- SITRANS F M MAG 6000 with USM II Modbus RTU module
Sensor (flow transmitter) · Modbus register map
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module Modbus register map
Updated 17 November 2026
The MAG 6000 electromagnetic flow transmitter gets a Modbus RTU slave by fitting the USM II RS-485 add-on module. Data is held in holding registers and coils only. This map covers volume flow and totalizers (float and double), driver and identity registers, basic, totalizer, output, input, sensor and display settings, system status and the totalizer/batch/zero-adjust coils.
This page lists 119 Modbus registers for the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module — 72 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Siemens’s own free documentation (linked below) and checked against it.
- Manufacturer
- Siemens
- Model
- SITRANS F M MAG 6000 with USM II Modbus RTU module
- Equipment type
- Sensor (flow transmitter)
- Registers
- 119 (72 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- MAG 6000, MAG 6000 I, SITRANS FM MAG 6000
Integration notes: Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
Read holding registers (FC 03) from address 3002 for volume flow and 3014/3018 for the double totalizers; values are big-endian IEEE, high word first. Use coils 9-12 to reset or hold the totalizers.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 3002 | Absolute Volumeflow | FLOAT32 ABCD | Volume flow | Read |
| HR 3014 | Totalizer 1 | FLOAT64 ABCD | Totalizer 1 (double) | Read |
| HR 3018 | Totalizer 2/Batch | FLOAT64 ABCD | Totalizer 2 / batch (double) | Read |
| HR 3200 | System status | BITMAP16 | System status bits | Read |
| HR 3201 | Error pending 1 | UINT16 | First pending error | Read |
| HR 2906 | Volumeflow unit | UINT16 | Volume flow unit ID | Read/write |
Enable Modbus control & writes
Fit the USM II Modbus RTU add-on module in the transmitter. The module adds a 'MODBUS RTU module' menu (between Reset mode and Service mode) for address, baud, parity/framing, timeouts and TAG; the same settings are writable at addresses 528-530.
Byte order & addressing
- Use the address column (0-based); 4:03003 is address 3002.
- Max 26 registers per read and 25 per write.
- No input registers or discrete inputs: everything is holding registers and coils.
Network setup
- Factory settings: address 1, 19200 baud, even parity, 1 stop bit; response delay 0, interframe space 3.5 characters.
- Baud 1200-115200; framing 8E1, 8O1, 8N2 or 8N1.
- RS-485 2-wire on screw terminals; up to 31 devices per segment without repeaters.
- Modbus settings live in the module; after swapping the module they must be written again from the master.
Watch out for
- The module does not react to broadcasts that need an answer; broadcast writes get no reply.
- If the reply is not ready within the response timeout the module returns exception 6 (busy); repeat the request.
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0:00001 | Restart MODBUS communication | Write 1 to restart; reads 0. | BIT | Read/write | ||||
