Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

Microprocessor-controlled hot-water mixing/recirculation valve that blends hot and cold water to a setpoint, with high/low alerts, an over-temperature error and a thermal-disinfection cycle. Over Modbus RTU it exposes holding registers for setpoint, status, outlet and inlet temperatures (0.1 °C), error codes, alarm limits, disinfection commands and an error log.

This page lists 46 Modbus registers for the Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU) — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Armstrong International’s own free documentation (linked below) and checked against it.

Manufacturer
Armstrong International
Model
Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)
Equipment type
Actuator / valve
Registers
46 (23 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
DRV25, DRV40, DRV80, Brain, IOM-776
Source document
Guide to The Brain Networking Installation and Operation - Brain Modbus Networking · IOM-776 (1345022-W2-E) · rev. 2024
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)

Integration in brief

Wire the DRV's RS-485 port at 9600 8N1, then read registers 4 (status), 6 (outlet temperature) and 8 (error code). Write the setpoint to register 1 in tenths of °C; set register 4 to Off before changing configuration registers 400-411 and back to On afterwards.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 6Valve Outlet TemperatureUINT16Outlet (blended) temperatureRead
HR 1Setpoint TemperatureUINT16SetpointRead/write
HR 4Valve StatusUINT16Valve status / on-off-full coldRead/write
HR 8Valve Error CodeUINT16Active error codeRead
HR 10Hot Inlet TemperatureUINT16Hot inlet temperatureRead/write
HR 11Cold Inlet TemperatureUINT16Cold inlet temperatureRead/write

Enable Modbus control & writes

Modbus RTU is fixed at 9600 bps, no parity, 8 data bits, 1 stop bit. Set the unit address (1-31, read back in register 0) before connecting to the network: on DRV40/80 with the DRV Programming Software through the CN3 port (valve Off), on DRV25 with the SAGE mobile app over Bluetooth. The same software switches the CN2 network port from SAGE BS to Modbus.

Byte order & addressing

Network setup

Watch out for

Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

46 of 46 shown
Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0Unit AddressModbus address 1-31.UINT16Read
HR1Setpoint TemperatureBlend (outlet) setpoint.UINT16× 0.1°CRead/write
HR4Valve StatusWrite 0/1/2 only; set Off before changing registers 400-411.UINT16Read/write0 = Off (R/W); 1 = On (R/W); 2 = Full cold (R/W); 6 = Disinfection (read only); 7 = Error (read only)
HR6Valve Outlet TemperatureUINT16× 0.1°CRead
HR8Valve Error CodeUINT16Read0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error
HR10Hot Inlet TemperatureUINT16× 0.1°CRead/write
HR11Cold Inlet TemperatureUINT16× 0.1°CRead/write
HR23Disinfection Target TemperatureFrom the DRV maximum setpoint up to 99.9 °C.UINT16× 0.1°CRead/write
HR110Valve Firmware Type NumberUINT16Read
HR111Valve Firmware Version NumberUINT16Read
HR112Valve Configuration IDUINT16Read
HR113Valve Configuration VersionUINT16Read
HR115Adaptor (Bluetooth) Firmware TypeUINT16Read
HR127ID of Valve Service EngineerUINT16Read
HR155Hours Since Last DisinfectionUINT16hRead
HR159Last Completed Disinfection ResultLogic value; meaning not listed.UINT16Read
HR306Arm Disinfection CommandWrite 0x6172 to arm; trigger within 10 s.UINT16Write
HR307Trigger Disinfection CommandWrite 0x5452 after arming to start disinfection.UINT16Write
HR308Abort Disinfection CommandWrite any value to stop disinfection; from full hot the valve goes full cold (Error Temp).UINT16Write
HR309Soft Valve Reset CommandWrite 0x1.UINT16Write
HR314Disinfection Cool DownWrite any value to end disinfection with full cold flow.UINT16Write
HR400DRV Serial Line AddressUINT16Read/write0 = Standard; 1 = Alternate
HR401Disinfection EnableUINT16Read/write0 = Disable; 64 = Enable
HR402Disinfection TimeoutAlerts/errors suppressed for this time; max 1800 min.UINT16minRead/write
HR403High AlertUINT16× 0.1°CRead/write
HR404Low AlertUINT16× 0.1°CRead/write
HR405Error TemperatureOutlet above this drives the valve full cold and latches an error.UINT16× 0.1°CRead/write
HR406Relay ActiveUINT16Read/write0 = Off; 1 = On
HR408Valve Temperature UnitsUINT16Read/write0 = °F; 1 = °C
HR409DRV Maximum SetpointUINT16× 0.1°CRead/write
HR410DRV Minimum SetpointUINT16× 0.1°CRead/write
HR411DRV Default SetpointSetpoint used after a power cycle.UINT16× 0.1°CRead/write
HR412Spare/Remote Thermistor 1UINT16× 0.1°CRead
HR413Thermistor 2Printed as 'DRV Default Setpoint Thermistor 2'.UINT16× 0.1°CRead
HR433Reset Usage Logs CommandWrite any value.UINT16Write
HR434Reset Error LogsWrite any value.UINT16Write
HR435Error 1 CodeUINT16Read0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error
HR438Error 2 CodeUINT16Read0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error
HR441Error 3 CodeUINT16Read0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error
HR444Error 4 CodeUINT16Read0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error
HR447Error 5 CodeUINT16Read0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error
HR450Error 6 CodeUINT16Read0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error
HR453Error 7 CodeUINT16Read0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error
HR456Error 8 CodeUINT16Read0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error
HR459Error 9 CodeUINT16Read0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error
HR462Error 10 CodeUINT16Read0 = No error; 1 = Over temperature; 2 = Stuck motor; 3 = Motor calibration; 4 = Valve failure; 5 = Thermistor failure; 6 = Unconfigured; 7 = A to D error; 8 = RAM error; 9 = EE error; 10 = Flash error; 11 = Algorithm error; 12 = Controller error; 13 = Battery error; 14 = Scheduler error

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)

What Modbus registers does the Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU) have?

This map lists 46 registers: 46 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. IOM-776 lists plain register numbers starting at 0 (Unit Address is register 0) and supports function codes 03, 06 and 16. A register numbered 0 can only be a protocol (PDU) address, so the listed numbers are used as wire addresses.

What are the minimum Modbus registers to integrate the Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)?

Start with HR 6 Valve Outlet Temperature (Outlet (blended) temperature); HR 1 Setpoint Temperature (Setpoint); HR 4 Valve Status (Valve status / on-off-full cold); HR 8 Valve Error Code (Active error code); HR 10 Hot Inlet Temperature (Hot inlet temperature); HR 11 Cold Inlet Temperature (Cold inlet temperature).

How do I enable Modbus control of the Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)?

Modbus RTU is fixed at 9600 bps, no parity, 8 data bits, 1 stop bit. Set the unit address (1-31, read back in register 0) before connecting to the network: on DRV40/80 with the DRV Programming Software through the CN3 port (valve Off), on DRV25 with the SAGE mobile app over Bluetooth. The same software switches the CN2 network port from SAGE BS to Modbus.

Where is the official Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU) Modbus documentation?

The source is Guide to The Brain Networking Installation and Operation - Brain Modbus Networking (IOM-776 (1345022-W2-E)), revision 2024, published free by Armstrong International at https://armstronginternational.com/wp-content/uploads/IOM_TheBrain_DRV_Networking_IOM_NA_EN_20241209.pdf.

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: Guide to The Brain Networking Installation and Operation - Brain Modbus Networking · IOM-776 (1345022-W2-E) · rev. 2024. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.