- BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP)
Sensor (Ethernet analog output module) · Modbus register map
Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) Modbus register map
Updated 19 November 2026
The Acromag BusWorks XT1531 is a Modbus TCP module with four 0-20/4-20 mA analog outputs and four digital I/O channels. The map has the output values, the digital output group (as coils or one holding register), input states and a heartbeat.
This page lists 15 Modbus registers for the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Acromag’s own free documentation (linked below) and checked against it.
- Manufacturer
- Acromag
- Model
- BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP)
- Equipment type
- Sensor (Ethernet analog output module)
- Registers
- 15 (9 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- XT1531-000, XT1531, BusWorks XT1531
Integration notes: Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP)
Write holding registers 1-4 with normalized counts (30000 = 100 % of range) to set the four current outputs; drive digital outputs with coils 0-3 or holding register 0 depending on the configured mode.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Set AO CH00 value | INT16 | AO channel 0 | Read/write |
| HR 2 | Set AO CH01 value | INT16 | AO channel 1 | Read/write |
| HR 0 | Set DO state CH0-3 | BITMAP16 | Digital outputs (holding mode) | Read/write |
| IR 0 | Digital I/O input states CH0-3 | BITMAP16 | Digital I/O states | Read |
| IR 1 | Heart beat | UINT16 | Heartbeat | Read |
Enable Modbus control & writes
Modbus TCP needs no enabling; set the IP address (default static 192.168.1.100), output ranges and coil-versus-holding mode with the USB configuration software.
Communication loss & watchdog
Each digital I/O channel has a watchdog time (1-65534 s, 0 or 65535 = off) and watchdog state (on/off) set in the USB software; with no read/write activity for that time the output goes to its watchdog state. The manual describes no watchdog for the analog outputs.
Byte order & addressing
- Digital outputs are off (40001 reads 0) after reset.
- Coil access and holding-register access to the digital outputs are mutually exclusive.
Network setup
- Digital outputs need excitation on EXC to work.
Watch out for
- If a digital output is on, the paired input reads high; turn the output off to monitor a field signal on that channel.
- If the module is an i2o target, coil access must be disabled.
Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Digital output CH0 | Only when coil access is enabled in the USB software. | BIT | Read/write | ||||
| CO | 1doc 00002 | Digital output CH1 | Only when coil access is enabled in the USB software. | BIT | Read/write | ||||
| CO | 2doc 00003 | Digital output CH2 | Only when coil access is enabled in the USB software. | BIT | Read/write | ||||
| CO | 3doc 00004 | Digital output CH3 | Only when coil access is enabled in the USB software. | BIT | Read/write | ||||
| DI | 0doc 10001 | Digital input CH0 | 1 = input high (above 2 V). | BIT | Read | ||||
| DI | 1doc 10002 | Digital input CH1 | 1 = input high (above 2 V). | BIT | Read | ||||
| DI | 2doc 10003 | Digital input CH2 | 1 = input high (above 2 V). | BIT | Read | ||||
| DI | 3doc 10004 | Digital input CH3 | 1 = input high (above 2 V). | BIT | Read | ||||
| IR | 0doc 30001 | Digital I/O input states CH0-3 | BITMAP16 | Read | bit 0 = CH0 ON; bit 1 = CH1 ON; bit 2 = CH2 ON; bit 3 = CH3 ON | ||||
| IR | 1doc 30002 | Heart beat | Counts 0-65535 on each host transfer, then wraps. | UINT16 | Read | ||||
| HR | 0doc 40001 | Set DO state CH0-3 | Only when coil access is disabled; writes all four outputs. | BITMAP16 | Read/write | bit 0 = DO CH0 ON; bit 1 = DO CH1 ON; bit 2 = DO CH2 ON; bit 3 = DO CH3 ON | |||
| HR | 1doc 40002 | Set AO CH00 value | Normalized count: 0-30000 = 0-100 % of the output range (0-20000 in legacy mode). | INT16 | Read/write | ||||
| HR | 2doc 40003 | Set AO CH01 value | Normalized count: 0-30000 = 0-100 % of the output range (0-20000 in legacy mode). | INT16 | Read/write | ||||
| HR | 3doc 40004 | Set AO CH02 value | Normalized count: 0-30000 = 0-100 % of the output range (0-20000 in legacy mode). | INT16 | Read/write | ||||
| HR | 4doc 40005 | Set AO CH03 value | Normalized count: 0-30000 = 0-100 % of the output range (0-20000 in legacy mode). | INT16 | Read/write |
Notes on this map
- Analog outputs are normalized counts: 0-30000 = 0-100 % of the selected 0-20 mA or 4-20 mA range (0-20000 with legacy support). The manual notes 20 mA corresponds to a raw DAC count of 29533 and 4 mA to 5907 on the 0-20 mA primary range.
