Easy Modbus
  1. Home
  2. Modbus register maps
  3. Machine Saver
  4. TriVibe vibration and temperature sensor (Modbus RTU)

Sensor (vibration / temperature) · Modbus register map

Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

TriVibe is a triaxial vibration and temperature sensor that talks Modbus RTU on RS-485 at 115200 baud. Overall acceleration, velocity and displacement per axis are 32-bit floats, high word first. This map covers system status, run time, temperature, overall vibration values from the external and internal accelerometers, alarm states and the four configurable alarm channels.

This page lists 78 Modbus registers for the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) — 27 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Machine Saver’s own free documentation (linked below) and checked against it.

Manufacturer
Machine Saver
Model
TriVibe vibration and temperature sensor (Modbus RTU)
Equipment type
Sensor (vibration / temperature)
Registers
78 (27 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
115200 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
TriVibe, Machine Saver TriVibe
Source document
TriVibe - Modbus Registers Map (Machine Saver Knowledge Base) · Revision #12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Machine Saver TriVibe vibration and temperature sensor (Modbus RTU)

Integration in brief

Poll at 115200 8N1 using the slave ID from the serial number label. Read FC03 block 172-189 for overall vibration and 226-229 for alarm states; write with FC16 only.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 178Axis 1 velocityFLOAT32 ABCDAxis 1 velocityRead
HR 180Axis 2 velocityFLOAT32 ABCDAxis 2 velocityRead
HR 182Axis 3 velocityFLOAT32 ABCDAxis 3 velocityRead
HR 172Axis 1 accelerationFLOAT32 ABCDAxis 1 accelerationRead
HR 31TEMPERATUREINT16TemperatureRead
HR 226ALARM_1_STATEUINT16Alarm 1 stateRead
HR 4SYSTEM_STATE2BITMAP16System state flagsRead

Enable Modbus control & writes

Modbus RTU is always on. Configuration and alarm registers are locked until the matching unlock command is written to SYSTEM_CONTROL (register 1), and must be saved with the matching save command.

