Easy Modbus
  1. Home
  2. Modbus register maps
  3. Siemens
  4. SITRANS F M MAG 6000 with USM II Modbus RTU module

Sensor (flow transmitter) · Modbus register map

Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module Modbus register map

Updated 17 November 2026

Short answer

The MAG 6000 electromagnetic flow transmitter gets a Modbus RTU slave by fitting the USM II RS-485 add-on module. Data is held in holding registers and coils only. This map covers volume flow and totalizers (float and double), driver and identity registers, basic, totalizer, output, input, sensor and display settings, system status and the totalizer/batch/zero-adjust coils.

This page lists 119 Modbus registers for the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module — 72 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.

Manufacturer
Siemens
Model
SITRANS F M MAG 6000 with USM II Modbus RTU module
Equipment type
Sensor (flow transmitter)
Registers
119 (72 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
MAG 6000, MAG 6000 I, SITRANS FM MAG 6000
Source document
SITRANS F Modbus RTU RS 485 (USM II) communication module, Operating Instructions · A5E00753974-AB · rev. 2021-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module

Integration in brief

Read holding registers (FC 03) from address 3002 for volume flow and 3014/3018 for the double totalizers; values are big-endian IEEE, high word first. Use coils 9-12 to reset or hold the totalizers.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 3002Absolute VolumeflowFLOAT32 ABCDVolume flowRead
HR 3014Totalizer 1FLOAT64 ABCDTotalizer 1 (double)Read
HR 3018Totalizer 2/BatchFLOAT64 ABCDTotalizer 2 / batch (double)Read
HR 3200System statusBITMAP16System status bitsRead
HR 3201Error pending 1UINT16First pending errorRead
HR 2906Volumeflow unitUINT16Volume flow unit IDRead/write

Enable Modbus control & writes

Fit the USM II Modbus RTU add-on module in the transmitter. The module adds a 'MODBUS RTU module' menu (between Reset mode and Service mode) for address, baud, parity/framing, timeouts and TAG; the same settings are writable at addresses 528-530.