| CO | 8doc 0:00009 | Start auto zero adjust | Write 1 to start; reads 1 while busy. | BIT | Read/write | ||||
| CO | 9doc 0:00010 | Reset totalizer 1 | Write 1 to reset; reads 0. | BIT | Read/write | ||||
| CO | 10doc 0:00011 | Hold totalizer 1 | 1 = hold, 0 = run; reads back held state. | BIT | Read/write | ||||
| CO | 11doc 0:00012 | Reset totalizer 2 | Write 1 to reset; reads 0. | BIT | Read/write | ||||
| CO | 12doc 0:00013 | Hold totalizer 2 | 1 = hold, 0 = run; reads back held state. | BIT | Read/write | ||||
| CO | 13doc 0:00014 | Start batch | 1 = start, 0 = stop batch. | BIT | Read/write | ||||
| CO | 14doc 0:00015 | Pause batch | 1 = pause, 0 = resume batch. | BIT | Read/write | ||||
| HR | 500doc 4:00501 | No. of ParityErrors | UINT16 | Read | |||||
| HR | 501doc 4:00502 | No. of FramingErrors | UINT16 | Read | |||||
| HR | 503doc 4:00504 | No. of CRC Errors | UINT16 | Read | |||||
| HR | 504doc 4:00505 | No. of Ok Messages (received) | UINT16 | Read | |||||
| HR | 507doc 4:00508 | InterFrameSpace | UINT32 | ABCD | us | Read | |||
| HR | 511doc 4:00512 | Response Timeout | UINT16 | ms | Read/write | ||||
| HR | 512doc 4:00513 | Response Delay | UINT16 | ms | Read/write | ||||
| HR | 513doc 4:00514 | 10xInterFrameSpace (10 x chars) | UINT16 | Read/write | |||||
| HR | 514doc 4:00515 | Baudrate as double word | UINT32 | ABCD | Read | ||||
| HR | 528doc 4:00529 | Device address (1 - 247) | UINT16 | Read/write | |||||
| HR | 529doc 4:00530 | Baudrate | UINT16 | Read/write | 0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 76800; 8 = 115200 | ||||
| HR | 530doc 4:00531 | Parity/framing | UINT16 | Read/write | 0 = 8, E, 1; 1 = 8, O, 1; 2 = 8, N, 2; 3 = 8, N, 1 | ||||
| HR | 600doc 4:00601 | Slave ID | UINT16 | Read | 0x2A = Siemens | ||||
| HR | 601doc 4:00602 | Run indicator | UINT16 | Read | 0x00 = not running; 0xFF = running | ||||
| HR | 602doc 4:00603 | Product code | UINT16 | Read | 24 = MAG 6000; 25 = MASS 6000 | ||||
| HR | 605doc 4:00606 | Flowmeter revision | UINT16 | Read | |||||
| HR | 606doc 4:00607 | MODBUS revision | UINT16 | Read | |||||
| HR | 607doc 4:00608 | Manufacturer name | STRING[12] | Read | |||||
| HR | 613doc 4:00614 | Product name | STRING[18] | Read | |||||
| HR | 622doc 4:00623 | MODBUS module name | STRING[12] | Read | |||||
| HR | 640doc 4:00641 | TAG | STRING[18] | Read/write | |||||
| HR | 649doc 4:00650 | MODBUS module SW version | STRING[20] | Read | |||||
| HR | 659doc 4:00660 | MODBUS module HW version | UINT16 | Read | |||||
| HR | 680doc 4:00681 | Last Coil Error (CoilAddr) | UINT16 | Read | |||||
| HR | 681doc 4:00682 | Last Coil Error (ErrorNo) | UINT16 | Read | |||||
| HR | 682doc 4:00683 | Last HoldReg Error (HoldReg Addr) | UINT16 | Read | |||||
| HR | 683doc 4:00684 | Last HoldReg Error (ErrorNo) | UINT16 | Read | |||||
| HR | 2000doc 4:02001 | Flow direction | UINT16 | Read/write | 0 = Negative; 1 = Positive | ||||
