32INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR992doc 993Outlet 32 - CurrentUINT16× 0.01ARead
HR993doc 994Outlet 32 - Peak CurrentUINT16× 0.01ARead
HR994doc 995Outlet 32 - Power FactorUINT16× 0.001Read
HR995doc 996Outlet 32 - Active PowerUINT16WRead
HR996doc 997Outlet 32 - Peak Active PowerUINT16WRead
HR997doc 998Outlet 32 - Apparent PowerUINT16VARead
HR998doc 999Outlet 32 - Active EnergyRegisters 999 (high) + 1000 (low).UINT32ABCD× 0.1kWhRead
HR1000doc 1001Outlet 32 - Custom Active EnergyRegisters 1001 (high) + 1002 (low).UINT32ABCD× 0.1kWhRead
HR1002doc 1003Outlet 32 - Apparent EnergyRegisters 1003 (high) + 1004 (low).UINT32ABCD× 0.1kVAhRead
HR1004doc 1005Outlet 32 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR1006doc 1007Status Outlet 33INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR1007doc 1008Outlet 33 - CurrentUINT16× 0.01ARead
HR1008doc 1009Outlet 33 - Peak CurrentUINT16× 0.01ARead
HR1009doc 1010Outlet 33 - Power FactorUINT16× 0.001Read
HR1010doc 1011Outlet 33 - Active PowerUINT16WRead
HR1011doc 1012Outlet 33 - Peak Active PowerUINT16WRead
HR1012doc 1013Outlet 33 - Apparent PowerUINT16VARead
HR1013doc 1014Outlet 33 - Active EnergyRegisters 1014 (high) + 1015 (low).UINT32ABCD× 0.1kWhRead
HR1015doc 1016Outlet 33 - Custom Active EnergyRegisters 1016 (high) + 1017 (low).UINT32ABCD× 0.1kWhRead
HR1017doc 1018Outlet 33 - Apparent EnergyRegisters 1018 (high) + 1019 (low).UINT32ABCD× 0.1kVAhRead
HR1019doc 1020Outlet 33 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR1021doc 1022Status Outlet 34INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR1022doc 1023Outlet 34 - CurrentUINT16× 0.01ARead
HR1023doc 1024Outlet 34 - Peak CurrentUINT16× 0.01ARead
HR1024doc 1025Outlet 34 - Power FactorUINT16× 0.001Read
HR1025doc 1026Outlet 34 - Active PowerUINT16WRead
HR1026doc 1027Outlet 34 - Peak Active PowerUINT16WRead
HR1027doc 1028Outlet 34 - Apparent PowerUINT16VARead
HR1028doc 1029Outlet 34 - Active EnergyRegisters 1029 (high) + 1030 (low).UINT32ABCD× 0.1kWhRead
HR1030doc 1031Outlet 34 - Custom Active EnergyRegisters 1031 (high) + 1032 (low).UINT32ABCD× 0.1kWhRead
HR1032doc 1033Outlet 34 - Apparent EnergyRegisters 1033 (high) + 1034 (low).UINT32ABCD× 0.1kVAhRead
HR1034doc 1035Outlet 34 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR1036doc 1037Status Outlet 35INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR1037doc 1038Outlet 35 - CurrentUINT16× 0.01ARead
HR1038doc 1039Outlet 35 - Peak CurrentUINT16× 0.01ARead
HR1039doc 1040Outlet 35 - Power FactorUINT16× 0.001Read
HR1040doc 1041Outlet 35 - Active PowerUINT16WRead
HR1041doc 1042Outlet 35 - Peak Active PowerUINT16WRead
HR1042doc 1043Outlet 35 - Apparent PowerUINT16VARead
HR1043doc 1044Outlet 35 - Active EnergyRegisters 1044 (high) + 1045 (low).UINT32ABCD× 0.1kWhRead
HR1045doc 1046Outlet 35 - Custom Active EnergyRegisters 1046 (high) + 1047 (low).UINT32ABCD× 0.1kWhRead
HR1047doc 1048Outlet 35 - Apparent EnergyRegisters 1048 (high) + 1049 (low).UINT32ABCD× 0.1kVAhRead
HR1049doc 1050Outlet 35 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR1051doc 1052Status Outlet 36INT16Read0 = On; 1 = Off; -1 = Offline; -2 = Connection Lost; -128 = Unknown Error
HR1052doc 1053Outlet 36 - CurrentUINT16× 0.01ARead
HR1053doc 1054Outlet 36 - Peak CurrentUINT16× 0.01ARead
HR1054doc 1055Outlet 36 - Power FactorUINT16× 0.001Read
HR1055doc 1056Outlet 36 - Active PowerUINT16WRead
HR1056doc 1057Outlet 36 - Peak Active PowerUINT16WRead
HR1057doc 1058Outlet 36 - Apparent PowerUINT16VARead
HR1058doc 1059Outlet 36 - Active EnergyRegisters 1059 (high) + 1060 (low).UINT32ABCD× 0.1kWhRead
HR1060doc 1061Outlet 36 - Custom Active EnergyRegisters 1061 (high) + 1062 (low).UINT32ABCD× 0.1kWhRead
