- Home
- Modbus register maps
- Walchem
- WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option
Water treatment controller (Sensor / controller) · Modbus register map
Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option Modbus register map
Updated 17 November 2026
WebMaster controllers manage cooling tower and boiler water chemistry. The Modbus TCP/IP option makes the controller a Modbus TCP server on port 502 with read (FC3) and write (FC6/FC16) of holding registers. This map covers the header strings, the live sensor, analog input, digital input and analog output values, and the writable alarm set points of the four direct sensor inputs.
This page lists 128 Modbus registers for the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option — 40 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Walchem’s own free documentation (linked below) and checked against it.
- Manufacturer
- Walchem
- Model
- WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option
- Equipment type
- Water treatment controller (Sensor / controller)
- Registers
- 128 (40 writable)
- Transport
- Modbus TCP
- Default unit ID
- 1
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- s800/s801/s802/s811/s830 v017 and higher
- Also known as
- WebMaster, WebMaster ONE, WM1, s800, s801, s802, s811, s830
Integration notes: Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option
Connect to port 502 with unit ID 1, read holding registers with FC3 in blocks of up to 125, and decode floats as CDAB. Poll no faster than every 4 seconds; set points are written as 2-register CDAB floats with FC16.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 3000 | Sensor input 1 calibrated value | FLOAT32 CDAB | Sensor input 1 calibrated value | Read |
| HR 3002 | Sensor input 2 calibrated value | FLOAT32 CDAB | Sensor input 2 calibrated value | Read |
| HR 3048 | Sensor input 1 temperature calibrated value | FLOAT32 CDAB | Sensor input 1 temperature | Read |
| HR 3096 | Analog input 1 scaled value | FLOAT32 CDAB | Analog input 1 scaled value | Read |
| HR 3321 | Digital input states (3322) | BITMAP16 | Digital input states (DI_C / DI_1) | Read |
| HR 20642 | Sensor input 1 low alarm | FLOAT32 CDAB | Sensor input 1 low alarm set point | Read/write |
| HR 20644 | Sensor input 1 high alarm | FLOAT32 CDAB | Sensor input 1 high alarm set point | Read/write |
Enable Modbus control & writes
The Modbus TCP/IP option must be installed/enabled on the WebMaster; set point writes need software v14 or higher.
Communication loss & watchdog
An idle TCP connection is closed after 1 minute of inactivity; up to 10 connections are accepted.
Byte order & addressing
- Addresses are 1-based: subtract 1.
- Floats are word-swapped (CDAB).
- Unit ID 0 is treated as broadcast and gets no reply.
Network setup
- Network settings are configured through the WebMaster browser interface.
- Read up to 125 registers per request.
Watch out for
- Data refreshes every 4 seconds; faster polling only returns the same values.
- Modbus RTU is not supported; serial masters need a TCP gateway.
Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Controller name | Header string, 32 characters (2 per register). | STRING[32] | Read | ||||
| HR | 16doc 17 | Controller location | Header string, 32 characters. | STRING[32] | Read | ||||
| HR | 3000doc 3001 | Sensor input 1 calibrated value | Direct sensor reading in its configured units. | FLOAT32 | CDAB | Read | |||
| HR | 3002doc 3003 | Sensor input 2 calibrated value | Direct sensor reading in its configured units. | FLOAT32 | CDAB | Read | |||
| HR | 3004doc 3005 | Sensor input 3 calibrated value | Direct sensor reading in its configured units. | FLOAT32 | CDAB | Read | |||
| HR | 3006doc 3007 | Sensor input 4 calibrated value | Direct sensor reading in its configured units. | FLOAT32 | CDAB | Read | |||
| HR | 3016doc 3017 | Sensor input 1 uncalibrated value | FLOAT32 | CDAB | Read | ||||
| HR | 3018doc 3019 | Sensor input 2 uncalibrated value | FLOAT32 | CDAB | Read | ||||
| HR | 3020doc 3021 | Sensor input 3 uncalibrated value | FLOAT32 | CDAB | Read | ||||
| HR | 3022doc 3023 | Sensor input 4 uncalibrated value | FLOAT32 | CDAB | Read | ||||
| HR | 3032doc 3033 | Sensor input 1 mV | FLOAT32 | CDAB | mV | Read | |||
| HR | 3034doc 3035 | Sensor input 2 mV | FLOAT32 | CDAB | mV | Read | |||
| HR | 3036doc 3037 | Sensor input 3 mV | FLOAT32 | CDAB | mV | Read | |||
| HR | 3038doc 3039 | Sensor input 4 mV | FLOAT32 | CDAB | mV | Read | |||
| HR | 3048doc 3049 | Sensor input 1 temperature calibrated value | FLOAT32 | CDAB | Read | ||||
| HR | 3050doc 3051 | Sensor input 2 temperature calibrated value | FLOAT32 | CDAB | Read | ||||
| HR | 3052doc 3053 | Sensor input 3 temperature calibrated value | FLOAT32 | CDAB | Read | ||||
| HR | 3054doc 3055 | Sensor input 4 temperature calibrated value | FLOAT32 | CDAB | Read | ||||
| HR | 3064doc 3065 | Sensor input 1 temperature uncalibrated value | FLOAT32 | CDAB | Read | ||||
| HR | 3066doc 3067 | Sensor input 2 temperature uncalibrated value | FLOAT32 | CDAB | Read | ||||
| HR | 3068doc 3069 | Sensor input 3 temperature uncalibrated value | FLOAT32 | CDAB | Read | ||||
| HR | 3070doc 3071 | Sensor input 4 temperature uncalibrated value | FLOAT32 | CDAB | Read | ||||
| HR | 3080doc 3081 | Sensor input 1 temperature mV | FLOAT32 | CDAB | mV | Read | |||
| HR | 3082doc 3083 | Sensor input 2 temperature mV | FLOAT32 | CDAB | mV | Read | |||
| HR | 3084doc 3085 | Sensor input 3 temperature mV | FLOAT32 | CDAB | mV | Read | |||
| HR | 3086doc 3087 | Sensor input 4 temperature mV | FLOAT32 | CDAB | mV | Read | |||
| HR | 3096doc 3097 | Analog input 1 scaled value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3098doc 3099 | Analog input 2 scaled value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3100doc 3101 | Analog input 3 scaled value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3102doc 3103 | Analog input 4 scaled value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3104doc 3105 | Analog input 5 scaled value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3106doc 3107 | Analog input 6 scaled value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3108doc 3109 | Analog input 7 scaled value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3110doc 3111 | Analog input 8 scaled value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3128doc 3129 | Analog input 1 mA value | FLOAT32 | CDAB | mA | Read | |||
| HR | 3130doc 3131 | Analog input 2 mA value | FLOAT32 | CDAB | mA | Read | |||
| HR | 3132doc 3133 | Analog input 3 mA value | FLOAT32 | CDAB | mA | Read | |||
| HR | 3134doc 3135 | Analog input 4 mA value | FLOAT32 | CDAB | mA | Read | |||
| HR | 3136doc 3137 | Analog input 5 mA value | FLOAT32 | CDAB | mA | Read | |||
| HR | 3138doc 3139 | Analog input 6 mA value | FLOAT32 | CDAB | mA | Read | |||
| HR | 3140doc 3141 | Analog input 7 mA value | FLOAT32 | CDAB | mA | Read | |||
| HR | 3142doc 3143 | Analog input 8 mA value | FLOAT32 | CDAB | mA | Read | |||
| HR | 3160doc 3161 | Analog input 1 total | Flow-type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3162doc 3163 | Analog input 2 total | Flow-type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3164doc 3165 | Analog input 3 total | Flow-type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3166doc 3167 | Analog input 4 total | Flow-type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3168doc 3169 | Analog input 5 total | Flow-type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3170doc 3171 | Analog input 6 total | Flow-type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3172doc 3173 | Analog input 7 total | Flow-type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3174doc 3175 | Analog input 8 total | Flow-type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3320doc 3321 | Digital input states (3321) | Bit set = input closed, clear = open. | BITMAP16 | Read | bit 0 = DI_B closed; bit 8 = DI_A closed | |||
