Sensor (vibration / temperature) · Modbus register map
Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) Modbus register map
Updated 17 November 2026
TriVibe is a triaxial vibration and temperature sensor that talks Modbus RTU on RS-485 at 115200 baud. Overall acceleration, velocity and displacement per axis are 32-bit floats, high word first. This map covers system status, run time, temperature, overall vibration values from the external and internal accelerometers, alarm states and the four configurable alarm channels.
This page lists 78 Modbus registers for the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) — 27 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Machine Saver’s own free documentation (linked below) and checked against it.
- Manufacturer
- Machine Saver
- Model
- TriVibe vibration and temperature sensor (Modbus RTU)
- Equipment type
- Sensor (vibration / temperature)
- Registers
- 78 (27 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 115200 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- TriVibe, Machine Saver TriVibe
Integration notes: Machine Saver TriVibe vibration and temperature sensor (Modbus RTU)
Poll at 115200 8N1 using the slave ID from the serial number label. Read FC03 block 172-189 for overall vibration and 226-229 for alarm states; write with FC16 only.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 178 | Axis 1 velocity | FLOAT32 ABCD | Axis 1 velocity | Read |
| HR 180 | Axis 2 velocity | FLOAT32 ABCD | Axis 2 velocity | Read |
| HR 182 | Axis 3 velocity | FLOAT32 ABCD | Axis 3 velocity | Read |
| HR 172 | Axis 1 acceleration | FLOAT32 ABCD | Axis 1 acceleration | Read |
| HR 31 | TEMPERATURE | INT16 | Temperature | Read |
| HR 226 | ALARM_1_STATE | UINT16 | Alarm 1 state | Read |
| HR 4 | SYSTEM_STATE2 | BITMAP16 | System state flags | Read |
Enable Modbus control & writes
Modbus RTU is always on. Configuration and alarm registers are locked until the matching unlock command is written to SYSTEM_CONTROL (register 1), and must be saved with the matching save command.
Byte order & addressing
- Only FC03 and FC16 are supported; write single registers with FC16 and a length of 1.
- Floats are high word first (ABCD).
- Default slave ID is not 1: it is the last two digits of the serial number.
Network setup
- Serial: 115200 baud, no parity, 8 data bits, 1 stop bit, no handshake.
- Each sensor on a multi-drop bus needs a unique slave ID.
Watch out for
- Writing the wrong SYSTEM_CONTROL value can reset the sensor or erase its EEPROM.
Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | SYSTEM_INFO | Firmware ID and revision. | UINT16 | Read | ||||
| HR | 1 | SYSTEM_CONTROL | Command register; use with care (some commands reset or erase). | UINT16 | Read/write | 0 = Idle; 1 = Reset; 2 = Clear alarms; 3 = Load data; 42074 = Unlock alarm registers; 42075 = Save alarm registers; 45555 = Unlock config registers; 45556 = Save config registers; 55555 = Restart firmware | |||
| HR | 2 | SYSTEM_STATUS | Progress of the last command (done / in progress / flagged). | UINT16 | Read | ||||
