- TLS weight transmitter with analog output (Modbus RTU)
Sensor (load-cell weight transmitter) · Modbus register map
Laumas TLS weight transmitter with analog output (Modbus RTU) Modbus register map
Updated 17 November 2026
The TLS is a single-channel load-cell transmitter with an analog output and RS-485. With the port set to Modbus RTU it gives gross, net and peak weight, a status word, two inputs and two outputs, two setpoints and the analog-output span as holding registers. Tare, zero, calibration and EEPROM saves are triggered by writing codes to one command register.
This page lists 20 Modbus registers for the Laumas TLS weight transmitter with analog output (Modbus RTU) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Laumas’s own free documentation (linked below) and checked against it.
- Manufacturer
- Laumas
- Model
- TLS weight transmitter with analog output (Modbus RTU)
- Equipment type
- Sensor (load-cell weight transmitter)
- Registers
- 20 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- TLS, TLS 4-20mA, TLS 0-10V, CASTLTASTATEX
Integration notes: Laumas TLS weight transmitter with analog output (Modbus RTU)
Set the serial port to Modbus RTU, then read 40007-40013 with FC3: status word, gross, net and peak weight. Use the status sign bits and the division index (40014) to get the real value. Write 7, 9 and 8 to 40006 for tare on, tare off and zero.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 6 | Status register | BITMAP16 | Status word | Read |
| HR 7 | Gross weight | UINT32 ABCD | Gross weight | Read |
| HR 9 | Net weight | UINT32 ABCD | Net weight | Read |
| HR 13 | Divisions and units of measure | UINT16 | Division index for decimals | Read |
| HR 5 | Command register | UINT16 | Command register | Write |
| HR 24 | Inputs | BITMAP16 | Digital inputs | Read |
Enable Modbus control & writes
In the serial communication menu choose the Modbus RTU protocol (communication is disabled by default), then set address (1-99, default 1), baud (default 9600), parity (default none) and stop bits (default 1).
Byte order & addressing
- Only FC3 and FC16 are supported; write single registers with FC16.
- Maximum 32 registers per request.
- A settable reply delay (0-200 ms) in the serial menu slows responses.
Network setup
- RS-485: if the line is over 100 m or runs above 9600 baud, close the two RS-485 termination jumpers (120 ohm) on the furthest instruments.
- Broadcast writes (address 0) are executed without reply.
Watch out for
- Outputs can be written only when configured for PLC control in the outputs menu.
- Changing the theoretical full scale or the sensitivity resets weight-based settings such as setpoints and hysteresis to their defaults.
Laumas TLS weight transmitter with analog output (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Firmware version | UINT16 | Read | |||||
| HR | 1doc 40002 | Instrument type | UINT16 | Read | |||||
| HR | 2doc 40003 | Year of manufacture | UINT16 | Read | |||||
| HR | 3doc 40004 | Serial number | UINT16 | Read | |||||
| HR | 4doc 40005 | Active program | UINT16 | Read | |||||
| HR | 5doc 40006 | Command register | Write a command code to run it. | UINT16 | Write | 0 = No command; 7 = Semi-automatic tare on (net display); 8 = Semi-automatic zero; 9 = Semi-automatic tare off (gross display); 21 = Keypad lock; 22 = Keypad and display unlock; 23 = Keypad and display lock; 99 = Save data in EEPROM; 100 = Tare weight zero setting for calibration; 101 = Save first sample weight for calibration; 104 = Cancel real calibration; 106 = Add sample weight for calibration; 130 = Enable preset tare; 6811 = Write requested analog output current (value in registers 40122-40123); 6812 = Read requested analog output current into 40122-40123; 6813 = Write requested analog output voltage (value in registers 40122-40123); 6814 = Read requested analog output voltage into 40122-40123 | |||
| HR | 6doc 40007 | Status register | Weight sign, stability and error flags. | BITMAP16 | Read | bit 0 = Load cell error; bit 1 = AD converter malfunction; bit 2 = Maximum weight exceeded by 9 divisions; bit 3 = Gross weight over 110% of full scale; bit 4 = Gross weight over 999999 or under -999999; bit 5 = Net weight over 999999 or under -999999; bit 7 = Gross weight negative sign; bit 8 = Net weight negative sign; bit 9 = Peak weight negative sign; bit 10 = Net display mode; bit 11 = Weight stable; bit 12 = Weight within +/- 1/4 division of zero | |||
| HR | 7doc 40008 | Gross weight | Magnitude without decimal point; sign is status bit 7. | UINT32 | ABCD | Read | |||
| HR | 9doc 40010 | Net weight | Magnitude without decimal point; sign is status bit 8. | UINT32 | ABCD | Read | |||
| HR | 11doc 40012 | Peak weight | Magnitude without decimal point; sign is status bit 9. | UINT32 | ABCD | Read | |||
| HR | 13doc 40014 | Divisions and units of measure | High byte = unit index, low byte = division index. | UINT16 | Read | ||||
| HR | 16doc 40017 | Setpoint 1 | Weight value without decimal point; RAM until command 99. | INT32 | ABCD | Read/write | |||
| HR | 18doc 40019 | Setpoint 2 | Weight value without decimal point; RAM until command 99. | INT32 | ABCD | Read/write | |||
| HR | 22doc 40023 | Hysteresis 2 | Subtracted from setpoint 2 for release. | INT32 | ABCD | Read/write | |||
| HR | 24doc 40025 | Inputs | BITMAP16 | Read | bit 0 = Input 1 status; bit 1 = Input 2 status | ||||
| HR | 25doc 40026 | Outputs | Writable only for outputs configured for PLC control. | BITMAP16 | Read/write | bit 0 = Output 1 status; bit 1 = Output 2 status | |||
| HR | 36doc 40037 | Sample weight for calibration | Test weight in divisions; use with command 101/106. Reads 0 after success. | INT32 | ABCD | Read/write | |||
| HR | 42doc 40043 | Analog output zero weight | Weight giving analog zero; save with command 99. | INT32 | ABCD | Read/write | |||
| HR | 44doc 40045 | Analog output full-scale weight | Weight giving analog full scale; save with command 99. | INT32 | ABCD | Read/write | |||
| HR | 121doc 40122 | Exchange register 1-2 (analog value) | mA or V x 10000 for commands 6811-6814 (REGISTER 1 = H, REGISTER 2 = L). | UINT32 | ABCD | × 0.0001 | Read/write |
Notes on this map
- Host: this copy is hosted by Massload, not by Laumas; a search did not turn up a public copy on laumas.com.