| HR | 2005doc 4:02006 | Q max. | FLOAT32 | ABCD | m3/s | Read/write | |||
| HR | 2007doc 4:02008 | Q max. 2 (Night) | FLOAT32 | ABCD | m3/s | Read/write | |||
| HR | 2025doc 4:02026 | Low flow cut off | FLOAT32 | ABCD | Read/write | ||||
| HR | 2029doc 4:02030 | Empty pipe on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2031doc 4:02032 | Error level | UINT16 | Read/write | 1 = Warning; 2 = Permanent; 3 = Fatal | ||||
| HR | 2032doc 4:02033 | Zero adjust mode | UINT16 | Read/write | 0 = Auto; 1 = Manual | ||||
| HR | 2033doc 4:02034 | Manual zero adjust | FLOAT32 | ABCD | m3/s | Read/write | |||
| HR | 2040doc 4:02041 | Mains Frequency | UINT16 | Read/write | 0 = 50 Hz; 1 = 60 Hz | ||||
| HR | 2101doc 4:02102 | Totalizer 1 direction | UINT16 | Read/write | 0 = Reverse; 1 = Forward; 2 = Net | ||||
| HR | 2103doc 4:02104 | Totalizer 2 direction | UINT16 | Read/write | 0 = Reverse; 1 = Forward; 2 = Net | ||||
| HR | 2200doc 4:02201 | Current Output 1 selection | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2201doc 4:02202 | Current Output 1 direction | UINT16 | Read/write | 1 = Unidirectional; 2 = Bidirectional | ||||
| HR | 2202doc 4:02203 | Current Output 1 range | UINT16 | Read/write | 0 = 0 - 20 mA; 1 = 4 - 20 mA; 2 = 4 - 20 mA + Alarm | ||||
| HR | 2203doc 4:02204 | Current Output 1 time constants | FLOAT32 | ABCD | Read/write | ||||
| HR | 2205doc 4:02206 | Digital Output 1 function | UINT16 | Read/write | 0 = Off; 1 = Pulse; 2 = Frequency; 3 = Error Level; 4 = Error Number; 5 = Direction/Limit; 6 = Batch | ||||
| HR | 2207doc 4:02208 | Pulse 1 direction | UINT16 | Read/write | 1 = Unidirectional; 2 = Bidirectional | ||||
| HR | 2208doc 4:02209 | Pulse 1 width | UINT16 | Read/write | 0 = 64 us; 1 = 130 us; 2 = 260 us; 3 = 510 us; 4 = 1.0 ms; 5 = 2.0 ms; 6 = 4.1 ms; 7 = 8.2 ms; 8 = 16 ms; 9 = 33 ms; 10 = 66 ms; 11 = 130 ms; 12 = 260 ms; 13 = 520 ms; 14 = 1.0 s; 15 = 2.1 s; 16 = 4.2 s | ||||
| HR | 2211doc 4:02212 | Frequency 1 Direction | UINT16 | Read/write | 1 = Unidirectional; 2 = Bidirectional | ||||
| HR | 2212doc 4:02213 | Frequency 1 Fmax. | UINT16 | Read/write | 0 = 10 kHz; 1 = 5 kHz; 2 = 1 kHz; 3 = 500 Hz | ||||
| HR | 2213doc 4:02214 | Frequency 1 Timeconstants | FLOAT32 | ABCD | Read/write | ||||
| HR | 2216doc 4:02217 | Limit Digital mode | UINT16 | Read/write | 0 = 1 setpoint; 1 = 2 setpoints | ||||
| HR | 2217doc 4:02218 | Limit Digital Setpoint min. | FLOAT32 | ABCD | 1/100% | Read/write | |||
| HR | 2219doc 4:02220 | Limit Digital Setpoint max. | FLOAT32 | ABCD | 1/100% | Read/write | |||
| HR | 2221doc 4:02222 | Limit Digital Hysteresis | FLOAT32 | ABCD | 1/100% | Read/write | |||
| HR | 2223doc 4:02224 | Relay Output 1 function | UINT16 | Read/write | 0 = Off; 3 = Error Level; 4 = Error Number; 5 = Direction/Limit; 6 = Batch; 7 = Cleaning | ||||
| HR | 2225doc 4:02226 | Limit Relay mode | UINT16 | Read/write | 0 = 1 setpoint; 1 = 2 setpoints | ||||