Byte order & addressing

Network setup

Watch out for

Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

78 of 78 shown
Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0SYSTEM_INFOFirmware ID and revision.UINT16Read
HR1SYSTEM_CONTROLCommand register; use with care (some commands reset or erase).UINT16Read/write0 = Idle; 1 = Reset; 2 = Clear alarms; 3 = Load data; 42074 = Unlock alarm registers; 42075 = Save alarm registers; 45555 = Unlock config registers; 45556 = Save config registers; 55555 = Restart firmware
HR2SYSTEM_STATUSProgress of the last command (done / in progress / flagged).UINT16Read
HR3SYSTEM_STATE1BITMAP16Readbit 0 = Machine on
HR4SYSTEM_STATE2Internal health flags.BITMAP16Readbit 0 = Power flag; bit 1 = DRAM flag; bit 2 = ADC flag; bit 3 = NVM flag; bit 4 = Temperature flag; bit 5 = Calibration flag; bit 6 = Collect flag; bit 7 = Impact flag; bit 8 = Alarm flag; bit 9 = Alarm level flag; bit 10 = Collect2 flag; bit 11 = Sine table flag; bit 12 = Detonation flag; bit 13 = Board type flag; bit 14 = On/off flag
HR5MINUTES_ONRun-time counter, minutes part.UINT16Read
HR6HOURS_ONRun-time counter, hours part.UINT16Read
HR7DAYS_ONRun-time counter, days part.UINT16Read
HR17SYSTEM_RTUModbus slave ID in use.UINT16Read
HR26doc 26-27Serial number (UIDL)High word at 26, low word at 27.UINT32ABCDRead
HR31TEMPERATURESensor temperature; divide by 10. Unit not stated on the page.INT16× 0.1Read
HR172doc 172-173Axis 1 accelerationExternal accelerometer input, overall value.FLOAT32ABCDg RMSRead
HR174doc 174-175Axis 2 accelerationExternal accelerometer input, overall value.FLOAT32ABCDg RMSRead
HR176doc 176-177Axis 3 accelerationExternal accelerometer input, overall value.FLOAT32ABCDg RMSRead
HR178doc 178-179Axis 1 velocityExternal accelerometer input, overall value.FLOAT32ABCDin/s RMSRead
HR180doc 180-181Axis 2 velocityExternal accelerometer input, overall value.FLOAT32ABCDin/s RMSRead
HR182doc 182-183Axis 3 velocityExternal accelerometer input, overall value.FLOAT32ABCDin/s RMSRead
HR184doc 184-185Axis 1 displacementExternal accelerometer input, overall value.FLOAT32ABCDmilsRead
HR186doc 186-187Axis 2 displacementExternal accelerometer input, overall value.FLOAT32ABCDmilsRead
HR188doc 188-189Axis 3 displacementExternal accelerometer input, overall value.FLOAT32ABCDmilsRead
HR190doc 190-191Internal accelerometer 1 axis 1 accelerationFLOAT32ABCDg RMSRead
HR192doc 192-193Internal accelerometer 1 axis 2 accelerationFLOAT32ABCDg RMSRead
HR194doc 194-195Internal accelerometer 1 axis 3 accelerationFLOAT32ABCDg RMSRead
HR196doc 196-197Internal accelerometer 1 axis 1 velocityFLOAT32ABCDin/s RMSRead
HR198doc 198-199Internal accelerometer 1 axis 2 velocityFLOAT32ABCDin/s RMSRead
HR200doc 200-201Internal accelerometer 1 axis 3 velocityFLOAT32ABCDin/s RMSRead
HR202doc 202-203Internal accelerometer 1 axis 1 displacementFLOAT32ABCDmilsRead
HR204doc 204-205Internal accelerometer 1 axis 2 displacementFLOAT32ABCDmilsRead
HR206doc 206-207Internal accelerometer 1 axis 3 displacementFLOAT32ABCDmilsRead
HR208doc 208-209Internal accelerometer 2 axis 1 accelerationFLOAT32ABCDg RMSRead
HR210doc 210-211Internal accelerometer 2 axis 2 accelerationFLOAT32ABCDg RMSRead
HR212doc 212-213Internal accelerometer 2 axis 3 accelerationFLOAT32ABCDg RMSRead
HR214doc 214-215Internal accelerometer 2 axis 1 velocityFLOAT32ABCDin/s RMSRead
HR216doc 216-217Internal accelerometer 2 axis 2 velocityFLOAT32ABCDin/s RMSRead
HR218doc 218-219Internal accelerometer 2 axis 3 velocityFLOAT32ABCDin/s RMSRead
HR220doc 220-221Internal accelerometer 2 axis 1 displacementFLOAT32ABCDmilsRead
HR222doc 222-223Internal accelerometer 2 axis 2 displacementFLOAT32ABCDmilsRead
HR224doc 224-225Internal accelerometer 2 axis 3 displacementFLOAT32ABCDmilsRead
HR226ALARM_1_STATEUINT16Read0 = No alarm; 1 = Lo alarm; 2 = Hi alarm; 3 = HiHi alarm; 4 = Normal
HR227ALARM_2_STATEUINT16Read0 = No alarm; 1 = Lo alarm; 2 = Hi alarm; 3 = HiHi alarm; 4 = Normal
HR228ALARM_3_STATEUINT16Read0 = No alarm; 1 = Lo alarm; 2 = Hi alarm; 3 = HiHi alarm; 4 = Normal
HR229ALARM_4_STATEUINT16Read0 = No alarm; 1 = Lo alarm; 2 = Hi alarm; 3 = HiHi alarm; 4 = Normal
HR230doc 230-231Alarm 1 highest valuePeak value seen by this alarm channel.FLOAT32ABCDRead
HR232doc 232-233Alarm 2 highest valuePeak value seen by this alarm channel.FLOAT32ABCDRead
HR234doc 234-235Alarm 3 highest valuePeak value seen by this alarm channel.FLOAT32ABCDRead
HR236doc 236-237Alarm 4 highest valuePeak value seen by this alarm channel.FLOAT32ABCDRead
HR238ALARM_CONTROLSet a bit to reset that alarm's highest value.BITMAP16Read/writebit 0 = Reset alarm 1 highest; bit 1 = Reset alarm 2 highest; bit 2 = Reset alarm 3 highest; bit 3 = Reset alarm 4 highest
HR290AXIS_1_SENSOR_1_EXT_IMPACT_SEVERITYImpact severity; raw = g peak x 10.UINT16× 0.1g peakRead
HR291AXIS_2_SENSOR_1_EXT_IMPACT_SEVERITYImpact severity; raw = g peak x 10.UINT16× 0.1g peakRead
HR292AXIS_3_SENSOR_1_EXT_IMPACT_SEVERITYImpact severity; raw = g peak x 10.UINT16× 0.1g peakRead
HR293AXIS_1_SENSOR_2_EXT_IMPACT_SEVERITYImpact severity; raw = g peak x 10.UINT16× 0.1g peakRead
HR294AXIS_2_SENSOR_2_EXT_IMPACT_SEVERITYImpact severity; raw = g peak x 10.UINT16× 0.1g peakRead
HR295AXIS_3_SENSOR_2_EXT_IMPACT_SEVERITYImpact severity; raw = g peak x 10.UINT16× 0.1g peakRead
HR311ALARM_TRIP_DELAYDelay applied to all 4 alarm channels.UINT16Read/write
HR312ALARM1_AXISWhich measurement this alarm watches.UINT16Read/write0 = Idle; 1 = Axis 1; 2 = Axis 2; 3 = Axis 3; 4 = T; 5 = IT; 6 = IC; 7 = Axis 1 D; 8 = Axis 2 D; 9 = Axis 3 D; 10 = Axis 1 IT; 11 = Axis 2 IT; 12 = Axis 3 IT; 13 = Axis 1 IC; 14 = Axis 2 IC; 15 = Axis 3 IC
HR313ALARM1_TYPEUINT16Read/write0 = Idle; 1 = Velocity; 2 = Acceleration; 3 = Displacement; 4 = Temperature; 5 = Alert; 6 = Danger; 7 = Detonation
HR314doc 314-315Alarm 1 Lo levelFLOAT32ABCDRead/write
HR316doc 316-317Alarm 1 Hi levelFLOAT32ABCDRead/write
HR318doc 318-319Alarm 1 HiHi levelFLOAT32ABCDRead/write
HR320doc 320-321Alarm 1 hysteresisFLOAT32ABCDRead/write
HR322ALARM2_AXISWhich measurement this alarm watches.UINT16Read/write0 = Idle; 1 = Axis 1; 2 = Axis 2; 3 = Axis 3; 4 = T; 5 = IT; 6 = IC; 7 = Axis 1 D; 8 = Axis 2 D; 9 = Axis 3 D; 10 = Axis 1 IT; 11 = Axis 2 IT; 12 = Axis 3 IT; 13 = Axis 1 IC; 14 = Axis 2 IC; 15 = Axis 3 IC
HR323ALARM2_TYPEUINT16Read/write0 = Idle; 1 = Velocity; 2 = Acceleration; 3 = Displacement; 4 = Temperature; 5 = Alert; 6 = Danger; 7 = Detonation
HR324doc 324-325Alarm 2 Lo levelFLOAT32ABCDRead/write
HR326doc 326-327Alarm 2 Hi levelFLOAT32ABCDRead/write
HR328doc 328-329Alarm 2 HiHi levelFLOAT32ABCDRead/write
HR330doc 330-331Alarm 2 hysteresisFLOAT32ABCDRead/write
HR332ALARM3_AXISWhich measurement this alarm watches.UINT16Read/write0 = Idle; 1 = Axis 1; 2 = Axis 2; 3 = Axis 3; 4 = T; 5 = IT; 6 = IC; 7 = Axis 1 D; 8 = Axis 2 D; 9 = Axis 3 D; 10 = Axis 1 IT; 11 = Axis 2 IT; 12 = Axis 3 IT; 13 = Axis 1 IC; 14 = Axis 2 IC; 15 = Axis 3 IC
HR333ALARM3_TYPEUINT16Read/write0 = Idle; 1 = Velocity; 2 = Acceleration; 3 = Displacement; 4 = Temperature; 5 = Alert; 6 = Danger; 7 = Detonation
HR334doc 334-335Alarm 3 Lo levelFLOAT32ABCDRead/write
HR336doc 336-337Alarm 3 Hi levelFLOAT32ABCDRead/write
HR338doc 338-339Alarm 3 HiHi levelFLOAT32ABCDRead/write
HR340doc 340-341Alarm 3 hysteresisFLOAT32ABCDRead/write
HR342ALARM4_AXISWhich measurement this alarm watches.UINT16Read/write0 = Idle; 1 = Axis 1; 2 = Axis 2; 3 = Axis 3; 4 = T; 5 = IT; 6 = IC; 7 = Axis 1 D; 8 = Axis 2 D; 9 = Axis 3 D; 10 = Axis 1 IT; 11 = Axis 2 IT; 12 = Axis 3 IT; 13 = Axis 1 IC; 14 = Axis 2 IC; 15 = Axis 3 IC
HR343ALARM4_TYPEUINT16Read/write0 = Idle; 1 = Velocity; 2 = Acceleration; 3 = Displacement; 4 = Temperature; 5 = Alert; 6 = Danger; 7 = Detonation
HR344doc 344-345Alarm 4 Lo levelFLOAT32ABCDRead/write
HR346doc 346-347Alarm 4 Hi levelFLOAT32ABCDRead/write
HR348doc 348-349Alarm 4 HiHi levelFLOAT32ABCDRead/write
HR350doc 350-351Alarm 4 hysteresisFLOAT32ABCDRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU)