| HR | 3321doc 3322 | Digital input states (3322) | Bit set = input closed, clear = open. | BITMAP16 | Read | bit 0 = DI_1 closed; bit 8 = DI_C closed | |||
| HR | 3322doc 3323 | Digital input states (3323) | Bit set = input closed, clear = open. | BITMAP16 | Read | bit 0 = DI_3 closed; bit 8 = DI_2 closed | |||
| HR | 3323doc 3324 | Digital input states (3324) | Bit set = input closed, clear = open. | BITMAP16 | Read | bit 0 = DI_5 closed; bit 8 = DI_4 closed | |||
| HR | 3324doc 3325 | Digital input states (3325) | Bit set = input closed, clear = open. | BITMAP16 | Read | bit 0 = DI_D closed; bit 8 = DI_6 closed | |||
| HR | 3325doc 3326 | Digital input states (3326) | Bit set = input closed, clear = open. | BITMAP16 | Read | bit 0 = DI_F closed; bit 8 = DI_E closed | |||
| HR | 3328doc 3329 | Digital input A rate | Paddlewheel and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3330doc 3331 | Digital input B rate | Paddlewheel and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3332doc 3333 | Digital input C rate | Paddlewheel and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3334doc 3335 | Digital input 1 rate | Paddlewheel and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3336doc 3337 | Digital input 2 rate | Paddlewheel and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3338doc 3339 | Digital input 3 rate | Paddlewheel and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3340doc 3341 | Digital input 4 rate | Paddlewheel and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3342doc 3343 | Digital input 5 rate | Paddlewheel and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3344doc 3345 | Digital input 6 rate | Paddlewheel and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3346doc 3347 | Digital input D rate | Paddlewheel and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3348doc 3349 | Digital input E rate | Paddlewheel and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3350doc 3351 | Digital input F rate | Paddlewheel and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3360doc 3361 | Digital input A total | Flowmeter, feed verification and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3362doc 3363 | Digital input B total | Flowmeter, feed verification and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3364doc 3365 | Digital input C total | Flowmeter, feed verification and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3366doc 3367 | Digital input 1 total | Flowmeter, feed verification and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3368doc 3369 | Digital input 2 total | Flowmeter, feed verification and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3370doc 3371 | Digital input 3 total | Flowmeter, feed verification and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3372doc 3373 | Digital input 4 total | Flowmeter, feed verification and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3374doc 3375 | Digital input 5 total | Flowmeter, feed verification and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3376doc 3377 | Digital input 6 total | Flowmeter, feed verification and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3378doc 3379 | Digital input D total | Flowmeter, feed verification and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3380doc 3381 | Digital input E total | Flowmeter, feed verification and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3382doc 3383 | Digital input F total | Flowmeter, feed verification and counter types only. | FLOAT32 | CDAB | Read | |||
| HR | 3680doc 3681 | Analog output 1 percent output | FLOAT32 | CDAB | % | Read | |||
| HR | 3682doc 3683 | Analog output 2 percent output | FLOAT32 | CDAB | % | Read | |||
| HR | 3684doc 3685 | Analog output 3 percent output | FLOAT32 | CDAB | % | Read | |||
| HR | 3686doc 3687 | Analog output 4 percent output | FLOAT32 | CDAB | % | Read | |||
| HR | 3696doc 3697 | Analog output 1 mA value | FLOAT32 | CDAB | mA | Read | |||
| HR | 3698doc 3699 | Analog output 2 mA value | FLOAT32 | CDAB | mA | Read | |||
| HR | 3700doc 3701 | Analog output 3 mA value | FLOAT32 | CDAB | mA | Read | |||
| HR | 3702doc 3703 | Analog output 4 mA value | FLOAT32 | CDAB | mA | Read | |||