HR1062doc 1063Outlet 36 - Apparent EnergyRegisters 1063 (high) + 1064 (low).UINT32ABCD× 0.1kVAhRead
HR1064doc 1065Outlet 36 - Power Factor SuffixINT16Read1 = LA - inductive load; -1 = LE - capacitive load
HR1261doc 1262GPIO Sensor Digital Output 1INT16Read0 = On; 1 = Off
HR1281doc 1282GPIO Sensor Digital Output 2INT16Read0 = On; 1 = Off
HR1301doc 1302GPIO Sensor Digital Input 1INT16Read0 = High; 1 = Low
HR1321doc 1322GPIO Sensor Digital Input 2INT16Read0 = High; 1 = Low
HR1341doc 1342Status Ext Sensor 1INT16Read0 = Okay (active); -1 = Offline; -2 = Connection Lost
HR1342doc 1343Ext. Sensor 1 - HumidityUINT16%Read
HR1343doc 1344Ext. Sensor 1 - Peak HumidityUINT16%Read
HR1344doc 1345Ext. Sensor 1 - TemperatureINT16× 0.1°CRead
HR1345doc 1346Ext. Sensor 1 - Peak TemperatureINT16× 0.1°CRead
HR1361doc 1362Status Ext Sensor 2INT16Read0 = Okay (active); -1 = Offline; -2 = Connection Lost
HR1362doc 1363Ext. Sensor 2 - HumidityUINT16%Read
HR1363doc 1364Ext. Sensor 2 - Peak HumidityUINT16%Read
HR1364doc 1365Ext. Sensor 2 - TemperatureINT16× 0.1°CRead
HR1365doc 1366Ext. Sensor 2 - Peak TemperatureINT16× 0.1°CRead
HR1381doc 1382Status Ext Sensor 3INT16Read0 = Okay (active); -1 = Offline; -2 = Connection Lost
HR1382doc 1383Ext. Sensor 3 - HumidityUINT16%Read
HR1383doc 1384Ext. Sensor 3 - Peak HumidityUINT16%Read
HR1384doc 1385Ext. Sensor 3 - TemperatureINT16× 0.1°CRead
HR1385doc 1386Ext. Sensor 3 - Peak TemperatureINT16× 0.1°CRead
HR1401doc 1402Status Ext Sensor 4INT16Read0 = Okay (active); -1 = Offline; -2 = Connection Lost
HR1402doc 1403Ext. Sensor 4 - HumidityUINT16%Read
HR1403doc 1404Ext. Sensor 4 - Peak HumidityUINT16%Read
HR1404doc 1405Ext. Sensor 4 - TemperatureINT16× 0.1°CRead
HR1405doc 1406Ext. Sensor 4 - Peak TemperatureINT16× 0.1°CRead
HR1421doc 1422Status Ext Sensor 5INT16Read0 = Okay (active); -1 = Offline; -2 = Connection Lost
HR1422doc 1423Ext. Sensor 5 - HumidityUINT16%Read
HR1423doc 1424Ext. Sensor 5 - Peak HumidityUINT16%Read
HR1424doc 1425Ext. Sensor 5 - TemperatureINT16× 0.1°CRead
HR1425doc 1426Ext. Sensor 5 - Peak TemperatureINT16× 0.1°CRead
HR1441doc 1442Status Ext Sensor 6INT16Read0 = Okay (active); -1 = Offline; -2 = Connection Lost
HR1442doc 1443Ext. Sensor 6 - HumidityUINT16%Read
HR1443doc 1444Ext. Sensor 6 - Peak HumidityUINT16%Read
HR1444doc 1445Ext. Sensor 6 - TemperatureINT16× 0.1°CRead
HR1445doc 1446Ext. Sensor 6 - Peak TemperatureINT16× 0.1°CRead
HR1461doc 1462Status Ext Sensor 7INT16Read0 = Okay (active); -1 = Offline; -2 = Connection Lost
HR1462doc 1463Ext. Sensor 7 - HumidityUINT16%Read
HR1463doc 1464Ext. Sensor 7 - Peak HumidityUINT16%Read
HR1464doc 1465Ext. Sensor 7 - TemperatureINT16× 0.1°CRead
HR1465doc 1466Ext. Sensor 7 - Peak TemperatureINT16× 0.1°CRead
HR1481doc 1482Status Ext Sensor 8INT16Read0 = Okay (active); -1 = Offline; -2 = Connection Lost
HR1482doc 1483Ext. Sensor 8 - HumidityUINT16%Read
HR1483doc 1484Ext. Sensor 8 - Peak HumidityUINT16%Read
HR1484doc 1485Ext. Sensor 8 - TemperatureINT16× 0.1°CRead
HR1485doc 1486Ext. Sensor 8 - Peak TemperatureINT16× 0.1°CRead
HR1501doc 1502Status Ext Sensor 9INT16Read0 = Okay (active); -1 = Offline; -2 = Connection Lost
HR1502doc 1503Ext. Sensor 9 - HumidityUINT16%Read
HR1503doc 1504Ext. Sensor 9 - Peak HumidityUINT16%Read
HR1504doc 1505Ext. Sensor 9 - TemperatureINT16× 0.1°CRead
HR1505doc 1506Ext. Sensor 9 - Peak TemperatureINT16× 0.1°CRead
HR1521doc 1522Status Ext Sensor 10INT16Read0 = Okay (active); -1 = Offline; -2 = Connection Lost
HR1522doc 1523Ext. Sensor 10 - HumidityUINT16%Read
HR1523doc 1524Ext. Sensor 10 - Peak HumidityUINT16%Read
HR1524doc 1525Ext. Sensor 10 - TemperatureINT16× 0.1°CRead
HR1525doc 1526Ext. Sensor 10 - Peak TemperatureINT16× 0.1°CRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP)