Byte order & addressing

Network setup

Watch out for

Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

119 of 119 shown
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 0:00001Restart MODBUS communicationWrite 1 to restart; reads 0.BITRead/write
CO8doc 0:00009Start auto zero adjustWrite 1 to start; reads 1 while busy.BITRead/write
CO9doc 0:00010Reset totalizer 1Write 1 to reset; reads 0.BITRead/write
CO10doc 0:00011Hold totalizer 11 = hold, 0 = run; reads back held state.BITRead/write
CO11doc 0:00012Reset totalizer 2Write 1 to reset; reads 0.BITRead/write
CO12doc 0:00013Hold totalizer 21 = hold, 0 = run; reads back held state.BITRead/write
CO13doc 0:00014Start batch1 = start, 0 = stop batch.BITRead/write
CO14doc 0:00015Pause batch1 = pause, 0 = resume batch.BITRead/write
HR500doc 4:00501No. of ParityErrorsUINT16Read
HR501doc 4:00502No. of FramingErrorsUINT16Read
HR503doc 4:00504No. of CRC ErrorsUINT16Read
HR504doc 4:00505No. of Ok Messages (received)UINT16Read
HR507doc 4:00508InterFrameSpaceUINT32ABCDusRead
HR511doc 4:00512Response TimeoutUINT16msRead/write
HR512doc 4:00513Response DelayUINT16msRead/write
HR513doc 4:0051410xInterFrameSpace (10 x chars)UINT16Read/write
HR514doc 4:00515Baudrate as double wordUINT32ABCDRead
HR528doc 4:00529Device address (1 - 247)UINT16Read/write
HR529doc 4:00530BaudrateUINT16Read/write0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 76800; 8 = 115200
HR530doc 4:00531Parity/framingUINT16Read/write0 = 8, E, 1; 1 = 8, O, 1; 2 = 8, N, 2; 3 = 8, N, 1
HR600doc 4:00601Slave IDUINT16Read0x2A = Siemens
HR601doc 4:00602Run indicatorUINT16Read0x00 = not running; 0xFF = running
HR602doc 4:00603Product codeUINT16Read24 = MAG 6000; 25 = MASS 6000
HR605doc 4:00606Flowmeter revisionUINT16Read
HR606doc 4:00607MODBUS revisionUINT16Read
HR607doc 4:00608Manufacturer nameSTRING[12]Read
HR613doc 4:00614Product nameSTRING[18]Read
HR622doc 4:00623MODBUS module nameSTRING[12]Read
HR640doc 4:00641TAGSTRING[18]Read/write
HR649doc 4:00650MODBUS module SW versionSTRING[20]Read
HR659doc 4:00660MODBUS module HW versionUINT16Read
HR680doc 4:00681Last Coil Error (CoilAddr)UINT16Read
HR681doc 4:00682Last Coil Error (ErrorNo)UINT16Read
HR682doc 4:00683Last HoldReg Error (HoldReg Addr)UINT16Read
HR683doc 4:00684Last HoldReg Error (ErrorNo)UINT16Read
HR2000doc 4:02001Flow directionUINT16Read/write0 = Negative; 1 = Positive
HR2005doc 4:02006Q max.FLOAT32ABCDm3/sRead/write
HR2007doc 4:02008Q max. 2 (Night)FLOAT32ABCDm3/sRead/write
HR2025doc 4:02026Low flow cut offFLOAT32ABCDRead/write
HR2029doc 4:02030Empty pipe on/offUINT16Read/write0 = Off; 1 = On
HR2031doc 4:02032Error levelUINT16Read/write1 = Warning; 2 = Permanent; 3 = Fatal
HR2032doc 4:02033Zero adjust modeUINT16Read/write0 = Auto; 1 = Manual
HR2033doc 4:02034Manual zero adjustFLOAT32ABCDm3/sRead/write
HR2040doc 4:02041Mains FrequencyUINT16Read/write0 = 50 Hz; 1 = 60 Hz
HR2101doc 4:02102Totalizer 1 directionUINT16Read/write0 = Reverse; 1 = Forward; 2 = Net
HR2103doc 4:02104Totalizer 2 directionUINT16Read/write0 = Reverse; 1 = Forward; 2 = Net
HR2200doc 4:02201Current Output 1 selectionUINT16Read/write0 = Off; 1 = On
HR2201doc 4:02202Current Output 1 directionUINT16Read/write1 = Unidirectional; 2 = Bidirectional
HR2202doc 4:02203Current Output 1 rangeUINT16Read/write0 = 0 - 20 mA; 1 = 4 - 20 mA; 2 = 4 - 20 mA + Alarm
HR2203doc 4:02204Current Output 1 time constantsFLOAT32ABCDRead/write
HR2205doc 4:02206Digital Output 1 functionUINT16Read/write0 = Off; 1 = Pulse; 2 = Frequency; 3 = Error Level; 4 = Error Number; 5 = Direction/Limit; 6 = Batch
HR2207doc 4:02208Pulse 1 directionUINT16Read/write1 = Unidirectional; 2 = Bidirectional
HR2208doc 4:02209Pulse 1 widthUINT16Read/write0 = 64 us; 1 = 130 us; 2 = 260 us; 3 = 510 us; 4 = 1.0 ms; 5 = 2.0 ms; 6 = 4.1 ms; 7 = 8.2 ms; 8 = 16 ms; 9 = 33 ms; 10 = 66 ms; 11 = 130 ms; 12 = 260 ms; 13 = 520 ms; 14 = 1.0 s; 15 = 2.1 s; 16 = 4.2 s
HR2211doc 4:02212Frequency 1 DirectionUINT16Read/write1 = Unidirectional; 2 = Bidirectional
HR2212doc 4:02213Frequency 1 Fmax.UINT16Read/write0 = 10 kHz; 1 = 5 kHz; 2 = 1 kHz; 3 = 500 Hz
HR2213doc 4:02214Frequency 1 TimeconstantsFLOAT32ABCDRead/write
HR2216doc 4:02217Limit Digital modeUINT16Read/write0 = 1 setpoint; 1 = 2 setpoints