| HR | 3 | SYSTEM_STATE1 | BITMAP16 | Read | bit 0 = Machine on | ||||
| HR | 4 | SYSTEM_STATE2 | Internal health flags. | BITMAP16 | Read | bit 0 = Power flag; bit 1 = DRAM flag; bit 2 = ADC flag; bit 3 = NVM flag; bit 4 = Temperature flag; bit 5 = Calibration flag; bit 6 = Collect flag; bit 7 = Impact flag; bit 8 = Alarm flag; bit 9 = Alarm level flag; bit 10 = Collect2 flag; bit 11 = Sine table flag; bit 12 = Detonation flag; bit 13 = Board type flag; bit 14 = On/off flag | |||
| HR | 5 | MINUTES_ON | Run-time counter, minutes part. | UINT16 | Read | ||||
| HR | 6 | HOURS_ON | Run-time counter, hours part. | UINT16 | Read | ||||
| HR | 7 | DAYS_ON | Run-time counter, days part. | UINT16 | Read | ||||
| HR | 17 | SYSTEM_RTU | Modbus slave ID in use. | UINT16 | Read | ||||
| HR | 26doc 26-27 | Serial number (UIDL) | High word at 26, low word at 27. | UINT32 | ABCD | Read | |||
| HR | 31 | TEMPERATURE | Sensor temperature; divide by 10. Unit not stated on the page. | INT16 | × 0.1 | Read | |||
| HR | 172doc 172-173 | Axis 1 acceleration | External accelerometer input, overall value. | FLOAT32 | ABCD | g RMS | Read | ||
| HR | 174doc 174-175 | Axis 2 acceleration | External accelerometer input, overall value. | FLOAT32 | ABCD | g RMS | Read | ||
| HR | 176doc 176-177 | Axis 3 acceleration | External accelerometer input, overall value. | FLOAT32 | ABCD | g RMS | Read | ||
| HR | 178doc 178-179 | Axis 1 velocity | External accelerometer input, overall value. | FLOAT32 | ABCD | in/s RMS | Read | ||
| HR | 180doc 180-181 | Axis 2 velocity | External accelerometer input, overall value. | FLOAT32 | ABCD | in/s RMS | Read | ||
| HR | 182doc 182-183 | Axis 3 velocity | External accelerometer input, overall value. | FLOAT32 | ABCD | in/s RMS | Read | ||
| HR | 184doc 184-185 | Axis 1 displacement | External accelerometer input, overall value. | FLOAT32 | ABCD | mils | Read | ||
| HR | 186doc 186-187 | Axis 2 displacement | External accelerometer input, overall value. | FLOAT32 | ABCD | mils | Read | ||
| HR | 188doc 188-189 | Axis 3 displacement | External accelerometer input, overall value. | FLOAT32 | ABCD | mils | Read | ||
| HR | 190doc 190-191 | Internal accelerometer 1 axis 1 acceleration | FLOAT32 | ABCD | g RMS | Read | |||
| HR | 192doc 192-193 | Internal accelerometer 1 axis 2 acceleration | FLOAT32 | ABCD | g RMS | Read | |||
| HR | 194doc 194-195 | Internal accelerometer 1 axis 3 acceleration | FLOAT32 | ABCD | g RMS | Read | |||
| HR | 196doc 196-197 | Internal accelerometer 1 axis 1 velocity | FLOAT32 | ABCD | in/s RMS | Read | |||
| HR | 198doc 198-199 | Internal accelerometer 1 axis 2 velocity | FLOAT32 | ABCD | in/s RMS | Read | |||
| HR | 200doc 200-201 | Internal accelerometer 1 axis 3 velocity | FLOAT32 | ABCD | in/s RMS | Read | |||
| HR | 202doc 202-203 | Internal accelerometer 1 axis 1 displacement | FLOAT32 | ABCD | mils | Read | |||
| HR | 204doc 204-205 | Internal accelerometer 1 axis 2 displacement | FLOAT32 | ABCD | mils | Read | |||
| HR | 206doc 206-207 | Internal accelerometer 1 axis 3 displacement | FLOAT32 | ABCD | mils | Read | |||
