- tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU)
Sensor (disinfectant / chlorine) · Modbus register map
JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU) Modbus register map
Updated 19 November 2026
JUMO tecLine sensors are amperometric membrane sensors for free and total chlorine, chlorine dioxide, ozone, hydrogen peroxide, peracetic acid and bromine, with a built-in RS-485 Modbus RTU interface. This map covers concentration, cell current and temperature, the unit and decimal settings, calibration zero/slope with history, device identification and serial settings.
This page lists 24 Modbus registers for the JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from JUMO’s own free documentation (linked below) and checked against it.
- Manufacturer
- JUMO
- Model
- tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU)
- Equipment type
- Sensor (disinfectant / chlorine)
- Registers
- 24 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 38400 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- 202630, 202631, 202634, 202636, 202637, 202681, tecLine Cl2, tecLine TC, tecLine ClO2, tecLine O3, tecLine H2O2, tecLine PAA, tecLine Br, tecLine Cl2 OM
Integration notes: JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU)
Read 6 registers from 0x0000 (function 03) for concentration, cell current and temperature as CDAB floats; read 0x0200 once for the unit.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Concentration | FLOAT32 CDAB | Concentration | Read |
| HR 4 | Temperature | FLOAT32 CDAB | Temperature | Read |
| HR 2 | Cell current | FLOAT32 CDAB | Cell current (for calibration) | Read |
| HR 512 | Unit | UINT16 | Unit code | Read |
Enable Modbus control & writes
Modbus RTU is the native interface; change address and serial format with JUMO DSM software or registers 0x0400-0x0402.
Byte order & addressing
- Floats are low word first (CDAB).
- Only RTU mode is supported.
Network setup
- M12 pins: 2 = +24 V, 3 = GND, 4 = RS-485 B, 5 = RS-485 A.
- Check the type-specific default address before commissioning several sensors on one bus.
Watch out for
- Sensors ship uncalibrated; a calibration only becomes active when the date/time stamp is written.
- Replace the membrane/electrolyte when the slope falls below 30 % of the nominal slope (0x030A).
JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0x0000 | Concentration | In the unit set at 0x0200. | FLOAT32 | CDAB | Read | |||
| HR | 2doc 0x0002 | Cell current | Sensor current referred to 25 °C. | FLOAT32 | CDAB | nA | Read | ||
| HR | 4doc 0x0004 | Temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 512doc 0x0200 | Unit | Unit of the concentration value. | UINT16 | Read | 0 = %; 2 = g/l; 3 = ppm; 4 = mg/l; 5 = ppb; 6 = µg/l | |||
| HR | 513doc 0x0201 | Decimal places | UINT16 | Read | 0 = 0000; 1 = 000.0; 2 = 00.00; 3 = 0.000 | ||||
| HR | 518doc 0x0206 | X_Zero (active calibration) | Zero-point current. | FLOAT32 | CDAB | nA | Read/write | ||
| HR | 520doc 0x0208 | X_Span (active calibration) | Slope. | FLOAT32 | CDAB | nA/unit | Read/write | ||
| HR | 528doc 0x0210 | X_Zero history 0 | Latest calibration. | FLOAT32 | CDAB | nA | Read | ||
| HR | 530doc 0x0212 | X_Span history 0 | FLOAT32 | CDAB | nA/unit | Read | |||
| HR | 534doc 0x0216 | X_Zero history 1 | FLOAT32 | CDAB | nA | Read | |||
| HR | 536doc 0x0218 | X_Span history 1 | FLOAT32 | CDAB | nA/unit | Read | |||
| HR | 540doc 0x021C | X_Zero history 2 | FLOAT32 | CDAB | nA | Read | |||
| HR | 542doc 0x021E | X_Span history 2 | FLOAT32 | CDAB | nA/unit | Read | |||
| HR | 552doc 0x0228 | X_Zero history 4 | Oldest calibration kept. | FLOAT32 | CDAB | nA | Read | ||
| HR | 554doc 0x022A | X_Span history 4 | FLOAT32 | CDAB | nA/unit | Read | |||
| HR | 558doc 0x022E | Measuring range | FLOAT32 | CDAB | Read | ||||
| HR | 776doc 0x0308 | Hardware version | E.g. 1130 = 1.130. | UINT16 | Read | ||||
| HR | 777doc 0x0309 | Firmware version | E.g. 1503 = 1.503. | UINT16 | Read | ||||
| HR | 778doc 0x030A | Nominal slope | FLOAT32 | CDAB | nA/unit | Read | |||
| HR | 780doc 0x030C | Fabrication number | 20 characters. | STRING[20] | Read | ||||
| HR | 791doc 0x0317 | Part number | 10 characters. | STRING[10] | Read | ||||
| HR | 1024doc 0x0400 | Slave address | 1-247; default depends on sensor type. | UINT16 | Read/write | ||||
| HR | 1025doc 0x0401 | Baud rate | Default 4 (38400). | UINT16 | Read/write | 0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200; 4 = 38400; 5 = 57600; 6 = 115200 | |||
| HR | 1026doc 0x0402 | Parity / stop bits | Default 3 (none/1). | UINT16 | Read/write | 0 = None, 2 stop; 1 = Even, 1 stop; 2 = Odd, 1 stop; 3 = None, 1 stop |
Notes on this map
- Copy hosted by the Australian distributor Onetemp; JUMO does not offer a public direct link to this document. The file is the unaltered JUMO interface description.