HR2217doc 4:02218Limit Digital Setpoint min.FLOAT32ABCD1/100%Read/write
HR2219doc 4:02220Limit Digital Setpoint max.FLOAT32ABCD1/100%Read/write
HR2221doc 4:02222Limit Digital HysteresisFLOAT32ABCD1/100%Read/write
HR2223doc 4:02224Relay Output 1 functionUINT16Read/write0 = Off; 3 = Error Level; 4 = Error Number; 5 = Direction/Limit; 6 = Batch; 7 = Cleaning
HR2225doc 4:02226Limit Relay modeUINT16Read/write0 = 1 setpoint; 1 = 2 setpoints
HR2226doc 4:02227Limit Relay Setpoint min.FLOAT32ABCD1/100%Read/write
HR2228doc 4:02229Limit Relay Setpoint max.FLOAT32ABCD1/100%Read/write
HR2230doc 4:02231Limit Relay HysteresisFLOAT32ABCD1/100%Read/write
HR2232doc 4:02233Error number (0-255)UINT16Read/write
HR2234doc 4:02235Batch QuantityFLOAT32ABCDm3Read/write
HR2236doc 4:02237Batch CompensationFLOAT32ABCDm3Read/write
HR2240doc 4:02241Batch Time error on/offUINT16Read/write0 = Off; 1 = On
HR2241doc 4:02242Batch timeUINT32ABCDsRead/write
HR2243doc 4:02244Batch overrun on/offUINT16Read/write0 = Off; 1 = On
HR2244doc 4:02245Batch overrun errorFLOAT32ABCDm3Read/write
HR2246doc 4:02247Batch counter up/downUINT16Read/write0 = Down; 1 = Up
HR2247doc 4:02248Batch Time constantsFLOAT32ABCDRead/write
HR2249doc 4:02250Batch cycle counterUINT32ABCDRead
HR2251doc 4:02252Cleaning cycle timeUINT32ABCDsRead/write
HR2290doc 4:02291Volume per pulseFLOAT32ABCDm3Read/write
HR2292doc 4:02293Pulse PolarityUINT16Read/write0 = Negative; 1 = Positive
HR2293doc 4:02294Pulse TimeoutFLOAT32ABCDsRead/write
HR2300doc 4:02301Input FunctionUINT16Read/write0 = Off; 1 = Start Batch; 2 = Hold/Continue; 3 = Stop Batch; 4 = Zero Adjust (only SV); 5 = Totalizer reset; 6 = Force output; 7 = Freeze output; 8 = Qmax 2 (night); 9 = Manual cleaning
HR2301doc 4:02302Totalizer resetUINT16Read/write0 = Totalizer 1; 1 = Totalizer 2; 2 = Totalizer 1 + 2
HR2302doc 4:02303Force outputFLOAT32ABCD1/100%Read/write
HR2400doc 4:02401Sensor sizeFLOAT32ABCDmRead/write
HR2402doc 4:02403Calibration factorFLOAT32ABCDRead/write
HR2404doc 4:02405Correction factorFLOAT32ABCDRead/write
HR2420doc 4:02421Excitation frequencyUINT16Read/write0 = 3.125 Hz (50 Hz); 1 = 6.25 Hz (50 Hz); 2 = 12.5 Hz (50 Hz); 3 = 25 Hz (50 Hz); 4 = 1.5625 Hz (50 Hz); 5 = 44 Hz (only SV); 6 = 2.0833 Hz; 7 = 1.875 Hz (60 Hz); 8 = 3.75 Hz (60 Hz); 9 = 7.5 Hz (60 Hz); 10 = 15 Hz (60 Hz); 11 = 30 Hz (60 Hz)
HR2500doc 4:02501Converter typeSTRING[20]Read
HR2510doc 4:02511Converter code no.STRING[20]Read
HR2520doc 4:02521Converter serial no.STRING[20]Read
HR2530doc 4:02531Converter SW versionSTRING[20]Read
HR2540doc 4:02541Sensor typeSTRING[20]Read
HR2550doc 4:02551Sensor code no.STRING[20]Read
HR2560doc 4:02561Sensor serial no.STRING[20]Read
HR2570doc 4:02571Sensor sizeSTRING[20]Read
HR2700doc 4:02701Operating timeUINT32ABCDsRead
HR2900doc 4:02901LanguageUINT16Read/write0 = English; 1 = Deutsch; 2 = Français; 3 = Dansk; 4 = Svenska; 5 = Suomeksi; 6 = Russian; 7 = Español; 8 = Italiano; 9 = Português; 10 = Polski
HR2906doc 4:02907Volumeflow unitUINT16Read/write
HR2907doc 4:02908Volumeflow pointUINT16Read/write
HR2912doc 4:02913Totalizer 1 unitUINT16Read/write
HR2913doc 4:02914Totalizer 1 pointUINT16Read/write
HR2914doc 4:02915Totalizer 2 unitUINT16Read/write
HR2915doc 4:02916Totalizer 2 pointUINT16Read/write
HR3002doc 4:03003Absolute VolumeflowFLOAT32ABCDRead
HR3014doc 4:03015Totalizer 1FLOAT64ABCDRead
HR3018doc 4:03019Totalizer 2/BatchFLOAT64ABCDRead
HR3022doc 4:03023Totalizer 1 (float)FLOAT32ABCDRead
HR3024doc 4:03025Totalizer 2/Batch (float)FLOAT32ABCDRead
HR3200doc 4:03201System statusBITMAP16Readbit 0 = RunIndicator; bit 1 = ErrorPendingOn; bit 2 = ErrPendChanged; bit 3 = Batching; bit 4 = BatchPaused; bit 5 = Zeroadjusting; bit 6 = Totalizer1Hold; bit 7 = Totalizer2Hold
HR3201doc 4:03202Error pending 1UINT16Read0xFFFF = no error
HR3202doc 4:03203Error pending 2UINT16Read
HR3203doc 4:03204Error pending 3UINT16Read
HR3204doc 4:03205Error pending 4UINT16Read
HR3205doc 4:03206Error pending 5UINT16Read
HR3206doc 4:03207Error pending 6UINT16Read
HR3207doc 4:03208Error pending 7UINT16Read
HR3208doc 4:03209Error pending 8UINT16Read
HR3209doc 4:03210Error pending 9UINT16Read
HR3210doc 4:03211Batch statusUINT16Read0 = Idle; 1 = Ready; 2 = Running; 3 = Paused
HR3211doc 4:03212Zero adjust progressUINT16Read0 = Idle; 1 = Ready; 2 = Running

