- Home
- Modbus register maps
- Teracom
- TCW280 Ethernet analog output module
Sensor (Ethernet analog / digital output module) · Modbus register map
Teracom TCW280 Ethernet analog output module Modbus register map
Updated 19 November 2026
The TCW280 is a Teracom Ethernet module with 2 isolated analog outputs (0-5/0-10 V or 0-20/4-20/0-24 mA), 4 open-drain digital outputs with ON/OFF or PWM mode and 2 relays. Over Modbus TCP the relays and digital outputs are coils, and modes, ranges, setpoints and alarms are holding registers.
This page lists 62 Modbus registers for the Teracom TCW280 Ethernet analog output module — 57 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teracom’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teracom
- Model
- TCW280 Ethernet analog output module
- Equipment type
- Sensor (Ethernet analog / digital output module)
- Registers
- 62 (57 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- TCW280
- Source document
- TCW280 User manual · TCW280_R1.8 · rev. 2026-10
Integration notes: Teracom TCW280 Ethernet analog output module
Enable Modbus TCP, set each analog output's mode and range (holding 18200/18300), then write the output value as a float to holding 18500/18502 with function 16.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 100 | Relay 1 | BIT | Relay 1 | Read/write |
| HR 18500 | Analog out 1 value | FLOAT32 ABCD | Analog output 1 value | Read/write |
| HR 18200 | Analog out 1 mode | UINT16 | Analog output 1 mode | Read/write |
| HR 18300 | Analog out 1 range | UINT16 | Analog output 1 range | Read/write |
| HR 18600 | Analog out 1 alarm | UINT16 | Analog output 1 alarm | Read |
| HR 16700 | Digital out 1 state | UINT16 | Digital output 1 state | Read/write |
Enable Modbus control & writes
Modbus TCP is off by default. Turn it on in the Modbus TCP/IP settings of the web interface (default port 502).
Byte order & addressing
- Floats are high word first (ABCD).
Network setup
- The factory IP is 192.168.1.2 (web login admin/admin); change it in the network settings, then enable Modbus TCP/IP.
Teracom TCW280 Ethernet analog output module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 100 | Relay 1 | Relay state; write with FC05/15. | BIT | Read/write | ||||
| CO | 101 | Relay 2 | Relay state; write with FC05/15. | BIT | Read/write | ||||
| CO | 102 | Digital out 1 | BIT | Read/write | |||||
| CO | 103 | Digital out 2 | BIT | Read/write | |||||
| CO | 104 | Digital out 3 | BIT | Read/write | |||||
| CO | 105 | Digital out 4 | BIT | Read/write | |||||
| HR | 15000 | Relay 1 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 15032 | Relay 2 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 15200 | Relay 1 pulse width | Pulse duration; the manual gives no unit here (the web page sets it in seconds, 0.1-999999). | FLOAT32 | ABCD | Read/write | |||
| HR | 15202 | Relay 2 pulse width | Pulse duration; the manual gives no unit here (the web page sets it in seconds, 0.1-999999). | FLOAT32 | ABCD | Read/write | |||
| HR | 15300 | Relay 1 activated from | UINT16 | Read/write | 0 = webORm2m; 1 = shedule1; 2 = shedle2; 3 = sheule3; 4 = shedule4 | ||||
| HR | 15301 | Relay 2 activated from | UINT16 | Read/write | 0 = webORm2m; 1 = shedule1; 2 = shedle2; 3 = sheule3; 4 = shedule4 | ||||
| HR | 15400 | Relay 1 state after restart | UINT16 | Read/write | 0 = lastState; 1 = on; 2 = off | ||||
| HR | 15401 | Relay 2 state after restart | UINT16 | Read/write | 0 = lastState; 1 = on; 2 = off | ||||
| HR | 16000 | Digital out 1 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 16032 | Digital out 2 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 16064 | Digital out 3 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 16096 | Digital out 4 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 16200 | Digital out 1 mode | UINT16 | Read/write | 0 = onoff; 1 = pwm | ||||
