- Home
- Modbus register maps
- Teracom
- TSV300 AC/DC voltage transducer with Modbus RTU
Sensor (AC/DC voltage transducer) · Modbus register map
Teracom TSV300 AC/DC voltage transducer with Modbus RTU Modbus register map
Updated 19 November 2026
The TSV300 is a Teracom 4-channel true-RMS voltage transducer (0-264 VAC or up to 370 VDC) with Modbus RTU over RS-485. It gives AC and DC readings with min/max as 32-bit floats and as 32-bit signed integers x1000.
This page lists 74 Modbus registers for the Teracom TSV300 AC/DC voltage transducer with Modbus RTU — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teracom’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teracom
- Model
- TSV300 AC/DC voltage transducer with Modbus RTU
- Equipment type
- Sensor (AC/DC voltage transducer)
- Registers
- 74 (21 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- V1.06 or later
- Also known as
- TSV300
- Source document
- TSV300 User manual · Revision R1.4 · rev. 2026-10
Integration notes: Teracom TSV300 AC/DC voltage transducer with Modbus RTU
Read the AC floats at PDU 100-107 or DC floats at PDU 500-507 with function 03; the x1000 int32 blocks suit masters without float support.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 100 | Input AC voltage 1 | FLOAT32 ABCD | AC voltage input 1 | Read |
| HR 102 | Input AC voltage 2 | FLOAT32 ABCD | AC voltage input 2 | Read |
| HR 500 | Input DC voltage 1 | FLOAT32 ABCD | DC voltage input 1 | Read |
| HR 150 | Input AC voltage 1 x 1000 | INT32 ABCD | AC voltage 1 x1000 (int32) | Read |
| HR 1000 | Reset min and max values | UINT16 | Reset min/max | Read/write |
Enable Modbus control & writes
Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.
Byte order & addressing
- Baud rate and framing changes only take effect after the device is powered off and on again.
- Word order for every 32-bit value is set by the Data order register (PDU 13); check it before blaming the scaling.
Network setup
- Set unit ID (PDU 10), baud (PDU 11) and framing (PDU 12), then power-cycle the device.
- Terminate both ends of the RS-485 bus with 120 ohm; the built-in resistor is enabled by wiring Term to RS485-. A daisy chain is recommended.
Teracom TSV300 AC/DC voltage transducer with Modbus RTU Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 10doc 40011 | RS-485 address | Modbus slave address of the device. | UINT16 | Read/write | ||||
| HR | 11doc 40012 | Baud rate | Serial baud rate; takes effect after a power cycle. | UINT16 | Read/write | ||||
| HR | 12doc 40013 | Parity, data, stop bits | Parity/data/stop framing; takes effect after a power cycle. | UINT16 | Read/write | 1 = 8 data bits, even parity, 1 stop (E81); 2 = 8 data bits, odd parity, 1 stop (O81); 3 = 8 data bits, no parity, 1 stop (N81) | |||
| HR | 13doc 40014 | Data order | Word order used for all 32-bit values. | UINT16 | Read/write | 1 = MSWF - most significant word first; 2 = LSWF - least significant word first | |||
| HR | 14doc 40015 | Device code | Fixed product identification code. | UINT16 | Read | ||||
| HR | 15doc 40016 | FW version | Firmware version number. | UINT16 | Read | ||||
| HR | 18doc 40019 | Vendor URL | Maker URL as UTF-8 text (64 bytes). | STRING[64] | Read | ||||
| HR | 86doc 40087 | Signed integer test value | INT16 | Read | |||||
| HR | 91doc 40092 | Unsigned integer test value | UINT16 | Read | |||||
| HR | 100doc 40101 | Input AC voltage 1 | FLOAT32 | ABCD | V | Read | |||
| HR | 102doc 40103 | Input AC voltage 2 | FLOAT32 | ABCD | V | Read | |||
| HR | 104doc 40105 | Input AC voltage 3 | FLOAT32 | ABCD | V | Read | |||
| HR | 106doc 40107 | Input AC voltage 4 | FLOAT32 | ABCD | V | Read | |||
| HR | 120doc 40121 | Input AC voltage 1 min. | FLOAT32 | ABCD | V | Read | |||
| HR | 122doc 40123 | Input AC voltage 2 min. | FLOAT32 | ABCD | V | Read | |||
| HR | 124doc 40125 | Input AC voltage 3 min. | FLOAT32 | ABCD | V | Read | |||
| HR | 126doc 40127 | Input AC voltage 4 min. | FLOAT32 | ABCD | V | Read | |||
| HR | 140doc 40141 | Input AC voltage 1 max. | FLOAT32 | ABCD | V | Read | |||
| HR | 142doc 40143 | Input AC voltage 2 max. | FLOAT32 | ABCD | V | Read | |||
| HR | 144doc 40145 | Input AC voltage 3 max. | FLOAT32 | ABCD | V | Read | |||
| HR | 146doc 40147 | Input AC voltage 4 max. | FLOAT32 | ABCD | V | Read | |||