- Word order: 32-bit values are H/L pairs, high word at the lower address. The read example returns gross 4000 as 0x0000 0x0FA0 at 40008-40009 and the -56 calibration example is 0xFFFF 0xFFC8 at 40037-40038, so ABCD is documented.
- Weights carry no sign and no decimal point: apply status bits 7-9 for the sign and the division index for decimals. Divisions/units register 40014: low byte = division index (0-18: 100, 50, 20, 10, 5, 2, 1 with 0 decimals; 0.5, 0.2, 0.1 with 1; 0.05, 0.02, 0.01 with 2; 0.005, 0.002, 0.001 with 3; 0.0005, 0.0002, 0.0001 with 4); high byte = unit index (0 kg, 1 g, 2 t, 3 lb, 4 N, 5 l, 6 bar, 7 atm, 8 pieces, 9 N m, 10 kg m, 11 other).
- Left out: Hysteresis 1 (40021-40022) because its access column is blank in the table; display coefficient 40015-40016 because the manual does not give its scaling for Modbus; exchange registers 40124-40131 whose use is not described.
- Command codes 1, 6, 20, 98 and 131 appear in the list with their name printed as display symbols that do not extract; they are not listed.
- Setpoints, hysteresis and analog-span values are written to RAM; send command 99 to keep them after power-off. EEPROM allows about 100000 writes.
- The manual says the calibration sample weight is a signed 32-bit number; it does not state signedness for setpoints, hysteresis or the analog-output weights, which are typed INT32 here (this only matters for negative values).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Laumas TLS weight transmitter with analog output (Modbus RTU)
What Modbus registers does the Laumas TLS weight transmitter with analog output (Modbus RTU) have?
This map lists 20 registers: 20 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Laumas TLS weight transmitter with analog output (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints registers as 40001-40131 and says to subtract 40001 for 0-based clients (40028 -> 27). Its read example asks for start address 0x0007 to read gross weight at 40008, which confirms it.
What byte order does the Laumas TLS weight transmitter with analog output (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Laumas TLS weight transmitter with analog output (Modbus RTU)?
Start with HR 6 Status register (Status word); HR 7 Gross weight (Gross weight); HR 9 Net weight (Net weight); HR 13 Divisions and units of measure (Division index for decimals); HR 5 Command register (Command register); HR 24 Inputs (Digital inputs).
How do I enable Modbus control of the Laumas TLS weight transmitter with analog output (Modbus RTU)?
In the serial communication menu choose the Modbus RTU protocol (communication is disabled by default), then set address (1-99, default 1), baud (default 9600), parity (default none) and stop bits (default 1).
Where is the official Laumas TLS weight transmitter with analog output (Modbus RTU) Modbus documentation?
The source is TLS Installation and User Manual (version 1.19). Laumas doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.massload.com/wp-content/uploads/2026/08/TLS_UserManual.pdf. It may be an older revision, so check it against the live unit.
More Laumas Modbus register maps
- Sensor (load-cell weight transmitter)
Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP)
Laumas TLB4 with the Modbus RTU port or the Modbus/TCP option; communication protocols manual version 1.12. Direct registers only.
Also known as: TLB4, TLB4 MODBUS, TLB4 Modbus/TCP - Sensor (load-cell weight indicator)
Laumas WLIGHT weight indicator / transmitter (Modbus RTU)
Laumas WLIGHT, installation and user manual version 1.03.
Also known as: WLIGHT, W LIGHT
Other valves, actuators & sensors register maps
- Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Sensor (duct humidity / temperature / CO2 / VOC)
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Siemens QFM9150/MO duct humidity/temperature sensor and QPM9152/MO duct air quality (CO2, VOC, humidity, temperature) sensor, basic documentation edition a (2022-12).
Also known as: QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585 - Sensor (Ethernet analog / digital output module)
Teracom TCW280 Ethernet analog output module
TCW280 per the Teracom TCW280 user manual TCW280_R1.8.
Also known as: TCW280 - Sensor (temperature)
Teracom TST300v3 / TST300v4 RS-485 precision temperature sensor
TST300v3/v4 per the Teracom TST300v3/v4 user manual Revision R1.19.
Also known as: TST300, TST300v3, TST300v4 - Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251 - Sensor (humidity and temperature transmitter)
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
HMW87 and HMW87D wall transmitters of the HMDW80 series (the Modbus models in user guide M211510EN-J).
Also known as: HMW87, HMW87D, HMDW80 Modbus
All valves, actuators & sensors Modbus register maps →
Source: TLS Installation and User Manual · version 1.19 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.