Water treatment controller (Sensor / controller) · Modbus register map

Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option Modbus register map

Updated 17 November 2026

Short answer

WebMaster controllers manage cooling tower and boiler water chemistry. The Modbus TCP/IP option makes the controller a Modbus TCP server on port 502 with read (FC3) and write (FC6/FC16) of holding registers. This map covers the header strings, the live sensor, analog input, digital input and analog output values, and the writable alarm set points of the four direct sensor inputs.

This page lists 128 Modbus registers for the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option — 40 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Walchem’s own free documentation (linked below) and checked against it.

Manufacturer
Walchem
Model
WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option
Equipment type
Water treatment controller (Sensor / controller)
Registers
128 (40 writable)
Transport
Modbus TCP
Default unit ID
1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Firmware
s800/s801/s802/s811/s830 v017 and higher
Also known as
WebMaster, WebMaster ONE, WM1, s800, s801, s802, s811, s830
Source document
WebMaster / WebMaster ONE Modbus TCP/IP Option Instruction Manual · 180422 Rev G · rev. 2014-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option

Integration in brief

Connect to port 502 with unit ID 1, read holding registers with FC3 in blocks of up to 125, and decode floats as CDAB. Poll no faster than every 4 seconds; set points are written as 2-register CDAB floats with FC16.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 3000Sensor input 1 calibrated valueFLOAT32 CDABSensor input 1 calibrated valueRead
HR 3002Sensor input 2 calibrated valueFLOAT32 CDABSensor input 2 calibrated valueRead
HR 3048Sensor input 1 temperature calibrated valueFLOAT32 CDABSensor input 1 temperatureRead
HR 3096Analog input 1 scaled valueFLOAT32 CDABAnalog input 1 scaled valueRead
HR 3321Digital input states (3322)BITMAP16Digital input states (DI_C / DI_1)Read
HR 20642Sensor input 1 low alarmFLOAT32 CDABSensor input 1 low alarm set pointRead/write
HR 20644Sensor input 1 high alarmFLOAT32 CDABSensor input 1 high alarm set pointRead/write

Enable Modbus control & writes

The Modbus TCP/IP option must be installed/enabled on the WebMaster; set point writes need software v14 or higher.

Communication loss & watchdog

An idle TCP connection is closed after 1 minute of inactivity; up to 10 connections are accepted.