| HR | 208doc 208-209 | Internal accelerometer 2 axis 1 acceleration | FLOAT32 | ABCD | g RMS | Read | |||
| HR | 210doc 210-211 | Internal accelerometer 2 axis 2 acceleration | FLOAT32 | ABCD | g RMS | Read | |||
| HR | 212doc 212-213 | Internal accelerometer 2 axis 3 acceleration | FLOAT32 | ABCD | g RMS | Read | |||
| HR | 214doc 214-215 | Internal accelerometer 2 axis 1 velocity | FLOAT32 | ABCD | in/s RMS | Read | |||
| HR | 216doc 216-217 | Internal accelerometer 2 axis 2 velocity | FLOAT32 | ABCD | in/s RMS | Read | |||
| HR | 218doc 218-219 | Internal accelerometer 2 axis 3 velocity | FLOAT32 | ABCD | in/s RMS | Read | |||
| HR | 220doc 220-221 | Internal accelerometer 2 axis 1 displacement | FLOAT32 | ABCD | mils | Read | |||
| HR | 222doc 222-223 | Internal accelerometer 2 axis 2 displacement | FLOAT32 | ABCD | mils | Read | |||
| HR | 224doc 224-225 | Internal accelerometer 2 axis 3 displacement | FLOAT32 | ABCD | mils | Read | |||
| HR | 226 | ALARM_1_STATE | UINT16 | Read | 0 = No alarm; 1 = Lo alarm; 2 = Hi alarm; 3 = HiHi alarm; 4 = Normal | ||||
| HR | 227 | ALARM_2_STATE | UINT16 | Read | 0 = No alarm; 1 = Lo alarm; 2 = Hi alarm; 3 = HiHi alarm; 4 = Normal | ||||
| HR | 228 | ALARM_3_STATE | UINT16 | Read | 0 = No alarm; 1 = Lo alarm; 2 = Hi alarm; 3 = HiHi alarm; 4 = Normal | ||||
| HR | 229 | ALARM_4_STATE | UINT16 | Read | 0 = No alarm; 1 = Lo alarm; 2 = Hi alarm; 3 = HiHi alarm; 4 = Normal | ||||
| HR | 230doc 230-231 | Alarm 1 highest value | Peak value seen by this alarm channel. | FLOAT32 | ABCD | Read | |||
| HR | 232doc 232-233 | Alarm 2 highest value | Peak value seen by this alarm channel. | FLOAT32 | ABCD | Read | |||
| HR | 234doc 234-235 | Alarm 3 highest value | Peak value seen by this alarm channel. | FLOAT32 | ABCD | Read | |||
| HR | 236doc 236-237 | Alarm 4 highest value | Peak value seen by this alarm channel. | FLOAT32 | ABCD | Read | |||
| HR | 238 | ALARM_CONTROL | Set a bit to reset that alarm's highest value. | BITMAP16 | Read/write | bit 0 = Reset alarm 1 highest; bit 1 = Reset alarm 2 highest; bit 2 = Reset alarm 3 highest; bit 3 = Reset alarm 4 highest | |||
| HR | 290 | AXIS_1_SENSOR_1_EXT_IMPACT_SEVERITY | Impact severity; raw = g peak x 10. | UINT16 | × 0.1 | g peak | Read | ||
| HR | 291 | AXIS_2_SENSOR_1_EXT_IMPACT_SEVERITY | Impact severity; raw = g peak x 10. | UINT16 | × 0.1 | g peak | Read | ||
| HR | 292 | AXIS_3_SENSOR_1_EXT_IMPACT_SEVERITY | Impact severity; raw = g peak x 10. | UINT16 | × 0.1 | g peak | Read | ||
| HR | 293 | AXIS_1_SENSOR_2_EXT_IMPACT_SEVERITY | Impact severity; raw = g peak x 10. | UINT16 | × 0.1 | g peak | Read | ||
| HR | 294 | AXIS_2_SENSOR_2_EXT_IMPACT_SEVERITY | Impact severity; raw = g peak x 10. | UINT16 | × 0.1 | g peak | Read | ||
| HR | 295 | AXIS_3_SENSOR_2_EXT_IMPACT_SEVERITY | Impact severity; raw = g peak x 10. | UINT16 | × 0.1 | g peak | Read | ||
| HR | 311 | ALARM_TRIP_DELAY | Delay applied to all 4 alarm channels. | UINT16 | Read/write | ||||