| HR | 150doc 40151 | Input AC voltage 1 x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 152doc 40153 | Input AC voltage 2 x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 154doc 40155 | Input AC voltage 3 x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 156doc 40157 | Input AC voltage 4 x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 160doc 40161 | Input AC voltage 1 min. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 162doc 40163 | Input AC voltage 2 min. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 164doc 40165 | Input AC voltage 3 min. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 166doc 40167 | Input AC voltage 4 min. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 170doc 40171 | Input AC voltage 1 max. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 172doc 40173 | Input AC voltage 2 max. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 174doc 40175 | Input AC voltage 3 max. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 176doc 40177 | Input AC voltage 4 max. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 500doc 40501 | Input DC voltage 1 | FLOAT32 | ABCD | V | Read | |||
| HR | 502doc 40503 | Input DC voltage 2 | FLOAT32 | ABCD | V | Read | |||
| HR | 504doc 40505 | Input DC voltage 3 | FLOAT32 | ABCD | V | Read | |||
| HR | 506doc 40507 | Input DC voltage 4 | FLOAT32 | ABCD | V | Read | |||
| HR | 520doc 40521 | Input DC voltage 1 min. | FLOAT32 | ABCD | V | Read | |||
| HR | 522doc 40523 | Input DC voltage 2 min. | FLOAT32 | ABCD | V | Read | |||
| HR | 524doc 40525 | Input DC voltage 3 min. | FLOAT32 | ABCD | V | Read | |||
| HR | 526doc 40527 | Input DC voltage 4 min. | FLOAT32 | ABCD | V | Read | |||
| HR | 540doc 40541 | Input DC voltage 1 max. | FLOAT32 | ABCD | V | Read | |||
| HR | 542doc 40543 | Input DC voltage 2 max. | FLOAT32 | ABCD | V | Read | |||
| HR | 544doc 40545 | Input DC voltage 3 max. | FLOAT32 | ABCD | V | Read | |||
| HR | 546doc 40547 | Input DC voltage 4 max. | FLOAT32 | ABCD | V | Read | |||
| HR | 550doc 40551 | Input DC voltage 1 x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 552doc 40553 | Input DC voltage 2 x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 554doc 40555 | Input DC voltage 3 x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 556doc 40557 | Input DC voltage 4 x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 560doc 40561 | Input DC voltage 1 min. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 562doc 40563 | Input DC voltage 2 min. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 564doc 40565 | Input DC voltage 3 min. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 566doc 40567 | Input DC voltage 4 min. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 570doc 40571 | Input DC voltage 1 max. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 572doc 40573 | Input DC voltage 2 max. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 574doc 40575 | Input DC voltage 3 max. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 576doc 40577 | Input DC voltage 4 max. x 1000 | INT32 | ABCD | × 0.001 | V | Read | ||
| HR | 1000doc 41001 | Reset min and max values | Write to clear the stored min/max values. | UINT16 | Read/write | ||||
| HR | 2101doc 42102 | Input AC voltage 1 multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2103doc 42104 | Input AC voltage 1 offset | FLOAT32 | ABCD | Read/write | ||||
| HR | 2111doc 42112 | Input AC voltage 2 multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2113doc 42114 | Input AC voltage 2 offset | FLOAT32 | ABCD | Read/write | ||||
| HR | 2121doc 42122 | Input AC voltage 3 multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2123doc 42124 | Input AC voltage 3 offset | FLOAT32 | ABCD | Read/write | ||||
| HR | 2131doc 42132 | Input AC voltage 4 multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2133doc 42134 | Input AC voltage 4 offset | FLOAT32 | ABCD | Read/write | ||||
| HR | 2201doc 42202 | Input DC voltage 1 multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2203doc 42204 | Input DC voltage 1 offset | FLOAT32 | ABCD | Read/write | ||||
| HR | 2211doc 42212 | Input DC voltage 2 multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2213doc 42214 | Input DC voltage 2 offset | FLOAT32 | ABCD | Read/write | ||||
| HR | 2221doc 42222 | Input DC voltage 3 multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2223doc 42224 | Input DC voltage 3 offset | FLOAT32 | ABCD | Read/write | ||||
| HR | 2231doc 42232 | Input DC voltage 4 multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2233doc 42234 | Input DC voltage 4 offset | FLOAT32 | ABCD | Read/write |
Notes on this map
- Addresses are taken from the manual's PDU address column (0-based); the logical column is the same number plus 40001, the holding-register offset the manual states.