| HR | 16201 | Digital out 2 mode | UINT16 | Read/write | 0 = onoff; 1 = pwm | ||||
| HR | 16202 | Digital out 3 mode | UINT16 | Read/write | 0 = onoff; 1 = pwm | ||||
| HR | 16203 | Digital out 4 mode | UINT16 | Read/write | 0 = onoff; 1 = pwm | ||||
| HR | 16300 | Digital out 1 pulse width | Pulse duration; the manual gives no unit here (the web page sets it in seconds, 0.1-999999). | FLOAT32 | ABCD | Read/write | |||
| HR | 16302 | Digital out 2 pulse width | Pulse duration; the manual gives no unit here (the web page sets it in seconds, 0.1-999999). | FLOAT32 | ABCD | Read/write | |||
| HR | 16304 | Digital out 3 pulse width | Pulse duration; the manual gives no unit here (the web page sets it in seconds, 0.1-999999). | FLOAT32 | ABCD | Read/write | |||
| HR | 16306 | Digital out 4 pulse width | Pulse duration; the manual gives no unit here (the web page sets it in seconds, 0.1-999999). | FLOAT32 | ABCD | Read/write | |||
| HR | 16400 | Digital out 1 activated from | UINT16 | Read/write | 0 = webORm2m; 1 = shedule1; 2 = shedle2; 3 = sheule3; 4 = shedule4 | ||||
| HR | 16401 | Digital out 2 activated from | UINT16 | Read/write | 0 = webORm2m; 1 = shedule1; 2 = shedle2; 3 = sheule3; 4 = shedule4 | ||||
| HR | 16402 | Digital out 3 activated from | UINT16 | Read/write | 0 = webORm2m; 1 = shedule1; 2 = shedle2; 3 = sheule3; 4 = shedule4 | ||||
| HR | 16403 | Digital out 4 activated from | UINT16 | Read/write | 0 = webORm2m; 1 = shedule1; 2 = shedle2; 3 = sheule3; 4 = shedule4 | ||||
| HR | 16500 | Digital out 1 state after restart | UINT16 | Read/write | 0 = lastState; 1 = on; 2 = off | ||||
| HR | 16501 | Digital out 2 state after restart | UINT16 | Read/write | 0 = lastState; 1 = on; 2 = off | ||||
| HR | 16502 | Digital out 3 state after restart | UINT16 | Read/write | 0 = lastState; 1 = on; 2 = off | ||||
| HR | 16503 | Digital out 4 state after restart | UINT16 | Read/write | 0 = lastState; 1 = on; 2 = off | ||||
| HR | 16600 | Digital out 1 pwm duty | PWM duty cycle, 0-100 %. | FLOAT32 | ABCD | % | Read/write | ||
| HR | 16602 | Digital out 2 pwm duty | PWM duty cycle, 0-100 %. | FLOAT32 | ABCD | % | Read/write | ||
| HR | 16604 | Digital out 3 pwm duty | PWM duty cycle, 0-100 %. | FLOAT32 | ABCD | % | Read/write | ||
| HR | 16606 | Digital out 4 pwm duty | PWM duty cycle, 0-100 %. | FLOAT32 | ABCD | % | Read/write | ||
| HR | 16700 | Digital out 1 state | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 16701 | Digital out 2 state | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 16702 | Digital out 3 state | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 16703 | Digital out 4 state | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 16800 | Digital out 1 pulse | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 16801 | Digital out 2 pulse | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 16802 | Digital out 3 pulse | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 16803 | Digital out 4 pulse | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 16900 | Digital out pwm frequency | UINT16 | Read/write | 0 = 1Hz; 1 = 5Hz; 2 = 10Hz; 3 = 50Hz; 4 = 100Hz; 5 = 500Hz; 6 = 1000Hz; 7 = 2000Hz | ||||
| HR | 18000 | Analog out 1 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18032 | Analog out 2 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18200 | Analog out 1 mode | UINT16 | Read/write | 0 = voltage; 1 = current | ||||
| HR | 18201 | Analog out 2 mode | UINT16 | Read/write | 0 = voltage; 1 = current | ||||
| HR | 18300 | Analog out 1 range | UINT16 | Read/write | 0 = 0V to 5V; 1 = 0V to 10V; 5 = 4mA to 20mA; 6 = 0mA to 20mA; 7 = 0mA to 24mA | ||||
| HR | 18301 | Analog out 2 range | UINT16 | Read/write | 0 = 0V to 5V; 1 = 0V to 10V; 5 = 4mA to 20mA; 6 = 0mA to 20mA; 7 = 0mA to 24mA | ||||
