- 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map)
Sensor (gas density) · Modbus register map
Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map) Modbus register map
Updated 17 November 2026
The Trafag 8775 sensor and 879x hybrid monitor measure the density of a specified gas or gas mixture with a pair of quartz oscillators, and report it over Modbus RTU. This map is the manual's 'Legacy' configuration: scaled 16-bit density, pressure and temperature, identification, serial settings and a sensor-status discrete input.
This page lists 13 Modbus registers for the Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trafag’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trafag
- Model
- 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map)
- Equipment type
- Sensor (gas density)
- Registers
- 13 (4 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- 8775, 8791, 8792, 8793, 879x, Trafag gas density monitor
Integration notes: Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map)
Read input registers 0-3 (function 04) for density, pressure and temperature as scaled integers, and discrete input 0 (function 02) for sensor status.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Gas density | UINT16 | Gas density, kg/m3 x 0.01 | Read |
| IR 1 | Gas pressure (abs, @20°C) | UINT16 | Pressure @20°C, kPa x 0.1 | Read |
| IR 2 | Gas temperature | UINT16 | Gas temperature, K x 0.1 | Read |
| DI 0 | Sensor status | BIT | Sensor error flag | Read |
Enable Modbus control & writes
Modbus RTU is always active. Server ID, baud rate and parity are holding registers 2-5; register 8 shows which of them are write-protected.
Byte order & addressing
- 0xFFFF in a measurement register means its range was exceeded.
- Temperature is in kelvin (x 0.1).
Network setup
- Terminate both bus ends with 120 Ohm (jumper J4 on hybrid units) and use 560 Ohm line polarisation.
Watch out for
- Confirm the unit runs the Legacy map; the Standard map puts floats at the same addresses.
Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| DI | 0 | Sensor status | 0 = working properly, 1 = sensor error. | BIT | Read | ||||
| IR | 0 | Gas density | 0xFFFF when out of range. | UINT16 | × 0.01 | kg/m3 | Read | ||
| IR | 1 | Gas pressure (abs, @20°C) | 0xFFFF when out of range. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 2 | Gas temperature | UINT16 | × 0.1 | K | Read | |||
| IR | 3 | Gas pressure (abs, at gas temperature) | 0xFFFF when out of range. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 4 | Server ID | 1-247. | UINT16 | Read | ||||
| IR | 5doc 5+6 | Serial number | Big-endian; e.g. 0x075BCD15 = 123456-789. | UINT32 | ABCD | Read | |||
| IR | 7 | Firmware release version | UINT16 | × 0.01 | Read | ||||
| HR | 2 | Server ID | 1-247. | UINT16 | Read/write | ||||
| HR | 3doc 3+4 | Baud rate | 1200, 2400, 4800, 9600, 14400, 19200, 28800, 38400, 56000 or 57600. | UINT32 | ABCD | baud | Read/write | ||
| HR | 5 | Parity | UINT16 | Read/write | 0 = None (2 stop bits); 1 = Odd (1 stop bit); 2 = Even (1 stop bit) | ||||
| HR | 7 | Change to bootloader | UINT16 | Read/write | 1 = Enter bootloader mode for 10 s | ||||
| HR | 8 | Write permissions | Bit = 0 means writable, 1 means locked. | BITMAP16 | Read | bit 0 = Server ID locked; bit 1 = Baud rate locked; bit 2 = Parity locked |
Notes on this map
- The manual describes two Modbus configurations, 'Legacy' and 'Standard', with different maps at the same addresses. This file is the Legacy map only; it does not say which units ship with which.
- Left out: the Standard map (float density/pressure/temperature at 0-48, hour meter, status flag words, serial number U64), because the manual gives no word order for its floats and 32/64-bit values.
- 32-bit values in the Legacy map are marked big-endian; the serial-number example (0x075BCD15 split as 0x075B, 0xCD15) shows high word first.
- Left out: 'Quartz frequency difference' (address 8), a fixed dummy value of 1000 from firmware V2.0, and 'Mode' (holding 6), marked non-functional.
- Parity choice also fixes stop bits: none = 2 stop bits, odd/even = 1 stop bit.
- Holding registers are stored in EEPROM; the manual warns that excessive writing can wear it out.
- Server ID can also be changed by broadcast using the serial number (section 5.4).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map)
What Modbus registers does the Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map) have?
This map lists 13 registers: 1 discrete input, 7 input registers, 5 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are protocol addresses. The manual's example reads density (address 0) with start address 0x0000 and the serial number (address 5) with 0x0005.
What byte order does the Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map)?
Start with IR 0 Gas density (Gas density, kg/m3 x 0.01); IR 1 Gas pressure (abs, @20°C) (Pressure @20°C, kPa x 0.1); IR 2 Gas temperature (Gas temperature, K x 0.1); DI 0 Sensor status (Sensor error flag).
How do I enable Modbus control of the Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map)?
Modbus RTU is always active. Server ID, baud rate and parity are holding registers 2-5; register 8 shows which of them are write-protected.
Where is the official Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map) Modbus documentation?
The source is Software Instruction Sensor/Monitor - 8775 Gas Density Sensor, 879x Hybrid Gas Density Monitor (H73622a), revision 2025-10, published free by Trafag at https://media.trafag.com/instruction/H73622a_87xx_Software-Instruction-Density-Sensor_A4.pdf.
Other valves, actuators & sensors register maps
- Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272 - Sensor (humidity and temperature probe)
Vaisala XMP10 humidity and temperature probe (Modbus RTU)
XMP10 probes ordered with (or switched to) Modbus RTU output, user guide M213279EN-A.
Also known as: XMP10, HUMICAP XMP10, Vaisala XMP10 - Water treatment controller (Sensor / controller)
Walchem WebMaster WIND series Modbus TCP/IP option (s825)
Walchem WebMaster WIND-series controllers with the Modbus TCP/IP option, software s825v008 and higher, per manual 180413 Rev A1.
Also known as: WIND, WebMaster WIND, s825 - Actuator / valve
Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)
Armstrong International Brain digital recirculation (thermostatic mixing) valves DRV25, DRV40 and DRV80 on their RS-485 Modbus RTU port, per IOM-776 Brain Modbus Networking (2024).
Also known as: DRV25, DRV40, DRV80, Brain, IOM-776 - Sensor (humidity / temperature probe)
E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU)
EE260 meteorological RH/T probe with RS-485 Modbus RTU, per Quick Guide QG_EE260 v1.3 (10-2025).
Also known as: EE260, E+E EE260, EE 260
All valves, actuators & sensors Modbus register maps →
Source: Software Instruction Sensor/Monitor - 8775 Gas Density Sensor, 879x Hybrid Gas Density Monitor · H73622a · rev. 2025-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.