| HR | 2226doc 4:02227 | Limit Relay Setpoint min. | FLOAT32 | ABCD | 1/100% | Read/write | |||
| HR | 2228doc 4:02229 | Limit Relay Setpoint max. | FLOAT32 | ABCD | 1/100% | Read/write | |||
| HR | 2230doc 4:02231 | Limit Relay Hysteresis | FLOAT32 | ABCD | 1/100% | Read/write | |||
| HR | 2232doc 4:02233 | Error number (0-255) | UINT16 | Read/write | |||||
| HR | 2234doc 4:02235 | Batch Quantity | FLOAT32 | ABCD | m3 | Read/write | |||
| HR | 2236doc 4:02237 | Batch Compensation | FLOAT32 | ABCD | m3 | Read/write | |||
| HR | 2240doc 4:02241 | Batch Time error on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2241doc 4:02242 | Batch time | UINT32 | ABCD | s | Read/write | |||
| HR | 2243doc 4:02244 | Batch overrun on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2244doc 4:02245 | Batch overrun error | FLOAT32 | ABCD | m3 | Read/write | |||
| HR | 2246doc 4:02247 | Batch counter up/down | UINT16 | Read/write | 0 = Down; 1 = Up | ||||
| HR | 2247doc 4:02248 | Batch Time constants | FLOAT32 | ABCD | Read/write | ||||
| HR | 2249doc 4:02250 | Batch cycle counter | UINT32 | ABCD | Read | ||||
| HR | 2251doc 4:02252 | Cleaning cycle time | UINT32 | ABCD | s | Read/write | |||
| HR | 2290doc 4:02291 | Volume per pulse | FLOAT32 | ABCD | m3 | Read/write | |||
| HR | 2292doc 4:02293 | Pulse Polarity | UINT16 | Read/write | 0 = Negative; 1 = Positive | ||||
| HR | 2293doc 4:02294 | Pulse Timeout | FLOAT32 | ABCD | s | Read/write | |||
| HR | 2300doc 4:02301 | Input Function | UINT16 | Read/write | 0 = Off; 1 = Start Batch; 2 = Hold/Continue; 3 = Stop Batch; 4 = Zero Adjust (only SV); 5 = Totalizer reset; 6 = Force output; 7 = Freeze output; 8 = Qmax 2 (night); 9 = Manual cleaning | ||||
| HR | 2301doc 4:02302 | Totalizer reset | UINT16 | Read/write | 0 = Totalizer 1; 1 = Totalizer 2; 2 = Totalizer 1 + 2 | ||||
| HR | 2302doc 4:02303 | Force output | FLOAT32 | ABCD | 1/100% | Read/write | |||
| HR | 2400doc 4:02401 | Sensor size | FLOAT32 | ABCD | m | Read/write | |||
| HR | 2402doc 4:02403 | Calibration factor | FLOAT32 | ABCD | Read/write | ||||
| HR | 2404doc 4:02405 | Correction factor | FLOAT32 | ABCD | Read/write | ||||
| HR | 2420doc 4:02421 | Excitation frequency | UINT16 | Read/write | 0 = 3.125 Hz (50 Hz); 1 = 6.25 Hz (50 Hz); 2 = 12.5 Hz (50 Hz); 3 = 25 Hz (50 Hz); 4 = 1.5625 Hz (50 Hz); 5 = 44 Hz (only SV); 6 = 2.0833 Hz; 7 = 1.875 Hz (60 Hz); 8 = 3.75 Hz (60 Hz); 9 = 7.5 Hz (60 Hz); 10 = 15 Hz (60 Hz); 11 = 30 Hz (60 Hz) | ||||
| HR | 2500doc 4:02501 | Converter type | STRING[20] | Read | |||||
| HR | 2510doc 4:02511 | Converter code no. | STRING[20] | Read | |||||
| HR | 2520doc 4:02521 | Converter serial no. | STRING[20] | Read | |||||
| HR | 2530doc 4:02531 | Converter SW version | STRING[20] | Read | |||||
| HR | 2540doc 4:02541 | Sensor type | STRING[20] | Read | |||||
| HR | 2550doc 4:02551 | Sensor code no. | STRING[20] | Read | |||||
| HR | 2560doc 4:02561 | Sensor serial no. | STRING[20] | Read | |||||
| HR | 2570doc 4:02571 | Sensor size | STRING[20] | Read | |||||