- Digital outputs are either coils 00001-00004 (coil option enabled) or bits 0-3 of holding register 40001 (coil option disabled), never both. With 40001, read the current states first and mask, because all four outputs are written at once.
- The digital output register 40001 reads 0 after reset (outputs off) and is not kept in non-volatile memory.
- The map prints the Modicon reference and a 0-based address column; the address column is sent on the wire.
- There are no configuration registers: ranges, IP settings, coil-versus-holding mode and DIO watchdogs are set only with the USB configuration software.
- The Unit ID is ignored and echoed back in Modbus TCP.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP)
What Modbus registers does the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) have?
This map lists 15 registers: 4 coils, 4 discrete inputs, 2 input registers, 5 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register map prints both the reference (00001, 10001, 30001, 40001) and the 0-based address column; the address column is what goes on the wire.
What are the minimum Modbus registers to integrate the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP)?
Start with HR 1 Set AO CH00 value (AO channel 0); HR 2 Set AO CH01 value (AO channel 1); HR 0 Set DO state CH0-3 (Digital outputs (holding mode)); IR 0 Digital I/O input states CH0-3 (Digital I/O states); IR 1 Heart beat (Heartbeat).
How do I enable Modbus control of the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP)?
Modbus TCP needs no enabling; set the IP address (default static 192.168.1.100), output ranges and coil-versus-holding mode with the USB configuration software.
What happens when the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) loses Modbus communication?
Each digital I/O channel has a watchdog time (1-65534 s, 0 or 65535 = off) and watchdog state (on/off) set in the USB software; with no read/write activity for that time the output goes to its watchdog state. The manual describes no watchdog for the analog outputs.
Where is the official Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) Modbus documentation?
The source is BusWorks XT Series Model XT1531-000 4 CH Current Output + 4 CH Digital I/O User's Manual (8501012H), revision 2022-11-18, published free by Acromag at https://www.acromag.com/wp-content/uploads/2019/06/Acromag-XT1531_012H-User-Manual.pdf.
More Acromag Modbus register maps
- Sensor (Ethernet digital I/O module)
Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP)
BusWorks XT1121-000 per user's manual 8500950P (revision P, 18 Nov 2022).
Also known as: XT1121-000, XT1121, BusWorks XT1121 - Sensor (Ethernet analog input module)
Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP)
BusWorks XT1211-000 (current) and XT1221-000 (voltage) per user's manual 8500951K.
Also known as: XT1211-000, XT1221-000, XT1211, XT1221, BusWorks XT1211, BusWorks XT1221 - Sensor (Ethernet analog output module)
Acromag BusWorks XT1541-000 8-channel voltage output + 4 digital I/O (Modbus TCP)
BusWorks XT1541-000 per its user's manual (file revision H, 18 Nov 2022).
Also known as: XT1541-000, XT1541, BusWorks XT1541
Other valves, actuators & sensors register maps
- Sensor (humidity / temperature transmitter)
Dwyer Series RHPX communicating humidity/temperature transmitter
Dwyer Series RHPX humidity and temperature transmitters with the BACnet MS/TP / Modbus RTU communication board, set to Modbus with DIP switch 9 (bulletin AQ-RHPX-C).
Also known as: RHPX, Dwyer RHPX BACnet/Modbus, 607xxx - Sensor (turbidity)
JUMO ecoLine NTU digital turbidity sensor (Modbus RTU)
JUMO ecoLine NTU type 202670 with RS-485 Modbus RTU (interface description V1.01).
Also known as: 202670, JUMO ecoLine NTU, ecoLine NTU type 202670 - Sensor (vibration / temperature)
Machine Saver TriVibe vibration and temperature sensor (Modbus RTU)
Machine Saver TriVibe triaxial vibration sensors on RS-485 Modbus RTU, per the 'Modbus Registers Map' page of the Machine Saver online library (revision #12).
Also known as: TriVibe, Machine Saver TriVibe - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (flow transmitter)
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
SITRANS F M MAG 6000 / MAG 6000 I electromagnetic flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MAG 6000, MAG 6000 I, SITRANS FM MAG 6000 - Sensor (humidity / temperature)
Teracom TSH300v3 RS-485 humidity and temperature sensor
TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.
Also known as: TSH300, TSH300v3
All valves, actuators & sensors Modbus register maps →
Source: BusWorks XT Series Model XT1531-000 4 CH Current Output + 4 CH Digital I/O User's Manual · 8501012H · rev. 2022-11-18. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.