- Home
- Modbus register maps
- Teracom
- TSH300v3 RS-485 humidity and temperature sensor
Sensor (humidity / temperature) · Modbus register map
Teracom TSH300v3 RS-485 humidity and temperature sensor Modbus register map
Updated 19 November 2026
The TSH300v3 is a Teracom humidity and temperature probe that talks Modbus RTU over RS-485 and takes its power from the bus cable (RJ45). It reports temperature, relative humidity and dew point as floats and as x100 integers in both Celsius and Fahrenheit, with user trim registers.
This page lists 26 Modbus registers for the Teracom TSH300v3 RS-485 humidity and temperature sensor — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teracom’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teracom
- Model
- TSH300v3 RS-485 humidity and temperature sensor
- Equipment type
- Sensor (humidity / temperature)
- Registers
- 26 (8 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- TSH300, TSH300v3
- Source document
- TSH300v3 User manual · Revision R1.17 · rev. 2026-10
Integration notes: Teracom TSH300v3 RS-485 humidity and temperature sensor
Read the float block at PDU 100-105 (temperature, humidity, dew point) with function 03, or the 16-bit x100 block at PDU 400-402 if your master has no float support. All registers are holding registers.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 100 | Temperature °C | FLOAT32 ABCD | Temperature °C (float) | Read |
| HR 102 | Humidity %RH | FLOAT32 ABCD | Humidity %RH (float) | Read |
| HR 104 | Dew point °C | FLOAT32 ABCD | Dew point °C (float) | Read |
| HR 400 | Temperature °C x 100 | INT16 | Temperature °C x100 (int16) | Read |
| HR 401 | Humidity %RH x 100 | INT16 | Humidity x100 | Read |
| HR 13 | Data order | UINT16 | Word order setting | Read/write |
Enable Modbus control & writes
Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.
Byte order & addressing
- Baud rate and framing changes only take effect after the device is powered off and on again.
- Word order for every 32-bit value is set by the Data order register (PDU 13); check it before blaming the scaling.
Network setup
- Set unit ID (PDU 10), baud (PDU 11) and framing (PDU 12), then power-cycle the device.
- Wire sensors as a daisy chain and fit a 120 ohm terminator in the free RJ45 socket of the last sensor.
Teracom TSH300v3 RS-485 humidity and temperature sensor Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 10doc 40011 | RS-485 address | Modbus slave address of the device. | UINT16 | Read/write | ||||
| HR | 11doc 40012 | Baud rate | Serial baud rate; takes effect after a power cycle. | UINT16 | Read/write | ||||
| HR | 12doc 40013 | Parity, data, stop bits | Parity/data/stop framing; takes effect after a power cycle. | UINT16 | Read/write | 1 = 8 data bits, even parity, 1 stop (E81); 2 = 8 data bits, odd parity, 1 stop (O81); 3 = 8 data bits, no parity, 1 stop (N81) | |||
| HR | 13doc 40014 | Data order | Word order used for all 32-bit values. | UINT16 | Read/write | 1 = MSWF - most significant word first; 2 = LSWF - least significant word first | |||
| HR | 14doc 40015 | Device code | Fixed product identification code. | UINT16 | Read | ||||
| HR | 15doc 40016 | FW version | Firmware version number. | UINT16 | Read | ||||
| HR | 18doc 40019 | Vendor URL | Maker URL as UTF-8 text (64 bytes). | STRING[64] | Read | ||||
| HR | 86doc 40087 | Signed integer test value | INT16 | Read | |||||
| HR | 91doc 40092 | Unsigned integer test value | UINT16 | Read | |||||
| HR | 100doc 40101 | Temperature °C | FLOAT32 | ABCD | °C | Read | |||
| HR | 102doc 40103 | Humidity %RH | FLOAT32 | ABCD | %RH | Read | |||
| HR | 104doc 40105 | Dew point °C | FLOAT32 | ABCD | °C | Read | |||
| HR | 200doc 40201 | Temperature °F | FLOAT32 | ABCD | °F | Read | |||
| HR | 202doc 40203 | Humidity %RH | FLOAT32 | ABCD | %RH | Read | |||
| HR | 204doc 40205 | Dew point °F | FLOAT32 | ABCD | °F | Read | |||
| HR | 400doc 40401 | Temperature °C x 100 | INT16 | × 0.01 | °C | Read | |||
| HR | 401doc 40402 | Humidity %RH x 100 | INT16 | × 0.01 | %RH | Read | |||
| HR | 402doc 40403 | Dew point °C x 100 | INT16 | × 0.01 | °C | Read | |||
| HR | 500doc 40501 | Temperature °F x 100 | INT16 | × 0.01 | °F | Read | |||
| HR | 501doc 40502 | Humidity %RH x 100 | INT16 | × 0.01 | %RH | Read | |||
| HR | 502doc 40503 | Dew point °F x 100 | INT16 | × 0.01 | °F | Read | |||
| HR | 2101doc 42102 | Temperature multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2103doc 42104 | Temperature offset °C | FLOAT32 | ABCD | °C | Read/write | |||
| HR | 2105doc 42106 | Temperature offset °F | FLOAT32 | ABCD | °F | Read | |||
| HR | 2111doc 42112 | Humidity multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2113doc 42114 | Humidity offset | FLOAT32 | ABCD | Read/write |
Notes on this map
- Addresses are taken from the manual's PDU address column (0-based); the logical column is the same number plus 40001, the holding-register offset the manual states.
