- TSM400-4-CP Modbus CO2 and barometric pressure sensor
Sensor (CO2 / pressure) · Modbus register map
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor Modbus register map
Updated 19 November 2026
The TSM400-4-CP is a Teracom wall-mount NDIR CO2 and barometric pressure sensor with Modbus RTU over RS-485. CO2 in ppm and pressure in hPa or mmHg are given as floats and 16-bit integers, with trim registers.
This page lists 24 Modbus registers for the Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teracom’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teracom
- Model
- TSM400-4-CP Modbus CO2 and barometric pressure sensor
- Equipment type
- Sensor (CO2 / pressure)
- Registers
- 24 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- TSM400-4-CP
- Source document
- TSM400-4-CP User manual · TSM400-4-CP-R1.9 · rev. 2026-10
Integration notes: Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
Read CO2 and pressure as floats at PDU 106-109 with function 03, or as plain 16-bit values at PDU 603-604.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 106 | CO2, ppm | FLOAT32 ABCD | CO2 ppm (float) | Read |
| HR 108 | Pressure, hPa | FLOAT32 ABCD | Pressure hPa (float) | Read |
| HR 603 | CO2, ppm | UINT16 | CO2 ppm (uint16) | Read |
| HR 604 | Pressure, hPa | UINT16 | Pressure hPa (uint16) | Read |
| HR 2002 | Automatic self-calibration (ASC) | UINT16 | CO2 self-calibration on/off | Read/write |
Enable Modbus control & writes
Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.
Byte order & addressing
- Baud rate and framing changes only take effect after the device is powered off and on again.
- Word order for every 32-bit value is set by the Data order register (PDU 13); check it before blaming the scaling.
Network setup
- Set unit ID (PDU 10), baud (PDU 11) and framing (PDU 12), then power-cycle the device.
- Terminate both ends of the RS-485 bus with 120 ohm; the built-in resistor is enabled by shorting the RS485- and TERM terminals. A daisy chain is recommended.
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 10doc 40011 | RS-485 address | Modbus slave address of the device. | UINT16 | Read/write | ||||
| HR | 11doc 40012 | Baud rate | Serial baud rate; takes effect after a power cycle. | UINT16 | Read/write | ||||
| HR | 12doc 40013 | Parity, data, stop bits | Parity/data/stop framing; takes effect after a power cycle. | UINT16 | Read/write | 1 = 8 data bits, even parity, 1 stop (E81); 2 = 8 data bits, odd parity, 1 stop (O81); 3 = 8 data bits, no parity, 1 stop (N81) | |||
| HR | 13doc 40014 | Data order | Word order used for all 32-bit values. | UINT16 | Read/write | 1 = MSWF - most significant word first; 2 = LSWF - least significant word first | |||
| HR | 14doc 40015 | Device code | Fixed product identification code. | UINT16 | Read | ||||
| HR | 15doc 40016 | FW version | Firmware version number. | UINT16 | Read | ||||
| HR | 18doc 40019 | Vendor URL | Maker URL as UTF-8 text (64 bytes). | STRING[64] | Read | ||||
| HR | 86doc 40087 | Signed integer test value | INT16 | Read | |||||
| HR | 91doc 40092 | Unsigned integer test value | UINT16 | Read | |||||
| HR | 106doc 40107 | CO2, ppm | FLOAT32 | ABCD | ppm | Read | |||
| HR | 108doc 40109 | Pressure, hPa | FLOAT32 | ABCD | hPa | Read | |||
| HR | 206doc 40207 | CO2, ppm | FLOAT32 | ABCD | ppm | Read | |||
| HR | 208doc 40209 | Pressure, mmHg | FLOAT32 | ABCD | mmHg | Read | |||
| HR | 603doc 40604 | CO2, ppm | UINT16 | ppm | Read | ||||
| HR | 604doc 40605 | Pressure, hPa | UINT16 | hPa | Read | ||||
| HR | 703doc 40704 | CO2, ppm | UINT16 | ppm | Read | ||||
| HR | 704doc 40705 | Pressure High-Word, mmHg x 100 | High word of pressure in mmHg x100. | UINT16 | Read | ||||
| HR | 705doc 40706 | Pressure Low-Word, mmHg x 100 | Low word of pressure in mmHg x100. | UINT16 | Read | ||||
| HR | 2002doc 42003 | Automatic self-calibration (ASC) | CO2 automatic self-calibration switch. | UINT16 | Read/write | 0 = disable; 1 = enable | |||
| HR | 2115doc 42116 | CO2 multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2117doc 42118 | CO2 offset | FLOAT32 | ABCD | Read/write | ||||
| HR | 2119doc 42120 | Pressure multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2121doc 42122 | Pressure hPa offset | FLOAT32 | ABCD | hPa | Read/write | |||
| HR | 2123doc 42124 | Pressure mmHg offset | FLOAT32 | ABCD | mmHg | Read |
Notes on this map
- Addresses are taken from the manual's PDU address column (0-based); the logical column is the same number plus 40001, the holding-register offset the manual states.