| HR | 2700doc 4:02701 | Operating time | UINT32 | ABCD | s | Read | |||
| HR | 2900doc 4:02901 | Language | UINT16 | Read/write | 0 = English; 1 = Deutsch; 2 = Français; 3 = Dansk; 4 = Svenska; 5 = Suomeksi; 6 = Russian; 7 = Español; 8 = Italiano; 9 = Português; 10 = Polski | ||||
| HR | 2906doc 4:02907 | Volumeflow unit | UINT16 | Read/write | |||||
| HR | 2907doc 4:02908 | Volumeflow point | UINT16 | Read/write | |||||
| HR | 2912doc 4:02913 | Totalizer 1 unit | UINT16 | Read/write | |||||
| HR | 2913doc 4:02914 | Totalizer 1 point | UINT16 | Read/write | |||||
| HR | 2914doc 4:02915 | Totalizer 2 unit | UINT16 | Read/write | |||||
| HR | 2915doc 4:02916 | Totalizer 2 point | UINT16 | Read/write | |||||
| HR | 3002doc 4:03003 | Absolute Volumeflow | FLOAT32 | ABCD | Read | ||||
| HR | 3014doc 4:03015 | Totalizer 1 | FLOAT64 | ABCD | Read | ||||
| HR | 3018doc 4:03019 | Totalizer 2/Batch | FLOAT64 | ABCD | Read | ||||
| HR | 3022doc 4:03023 | Totalizer 1 (float) | FLOAT32 | ABCD | Read | ||||
| HR | 3024doc 4:03025 | Totalizer 2/Batch (float) | FLOAT32 | ABCD | Read | ||||
| HR | 3200doc 4:03201 | System status | BITMAP16 | Read | bit 0 = RunIndicator; bit 1 = ErrorPendingOn; bit 2 = ErrPendChanged; bit 3 = Batching; bit 4 = BatchPaused; bit 5 = Zeroadjusting; bit 6 = Totalizer1Hold; bit 7 = Totalizer2Hold | ||||
| HR | 3201doc 4:03202 | Error pending 1 | UINT16 | Read | 0xFFFF = no error | ||||
| HR | 3202doc 4:03203 | Error pending 2 | UINT16 | Read | |||||
| HR | 3203doc 4:03204 | Error pending 3 | UINT16 | Read | |||||
| HR | 3204doc 4:03205 | Error pending 4 | UINT16 | Read | |||||
| HR | 3205doc 4:03206 | Error pending 5 | UINT16 | Read | |||||
| HR | 3206doc 4:03207 | Error pending 6 | UINT16 | Read | |||||
| HR | 3207doc 4:03208 | Error pending 7 | UINT16 | Read | |||||
| HR | 3208doc 4:03209 | Error pending 8 | UINT16 | Read | |||||
| HR | 3209doc 4:03210 | Error pending 9 | UINT16 | Read | |||||
| HR | 3210doc 4:03211 | Batch status | UINT16 | Read | 0 = Idle; 1 = Ready; 2 = Running; 3 = Paused | ||||
| HR | 3211doc 4:03212 | Zero adjust progress | UINT16 | Read | 0 = Idle; 1 = Ready; 2 = Running |
Notes on this map
- Word order: the manual states the module is big-endian, most significant byte first, and its float table and example frame (4:03001 read as 40 C3 52 93 = 6.10383 kg/s) put the high word in register N. Floats, doubles and double words are therefore listed as ABCD.
- 'Byte' values sit in the low byte of one register and are listed as UINT16 (0-255).
- Units of the process values and totalizers follow the unit registers (2904-2917, ID tables in Appendix B.1/B.2). The 'point' registers set the number of decimals (0-6) shown on the display.
- Adding 10000 to the address of a writable register returns its minimum allowed value, adding 20000 returns its maximum (these mirror registers are not listed).
- Values printed as (1/100%) are fractions where 1.0 = 100 % (the manual's example: 0.02 = 2 %).
