- XMP10 humidity and temperature probe (Modbus RTU)
Sensor (humidity and temperature probe) · Modbus register map
Vaisala XMP10 humidity and temperature probe (Modbus RTU) Modbus register map
Updated 19 November 2026
XMP10 is a small Vaisala HUMICAP humidity and temperature probe that works stand-alone or as the sensing part of a transmitter such as Origo10. With the Modbus option it talks Modbus RTU on RS-485 and can be daisy-chained. This map covers humidity, temperature and the calculated humidity values as floats and scaled integers, error and status registers, filtering, serial settings and the test registers.
This page lists 26 Modbus registers for the Vaisala XMP10 humidity and temperature probe (Modbus RTU) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vaisala
- Model
- XMP10 humidity and temperature probe (Modbus RTU)
- Equipment type
- Sensor (humidity and temperature probe)
- Registers
- 26 (7 writable)
- Transport
- Modbus RTU
- Default unit ID
- 240
- Default serial
- 19200 baud, 8N2
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- XMP10, HUMICAP XMP10, Vaisala XMP10
- Source document
- XMP10 User Guide · M213279EN-A · rev. 2026-04
Integration notes: Vaisala XMP10 humidity and temperature probe (Modbus RTU)
Read holding registers 1-4 (wire 0-3) for RH and temperature as low-word-first floats, or 257-258 as integers divided by 10. Check register 513 and the error code at 516 for faults.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Relative humidity | FLOAT32 CDAB | Relative humidity | Read |
| HR 2 | Temperature | FLOAT32 CDAB | Temperature | Read |
| HR 8 | Dew/frost point temperature | FLOAT32 CDAB | Dew/frost point | Read |
| HR 26 | Enthalpy | FLOAT32 CDAB | Enthalpy | Read |
| HR 512 | Error status | INT16 | Error status | Read |
| HR 515 | Error code | INT32 CDAB | Error code | Read |
Enable Modbus control & writes
Order the probe with Modbus RTU output (output code M), or from the serial command interface give smode modbus and then reset or power cycle the probe. Serial setting changes also need a power cycle before they apply.
Byte order & addressing
- Floats are low word first (CDAB); choose a word-swapped float format in masters that default to high word first.
- Read or write each 32-bit value in one transaction.
Network setup
- Defaults: address 240, 19200 baud, no parity, 8 data bits, 2 stop bits, response delay 0.
- Up to 32 probes per RS-485 line at 19200 bps or lower; give each a unique address with Insight.
- Terminate the last device when the line is over 100 m.
- Allow up to 2 s after power-up before the first request.
Watch out for
- Read the test registers 7937-7939 first to confirm addressing and float format; a wrong float setting can still give plausible-looking numbers.
Vaisala XMP10 humidity and temperature probe (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Relative humidity | FLOAT32 | CDAB | %RH | Read | |||
| HR | 2doc 3 | Temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 8doc 9 | Dew/frost point temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 14doc 15 | Absolute humidity | FLOAT32 | CDAB | g/m3 | Read | |||
| HR | 16doc 17 | Mixing ratio | FLOAT32 | CDAB | g/kg | Read | |||
| HR | 18doc 19 | Wet-bulb temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 26doc 27 | Enthalpy | FLOAT32 | CDAB | kJ/kg | Read | |||
| HR | 256doc 257 | Relative humidity (integer) | INT16 | × 0.1 | %RH | Read | |||
| HR | 257doc 258 | Temperature (integer) | INT16 | × 0.1 | °C | Read | |||
| HR | 260doc 261 | Dew/frost point temperature (integer) | INT16 | × 0.1 | °C | Read | |||
| HR | 263doc 264 | Absolute humidity (integer) | INT16 | × 0.1 | g/m3 | Read | |||
| HR | 264doc 265 | Mixing ratio (integer) | INT16 | × 0.1 | g/kg | Read | |||
| HR | 265doc 266 | Wet-bulb temperature (integer) | INT16 | × 0.1 | °C | Read | |||
| HR | 269doc 270 | Enthalpy (integer) | INT16 | × 0.1 | kJ/kg | Read | |||
| HR | 512doc 513 | Error status | INT16 | Read | 0 = One or more errors active; 1 = No errors | ||||
| HR | 515doc 516 | Error code | Sum of active error codes (see bits). | INT32 | CDAB | Read | bit 0 = Temperature measurement error; bit 1 = Humidity measurement error; bit 2 = Humidity sensor failure; bit 3 = Capacitance reference error; bit 4 = Ambient temperature out of range; bit 5 = Firmware checksum mismatch; bit 6 = Device settings corrupted; bit 7 = Additional configuration settings corrupted; bit 8 = Sensor coefficients corrupted; bit 9 = Main configuration settings corrupted; bit 11 = Supply voltage out of range; bit 13 = Non-volatile memory read/write failure | ||
| HR | 517doc 518 | Security hash | Changes whenever settings or adjustments change. | INT32 | CDAB | Read | |||
| HR | 784doc 785 | Measurement filtering factor | 0.001 = maximum filtering, 1.000 = no filtering. | FLOAT32 | CDAB | Read/write | |||
