Easy Modbus
  1. Home
  2. Modbus register maps
  3. Vaisala
  4. MMT143 moisture in oil transmitter (Modbus RTU)

Sensor (moisture in oil transmitter) · Modbus register map

Vaisala MMT143 moisture in oil transmitter (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The MMT143 is a compact Vaisala transmitter for moisture in transformer, lubrication and hydraulic oils. Units with the Modbus option are Modbus RTU slaves on RS-485. This map covers water activity, ppm water content, relative saturation and temperature, oil type coefficients, serial settings and test registers.

This page lists 23 Modbus registers for the Vaisala MMT143 moisture in oil transmitter (Modbus RTU) — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.

Manufacturer
Vaisala
Model
MMT143 moisture in oil transmitter (Modbus RTU)
Equipment type
Sensor (moisture in oil transmitter)
Registers
23 (11 writable)
Transport
Modbus RTU
Default unit ID
240
Default serial
19200 baud, 8N1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Also known as
MMT143
Source document
MMT143 User Guide · M213308EN-B · rev. 2026-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vaisala MMT143 moisture in oil transmitter (Modbus RTU)

Integration in brief

Read holding registers 3-4 and 29-42 for temperature, water activity, ppm and relative saturation (CDAB floats). Set the oil type first so ppm is meaningful.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 34Water contentFLOAT32 CDABWater content ppmRead
HR 28Water activityFLOAT32 CDABWater activityRead
HR 2TemperatureFLOAT32 CDABOil temperatureRead
HR 512Error statusUINT16Error statusRead
HR 770Oil typeUINT16Oil typeRead/write

Enable Modbus control & writes

Order the transmitter with the Modbus configuration option, or set the serial mode to MODBUS with the SMODE serial command (applied at the next power-up).

Byte order & addressing

Network setup

Watch out for

Vaisala MMT143 moisture in oil transmitter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

23 of 23 shown
Vaisala MMT143 moisture in oil transmitter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2doc 3TemperatureFLOAT32CDAB°CRead
HR28doc 29Water activityFLOAT32CDABRead
HR34doc 35Water contentFLOAT32CDABppmwRead
HR40doc 41Relative saturationFLOAT32CDAB%RSRead
HR257doc 258Temperature (integer)INT16× 0.1°CRead
HR270doc 271Water activity (integer)INT16× 0.001Read
HR273doc 274Water content (integer)INT16ppmwRead
HR276doc 277Relative saturation (integer)INT16× 0.1%RSRead
HR512doc 513Error statusUINT16Read1 = No errors
HR770doc 771Oil typeCustom uses coefficients A and B.UINT16Read/write0 = Custom; 1 = Mineral oil; 2 = Synthetic ester (Midel 7131); 3 = Natural ester (FR3); 4 = Silicone liquid (Dow Corning 561)
HR776doc 777Oil coefficient A-100000...0.FLOAT32CDABRead/write
HR778doc 779Oil coefficient B-100...100.FLOAT32CDABRead/write
HR794doc 795Measurement filtering factor0.00001-1.FLOAT32CDABRead/write
HR1536doc 1537Modbus address1-247.INT16Read/write
HR1537doc 1538Bit rateUINT16Read/write5 = 9600; 6 = 19200
HR1538doc 1539Parity, data, stop bitsUINT16Read/write0 = N81; 1 = N82; 2 = E81; 3 = E82; 4 = O81; 5 = O82
HR1539doc 1540Response delay0-1020 ms.INT16msRead/write
HR1540doc 1541Interface modeUINT16Read/write6 = Modbus
HR1541doc 1542Restart deviceWrite 1 to restart.INT16Write
HR7680doc 7681Restore settingsWrite 1 to restore factory settings.INT16Write
HR7936doc 7937Signed integer testAlways reads -12345.INT16Read
HR7937doc 7938Floating point testAlways reads -123.45.FLOAT32CDABRead
HR7939doc 7940Text string testReads the text "-123.45".STRING[8]Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vaisala MMT143 moisture in oil transmitter (Modbus RTU)

What Modbus registers does the Vaisala MMT143 moisture in oil transmitter (Modbus RTU) have?

This map lists 23 registers: 23 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vaisala MMT143 moisture in oil transmitter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.

What byte order does the Vaisala MMT143 moisture in oil transmitter (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Vaisala MMT143 moisture in oil transmitter (Modbus RTU)?

Start with HR 34 Water content (Water content ppm); HR 28 Water activity (Water activity); HR 2 Temperature (Oil temperature); HR 512 Error status (Error status); HR 770 Oil type (Oil type).

How do I enable Modbus control of the Vaisala MMT143 moisture in oil transmitter (Modbus RTU)?

Order the transmitter with the Modbus configuration option, or set the serial mode to MODBUS with the SMODE serial command (applied at the next power-up).

Where is the official Vaisala MMT143 moisture in oil transmitter (Modbus RTU) Modbus documentation?

The source is MMT143 User Guide (M213308EN-B), revision 2026-11, published free by Vaisala at https://docs.vaisala.com/r/M213308EN-B/en-US.

More Vaisala Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: MMT143 User Guide · M213308EN-B · rev. 2026-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.