Sensor (dew point transmitter) · Modbus register map
Vaisala DMT143 miniature dew point transmitter (Modbus RTU) Modbus register map
Updated 19 November 2026
The DMT143 is a compact Vaisala DRYCAP dew point transmitter for compressed air and dryers. Units with the Modbus option are Modbus RTU slaves on RS-485. This map covers dew/frost point and ppm readings, pressure compensation, filtering, serial settings, the LED alarm and test registers.
This page lists 26 Modbus registers for the Vaisala DMT143 miniature dew point transmitter (Modbus RTU) — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vaisala
- Model
- DMT143 miniature dew point transmitter (Modbus RTU)
- Equipment type
- Sensor (dew point transmitter)
- Registers
- 26 (13 writable)
- Transport
- Modbus RTU
- Default unit ID
- 240
- Default serial
- 19200 baud, 8N2
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- DMT143, DRYCAP DMT143
- Source document
- DMT143 User Guide · M211435EN-L · rev. 2026-01
Integration notes: Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
Read holding registers 7-12 for dew/frost point values (CDAB floats). Write the line pressure (bar absolute) to 771 so the dew point converted to 1 atm is correct.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 6 | Dew/frost point temperature | FLOAT32 CDAB | Dew/frost point | Read |
| HR 20 | Water concentration | FLOAT32 CDAB | Water ppm | Read |
| HR 512 | Error status | UINT16 | Error status | Read |
| HR 513 | Online status | UINT16 | Online / frozen | Read |
| HR 770 | Pressure | FLOAT32 CDAB | Live pressure compensation | Read/write |
Enable Modbus control & writes
Order the transmitter with the Modbus configuration option, or set the serial mode to MODBUS with the SMODE serial command (takes effect at the next reset or power-up).
Byte order & addressing
- Floats are low word first (CDAB); pick "word-swapped" float in masters that default to high word first.
- Read or write each 32-bit value in one transaction.
Network setup
- Defaults: address 240, 19200 baud, None parity, 8 data bits, 2 stop bits.
- Give each device on a shared bus a unique address (1-247); change serial settings with Insight or registers 1537-1540.
Watch out for
- Use the test registers (7937 on) to confirm float format and addressing before trusting readings.
Vaisala DMT143 miniature dew point transmitter (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 6doc 7 | Dew/frost point temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 8doc 9 | Dew point temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 10doc 11 | Dew/frost point at 1 atm | FLOAT32 | CDAB | °C | Read | |||
| HR | 20doc 21 | Water concentration | FLOAT32 | CDAB | ppm | Read | |||
| HR | 259doc 260 | Dew/frost point (integer) | INT16 | × 0.01 | °C | Read | |||
| HR | 260doc 261 | Dew point (integer) | INT16 | × 0.01 | °C | Read | |||
| HR | 261doc 262 | Dew/frost point at 1 atm (integer) | INT16 | × 0.01 | °C | Read | |||
| HR | 266doc 267 | Water concentration (integer) | INT16 | ppm | Read | ||||
| HR | 512doc 513 | Error status | UINT16 | Read | 1 = No errors | ||||
| HR | 513doc 514 | Online status | UINT16 | Read | 0 = Outputs frozen (autocalibration or purge); 1 = Data available | ||||
| HR | 768doc 769 | Pressure, power-up default | Absolute, 0.001-50 bar; stored. | FLOAT32 | CDAB | bar | Read/write | ||
| HR | 770doc 771 | Pressure | Absolute, 0.001-50 bar; live value. | FLOAT32 | CDAB | bar | Read/write | ||
| HR | 794doc 795 | Filtering factor | 0.00001-1. | FLOAT32 | CDAB | Read/write | |||
| HR | 1536doc 1537 | Modbus address | 1-247. | INT16 | Read/write | ||||
| HR | 1537doc 1538 | Bit rate | UINT16 | Read/write | 5 = 9600; 6 = 19200 | ||||
| HR | 1538doc 1539 | Parity, data, stop bits | UINT16 | Read/write | 0 = N81; 1 = N82; 2 = E81; 3 = E82; 4 = O81; 5 = O82 | ||||
| HR | 1539doc 1540 | Response delay | 0-1020 ms. | INT16 | ms | Read/write | |||
| HR | 1540doc 1541 | Interface mode | UINT16 | Read/write | 6 = Modbus | ||||
| HR | 1541doc 1542 | Restart device | Write 1 to restart. | INT16 | Write | ||||
| HR | 3072doc 3073 | LED indicator mode | UINT16 | Read/write | 0 = Off; 1 = Status only; 2 = Alarm | ||||
| HR | 3073doc 3074 | LED alarm parameter | UINT16 | Read/write | 6 = Td/f | ||||
| HR | 3074doc 3075 | LED alarm setpoint | -70...+60 °C. | FLOAT32 | CDAB | °C | Read/write | ||
| HR | 7680doc 7681 | Restore settings | Write 1 to restore factory settings. | INT16 | Write | ||||
| HR | 7936doc 7937 | Signed integer test | Always reads -12345. | INT16 | Read | ||||
| HR | 7937doc 7938 | Floating point test | Always reads -123.45. | FLOAT32 | CDAB | Read | |||
| HR | 7939doc 7940 | Text string test | Reads the text "-123.45". | STRING[8] | Read |
Notes on this map
- All registers are holding registers: read with function 03, write with function 16.