| HR | 18400 | Analog out 1 value after restart | UINT16 | Read/write | 0 = lastValue; 1 = 0V of 5V; 2 = 2.5V of 5V; 3 = 5V of 5V; 4 = 0V of 10V; 5 = 5V of 10V; 6 = 10V of 10V; 7 = 0mA; 8 = 2mA; 9 = 4mA; 10 = 10mA; 11 = 12mA; 12 = 20mA; 13 = 22mA; 14 = 24mA | ||||
| HR | 18401 | Analog out 2 value after restart | UINT16 | Read/write | 0 = lastValue; 1 = 0V of 5V; 2 = 2.5V of 5V; 3 = 5V of 5V; 4 = 0V of 10V; 5 = 5V of 10V; 6 = 10V of 10V; 7 = 0mA; 8 = 2mA; 9 = 4mA; 10 = 10mA; 11 = 12mA; 12 = 20mA; 13 = 22mA; 14 = 24mA | ||||
| HR | 18500 | Analog out 1 value | Analog output setpoint in the units of the selected range (V or mA). | FLOAT32 | ABCD | Read/write | |||
| HR | 18502 | Analog out 2 value | Analog output setpoint in the units of the selected range (V or mA). | FLOAT32 | ABCD | Read/write | |||
| HR | 18600 | Analog out 1 alarm | UINT16 | Read | 0 = none; 1 = over temperature; 4 = out fault; 5 = over temperature and out fault | ||||
| HR | 18601 | Analog out 2 alarm | UINT16 | Read | 0 = none; 1 = over temperature; 4 = out fault; 5 = over temperature and out fault | ||||
| HR | 50100 | Device ID | Sensor ROM ID as text. | STRING[18] | Read | ||||
| HR | 50200 | Hostname | STRING[16] | Read | |||||
| HR | 50300 | Device IP | STRING[16] | Read |
Notes on this map
- Word order: the manual says float registers are sent big-endian and its example response 3FA0 0000 is given as 1.25, i.e. high word first (ABCD).
- Strings are fixed-length UTF-8, zero padded; 64-byte fields span 32 registers.
- Left out: Save configuration, Restart device and HW error (PDU 50000-50002), whose data size column is empty in this manual.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teracom TCW280 Ethernet analog output module
What Modbus registers does the Teracom TCW280 Ethernet analog output module have?
This map lists 62 registers: 6 coils, 56 holding registers. 57 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teracom TCW280 Ethernet analog output module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The address table prints PDU (wire) addresses in decimal. The manual's example frames use them directly (coil 100 = 0x0064, holding register 500 = 0x01F4), so no offset is applied.
What byte order does the Teracom TCW280 Ethernet analog output module use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Teracom TCW280 Ethernet analog output module?
Start with CO 100 Relay 1 (Relay 1); HR 18500 Analog out 1 value (Analog output 1 value); HR 18200 Analog out 1 mode (Analog output 1 mode); HR 18300 Analog out 1 range (Analog output 1 range); HR 18600 Analog out 1 alarm (Analog output 1 alarm); HR 16700 Digital out 1 state (Digital output 1 state).
How do I enable Modbus control of the Teracom TCW280 Ethernet analog output module?
Modbus TCP is off by default. Turn it on in the Modbus TCP/IP settings of the web interface (default port 502).
Where is the official Teracom TCW280 Ethernet analog output module Modbus documentation?
The source is TCW280 User manual (TCW280_R1.8), revision 2026-10, published free by Teracom at https://www.teracomsystems.com/download/analog-output-module-tcw280-user-manual/.
More Teracom Modbus register maps
- Sensor (temperature / humidity data logger)
Teracom TCW210-TH temperature and humidity data logger
TCW210-TH per the Teracom TCW210-TH user manual Revision R1.26, firmware V2.012 or later.
Also known as: TCW210-TH, TCW210 - Sensor (Ethernet data logger / I/O module)
Teracom TCW220 Ethernet data logger
TCW220 per the Teracom TCW220 user manual Revision R4.24, firmware V2.012 or later.
Also known as: TCW220 - Sensor (Ethernet I/O module)
Teracom TCW241 Ethernet I/O module
TCW241 per the Teracom TCW241 user manual Revision R4.30, firmware v2.012 or later.
Also known as: TCW241 - Energy meter (Ethernet energy monitoring / data logger)
Teracom TCW260 Ethernet energy monitoring module
TCW260 per the Teracom TCW260 user manual Revision R1.19, firmware V3.009 or later.