- All 32-bit values follow the Data order register (PDU 13): 1 = most significant word first (factory default), 2 = least significant word first. The map shows the default, ABCD.
- Left out: the 32-bit float/integer test-value registers (PDU 82-95), which only exist to check word order; the 16-bit test values are kept.
- AC blocks start at PDU 100 (float) and 150 (x1000 int32); DC blocks at PDU 500 and 550. Min/max registers start as NaN after a reset and track readings from then on.
- A missing reading returns NaN (float) or -2147483648 (int32).
- The manual lists function codes 3 and 6 for the float multiplier/offset registers; a 2-register write normally needs function 16.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teracom TSV300 AC/DC voltage transducer with Modbus RTU
What Modbus registers does the Teracom TSV300 AC/DC voltage transducer with Modbus RTU have?
This map lists 74 registers: 74 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teracom TSV300 AC/DC voltage transducer with Modbus RTU Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table prints both a PDU (wire) address and a logical address (PDU + 40001 for holding registers). 'documented' holds the logical number; the PDU number is what goes in the request, e.g. logical 40101 = PDU 100.
What byte order does the Teracom TSV300 AC/DC voltage transducer with Modbus RTU use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Teracom TSV300 AC/DC voltage transducer with Modbus RTU?
Start with HR 100 Input AC voltage 1 (AC voltage input 1); HR 102 Input AC voltage 2 (AC voltage input 2); HR 500 Input DC voltage 1 (DC voltage input 1); HR 150 Input AC voltage 1 x 1000 (AC voltage 1 x1000 (int32)); HR 1000 Reset min and max values (Reset min/max).
How do I enable Modbus control of the Teracom TSV300 AC/DC voltage transducer with Modbus RTU?
Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.
Where is the official Teracom TSV300 AC/DC voltage transducer with Modbus RTU Modbus documentation?
The source is TSV300 User manual (Revision R1.4), revision 2026-10, published free by Teracom at https://www.teracomsystems.com/download/tsv300-ac-voltage-transducer-with-modbus-rtu-interface/.
More Teracom Modbus register maps
- Sensor (temperature / humidity data logger)
Teracom TCW210-TH temperature and humidity data logger
TCW210-TH per the Teracom TCW210-TH user manual Revision R1.26, firmware V2.012 or later.
Also known as: TCW210-TH, TCW210 - Sensor (Ethernet data logger / I/O module)
Teracom TCW220 Ethernet data logger
TCW220 per the Teracom TCW220 user manual Revision R4.24, firmware V2.012 or later.
Also known as: TCW220 - Sensor (Ethernet I/O module)
Teracom TCW241 Ethernet I/O module
TCW241 per the Teracom TCW241 user manual Revision R4.30, firmware v2.012 or later.
Also known as: TCW241 - Energy meter (Ethernet energy monitoring / data logger)
Teracom TCW260 Ethernet energy monitoring module
TCW260 per the Teracom TCW260 user manual Revision R1.19, firmware V3.009 or later.
Also known as: TCW260 - Sensor (Ethernet analog / digital output module)
Teracom TCW280 Ethernet analog output module
TCW280 per the Teracom TCW280 user manual TCW280_R1.8.