| HR | 312 | ALARM1_AXIS | Which measurement this alarm watches. | UINT16 | Read/write | 0 = Idle; 1 = Axis 1; 2 = Axis 2; 3 = Axis 3; 4 = T; 5 = IT; 6 = IC; 7 = Axis 1 D; 8 = Axis 2 D; 9 = Axis 3 D; 10 = Axis 1 IT; 11 = Axis 2 IT; 12 = Axis 3 IT; 13 = Axis 1 IC; 14 = Axis 2 IC; 15 = Axis 3 IC | |||
| HR | 313 | ALARM1_TYPE | UINT16 | Read/write | 0 = Idle; 1 = Velocity; 2 = Acceleration; 3 = Displacement; 4 = Temperature; 5 = Alert; 6 = Danger; 7 = Detonation | ||||
| HR | 314doc 314-315 | Alarm 1 Lo level | FLOAT32 | ABCD | Read/write | ||||
| HR | 316doc 316-317 | Alarm 1 Hi level | FLOAT32 | ABCD | Read/write | ||||
| HR | 318doc 318-319 | Alarm 1 HiHi level | FLOAT32 | ABCD | Read/write | ||||
| HR | 320doc 320-321 | Alarm 1 hysteresis | FLOAT32 | ABCD | Read/write | ||||
| HR | 322 | ALARM2_AXIS | Which measurement this alarm watches. | UINT16 | Read/write | 0 = Idle; 1 = Axis 1; 2 = Axis 2; 3 = Axis 3; 4 = T; 5 = IT; 6 = IC; 7 = Axis 1 D; 8 = Axis 2 D; 9 = Axis 3 D; 10 = Axis 1 IT; 11 = Axis 2 IT; 12 = Axis 3 IT; 13 = Axis 1 IC; 14 = Axis 2 IC; 15 = Axis 3 IC | |||
| HR | 323 | ALARM2_TYPE | UINT16 | Read/write | 0 = Idle; 1 = Velocity; 2 = Acceleration; 3 = Displacement; 4 = Temperature; 5 = Alert; 6 = Danger; 7 = Detonation | ||||
| HR | 324doc 324-325 | Alarm 2 Lo level | FLOAT32 | ABCD | Read/write | ||||
| HR | 326doc 326-327 | Alarm 2 Hi level | FLOAT32 | ABCD | Read/write | ||||
| HR | 328doc 328-329 | Alarm 2 HiHi level | FLOAT32 | ABCD | Read/write | ||||
| HR | 330doc 330-331 | Alarm 2 hysteresis | FLOAT32 | ABCD | Read/write | ||||
| HR | 332 | ALARM3_AXIS | Which measurement this alarm watches. | UINT16 | Read/write | 0 = Idle; 1 = Axis 1; 2 = Axis 2; 3 = Axis 3; 4 = T; 5 = IT; 6 = IC; 7 = Axis 1 D; 8 = Axis 2 D; 9 = Axis 3 D; 10 = Axis 1 IT; 11 = Axis 2 IT; 12 = Axis 3 IT; 13 = Axis 1 IC; 14 = Axis 2 IC; 15 = Axis 3 IC | |||
| HR | 333 | ALARM3_TYPE | UINT16 | Read/write | 0 = Idle; 1 = Velocity; 2 = Acceleration; 3 = Displacement; 4 = Temperature; 5 = Alert; 6 = Danger; 7 = Detonation | ||||
| HR | 334doc 334-335 | Alarm 3 Lo level | FLOAT32 | ABCD | Read/write | ||||
| HR | 336doc 336-337 | Alarm 3 Hi level | FLOAT32 | ABCD | Read/write | ||||
| HR | 338doc 338-339 | Alarm 3 HiHi level | FLOAT32 | ABCD | Read/write | ||||
| HR | 340doc 340-341 | Alarm 3 hysteresis | FLOAT32 | ABCD | Read/write | ||||
| HR | 342 | ALARM4_AXIS | Which measurement this alarm watches. | UINT16 | Read/write | 0 = Idle; 1 = Axis 1; 2 = Axis 2; 3 = Axis 3; 4 = T; 5 = IT; 6 = IC; 7 = Axis 1 D; 8 = Axis 2 D; 9 = Axis 3 D; 10 = Axis 1 IT; 11 = Axis 2 IT; 12 = Axis 3 IT; 13 = Axis 1 IC; 14 = Axis 2 IC; 15 = Axis 3 IC | |||
| HR | 343 | ALARM4_TYPE | UINT16 | Read/write | 0 = Idle; 1 = Velocity; 2 = Acceleration; 3 = Displacement; 4 = Temperature; 5 = Alert; 6 = Danger; 7 = Detonation | ||||
| HR | 344doc 344-345 | Alarm 4 Lo level | FLOAT32 | ABCD | Read/write | ||||
| HR | 346doc 346-347 | Alarm 4 Hi level | FLOAT32 | ABCD | Read/write | ||||
| HR | 348doc 348-349 | Alarm 4 HiHi level | FLOAT32 | ABCD | Read/write | ||||
| HR | 350doc 350-351 | Alarm 4 hysteresis | FLOAT32 | ABCD | Read/write |
Notes on this map