What Modbus registers does the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) have?

This map lists 518 registers: 518 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints a 1-based register number plus the 0-based wire address in hex and decimal. The 'documented' column here is the register number; the address is the printed decimal address (register - 1). Register 18 (inlet current) is requested as address 17 (0x0011).

What byte order does the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP)?

Start with HR 16 Status Inlet State (Inlet status); HR 17 Inlet level - Current (Inlet current); HR 19 Inlet level - Active Power (Inlet active power); HR 22 Inlet level - Active Energy (Inlet active energy); HR 143 Phase 1 level - Voltage (Phase 1 voltage); HR 28 Inlet level - Frequency (Frequency); HR 443 RCM 1 - RCM AC (RCM 1 AC residual current).

How do I enable Modbus control of the Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP)?

The register list does not say how Modbus TCP is enabled on the PDU or which TCP port it uses; check the BlueNet PDU documentation.

Where is the official Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP) Modbus documentation?

The source is BlueNet BN PRO Modbus TCP v1.00 Protocol - ModBus Register (Read Holding Register 0x03) (BN_PRO_Modbus-Register v1.00 REV00), published free by Bachmann at https://www.bachmann.com/fileadmin/05a_Downloads/BlueNet/BN_PRO/BN_PRO_Modbus-Register_v1.00_REV00.pdf.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: BlueNet BN PRO Modbus TCP v1.00 Protocol - ModBus Register (Read Holding Register 0x03) · BN_PRO_Modbus-Register v1.00 REV00. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.