Also known as: TCW260 - Sensor (1-Wire to Modbus gateway)
Teracom TCW320x-WMG 1-Wire to Modbus gateway
TCW320E-WMG (Ethernet) and TCW320W-WMG (Wi-Fi) per the user manual Revision R1.0; both share one fixed register map.
Also known as: TCW320E-WMG, TCW320W-WMG - Energy meter (S0 pulse counter / digital input module)
Teracom TDI340 4-channel S0 pulse counter with Modbus RTU
TDI340 per the Teracom TDI340 user manual Revision R1.11, firmware V1.06 or later.
Also known as: TDI340 - Sensor (relay output module)
Teracom TDO340 4-channel Modbus RTU relay output module
TDO340 per the Teracom TDO340 user manual Revision R1.2, firmware V1.03 or later.
Also known as: TDO340 - Sensor (water leak detector)
Teracom TSF400-4 water-leak detector with Modbus RTU
TSF400-4 per the Teracom TSF400-4 user manual Revision R1.2.
Also known as: TSF400-4 - Sensor (humidity / temperature)
Teracom TSH300v3 RS-485 humidity and temperature sensor
TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.
Also known as: TSH300, TSH300v3 - Sensor (humidity / temperature)
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor
TSH331 per the Teracom TSH331 user manual Rev. 1.5, firmware v1.08 or later.
Also known as: TSH331 - Sensor (CO2 / pressure)
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
TSM400-4-CP per the Teracom TSM400-4-CP user manual TSM400-4-CP-R1.9.
Also known as: TSM400-4-CP - Sensor (CO2 / humidity / temperature / pressure)
Teracom TSM400-4-CPTH Modbus CO2, humidity, temperature and pressure multi-sensor
TSM400-4-CPTH per the Teracom TSM400-4-CPTH user manual TSM400-4-CPTH-R1.9.
Also known as: TSM400-4-CPTH - Sensor (humidity / temperature)
Teracom TSM400-4-TH Modbus humidity and temperature sensor
TSM400-4-TH per the Teracom TSM400-4-TH user manual TSM400-4-TH-R1.10.
Also known as: TSM400-4-TH - Sensor (temperature)
Teracom TST300v3 / TST300v4 RS-485 precision temperature sensor
TST300v3/v4 per the Teracom TST300v3/v4 user manual Revision R1.19.
Also known as: TST300, TST300v3, TST300v4 - Sensor (thermocouple input module)
Teracom TST320 2-channel thermocouple module with Modbus RTU
TST320 per the Teracom TST320 user manual Revision R1.6.
Also known as: TST320 - Sensor (AC/DC voltage transducer)
Teracom TSV300 AC/DC voltage transducer with Modbus RTU
TSV300 per the Teracom TSV300 user manual Revision R1.4, firmware V1.06 or later.
Also known as: TSV300
Other valves, actuators & sensors register maps
- Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251 - Sensor (humidity and temperature transmitter)
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
HMW87 and HMW87D wall transmitters of the HMDW80 series (the Modbus models in user guide M211510EN-J).
Also known as: HMW87, HMW87D, HMDW80 Modbus - Sensor (ultrasonic wind)
Vaisala WM80 ultrasonic wind sensor (Modbus RTU)
WM80 sensors with RS-485 in Modbus mode (e.g. ordering option C), per user guide M212995EN-F.
Also known as: WM80, Vaisala WM80, Ultrasonic Wind Sensor WM80 - Water treatment controller (Sensor / controller)
Walchem W900 water treatment controller (Modbus/TCP)
Walchem W900 controllers (software 3.01 and up) with the Modbus/TCP feature, per Modbus manual 180676.K. W600, Intuition-6 and Intuition-9 use the same type maps but different block start addresses.
Also known as: W900 series - Sensor (Ethernet analog output module)
Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP)
BusWorks XT1531-000 per its user's manual (file revision H, 18 Nov 2022).
Also known as: XT1531-000, XT1531, BusWorks XT1531 - Sensor (humidity / temperature transmitter)
Dwyer Series RHPX communicating humidity/temperature transmitter
Dwyer Series RHPX humidity and temperature transmitters with the BACnet MS/TP / Modbus RTU communication board, set to Modbus with DIP switch 9 (bulletin AQ-RHPX-C).
Also known as: RHPX, Dwyer RHPX BACnet/Modbus, 607xxx
All valves, actuators & sensors Modbus register maps →
Source: TCW280 User manual · TCW280_R1.8 · rev. 2026-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.