| HR | 1536doc 1537 | Modbus address | 1-247. | INT16 | Read/write | ||||
| HR | 1537doc 1538 | Bit rate | Takes effect after restart. | INT16 | Read/write | 5 = 9600; 6 = 19200; 7 = 38400; 8 = 57600 | |||
| HR | 1538doc 1539 | Parity, data, stop bits | Takes effect after restart. | INT16 | Read/write | 0 = None, 8, 1; 1 = None, 8, 2; 2 = Even, 8, 1; 3 = Even, 8, 2; 4 = Odd, 8, 1; 5 = Odd, 8, 2 | |||
| HR | 1539doc 1540 | Response delay | 0-1020 ms in 4 ms steps. | INT16 | ms | Read/write | |||
| HR | 1540doc 1541 | Protocol | INT16 | Read/write | 6 = Modbus RTU | ||||
| HR | 1541doc 1542 | Restart device | Write 1 to restart. | INT16 | Write | ||||
| HR | 7936doc 7937 | Signed integer test | Always reads -12345. | INT16 | Read | ||||
| HR | 7937doc 7938 | Floating point test | Always reads -123.45. | FLOAT32 | CDAB | Read |
Notes on this map
- All registers are holding registers: read with function 03, write with function 16.
- 32-bit floats and 32-bit integers put the least significant word at the listed register (CDAB), as the guide states; its example response for RH shows the low word first.
- Integer registers are printed with units such as '%RH * 10', so divide the raw value by 10 (scale 0.1). 0x8000 (32768) means the value is not available; 0x7FFF and 0x8001 mean at or beyond the 16-bit range.
- Register 513 reads 0 when an error is active and 1 when there is none, exactly as printed.
- Error codes 1024, 16384 and 32768 (calibration expiry and invalid communication settings) are visible only in Insight or Indigo80, so they are not listed as Modbus bits.
- The text-string test register (7940) is left out because the guide does not give its register length in a way that fixes the read size.
- Bit rate and parity changes take effect after a restart (register 1542). Incompatible settings can lock out Modbus; Insight can override them.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vaisala XMP10 humidity and temperature probe (Modbus RTU)
What Modbus registers does the Vaisala XMP10 humidity and temperature probe (Modbus RTU) have?
This map lists 26 registers: 26 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vaisala XMP10 humidity and temperature probe (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal from 1 and also prints the 0-based hex address used in the request. Register 1 is address 0x0000 on the wire; the guide's example frame reads relative humidity at address 0x0000.
What byte order does the Vaisala XMP10 humidity and temperature probe (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Vaisala XMP10 humidity and temperature probe (Modbus RTU)?
Start with HR 0 Relative humidity (Relative humidity); HR 2 Temperature (Temperature); HR 8 Dew/frost point temperature (Dew/frost point); HR 26 Enthalpy (Enthalpy); HR 512 Error status (Error status); HR 515 Error code (Error code).
How do I enable Modbus control of the Vaisala XMP10 humidity and temperature probe (Modbus RTU)?
Order the probe with Modbus RTU output (output code M), or from the serial command interface give smode modbus and then reset or power cycle the probe. Serial setting changes also need a power cycle before they apply.
Where is the official Vaisala XMP10 humidity and temperature probe (Modbus RTU) Modbus documentation?
The source is XMP10 User Guide (M213279EN-A), revision 2026-04, published free by Vaisala at https://docs.vaisala.com/r/M213279EN-A/en-US.
More Vaisala Modbus register maps
- Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series - Sensor (dew point transmitter)
Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
DMT143 dew point transmitters ordered with the Modbus RTU option (user guide M211435EN-L).
Also known as: DMT143, DRYCAP DMT143 - Sensor (dew point transmitter)
Vaisala DMT153 dew point transmitter (Modbus RTU)
DMT153 trace-moisture dew point transmitter, Modbus RTU interface (user guide M213149EN-B).
Also known as: DMT153, DRYCAP DMT153 - Sensor (CO2 duct transmitter)
Vaisala GMD110 duct CO2 transmitter (Modbus RTU)
GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).
Also known as: GMD110, CARBOCAP GMD110 - Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251 - Sensor (CO2 probe)
Vaisala GMP252 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP252 probe in Modbus RTU mode, user guide M211897EN-G.
Also known as: GMP252, CARBOCAP GMP252, Vaisala GMP252 - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (humidity and temperature transmitter)
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
HMDW110-series duct, wall and outdoor transmitters and TMI110 ordered with the Modbus RTU option (user guide M211726EN-L).
Also known as: HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110 - Sensor (humidity and temperature module)
Vaisala HMM170 humidity module (Modbus RTU)
HMM170 OEM humidity and temperature module with the Modbus RTU interface (user guide M212259EN-D).