- All 32-bit values follow the Data order register (PDU 13): 1 = most significant word first (factory default), 2 = least significant word first. The map shows the default, ABCD.
- Left out: the 32-bit float/integer test-value registers (PDU 82-95), which only exist to check word order; the 16-bit test values are kept.
- Float blocks: PDU 100+ in °C and PDU 200+ in °F; the integer blocks (PDU 400+ °C, 500+ °F) hold the same values x100 as 16-bit words. A missing reading returns NaN (float) or -32768 (16-bit integer).
- Readings can be trimmed with the multiplier and offset floats near PDU 2100: corrected = measured x multiplier + offset.
- The download is titled TSH300 but the manual covers the TSH300v3 successor.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teracom TSH300v3 RS-485 humidity and temperature sensor
What Modbus registers does the Teracom TSH300v3 RS-485 humidity and temperature sensor have?
This map lists 26 registers: 26 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teracom TSH300v3 RS-485 humidity and temperature sensor Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table prints both a PDU (wire) address and a logical address (PDU + 40001 for holding registers). 'documented' holds the logical number; the PDU number is what goes in the request, e.g. logical 40101 = PDU 100.
What byte order does the Teracom TSH300v3 RS-485 humidity and temperature sensor use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Teracom TSH300v3 RS-485 humidity and temperature sensor?
Start with HR 100 Temperature °C (Temperature °C (float)); HR 102 Humidity %RH (Humidity %RH (float)); HR 104 Dew point °C (Dew point °C (float)); HR 400 Temperature °C x 100 (Temperature °C x100 (int16)); HR 401 Humidity %RH x 100 (Humidity x100); HR 13 Data order (Word order setting).
How do I enable Modbus control of the Teracom TSH300v3 RS-485 humidity and temperature sensor?
Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.
Where is the official Teracom TSH300v3 RS-485 humidity and temperature sensor Modbus documentation?
The source is TSH300v3 User manual (Revision R1.17), revision 2026-10, published free by Teracom at https://www.teracomsystems.com/download/rs-485-humidity-temperature-sensor-tsh300/.
More Teracom Modbus register maps
- Sensor (temperature / humidity data logger)
Teracom TCW210-TH temperature and humidity data logger
TCW210-TH per the Teracom TCW210-TH user manual Revision R1.26, firmware V2.012 or later.
Also known as: TCW210-TH, TCW210 - Sensor (Ethernet data logger / I/O module)
Teracom TCW220 Ethernet data logger
TCW220 per the Teracom TCW220 user manual Revision R4.24, firmware V2.012 or later.
Also known as: TCW220 - Sensor (Ethernet I/O module)
Teracom TCW241 Ethernet I/O module
TCW241 per the Teracom TCW241 user manual Revision R4.30, firmware v2.012 or later.
Also known as: TCW241 - Energy meter (Ethernet energy monitoring / data logger)
Teracom TCW260 Ethernet energy monitoring module
TCW260 per the Teracom TCW260 user manual Revision R1.19, firmware V3.009 or later.