- All 32-bit values follow the Data order register (PDU 13): 1 = most significant word first (factory default), 2 = least significant word first. The map shows the default, ABCD.
- Left out: the 32-bit float/integer test-value registers (PDU 82-95), which only exist to check word order; the 16-bit test values are kept.
- The mmHg x100 pressure in the integer block is split into a high word and a low word (PDU 704/705); they are listed as two 16-bit registers as the manual does. Combine as high x 65536 + low, then divide by 100.
- CO2 automatic self-calibration is switched by PDU 2002 (0 = off, 1 = on); it assumes the sensor sees about 400 ppm fresh air at least weekly.
- Readings can be trimmed with the multiplier and offset floats near PDU 2115: corrected = measured x multiplier + offset.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
What Modbus registers does the Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor have?
This map lists 24 registers: 24 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table prints both a PDU (wire) address and a logical address (PDU + 40001 for holding registers). 'documented' holds the logical number; the PDU number is what goes in the request, e.g. logical 40101 = PDU 100.
What byte order does the Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor?
Start with HR 106 CO2, ppm (CO2 ppm (float)); HR 108 Pressure, hPa (Pressure hPa (float)); HR 603 CO2, ppm (CO2 ppm (uint16)); HR 604 Pressure, hPa (Pressure hPa (uint16)); HR 2002 Automatic self-calibration (ASC) (CO2 self-calibration on/off).
How do I enable Modbus control of the Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor?
Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.
Where is the official Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor Modbus documentation?
The source is TSM400-4-CP User manual (TSM400-4-CP-R1.9), revision 2026-10, published free by Teracom at https://www.teracomsystems.com/download/tsm400-4-cp-modbus-co2-and-pressure-sensor/.
More Teracom Modbus register maps
- Sensor (temperature / humidity data logger)
Teracom TCW210-TH temperature and humidity data logger
TCW210-TH per the Teracom TCW210-TH user manual Revision R1.26, firmware V2.012 or later.
Also known as: TCW210-TH, TCW210 - Sensor (Ethernet data logger / I/O module)
Teracom TCW220 Ethernet data logger
TCW220 per the Teracom TCW220 user manual Revision R4.24, firmware V2.012 or later.
Also known as: TCW220 - Sensor (Ethernet I/O module)
Teracom TCW241 Ethernet I/O module
TCW241 per the Teracom TCW241 user manual Revision R4.30, firmware v2.012 or later.
Also known as: TCW241 - Energy meter (Ethernet energy monitoring / data logger)
Teracom TCW260 Ethernet energy monitoring module
TCW260 per the Teracom TCW260 user manual Revision R1.19, firmware V3.009 or later.
Also known as: TCW260 - Sensor (Ethernet analog / digital output module)
Teracom TCW280 Ethernet analog output module
TCW280 per the Teracom TCW280 user manual TCW280_R1.8.
Also known as: TCW280 - Sensor (1-Wire to Modbus gateway)
Teracom TCW320x-WMG 1-Wire to Modbus gateway
TCW320E-WMG (Ethernet) and TCW320W-WMG (Wi-Fi) per the user manual Revision R1.0; both share one fixed register map.