- Left out: capability bits (603, 3-byte array) and the 54-byte error pending / error log lists (2702, 2729); their record layout is in Appendix B.4.
- Error numbers are listed in the SITRANS F M / F C transmitter operating instructions, not in this manual.
- MAG 6000 has no mass, density or temperature values; 3000 and 3004-3012 are MASS 6000 only.
- Volume flow (3002) and totalizers are in the customer units set at 2906, 2912 and 2914 (defaults m3/s and m3); Q max and other settings are always in m3/s / m3.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
What Modbus registers does the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module have?
This map lists 119 registers: 8 coils, 111 holding registers. 72 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every row prints both the Modbus register (4:0xxxx / 0:0xxxx, 1-based) and the Modbus address (0-based) sent on the wire; this map uses the address column. The manual's own example reads absolute massflow 4:03001 with query address 0x0BB8 (3000).
What byte order does the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module?
Start with HR 3002 Absolute Volumeflow (Volume flow); HR 3014 Totalizer 1 (Totalizer 1 (double)); HR 3018 Totalizer 2/Batch (Totalizer 2 / batch (double)); HR 3200 System status (System status bits); HR 3201 Error pending 1 (First pending error); HR 2906 Volumeflow unit (Volume flow unit ID).
How do I enable Modbus control of the Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module?
Fit the USM II Modbus RTU add-on module in the transmitter. The module adds a 'MODBUS RTU module' menu (between Reset mode and Service mode) for address, baud, parity/framing, timeouts and TAG; the same settings are writable at addresses 528-530.
Where is the official Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module Modbus documentation?
The source is SITRANS F Modbus RTU RS 485 (USM II) communication module, Operating Instructions (A5E00753974-AB), revision 2021-03, published free by Siemens at https://cache.industry.siemens.com/dl/files/906/44880906/att_70364/v1/A5E00753974-ABen_USMII_MODBUS_AOM_OI_en-US.pdf.
More Siemens Modbus register maps
- Sensor (room humidity / temperature)
Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)
Siemens QFA3150/MO room relative humidity and temperature sensor, basic documentation edition a (2021-01).
Also known as: QFA3150/MO, S55720-S535 - Sensor (duct humidity / temperature / CO2 / VOC)
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Siemens QFM9150/MO duct humidity/temperature sensor and QPM9152/MO duct air quality (CO2, VOC, humidity, temperature) sensor, basic documentation edition a (2022-12).
Also known as: QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585 - Protection relay
Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)
Reyrolle 7SR10 overcurrent / earth-fault relays, default Modbus RTU point list per Communication Protocols manual C53000-L7040-C002-7 (edition 11.2025, V01.00).
Also known as: 7SR10 Argus, Reyrolle 7SR10, 7SR1003, 7SR1004 - Protection relay
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Reyrolle 7SR11 (non-directional) and 7SR12 (directional) Argus overcurrent relays, default Modbus RTU point list in the 7SR11 & 7SR12 Complete Technical Manual (Chapter 4, Data Communications, 2015).
Also known as: 7SR11 Argus, 7SR12 Argus, Reyrolle 7SR11, Reyrolle 7SR12, 7SR120 - Energy meter
Siemens SENTRON PAC2200
SENTRON 7KM PAC2200 Modbus TCP and Modbus RTU variants (5 A and 65 A), per Equipment Manual 12/2022.
Also known as: 7KM PAC2200 - Power meter
Siemens SENTRON PAC3200
SENTRON PAC3200 (7KM2111/7KM2112), Ethernet port and optional PAC RS485 expansion module, per manual edition 02/2008.
Also known as: 7KM2112-0BA00-2AA0, 7KM2112-0BA00-3AA0, 7KM2111-1BA00-3AA0, 7KM PAC3200 - Circuit breaker trip unit (power meter)
Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
Siemens SENTRON 3WL air circuit breakers with a COM16 Modbus RTU communication module and, for voltage/power/energy values, the metering function (PLUS), per system manual A5E02126891-02.
