Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) Modbus register map

Updated 19 November 2026

Short answer

The Acromag BusWorks XT1531 is a Modbus TCP module with four 0-20/4-20 mA analog outputs and four digital I/O channels. The map has the output values, the digital output group (as coils or one holding register), input states and a heartbeat.

This page lists 15 Modbus registers for the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Acromag’s own free documentation (linked below) and checked against it.

Manufacturer
Acromag
Model
BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP)
Equipment type
Sensor (Ethernet analog output module)
Registers
15 (9 writable)
Transport
Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
XT1531-000, XT1531, BusWorks XT1531
Source document
BusWorks XT Series Model XT1531-000 4 CH Current Output + 4 CH Digital I/O User's Manual · 8501012H · rev. 2022-11-18
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP)

Integration in brief

Write holding registers 1-4 with normalized counts (30000 = 100 % of range) to set the four current outputs; drive digital outputs with coils 0-3 or holding register 0 depending on the configured mode.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Set AO CH00 valueINT16AO channel 0Read/write
HR 2Set AO CH01 valueINT16AO channel 1Read/write
HR 0Set DO state CH0-3BITMAP16Digital outputs (holding mode)Read/write
IR 0Digital I/O input states CH0-3BITMAP16Digital I/O statesRead
IR 1Heart beatUINT16HeartbeatRead

Enable Modbus control & writes

Modbus TCP needs no enabling; set the IP address (default static 192.168.1.100), output ranges and coil-versus-holding mode with the USB configuration software.

Communication loss & watchdog

Each digital I/O channel has a watchdog time (1-65534 s, 0 or 65535 = off) and watchdog state (on/off) set in the USB software; with no read/write activity for that time the output goes to its watchdog state. The manual describes no watchdog for the analog outputs.

Byte order & addressing

Network setup

Watch out for

Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

15 of 15 shown
Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001Digital output CH0Only when coil access is enabled in the USB software.BITRead/write
CO1doc 00002Digital output CH1Only when coil access is enabled in the USB software.BITRead/write
CO2doc 00003Digital output CH2Only when coil access is enabled in the USB software.BITRead/write
CO3doc 00004Digital output CH3Only when coil access is enabled in the USB software.BITRead/write
DI0doc 10001Digital input CH01 = input high (above 2 V).BITRead
DI1doc 10002Digital input CH11 = input high (above 2 V).BITRead
DI2doc 10003Digital input CH21 = input high (above 2 V).BITRead
DI3doc 10004Digital input CH31 = input high (above 2 V).BITRead
IR0doc 30001Digital I/O input states CH0-3BITMAP16Readbit 0 = CH0 ON; bit 1 = CH1 ON; bit 2 = CH2 ON; bit 3 = CH3 ON
IR1doc 30002Heart beatCounts 0-65535 on each host transfer, then wraps.UINT16Read
HR0doc 40001Set DO state CH0-3Only when coil access is disabled; writes all four outputs.BITMAP16Read/writebit 0 = DO CH0 ON; bit 1 = DO CH1 ON; bit 2 = DO CH2 ON; bit 3 = DO CH3 ON
HR1doc 40002Set AO CH00 valueNormalized count: 0-30000 = 0-100 % of the output range (0-20000 in legacy mode).INT16Read/write
HR2doc 40003Set AO CH01 valueNormalized count: 0-30000 = 0-100 % of the output range (0-20000 in legacy mode).INT16Read/write
HR3doc 40004Set AO CH02 valueNormalized count: 0-30000 = 0-100 % of the output range (0-20000 in legacy mode).INT16Read/write
HR4doc 40005Set AO CH03 valueNormalized count: 0-30000 = 0-100 % of the output range (0-20000 in legacy mode).INT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP)

What Modbus registers does the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) have?

This map lists 15 registers: 4 coils, 4 discrete inputs, 2 input registers, 5 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register map prints both the reference (00001, 10001, 30001, 40001) and the 0-based address column; the address column is what goes on the wire.

What are the minimum Modbus registers to integrate the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP)?

Start with HR 1 Set AO CH00 value (AO channel 0); HR 2 Set AO CH01 value (AO channel 1); HR 0 Set DO state CH0-3 (Digital outputs (holding mode)); IR 0 Digital I/O input states CH0-3 (Digital I/O states); IR 1 Heart beat (Heartbeat).

How do I enable Modbus control of the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP)?

Modbus TCP needs no enabling; set the IP address (default static 192.168.1.100), output ranges and coil-versus-holding mode with the USB configuration software.

What happens when the Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) loses Modbus communication?

Each digital I/O channel has a watchdog time (1-65534 s, 0 or 65535 = off) and watchdog state (on/off) set in the USB software; with no read/write activity for that time the output goes to its watchdog state. The manual describes no watchdog for the analog outputs.

Where is the official Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP) Modbus documentation?

The source is BusWorks XT Series Model XT1531-000 4 CH Current Output + 4 CH Digital I/O User's Manual (8501012H), revision 2022-11-18, published free by Acromag at https://www.acromag.com/wp-content/uploads/2019/06/Acromag-XT1531_012H-User-Manual.pdf.

More Acromag Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: BusWorks XT Series Model XT1531-000 4 CH Current Output + 4 CH Digital I/O User's Manual · 8501012H · rev. 2022-11-18. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.