- Floats are sent low word first (CDAB): the guide says the bytes come as 3-4-1-2, and its temperature example returns BA 2F 41 C0 = 24.09 °C.
- Default slave address depends on type: 20 Cl2, 30 TC, 50 O3, 80 ClO2, 60 H2O2, 70 PAA, 90 Br, 100 Cl2 OM. Default serial format reads 38400 baud, none parity, 1 stop bit in the settings table.
- Left out: the calibration date/time stamps (0x020A and history), which are unsigned 32-bit integers with no stated word order; writing the stamp at 0x020A is what activates a new calibration, so use JUMO DSM software or test word order first.
- Left out: history entry 3, because the table prints the same addresses (0x0212/0x0214) as entry 0.
- Unit code 1 is printed as an unreadable symbol in the table and is left out of the enum.
- Function 03 and 04 both read all parameters; writes use 06 or 16.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU)
What Modbus registers does the JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU) have?
This map lists 24 registers: 24 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex and sent unchanged; the example reads the temperature with start address 0x0004.
What byte order does the JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU)?
Start with HR 0 Concentration (Concentration); HR 4 Temperature (Temperature); HR 2 Cell current (Cell current (for calibration)); HR 512 Unit (Unit code).
How do I enable Modbus control of the JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU)?
Modbus RTU is the native interface; change address and serial format with JUMO DSM software or registers 0x0400-0x0402.
Where is the official JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU) Modbus documentation?
The source is JUMO tecLine Cl2 (202630), TC (202631), ClO2+O3 (202634), H2O2+PAA (202636), Br (202637), Cl2 OM (202681) - Modbus interface description (20263000T92Z001K000 V2.00/EN/00718260), revision 2022-03-24. JUMO doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.onetemp.com.au/wp-content/uploads/2024/02/Jumo-tecLine-Modbus-Interface-Description-for-CI2-TC-CIO2O3-H2O2PAA-Br-CI2-OM.pdf. It may be an older revision, so check it against the live unit.
More JUMO Modbus register maps
- Sensor (dissolved oxygen)
JUMO digiLine O-DO S10 optical oxygen sensor (Modbus RTU)
JUMO digiLine O-DO S10 digital oxygen sensor on RS-485 Modbus RTU (interface description V2.00, 2021-08-20).
Also known as: JUMO digiLine O-DO S10, digiLine O-DO - Sensor (turbidity)
JUMO ecoLine NTU digital turbidity sensor (Modbus RTU)
JUMO ecoLine NTU type 202670 with RS-485 Modbus RTU (interface description V1.01).
Also known as: 202670, JUMO ecoLine NTU, ecoLine NTU type 202670 - Sensor (dissolved oxygen)
JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU)
JUMO ecoLine O-DO type 202613 with RS-485 Modbus RTU (interface description V1.01).
Also known as: 202613, JUMO ecoLine O-DO, ecoLine O-DO type 202613
Other valves, actuators & sensors register maps
- Sensor (weighing indicator)
Radwag PUE C32 / PUE HX7 / PUE HX5.EX weighing indicators
Radwag PUE C32, PUE HX7 and PUE HX5.EX weighing indicators per the May 2024 Modbus manual; platform 2 registers exist on PUE HX7 only.
Also known as: PUE C32, PUE HX7, PUE HX5.EX - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Actuator / valve (comfort module air damper)
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Swegon REACT Parasol Zenith comfort modules fitted with the Belimo Modbus actuator; Swegon Modbus settings sheet dated 2022-08-10.
Also known as: Parasol Zenith REACT, REACT damper actuator - Sensor (CO2 / pressure)
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
TSM400-4-CP per the Teracom TSM400-4-CP user manual TSM400-4-CP-R1.9.
Also known as: TSM400-4-CP - Sensor (dew point transmitter)
Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
DMT143 dew point transmitters ordered with the Modbus RTU option (user guide M211435EN-L).
Also known as: DMT143, DRYCAP DMT143 - Sensor (humidity and temperature module)
Vaisala HMM170 humidity module (Modbus RTU)
HMM170 OEM humidity and temperature module with the Modbus RTU interface (user guide M212259EN-D).
Also known as: HMM170, HUMICAP HMM170
All valves, actuators & sensors Modbus register maps →
Source: JUMO tecLine Cl2 (202630), TC (202631), ClO2+O3 (202634), H2O2+PAA (202636), Br (202637), Cl2 OM (202681) - Modbus interface description · 20263000T92Z001K000 V2.00/EN/00718260 · rev. 2022-03-24 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.