- 32-bit floats put the least significant word at the listed register (CDAB). The guide states this and its worked read example confirms it.
- Unavailable data reads as quiet NaN (float) or 0x8000 (16-bit integer) rather than an exception.
- Integer dew point registers are value x 100 (raw x 0.01).
- Left out: the error code register. The guide prints it as number 515 with address 0x0203, which do not match (515 would be 0x0202), so the correct address is not clear.
- Pressure registers 769 and 771 are in bar (absolute), not hPa.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
What Modbus registers does the Vaisala DMT143 miniature dew point transmitter (Modbus RTU) have?
This map lists 26 registers: 26 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vaisala DMT143 miniature dew point transmitter (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.
What byte order does the Vaisala DMT143 miniature dew point transmitter (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Vaisala DMT143 miniature dew point transmitter (Modbus RTU)?
Start with HR 6 Dew/frost point temperature (Dew/frost point); HR 20 Water concentration (Water ppm); HR 512 Error status (Error status); HR 513 Online status (Online / frozen); HR 770 Pressure (Live pressure compensation).
How do I enable Modbus control of the Vaisala DMT143 miniature dew point transmitter (Modbus RTU)?
Order the transmitter with the Modbus configuration option, or set the serial mode to MODBUS with the SMODE serial command (takes effect at the next reset or power-up).
Where is the official Vaisala DMT143 miniature dew point transmitter (Modbus RTU) Modbus documentation?
The source is DMT143 User Guide (M211435EN-L), revision 2026-01, published free by Vaisala at https://docs.vaisala.com/r/M211435EN-L/en-US.
More Vaisala Modbus register maps
- Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series - Sensor (dew point transmitter)
Vaisala DMT153 dew point transmitter (Modbus RTU)
DMT153 trace-moisture dew point transmitter, Modbus RTU interface (user guide M213149EN-B).
Also known as: DMT153, DRYCAP DMT153 - Sensor (CO2 duct transmitter)
Vaisala GMD110 duct CO2 transmitter (Modbus RTU)
GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).
Also known as: GMD110, CARBOCAP GMD110 - Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251 - Sensor (CO2 probe)
Vaisala GMP252 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP252 probe in Modbus RTU mode, user guide M211897EN-G.
Also known as: GMP252, CARBOCAP GMP252, Vaisala GMP252 - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (humidity and temperature transmitter)
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
HMDW110-series duct, wall and outdoor transmitters and TMI110 ordered with the Modbus RTU option (user guide M211726EN-L).
Also known as: HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110 - Sensor (humidity and temperature module)
Vaisala HMM170 humidity module (Modbus RTU)
HMM170 OEM humidity and temperature module with the Modbus RTU interface (user guide M212259EN-D).
Also known as: HMM170, HUMICAP HMM170 - Sensor (humidity and temperature probe)
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Vaisala HMP1/3/4/5/7/8/9, TMP1 and MMP8 probes with the Modbus RTU interface (user guide M212022EN-M).
Also known as: HMP1, HMP3, HMP4, HMP5, HMP7, HMP8, HMP9, TMP1, MMP8 - Sensor (humidity and temperature probe)
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
HMP60/HMP110-series probes ordered with the Modbus RTU option (user guide M211060EN-N).
Also known as: HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T - Sensor (humidity and temperature transmitter)
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
HMW87 and HMW87D wall transmitters of the HMDW80 series (the Modbus models in user guide M211510EN-J).