Also known as: TCW260 - Sensor (Ethernet analog / digital output module)
Teracom TCW280 Ethernet analog output module
TCW280 per the Teracom TCW280 user manual TCW280_R1.8.
Also known as: TCW280 - Sensor (1-Wire to Modbus gateway)
Teracom TCW320x-WMG 1-Wire to Modbus gateway
TCW320E-WMG (Ethernet) and TCW320W-WMG (Wi-Fi) per the user manual Revision R1.0; both share one fixed register map.
Also known as: TCW320E-WMG, TCW320W-WMG - Energy meter (S0 pulse counter / digital input module)
Teracom TDI340 4-channel S0 pulse counter with Modbus RTU
TDI340 per the Teracom TDI340 user manual Revision R1.11, firmware V1.06 or later.
Also known as: TDI340 - Sensor (relay output module)
Teracom TDO340 4-channel Modbus RTU relay output module
TDO340 per the Teracom TDO340 user manual Revision R1.2, firmware V1.03 or later.
Also known as: TDO340 - Sensor (water leak detector)
Teracom TSF400-4 water-leak detector with Modbus RTU
TSF400-4 per the Teracom TSF400-4 user manual Revision R1.2.
Also known as: TSF400-4 - Sensor (humidity / temperature)
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor
TSH331 per the Teracom TSH331 user manual Rev. 1.5, firmware v1.08 or later.
Also known as: TSH331 - Sensor (CO2 / pressure)
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
TSM400-4-CP per the Teracom TSM400-4-CP user manual TSM400-4-CP-R1.9.
Also known as: TSM400-4-CP - Sensor (CO2 / humidity / temperature / pressure)
Teracom TSM400-4-CPTH Modbus CO2, humidity, temperature and pressure multi-sensor
TSM400-4-CPTH per the Teracom TSM400-4-CPTH user manual TSM400-4-CPTH-R1.9.
Also known as: TSM400-4-CPTH - Sensor (humidity / temperature)
Teracom TSM400-4-TH Modbus humidity and temperature sensor
TSM400-4-TH per the Teracom TSM400-4-TH user manual TSM400-4-TH-R1.10.
Also known as: TSM400-4-TH - Sensor (temperature)
Teracom TST300v3 / TST300v4 RS-485 precision temperature sensor
TST300v3/v4 per the Teracom TST300v3/v4 user manual Revision R1.19.
Also known as: TST300, TST300v3, TST300v4 - Sensor (thermocouple input module)
Teracom TST320 2-channel thermocouple module with Modbus RTU
TST320 per the Teracom TST320 user manual Revision R1.6.
Also known as: TST320 - Sensor (AC/DC voltage transducer)
Teracom TSV300 AC/DC voltage transducer with Modbus RTU
TSV300 per the Teracom TSV300 user manual Revision R1.4, firmware V1.06 or later.
Also known as: TSV300
Other valves, actuators & sensors register maps
- Sensor (gas density)
Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map)
Trafag 8775 and 879x (8791/8792/8793) running the 'Legacy' Modbus configuration of software description H73622a (10/2025).
Also known as: 8775, 8791, 8792, 8793, 879x, Trafag gas density monitor - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272 - Sensor (humidity and temperature probe)
Vaisala XMP10 humidity and temperature probe (Modbus RTU)
XMP10 probes ordered with (or switched to) Modbus RTU output, user guide M213279EN-A.
Also known as: XMP10, HUMICAP XMP10, Vaisala XMP10 - Water treatment controller (Sensor / controller)
Walchem WebMaster WIND series Modbus TCP/IP option (s825)
Walchem WebMaster WIND-series controllers with the Modbus TCP/IP option, software s825v008 and higher, per manual 180413 Rev A1.
Also known as: WIND, WebMaster WIND, s825 - Actuator / valve
Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)
Armstrong International Brain digital recirculation (thermostatic mixing) valves DRV25, DRV40 and DRV80 on their RS-485 Modbus RTU port, per IOM-776 Brain Modbus Networking (2024).
Also known as: DRV25, DRV40, DRV80, Brain, IOM-776
All valves, actuators & sensors Modbus register maps →
Source: TSH300v3 User manual · Revision R1.17 · rev. 2026-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.