Sensor (dew point transmitter) · Modbus register map

Vaisala DMT143 miniature dew point transmitter (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The DMT143 is a compact Vaisala DRYCAP dew point transmitter for compressed air and dryers. Units with the Modbus option are Modbus RTU slaves on RS-485. This map covers dew/frost point and ppm readings, pressure compensation, filtering, serial settings, the LED alarm and test registers.

This page lists 26 Modbus registers for the Vaisala DMT143 miniature dew point transmitter (Modbus RTU) — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.

Manufacturer
Vaisala
Model
DMT143 miniature dew point transmitter (Modbus RTU)
Equipment type
Sensor (dew point transmitter)
Registers
26 (13 writable)
Transport
Modbus RTU
Default unit ID
240
Default serial
19200 baud, 8N2
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Also known as
DMT143, DRYCAP DMT143
Source document
DMT143 User Guide · M211435EN-L · rev. 2026-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vaisala DMT143 miniature dew point transmitter (Modbus RTU)

Integration in brief

Read holding registers 7-12 for dew/frost point values (CDAB floats). Write the line pressure (bar absolute) to 771 so the dew point converted to 1 atm is correct.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 6Dew/frost point temperatureFLOAT32 CDABDew/frost pointRead
HR 20Water concentrationFLOAT32 CDABWater ppmRead
HR 512Error statusUINT16Error statusRead
HR 513Online statusUINT16Online / frozenRead
HR 770PressureFLOAT32 CDABLive pressure compensationRead/write

Enable Modbus control & writes

Order the transmitter with the Modbus configuration option, or set the serial mode to MODBUS with the SMODE serial command (takes effect at the next reset or power-up).

Byte order & addressing

Network setup

Watch out for

Vaisala DMT143 miniature dew point transmitter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

26 of 26 shown
Vaisala DMT143 miniature dew point transmitter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR6doc 7Dew/frost point temperatureFLOAT32CDAB°CRead
HR8doc 9Dew point temperatureFLOAT32CDAB°CRead
HR10doc 11Dew/frost point at 1 atmFLOAT32CDAB°CRead
HR20doc 21Water concentrationFLOAT32CDABppmRead
HR259doc 260Dew/frost point (integer)INT16× 0.01°CRead
HR260doc 261Dew point (integer)INT16× 0.01°CRead
HR261doc 262Dew/frost point at 1 atm (integer)INT16× 0.01°CRead
HR266doc 267Water concentration (integer)INT16ppmRead
HR512doc 513Error statusUINT16Read1 = No errors
HR513doc 514Online statusUINT16Read0 = Outputs frozen (autocalibration or purge); 1 = Data available
HR768doc 769Pressure, power-up defaultAbsolute, 0.001-50 bar; stored.FLOAT32CDABbarRead/write
HR770doc 771PressureAbsolute, 0.001-50 bar; live value.FLOAT32CDABbarRead/write
HR794doc 795Filtering factor0.00001-1.FLOAT32CDABRead/write
HR1536doc 1537Modbus address1-247.INT16Read/write
HR1537doc 1538Bit rateUINT16Read/write5 = 9600; 6 = 19200
HR1538doc 1539Parity, data, stop bitsUINT16Read/write0 = N81; 1 = N82; 2 = E81; 3 = E82; 4 = O81; 5 = O82
HR1539doc 1540Response delay0-1020 ms.INT16msRead/write
HR1540doc 1541Interface modeUINT16Read/write6 = Modbus
HR1541doc 1542Restart deviceWrite 1 to restart.INT16Write
HR3072doc 3073LED indicator modeUINT16Read/write0 = Off; 1 = Status only; 2 = Alarm
HR3073doc 3074LED alarm parameterUINT16Read/write6 = Td/f
HR3074doc 3075LED alarm setpoint-70...+60 °C.FLOAT32CDAB°CRead/write
HR7680doc 7681Restore settingsWrite 1 to restore factory settings.INT16Write
HR7936doc 7937Signed integer testAlways reads -12345.INT16Read
HR7937doc 7938Floating point testAlways reads -123.45.FLOAT32CDABRead
HR7939doc 7940Text string testReads the text "-123.45".STRING[8]Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vaisala DMT143 miniature dew point transmitter (Modbus RTU)

What Modbus registers does the Vaisala DMT143 miniature dew point transmitter (Modbus RTU) have?

This map lists 26 registers: 26 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vaisala DMT143 miniature dew point transmitter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.

What byte order does the Vaisala DMT143 miniature dew point transmitter (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Vaisala DMT143 miniature dew point transmitter (Modbus RTU)?

Start with HR 6 Dew/frost point temperature (Dew/frost point); HR 20 Water concentration (Water ppm); HR 512 Error status (Error status); HR 513 Online status (Online / frozen); HR 770 Pressure (Live pressure compensation).

How do I enable Modbus control of the Vaisala DMT143 miniature dew point transmitter (Modbus RTU)?

Order the transmitter with the Modbus configuration option, or set the serial mode to MODBUS with the SMODE serial command (takes effect at the next reset or power-up).

Where is the official Vaisala DMT143 miniature dew point transmitter (Modbus RTU) Modbus documentation?

The source is DMT143 User Guide (M211435EN-L), revision 2026-01, published free by Vaisala at https://docs.vaisala.com/r/M211435EN-L/en-US.