Also known as: HMM170, HUMICAP HMM170 - Sensor (humidity and temperature probe)
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Vaisala HMP1/3/4/5/7/8/9, TMP1 and MMP8 probes with the Modbus RTU interface (user guide M212022EN-M).
Also known as: HMP1, HMP3, HMP4, HMP5, HMP7, HMP8, HMP9, TMP1, MMP8 - Sensor (humidity and temperature probe)
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
HMP60/HMP110-series probes ordered with the Modbus RTU option (user guide M211060EN-N).
Also known as: HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T - Sensor (humidity and temperature transmitter)
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
HMW87 and HMW87D wall transmitters of the HMDW80 series (the Modbus models in user guide M211510EN-J).
Also known as: HMW87, HMW87D, HMDW80 Modbus - Sensor (H2O2 probe)
Vaisala HPP271 hydrogen peroxide probe (Modbus RTU)
HPP271 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211888EN-E).
Also known as: HPP271, PEROXCAP HPP271 - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272 - Sensor transmitter (host for Vaisala probes)
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)
Indigo510 and Indigo520 transmitter registers (unit ID 240) over Modbus TCP (user guide M212287EN-AJ).
Also known as: Indigo510, Indigo520, Indigo500 series - Sensor (transformer oil monitor)
Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)
MHT410 transformer oil monitor, Modbus RTU on the RS-485 screw terminals (user guide M211737EN-J).
Also known as: MHT410 - Sensor (moisture in oil transmitter)
Vaisala MMT143 moisture in oil transmitter (Modbus RTU)
MMT143 moisture-in-oil transmitter ordered with the Modbus RTU option (user guide M213308EN-B).
Also known as: MMT143 - Sensor (HVAC humidity, temperature and CO2 transmitter)
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Origo10A duct and wall transmitters ordered with the Modbus RTU output (user guide M213293EN-B). Origo10L has no Modbus.
Also known as: Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter - Sensor (precipitation)
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)
RM60 sensors ordered with communication option 1 (RS-485 Modbus RTU) or switched to Modbus, per user guide M213218EN-B.
Also known as: RM60, PRECICAP RM60, Vaisala RM60 - Sensor (ultrasonic wind)
Vaisala WM80 ultrasonic wind sensor (Modbus RTU)
WM80 sensors with RS-485 in Modbus mode (e.g. ordering option C), per user guide M212995EN-F.
Also known as: WM80, Vaisala WM80, Ultrasonic Wind Sensor WM80 - Sensor (weather transmitter)
Vaisala WXT530 series weather transmitters (Modbus RTU)
WXT531-WXT536 weather transmitters with firmware 3.85 or later in Modbus RTU mode (user guide M211840EN-G).
Also known as: WXT531, WXT532, WXT533, WXT534, WXT535, WXT536 - Sensor (CO2/humidity wall transmitter)
Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
XMW85 wall transmitter, Modbus RTU interface (user guide M213257EN-B).
Also known as: XMW85
Other valves, actuators & sensors register maps
- Water treatment controller (Sensor / controller)
Walchem WebMaster WIND series Modbus TCP/IP option (s825)
Walchem WebMaster WIND-series controllers with the Modbus TCP/IP option, software s825v008 and higher, per manual 180413 Rev A1.
Also known as: WIND, WebMaster WIND, s825 - Actuator / valve
Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)
Armstrong International Brain digital recirculation (thermostatic mixing) valves DRV25, DRV40 and DRV80 on their RS-485 Modbus RTU port, per IOM-776 Brain Modbus Networking (2024).
Also known as: DRV25, DRV40, DRV80, Brain, IOM-776 - Sensor (humidity / temperature probe)
E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU)
EE260 meteorological RH/T probe with RS-485 Modbus RTU, per Quick Guide QG_EE260 v1.3 (10-2025).
Also known as: EE260, E+E EE260, EE 260 - Sensor (disinfectant / chlorine)
JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU)
JUMO tecLine 202630, 202631, 202634, 202636, 202637 and 202681 sensors with RS-485 Modbus RTU (interface description V2.00, 2022-03-24).
Also known as: 202630, 202631, 202634, 202636, 202637, 202681, tecLine Cl2, tecLine TC, tecLine ClO2, tecLine O3, tecLine H2O2, tecLine PAA, tecLine Br, tecLine Cl2 OM - Sensor (weighing indicator)
Radwag PUE C32 / PUE HX7 / PUE HX5.EX weighing indicators
Radwag PUE C32, PUE HX7 and PUE HX5.EX weighing indicators per the May 2024 Modbus manual; platform 2 registers exist on PUE HX7 only.
Also known as: PUE C32, PUE HX7, PUE HX5.EX - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700
All valves, actuators & sensors Modbus register maps →
Source: XMP10 User Guide · M213279EN-A · rev. 2026-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.