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module

What Modbus registers does the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module have?

This map lists 119 registers: 8 coils, 111 holding registers. 72 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every row prints both the Modbus register (4:0xxxx / 0:0xxxx, 1-based) and the Modbus address (0-based) sent on the wire; this map uses the address column. The manual's own example reads absolute massflow 4:03001 with query address 0x0BB8 (3000).

What byte order does the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module?

Start with HR 3002 Absolute Volumeflow (Volume flow); HR 3014 Totalizer 1 (Totalizer 1 (double)); HR 3018 Totalizer 2/Batch (Totalizer 2 / batch (double)); HR 3200 System status (System status bits); HR 3201 Error pending 1 (First pending error); HR 2906 Volumeflow unit (Volume flow unit ID).

How do I enable Modbus control of the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module?

Fit the USM II Modbus RTU add-on module in the transmitter. The module adds a 'MODBUS RTU module' menu (between Reset mode and Service mode) for address, baud, parity/framing, timeouts and TAG; the same settings are writable at addresses 528-530.

Where is the official Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module Modbus documentation?

The source is SITRANS F Modbus RTU RS 485 (USM II) communication module, Operating Instructions (A5E00753974-AB), revision 2021-03, published free by Siemens at https://cache.industry.siemens.com/dl/files/906/44880906/att_70364/v1/A5E00753974-ABen_USMII_MODBUS_AOM_OI_en-US.pdf.

More Siemens Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: SITRANS F Modbus RTU RS 485 (USM II) communication module, Operating Instructions · A5E00753974-AB · rev. 2021-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.