- 32-bit values are listed as a HIGH_ register followed by a LOW_ register, and the page says the sensor is big-endian, so the high word is at the lower address (ABCD).
- The default slave ID is the last two digits of the sensor's serial number (white label on the side).
- Left out: the dynamic data clip registers (49-171), DDR/capture engine controls, detonation and impact alert counters, unique ID words and sensitivity calibration registers - they are for waveform capture or factory use.
- TEMPERATURE (31) is divided by 10; the page does not give the unit.
- Units for alarm levels follow the alarm type (velocity, acceleration, displacement or temperature) chosen in ALARMn_TYPE.
- Alarm configuration writes need the alarm registers unlocked (SYSTEM_CONTROL = 42074) and saved afterwards (42075).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU)
What Modbus registers does the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) have?
This map lists 78 registers: 78 holding registers. 27 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The page states the listed registers are 0-indexed; use the number unchanged on the wire.
What byte order does the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU)?
Start with HR 178 Axis 1 velocity (Axis 1 velocity); HR 180 Axis 2 velocity (Axis 2 velocity); HR 182 Axis 3 velocity (Axis 3 velocity); HR 172 Axis 1 acceleration (Axis 1 acceleration); HR 31 TEMPERATURE (Temperature); HR 226 ALARM_1_STATE (Alarm 1 state); HR 4 SYSTEM_STATE2 (System state flags).
How do I enable Modbus control of the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU)?
Modbus RTU is always on. Configuration and alarm registers are locked until the matching unlock command is written to SYSTEM_CONTROL (register 1), and must be saved with the matching save command.
Where is the official Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) Modbus documentation?
The source is TriVibe - Modbus Registers Map (Machine Saver Knowledge Base) (Revision #12), published free by Machine Saver at https://library.machinesaver.com/books/trivibe/page/modbus-registers.
Other valves, actuators & sensors register maps
- Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (flow transmitter)
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
SITRANS F M MAG 6000 / MAG 6000 I electromagnetic flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MAG 6000, MAG 6000 I, SITRANS FM MAG 6000 - Sensor (humidity / temperature)
Teracom TSH300v3 RS-485 humidity and temperature sensor
TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.
Also known as: TSH300, TSH300v3 - Sensor (gas density)
Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map)
Trafag 8775 and 879x (8791/8792/8793) running the 'Legacy' Modbus configuration of software description H73622a (10/2025).
Also known as: 8775, 8791, 8792, 8793, 879x, Trafag gas density monitor - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272
All valves, actuators & sensors Modbus register maps →
Source: TriVibe - Modbus Registers Map (Machine Saver Knowledge Base) · Revision #12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.