Also known as: HMW87, HMW87D, HMDW80 Modbus - Sensor (H2O2 probe)
Vaisala HPP271 hydrogen peroxide probe (Modbus RTU)
HPP271 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211888EN-E).
Also known as: HPP271, PEROXCAP HPP271 - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272 - Sensor transmitter (host for Vaisala probes)
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)
Indigo510 and Indigo520 transmitter registers (unit ID 240) over Modbus TCP (user guide M212287EN-AJ).
Also known as: Indigo510, Indigo520, Indigo500 series - Sensor (transformer oil monitor)
Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)
MHT410 transformer oil monitor, Modbus RTU on the RS-485 screw terminals (user guide M211737EN-J).
Also known as: MHT410 - Sensor (moisture in oil transmitter)
Vaisala MMT143 moisture in oil transmitter (Modbus RTU)
MMT143 moisture-in-oil transmitter ordered with the Modbus RTU option (user guide M213308EN-B).
Also known as: MMT143 - Sensor (HVAC humidity, temperature and CO2 transmitter)
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Origo10A duct and wall transmitters ordered with the Modbus RTU output (user guide M213293EN-B). Origo10L has no Modbus.
Also known as: Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter - Sensor (precipitation)
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)
RM60 sensors ordered with communication option 1 (RS-485 Modbus RTU) or switched to Modbus, per user guide M213218EN-B.
Also known as: RM60, PRECICAP RM60, Vaisala RM60 - Sensor (ultrasonic wind)
Vaisala WM80 ultrasonic wind sensor (Modbus RTU)
WM80 sensors with RS-485 in Modbus mode (e.g. ordering option C), per user guide M212995EN-F.
Also known as: WM80, Vaisala WM80, Ultrasonic Wind Sensor WM80 - Sensor (weather transmitter)
Vaisala WXT530 series weather transmitters (Modbus RTU)
WXT531-WXT536 weather transmitters with firmware 3.85 or later in Modbus RTU mode (user guide M211840EN-G).
Also known as: WXT531, WXT532, WXT533, WXT534, WXT535, WXT536 - Sensor (humidity and temperature probe)
Vaisala XMP10 humidity and temperature probe (Modbus RTU)
XMP10 probes ordered with (or switched to) Modbus RTU output, user guide M213279EN-A.
Also known as: XMP10, HUMICAP XMP10, Vaisala XMP10 - Sensor (CO2/humidity wall transmitter)
Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
XMW85 wall transmitter, Modbus RTU interface (user guide M213257EN-B).
Also known as: XMW85
Other valves, actuators & sensors register maps
- Sensor
VTS CO2-SENS-D-MODRTU
VTS CO2-SENS-D-MODRTU duct CO2 transducer (MH-Z19B sensing module), manual ver. 2.0 (11.2021).
Also known as: CO2 transducer CO2-SENS-D-MODRTU, VTS duct CO2 sensor - Sensor (limit controller)
Yokogawa UTAdvanced UT35A-L limit controller
Yokogawa UT35A-L limit controllers with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 12.
Also known as: UT35A-L - Actuator / valve (6-way pressure-independent change-over valve)
Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC)
Belimo 6-way EPIV EP..R-R6+BAC on Modbus RTU, per 6-way EPIV Modbus Register en-gb 2024-01 (general notes dated 16.12.2019).
Also known as: EP..R-R6+BAC, 6-way pressure-independent valve - Sensor
Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307)
A Fronius Sensor Card connected to a Fronius Datamanager over Solar Net and republished by it as a SunSpec device; the same layout is used for the float and int+SF settings.
Also known as: Fronius Sensor Card, IG Sensor Card - Sensor (load-cell weight transmitter)
Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP)
Laumas TLB4 with the Modbus RTU port or the Modbus/TCP option; communication protocols manual version 1.12. Direct registers only.
Also known as: TLB4, TLB4 MODBUS, TLB4 Modbus/TCP - Actuator / valve
Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)
Rotork Modbus RTU Mk3 option module (MFU) in IQ3, SI3, SI4, CK, CVA (firmware CVA1.14 or later), CMA and K-range actuators, using the default Rotork database (register 80 = 0), per PUB091-004-00 issue 08/25.
Also known as: IQ3 Modbus, Rotork MFU Mk3, Modbus Mk3 module, SI3 Modbus, SI4 Modbus, CK Modbus, CVA Modbus, CMA Modbus, K-range Modbus
All valves, actuators & sensors Modbus register maps →
Source: DMT143 User Guide · M211435EN-L · rev. 2026-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.