| HR | 20640doc 20641 | Sensor input 1 Low Low alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20642doc 20643 | Sensor input 1 low alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20644doc 20645 | Sensor input 1 high alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20646doc 20647 | Sensor input 1 high high alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20648doc 20649 | Sensor input 1 manual temp | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20650doc 20651 | Sensor input 1 temp hi alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20652doc 20653 | Sensor input 1 temp lo alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20654doc 20655 | Sensor input 1 alarm deadband | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20656doc 20657 | Sensor input 1 damping | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20658doc 20659 | Sensor input 1 deviation from primary sensor | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20670doc 20671 | Sensor input 2 Low Low alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20672doc 20673 | Sensor input 2 low alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20674doc 20675 | Sensor input 2 high alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20676doc 20677 | Sensor input 2 high high alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20678doc 20679 | Sensor input 2 manual temp | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20680doc 20681 | Sensor input 2 temp hi alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20682doc 20683 | Sensor input 2 temp lo alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20684doc 20685 | Sensor input 2 alarm deadband | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20686doc 20687 | Sensor input 2 damping | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20688doc 20689 | Sensor input 2 deviation from primary sensor | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20700doc 20701 | Sensor input 3 Low Low alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20702doc 20703 | Sensor input 3 low alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20704doc 20705 | Sensor input 3 high alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20706doc 20707 | Sensor input 3 high high alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20708doc 20709 | Sensor input 3 manual temp | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20710doc 20711 | Sensor input 3 temp hi alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20712doc 20713 | Sensor input 3 temp lo alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20714doc 20715 | Sensor input 3 alarm deadband | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20716doc 20717 | Sensor input 3 damping | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20718doc 20719 | Sensor input 3 deviation from primary sensor | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20730doc 20731 | Sensor input 4 Low Low alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20732doc 20733 | Sensor input 4 low alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20734doc 20735 | Sensor input 4 high alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20736doc 20737 | Sensor input 4 high high alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20738doc 20739 | Sensor input 4 manual temp | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20740doc 20741 | Sensor input 4 temp hi alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20742doc 20743 | Sensor input 4 temp lo alarm | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20744doc 20745 | Sensor input 4 alarm deadband | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20746doc 20747 | Sensor input 4 damping | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write | |||
| HR | 20748doc 20749 | Sensor input 4 deviation from primary sensor | Writable set point; range depends on sensor type. | FLOAT32 | CDAB | Read/write |
Notes on this map
- Floats use Walchem's 'float inverse' format: the two words are swapped, so 5000.0 (0x459C4000) arrives as 0x4000 0x459C - low word first (CDAB).
- Digital input states are single bits: the manual's 'register/bit' notation counts bits 1-16 from the least significant bit, so '/1' is bit 0 and '/9' is bit 8 here.
- Left out: the status, relay hand-off-auto and relay output state registers (2002-2144). The manual calls them 32-bit integers but lists a size of 1 word and an example that reads 1 register, so the register that holds the value is unclear.
- Left out: the bit-packed alarm registers (1001-1058); several alarm rows share registers with different bit positions per hardware variant and could not be transcribed reliably.
- Left out: analog input, digital input, analog output and relay set points (20001+, 20881+, 23601+, relay tables) - their meaning depends on the configured input/output type.
- Values only exist for hardware that is installed; e.g. analog inputs need the analog input card and DI_A..DI_F depend on the controller variant.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option
What Modbus registers does the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option have?
This map lists 128 registers: 128 holding registers. 40 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Sections 4.5.1 and 4.6.1 state that the published addresses are 1-based and the packet is 0-based; subtract 1 on the wire (sensor 1 calibrated value 3001 / 43001 is wire address 3000).
What byte order does the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option?