Also known as: TCW280 - Sensor (1-Wire to Modbus gateway)
Teracom TCW320x-WMG 1-Wire to Modbus gateway
TCW320E-WMG (Ethernet) and TCW320W-WMG (Wi-Fi) per the user manual Revision R1.0; both share one fixed register map.
Also known as: TCW320E-WMG, TCW320W-WMG - Energy meter (S0 pulse counter / digital input module)
Teracom TDI340 4-channel S0 pulse counter with Modbus RTU
TDI340 per the Teracom TDI340 user manual Revision R1.11, firmware V1.06 or later.
Also known as: TDI340 - Sensor (relay output module)
Teracom TDO340 4-channel Modbus RTU relay output module
TDO340 per the Teracom TDO340 user manual Revision R1.2, firmware V1.03 or later.
Also known as: TDO340 - Sensor (water leak detector)
Teracom TSF400-4 water-leak detector with Modbus RTU
TSF400-4 per the Teracom TSF400-4 user manual Revision R1.2.
Also known as: TSF400-4 - Sensor (humidity / temperature)
Teracom TSH300v3 RS-485 humidity and temperature sensor
TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.
Also known as: TSH300, TSH300v3 - Sensor (humidity / temperature)
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor
TSH331 per the Teracom TSH331 user manual Rev. 1.5, firmware v1.08 or later.
Also known as: TSH331 - Sensor (CO2 / pressure)
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
TSM400-4-CP per the Teracom TSM400-4-CP user manual TSM400-4-CP-R1.9.
Also known as: TSM400-4-CP - Sensor (CO2 / humidity / temperature / pressure)
Teracom TSM400-4-CPTH Modbus CO2, humidity, temperature and pressure multi-sensor
TSM400-4-CPTH per the Teracom TSM400-4-CPTH user manual TSM400-4-CPTH-R1.9.
Also known as: TSM400-4-CPTH - Sensor (humidity / temperature)
Teracom TSM400-4-TH Modbus humidity and temperature sensor
TSM400-4-TH per the Teracom TSM400-4-TH user manual TSM400-4-TH-R1.10.
Also known as: TSM400-4-TH - Sensor (temperature)
Teracom TST300v3 / TST300v4 RS-485 precision temperature sensor
TST300v3/v4 per the Teracom TST300v3/v4 user manual Revision R1.19.
Also known as: TST300, TST300v3, TST300v4 - Sensor (thermocouple input module)
Teracom TST320 2-channel thermocouple module with Modbus RTU
TST320 per the Teracom TST320 user manual Revision R1.6.
Also known as: TST320
Other valves, actuators & sensors register maps
- Sensor (CO2 probe)
Vaisala GMP252 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP252 probe in Modbus RTU mode, user guide M211897EN-G.
Also known as: GMP252, CARBOCAP GMP252, Vaisala GMP252 - Sensor (H2O2 probe)
Vaisala HPP271 hydrogen peroxide probe (Modbus RTU)
HPP271 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211888EN-E).
Also known as: HPP271, PEROXCAP HPP271 - Sensor (weather transmitter)
Vaisala WXT530 series weather transmitters (Modbus RTU)
WXT531-WXT536 weather transmitters with firmware 3.85 or later in Modbus RTU mode (user guide M211840EN-G).
Also known as: WXT531, WXT532, WXT533, WXT534, WXT535, WXT536 - Water treatment controller (Sensor / controller)
Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option
Walchem WebMaster and WebMaster ONE controllers with the Modbus TCP/IP option, software s800/s801/s802/s811/s830 v017 and higher, per manual 180422 Rev G.
Also known as: WebMaster, WebMaster ONE, WM1, s800, s801, s802, s811, s830 - Sensor (Ethernet analog output module)
Acromag BusWorks XT1541-000 8-channel voltage output + 4 digital I/O (Modbus TCP)
BusWorks XT1541-000 per its user's manual (file revision H, 18 Nov 2022).
Also known as: XT1541-000, XT1541, BusWorks XT1541 - Sensor (humidity / temperature transmitter)
E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU)
EE160 RH/T room/duct sensor with RS-485 interface in Modbus RTU mode, per user manual BA_EE160 v2.7 (04-2026).
Also known as: EE160, EE160-HT6, E+E EE160, EE 160
All valves, actuators & sensors Modbus register maps →
Source: TSV300 User manual · Revision R1.4 · rev. 2026-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.