- Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)
Actuator / valve · Modbus register map
Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU) Modbus register map
Updated 17 November 2026
Microprocessor-controlled hot-water mixing/recirculation valve that blends hot and cold water to a setpoint, with high/low alerts, an over-temperature error and a thermal-disinfection cycle. Over Modbus RTU it exposes holding registers for setpoint, status, outlet and inlet temperatures (0.1 °C), error codes, alarm limits, disinfection commands and an error log.
This page lists 46 Modbus registers for the Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU) — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Armstrong International’s own free documentation (linked below) and checked against it.
- Manufacturer
- Armstrong International
- Model
- Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)
- Equipment type
- Actuator / valve
- Registers
- 46 (23 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- DRV25, DRV40, DRV80, Brain, IOM-776
Integration notes: Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)
Wire the DRV's RS-485 port at 9600 8N1, then read registers 4 (status), 6 (outlet temperature) and 8 (error code). Write the setpoint to register 1 in tenths of °C; set register 4 to Off before changing configuration registers 400-411 and back to On afterwards.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 6 | Valve Outlet Temperature | UINT16 | Outlet (blended) temperature | Read |
| HR 1 | Setpoint Temperature | UINT16 | Setpoint | Read/write |
| HR 4 | Valve Status | UINT16 | Valve status / on-off-full cold | Read/write |
| HR 8 | Valve Error Code | UINT16 | Active error code | Read |
| HR 10 | Hot Inlet Temperature | UINT16 | Hot inlet temperature | Read/write |
| HR 11 | Cold Inlet Temperature | UINT16 | Cold inlet temperature | Read/write |
Enable Modbus control & writes
Modbus RTU is fixed at 9600 bps, no parity, 8 data bits, 1 stop bit. Set the unit address (1-31, read back in register 0) before connecting to the network: on DRV40/80 with the DRV Programming Software through the CN3 port (valve Off), on DRV25 with the SAGE mobile app over Bluetooth. The same software switches the CN2 network port from SAGE BS to Modbus.
Byte order & addressing
- Disinfection needs registers 23, 401 and 402 set up, then 0x6172 to 306 and 0x5452 to 307 within 10 seconds; writes out of order are rejected.
- DRV25: fit the CN10 jumper to switch in the end-of-line termination resistor if long cables or reflections make communication unreliable.
Network setup
- Function codes 03, 06 and 16 only.
- Modbus is 9600 bps only (BACnet supports higher rates).
- Use Cat5 twisted pair in a daisy chain; do not wire the valves in a star.
Watch out for
- An over-temperature error drives the valve full cold and stays latched until power is cycled.
- Abort (308) while the cycle is at full hot sends the valve full cold and shows Error Temp until power is cycled.
Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | Unit Address | Modbus address 1-31. | UINT16 | Read | ||||
| HR | 1 | Setpoint Temperature | Blend (outlet) setpoint. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 4 | Valve Status | Write 0/1/2 only; set Off before changing registers 400-411. | UINT16 | Read/write | 0 = Off (R/W); 1 = On (R/W); 2 = Full cold (R/W); 6 = Disinfection (read only); 7 = Error (read only) | |||
| HR | 6 | Valve Outlet Temperature | UINT16 | × 0.1 | °C | Read | |||
| HR | 8 | Valve Error Code | UINT16 | Read | 0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error | ||||
| HR | 10 | Hot Inlet Temperature | UINT16 | × 0.1 | °C | Read/write | |||
| HR | 11 | Cold Inlet Temperature | UINT16 | × 0.1 | °C | Read/write | |||
| HR | 23 | Disinfection Target Temperature | From the DRV maximum setpoint up to 99.9 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 110 | Valve Firmware Type Number | UINT16 | Read | |||||
| HR | 111 | Valve Firmware Version Number | UINT16 | Read | |||||