Also known as: TCW320E-WMG, TCW320W-WMG - Energy meter (S0 pulse counter / digital input module)
Teracom TDI340 4-channel S0 pulse counter with Modbus RTU
TDI340 per the Teracom TDI340 user manual Revision R1.11, firmware V1.06 or later.
Also known as: TDI340 - Sensor (relay output module)
Teracom TDO340 4-channel Modbus RTU relay output module
TDO340 per the Teracom TDO340 user manual Revision R1.2, firmware V1.03 or later.
Also known as: TDO340 - Sensor (water leak detector)
Teracom TSF400-4 water-leak detector with Modbus RTU
TSF400-4 per the Teracom TSF400-4 user manual Revision R1.2.
Also known as: TSF400-4 - Sensor (humidity / temperature)
Teracom TSH300v3 RS-485 humidity and temperature sensor
TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.
Also known as: TSH300, TSH300v3 - Sensor (humidity / temperature)
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor
TSH331 per the Teracom TSH331 user manual Rev. 1.5, firmware v1.08 or later.
Also known as: TSH331 - Sensor (CO2 / humidity / temperature / pressure)
Teracom TSM400-4-CPTH Modbus CO2, humidity, temperature and pressure multi-sensor
TSM400-4-CPTH per the Teracom TSM400-4-CPTH user manual TSM400-4-CPTH-R1.9.
Also known as: TSM400-4-CPTH - Sensor (humidity / temperature)
Teracom TSM400-4-TH Modbus humidity and temperature sensor
TSM400-4-TH per the Teracom TSM400-4-TH user manual TSM400-4-TH-R1.10.
Also known as: TSM400-4-TH - Sensor (temperature)
Teracom TST300v3 / TST300v4 RS-485 precision temperature sensor
TST300v3/v4 per the Teracom TST300v3/v4 user manual Revision R1.19.
Also known as: TST300, TST300v3, TST300v4 - Sensor (thermocouple input module)
Teracom TST320 2-channel thermocouple module with Modbus RTU
TST320 per the Teracom TST320 user manual Revision R1.6.
Also known as: TST320 - Sensor (AC/DC voltage transducer)
Teracom TSV300 AC/DC voltage transducer with Modbus RTU
TSV300 per the Teracom TSV300 user manual Revision R1.4, firmware V1.06 or later.
Also known as: TSV300
Other valves, actuators & sensors register maps
- Sensor (dew point transmitter)
Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
DMT143 dew point transmitters ordered with the Modbus RTU option (user guide M211435EN-L).
Also known as: DMT143, DRYCAP DMT143 - Sensor (humidity and temperature module)
Vaisala HMM170 humidity module (Modbus RTU)
HMM170 OEM humidity and temperature module with the Modbus RTU interface (user guide M212259EN-D).
Also known as: HMM170, HUMICAP HMM170 - Sensor (transformer oil monitor)
Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)
MHT410 transformer oil monitor, Modbus RTU on the RS-485 screw terminals (user guide M211737EN-J).
Also known as: MHT410 - Sensor
VTS CO2-SENS-D-MODRTU
VTS CO2-SENS-D-MODRTU duct CO2 transducer (MH-Z19B sensing module), manual ver. 2.0 (11.2021).
Also known as: CO2 transducer CO2-SENS-D-MODRTU, VTS duct CO2 sensor - Sensor (limit controller)
Yokogawa UTAdvanced UT35A-L limit controller
Yokogawa UT35A-L limit controllers with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 12.
Also known as: UT35A-L - Actuator / valve (6-way pressure-independent change-over valve)
Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC)
Belimo 6-way EPIV EP..R-R6+BAC on Modbus RTU, per 6-way EPIV Modbus Register en-gb 2024-01 (general notes dated 16.12.2019).
Also known as: EP..R-R6+BAC, 6-way pressure-independent valve
All valves, actuators & sensors Modbus register maps →
Source: TSM400-4-CP User manual · TSM400-4-CP-R1.9 · rev. 2026-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.