What Modbus registers does the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) have?

This map lists 78 registers: 78 holding registers. 27 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The page states the listed registers are 0-indexed; use the number unchanged on the wire.

What byte order does the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU)?

Start with HR 178 Axis 1 velocity (Axis 1 velocity); HR 180 Axis 2 velocity (Axis 2 velocity); HR 182 Axis 3 velocity (Axis 3 velocity); HR 172 Axis 1 acceleration (Axis 1 acceleration); HR 31 TEMPERATURE (Temperature); HR 226 ALARM_1_STATE (Alarm 1 state); HR 4 SYSTEM_STATE2 (System state flags).

How do I enable Modbus control of the Machine Saver TriVibe vibration and temperature sensor (Modbus RTU)?

Modbus RTU is always on. Configuration and alarm registers are locked until the matching unlock command is written to SYSTEM_CONTROL (register 1), and must be saved with the matching save command.

Where is the official Machine Saver TriVibe vibration and temperature sensor (Modbus RTU) Modbus documentation?

The source is TriVibe - Modbus Registers Map (Machine Saver Knowledge Base) (Revision #12), published free by Machine Saver at https://library.machinesaver.com/books/trivibe/page/modbus-registers.

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: TriVibe - Modbus Registers Map (Machine Saver Knowledge Base) · Revision #12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.