| HR | 112 | Valve Configuration ID | UINT16 | Read | |||||
| HR | 113 | Valve Configuration Version | UINT16 | Read | |||||
| HR | 115 | Adaptor (Bluetooth) Firmware Type | UINT16 | Read | |||||
| HR | 127 | ID of Valve Service Engineer | UINT16 | Read | |||||
| HR | 155 | Hours Since Last Disinfection | UINT16 | h | Read | ||||
| HR | 159 | Last Completed Disinfection Result | Logic value; meaning not listed. | UINT16 | Read | ||||
| HR | 306 | Arm Disinfection Command | Write 0x6172 to arm; trigger within 10 s. | UINT16 | Write | ||||
| HR | 307 | Trigger Disinfection Command | Write 0x5452 after arming to start disinfection. | UINT16 | Write | ||||
| HR | 308 | Abort Disinfection Command | Write any value to stop disinfection; from full hot the valve goes full cold (Error Temp). | UINT16 | Write | ||||
| HR | 309 | Soft Valve Reset Command | Write 0x1. | UINT16 | Write | ||||
| HR | 314 | Disinfection Cool Down | Write any value to end disinfection with full cold flow. | UINT16 | Write | ||||
| HR | 400 | DRV Serial Line Address | UINT16 | Read/write | 0 = Standard; 1 = Alternate | ||||
| HR | 401 | Disinfection Enable | UINT16 | Read/write | 0 = Disable; 64 = Enable | ||||
| HR | 402 | Disinfection Timeout | Alerts/errors suppressed for this time; max 1800 min. | UINT16 | min | Read/write | |||
| HR | 403 | High Alert | UINT16 | × 0.1 | °C | Read/write | |||
| HR | 404 | Low Alert | UINT16 | × 0.1 | °C | Read/write | |||
| HR | 405 | Error Temperature | Outlet above this drives the valve full cold and latches an error. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 406 | Relay Active | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 408 | Valve Temperature Units | UINT16 | Read/write | 0 = °F; 1 = °C | ||||
| HR | 409 | DRV Maximum Setpoint | UINT16 | × 0.1 | °C | Read/write | |||
| HR | 410 | DRV Minimum Setpoint | UINT16 | × 0.1 | °C | Read/write | |||
| HR | 411 | DRV Default Setpoint | Setpoint used after a power cycle. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 412 | Spare/Remote Thermistor 1 | UINT16 | × 0.1 | °C | Read | |||
| HR | 413 | Thermistor 2 | Printed as 'DRV Default Setpoint Thermistor 2'. | UINT16 | × 0.1 | °C | Read | ||
| HR | 433 | Reset Usage Logs Command | Write any value. | UINT16 | Write | ||||
| HR | 434 | Reset Error Logs | Write any value. | UINT16 | Write | ||||
| HR | 435 | Error 1 Code | UINT16 | Read | 0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error | ||||
| HR | 438 | Error 2 Code | UINT16 | Read | 0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error | ||||
| HR | 441 | Error 3 Code | UINT16 | Read | 0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error | ||||
| HR | 444 | Error 4 Code | UINT16 | Read | 0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error | ||||
| HR | 447 | Error 5 Code | UINT16 | Read | 0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error | ||||
| HR | 450 | Error 6 Code | UINT16 | Read | 0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error | ||||
| HR | 453 | Error 7 Code | UINT16 | Read | 0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error | ||||
| HR | 456 | Error 8 Code | UINT16 | Read | 0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error | ||||
| HR | 459 | Error 9 Code | UINT16 | Read | 0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error | ||||
| HR | 462 | Error 10 Code | UINT16 | Read | 0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error |
Notes on this map
- Armstrong International (hot-water group) is a different company from Armstrong Fluid Technology (pumps).
- Addressing: resolved as 0-based because the table includes a real register 0 (Unit Address), which only exists in 0-based numbering; the guide gives no example frame.
- Temperatures are listed as '0.1 Deg C' and are used with scale 0.1. Signedness is not stated; they are typed UINT16 (hot-water temperatures). Offset Temperature (407, 0.1 Deg C, R/W) is left out because an offset can be negative and the guide does not say whether it is signed.