Start with HR 3000 Sensor input 1 calibrated value (Sensor input 1 calibrated value); HR 3002 Sensor input 2 calibrated value (Sensor input 2 calibrated value); HR 3048 Sensor input 1 temperature calibrated value (Sensor input 1 temperature); HR 3096 Analog input 1 scaled value (Analog input 1 scaled value); HR 3321 Digital input states (3322) (Digital input states (DI_C / DI_1)); HR 20642 Sensor input 1 low alarm (Sensor input 1 low alarm set point); HR 20644 Sensor input 1 high alarm (Sensor input 1 high alarm set point).
How do I enable Modbus control of the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option?
The Modbus TCP/IP option must be installed/enabled on the WebMaster; set point writes need software v14 or higher.
What happens when the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option loses Modbus communication?
An idle TCP connection is closed after 1 minute of inactivity; up to 10 connections are accepted.
Where is the official Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option Modbus documentation?
The source is WebMaster / WebMaster ONE Modbus TCP/IP Option Instruction Manual (180422 Rev G), revision 2014-02, published free by Walchem at https://www.walchem.com/Literature/Controllers/WM/180422_WM1%20Modbus_V17.pdf.
More Walchem Modbus register maps
- Water treatment controller (Sensor / controller)
Walchem W600 water treatment controller (Modbus/TCP)
Walchem W600 controllers (software 3.01 and up) with the Modbus/TCP feature, per Modbus manual 180676.K. W900, Intuition-6 and Intuition-9 use the same type maps but different block start addresses.
Also known as: W600 series - Water treatment controller (Sensor / controller)
Walchem W900 water treatment controller (Modbus/TCP)
Walchem W900 controllers (software 3.01 and up) with the Modbus/TCP feature, per Modbus manual 180676.K. W600, Intuition-6 and Intuition-9 use the same type maps but different block start addresses.
Also known as: W900 series - Water treatment controller (Sensor / controller)
Walchem WebMaster WIND series Modbus TCP/IP option (s825)
Walchem WebMaster WIND-series controllers with the Modbus TCP/IP option, software s825v008 and higher, per manual 180413 Rev A1.
Also known as: WIND, WebMaster WIND, s825
Other valves, actuators & sensors register maps
- Sensor (Ethernet analog output module)
Acromag BusWorks XT1541-000 8-channel voltage output + 4 digital I/O (Modbus TCP)
BusWorks XT1541-000 per its user's manual (file revision H, 18 Nov 2022).
Also known as: XT1541-000, XT1541, BusWorks XT1541 - Sensor (humidity / temperature transmitter)
E+E Elektronik EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU)
EE160 RH/T room/duct sensor with RS-485 interface in Modbus RTU mode, per user manual BA_EE160 v2.7 (04-2026).
Also known as: EE160, EE160-HT6, E+E EE160, EE 160 - Sensor (dissolved oxygen)
JUMO ecoLine O-DO digital optical dissolved oxygen sensor (Modbus RTU)
JUMO ecoLine O-DO type 202613 with RS-485 Modbus RTU (interface description V1.01).
Also known as: 202613, JUMO ecoLine O-DO, ecoLine O-DO type 202613 - Sensor (weighing transmitter / mass converter)
Radwag MW-01-A / MW-01-A7 mass converter
Radwag MW-01-A and MW-01-A7 mass converters per the November 2021 Modbus manual.
Also known as: MW-01-A, MW-01-A7 - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Actuator / valve (ventilation damper and VAV actuator)
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Swegon REACT demand-controlled-ventilation dampers with the Modbus actuators named in the sheet (309C-024-150-MB/SL8/ST15/SWE, 227VM-024-**-MB/SWE), sheet dated 2018-11-08.
Also known as: REACT A, REACT Modbus, Swegon REACT damper, 309C-024-150-MB/SL8/ST15/SWE, 227VM-024-MB/SWE
All valves, actuators & sensors Modbus register maps →
Source: WebMaster / WebMaster ONE Modbus TCP/IP Option Instruction Manual · 180422 Rev G · rev. 2014-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.