Also known as: SENTRON WL, 3WL, 3WL COM16, COM16 - Power meter
Siemens SICAM P power meter (Modbus RTU/ASCII)
SICAM P (7KG7xxx) power meters with the Modbus serial interface, per manual E50417-B1076-C241-A5 (release 11.2012).
Also known as: 7KG7750, 7KG7751, 7KG7755, SICAM P50, SICAM P55, 7KG7610, 7KG7660 - Power meter (power quality)
Siemens SICAM P850 / P855 power monitoring and PQ device
SICAM P850 / P855 (7KG85x) with Modbus TCP or Modbus RTU, firmware V3.11, per communication manual E50417-C1040-C482-B1 (05.2024).
Also known as: 7KG85, 7KG85X, SICAM P850, SICAM P855 - Motor management and protection relay
Siemens SIMOCODE pro V Modbus RTU basic unit
SIMOCODE pro V Modbus RTU basic units, per Configuration Manual 04/2015 (A5E33498234002A/RS-AA/001).
Also known as: SIMOCODE pro V Modbus, SIMOCODE pro V Modbus RTU - Variable frequency drive
Siemens SINAMICS G120 / G120C (Modbus RTU)
SINAMICS G120 with an RS485 Control Unit (CU230P-2 HVAC/BT, CU240B-2, CU240E-2 / -2 F, CU250S-2), G120C USS/MB and G110M CU240M USS, firmware V4.7, per Fieldbuses function manual A5E34229197B AA. Not SINAMICS G120X, which has its own documentation.
Also known as: G120C USS/MB, CU230P-2 HVAC, CU230P-2 BT, CU240B-2, CU240E-2, CU240E-2 F, CU250S-2, G110M CU240M USS, G120P - Variable frequency drive
Siemens SINAMICS V20 inverter (Modbus RTU)
SINAMICS V20 basic inverters (1AC 230 V 6SL3210-5BB.. and 3AC 400 V 6SL3210-5BE..) using the built-in RS485 port with P2023 = 2 (Modbus), per operating instructions A5E34559884-006 (11/2016).
Also known as: V20, 6SL3210-5BB, 6SL3210-5BE - Sensor (flow transmitter)
Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module
SITRANS F C MASS 6000 Coriolis flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MASS 6000, SITRANS FC MASS 6000 - EV charger
Siemens VersiCharge AC series wallbox (Modbus map)
VersiCharge AC series chargers with firmware V2.135 or later (per-register minimum firmware is given in the source).
Also known as: VersiCharge, VersiCharge AC
Other valves, actuators & sensors register maps
- Sensor (humidity / temperature)
Teracom TSH300v3 RS-485 humidity and temperature sensor
TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.
Also known as: TSH300, TSH300v3 - Sensor (gas density)
Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map)
Trafag 8775 and 879x (8791/8792/8793) running the 'Legacy' Modbus configuration of software description H73622a (10/2025).
Also known as: 8775, 8791, 8792, 8793, 879x, Trafag gas density monitor - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272 - Sensor (humidity and temperature probe)
Vaisala XMP10 humidity and temperature probe (Modbus RTU)
XMP10 probes ordered with (or switched to) Modbus RTU output, user guide M213279EN-A.
Also known as: XMP10, HUMICAP XMP10, Vaisala XMP10 - Water treatment controller (Sensor / controller)
Walchem WebMaster WIND series Modbus TCP/IP option (s825)
Walchem WebMaster WIND-series controllers with the Modbus TCP/IP option, software s825v008 and higher, per manual 180413 Rev A1.
Also known as: WIND, WebMaster WIND, s825
All valves, actuators & sensors Modbus register maps →
Source: SITRANS F Modbus RTU RS 485 (USM II) communication module, Operating Instructions · A5E00753974-AB · rev. 2021-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.