- Left out: all two-part 'Long' values (serial number 106-107, manufacture date 108-109, commissioning date 116-117, operation count 121-122, on time 123-124, unused hours 128-129, disinfection dates 156-157, clock 288-289 and the error log dates), because the guide does not say which half is high; the 16-register Valve Identity/Location string (139-154), because character order is not stated; and register 114, printed with two conflicting rows.
- The DRV25/DRV40/DRV80 support columns in the table are graphical marks and are not reproduced; some registers (alerts, relay) apply only to DRV40/80.
- Allow at least 5 s between a write and the next read.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)
What Modbus registers does the Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU) have?
This map lists 46 registers: 46 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. IOM-776 lists plain register numbers starting at 0 (Unit Address is register 0) and supports function codes 03, 06 and 16. A register numbered 0 can only be a protocol (PDU) address, so the listed numbers are used as wire addresses.
What are the minimum Modbus registers to integrate the Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)?
Start with HR 6 Valve Outlet Temperature (Outlet (blended) temperature); HR 1 Setpoint Temperature (Setpoint); HR 4 Valve Status (Valve status / on-off-full cold); HR 8 Valve Error Code (Active error code); HR 10 Hot Inlet Temperature (Hot inlet temperature); HR 11 Cold Inlet Temperature (Cold inlet temperature).
How do I enable Modbus control of the Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)?
Modbus RTU is fixed at 9600 bps, no parity, 8 data bits, 1 stop bit. Set the unit address (1-31, read back in register 0) before connecting to the network: on DRV40/80 with the DRV Programming Software through the CN3 port (valve Off), on DRV25 with the SAGE mobile app over Bluetooth. The same software switches the CN2 network port from SAGE BS to Modbus.
Where is the official Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU) Modbus documentation?
The source is Guide to The Brain Networking Installation and Operation - Brain Modbus Networking (IOM-776 (1345022-W2-E)), revision 2024, published free by Armstrong International at https://armstronginternational.com/wp-content/uploads/IOM_TheBrain_DRV_Networking_IOM_NA_EN_20241209.pdf.
Other valves, actuators & sensors register maps
- Sensor (humidity / temperature probe)
E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU)
EE260 meteorological RH/T probe with RS-485 Modbus RTU, per Quick Guide QG_EE260 v1.3 (10-2025).
Also known as: EE260, E+E EE260, EE 260 - Sensor (disinfectant / chlorine)
JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU)
JUMO tecLine 202630, 202631, 202634, 202636, 202637 and 202681 sensors with RS-485 Modbus RTU (interface description V2.00, 2022-03-24).
Also known as: 202630, 202631, 202634, 202636, 202637, 202681, tecLine Cl2, tecLine TC, tecLine ClO2, tecLine O3, tecLine H2O2, tecLine PAA, tecLine Br, tecLine Cl2 OM - Sensor (weighing indicator)
Radwag PUE C32 / PUE HX7 / PUE HX5.EX weighing indicators
Radwag PUE C32, PUE HX7 and PUE HX5.EX weighing indicators per the May 2024 Modbus manual; platform 2 registers exist on PUE HX7 only.
Also known as: PUE C32, PUE HX7, PUE HX5.EX - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Actuator / valve (comfort module air damper)
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Swegon REACT Parasol Zenith comfort modules fitted with the Belimo Modbus actuator; Swegon Modbus settings sheet dated 2022-08-10.
Also known as: Parasol Zenith REACT, REACT damper actuator - Sensor (CO2 / pressure)
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
TSM400-4-CP per the Teracom TSM400-4-CP user manual TSM400-4-CP-R1.9.
Also known as: TSM400-4-CP
All valves, actuators & sensors Modbus register maps →
Source: Guide to The Brain Networking Installation and Operation - Brain Modbus Networking · IOM-776 (1345022-W2-E) · rev. 2024. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.