Byte order & addressing

Network setup

Watch out for

Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

128 of 128 shown
Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Controller nameHeader string, 32 characters (2 per register).STRING[32]Read
HR16doc 17Controller locationHeader string, 32 characters.STRING[32]Read
HR3000doc 3001Sensor input 1 calibrated valueDirect sensor reading in its configured units.FLOAT32CDABRead
HR3002doc 3003Sensor input 2 calibrated valueDirect sensor reading in its configured units.FLOAT32CDABRead
HR3004doc 3005Sensor input 3 calibrated valueDirect sensor reading in its configured units.FLOAT32CDABRead
HR3006doc 3007Sensor input 4 calibrated valueDirect sensor reading in its configured units.FLOAT32CDABRead
HR3016doc 3017Sensor input 1 uncalibrated valueFLOAT32CDABRead
HR3018doc 3019Sensor input 2 uncalibrated valueFLOAT32CDABRead
HR3020doc 3021Sensor input 3 uncalibrated valueFLOAT32CDABRead
HR3022doc 3023Sensor input 4 uncalibrated valueFLOAT32CDABRead
HR3032doc 3033Sensor input 1 mVFLOAT32CDABmVRead
HR3034doc 3035Sensor input 2 mVFLOAT32CDABmVRead
HR3036doc 3037Sensor input 3 mVFLOAT32CDABmVRead
HR3038doc 3039Sensor input 4 mVFLOAT32CDABmVRead
HR3048doc 3049Sensor input 1 temperature calibrated valueFLOAT32CDABRead
HR3050doc 3051Sensor input 2 temperature calibrated valueFLOAT32CDABRead
HR3052doc 3053Sensor input 3 temperature calibrated valueFLOAT32CDABRead
HR3054doc 3055Sensor input 4 temperature calibrated valueFLOAT32CDABRead
HR3064doc 3065Sensor input 1 temperature uncalibrated valueFLOAT32CDABRead
HR3066doc 3067Sensor input 2 temperature uncalibrated valueFLOAT32CDABRead
HR3068doc 3069Sensor input 3 temperature uncalibrated valueFLOAT32CDABRead
HR3070doc 3071Sensor input 4 temperature uncalibrated valueFLOAT32CDABRead
HR3080doc 3081Sensor input 1 temperature mVFLOAT32CDABmVRead
HR3082doc 3083Sensor input 2 temperature mVFLOAT32CDABmVRead
HR3084doc 3085Sensor input 3 temperature mVFLOAT32CDABmVRead
HR3086doc 3087Sensor input 4 temperature mVFLOAT32CDABmVRead
HR3096doc 3097Analog input 1 scaled value4-20 mA input in engineering units.FLOAT32CDABRead
HR3098doc 3099Analog input 2 scaled value4-20 mA input in engineering units.FLOAT32CDABRead
HR3100doc 3101Analog input 3 scaled value4-20 mA input in engineering units.FLOAT32CDABRead
HR3102doc 3103Analog input 4 scaled value4-20 mA input in engineering units.FLOAT32CDABRead
HR3104doc 3105Analog input 5 scaled value4-20 mA input in engineering units.FLOAT32CDABRead
HR3106doc 3107Analog input 6 scaled value4-20 mA input in engineering units.FLOAT32CDABRead
HR3108doc 3109Analog input 7 scaled value4-20 mA input in engineering units.FLOAT32CDABRead
HR3110doc 3111Analog input 8 scaled value4-20 mA input in engineering units.FLOAT32CDABRead
HR3128doc 3129Analog input 1 mA valueFLOAT32CDABmARead
HR3130doc 3131Analog input 2 mA valueFLOAT32CDABmARead
HR3132doc 3133Analog input 3 mA valueFLOAT32CDABmARead
HR3134doc 3135Analog input 4 mA valueFLOAT32CDABmARead
HR3136doc 3137Analog input 5 mA valueFLOAT32CDABmARead
HR3138doc 3139Analog input 6 mA valueFLOAT32CDABmARead
HR3140doc 3141Analog input 7 mA valueFLOAT32CDABmARead
HR3142doc 3143Analog input 8 mA valueFLOAT32CDABmARead
HR3160doc 3161Analog input 1 totalFlow-type analog inputs only.FLOAT32CDABRead
HR3162doc 3163Analog input 2 totalFlow-type analog inputs only.FLOAT32CDABRead
HR3164doc 3165Analog input 3 totalFlow-type analog inputs only.FLOAT32CDABRead
HR3166doc 3167Analog input 4 totalFlow-type analog inputs only.FLOAT32CDABRead
HR3168doc 3169Analog input 5 totalFlow-type analog inputs only.FLOAT32CDABRead
HR3170doc 3171Analog input 6 totalFlow-type analog inputs only.FLOAT32CDABRead
HR3172doc 3173Analog input 7 totalFlow-type analog inputs only.FLOAT32CDABRead
HR3174doc 3175Analog input 8 totalFlow-type analog inputs only.FLOAT32CDABRead
HR3320doc 3321Digital input states (3321)Bit set = input closed, clear = open.BITMAP16Readbit 0 = DI_B closed; bit 8 = DI_A closed
HR3321doc 3322Digital input states (3322)Bit set = input closed, clear = open.BITMAP16Readbit 0 = DI_1 closed; bit 8 = DI_C closed
HR3322doc 3323Digital input states (3323)Bit set = input closed, clear = open.BITMAP16Readbit 0 = DI_3 closed; bit 8 = DI_2 closed
HR3323doc 3324Digital input states (3324)Bit set = input closed, clear = open.BITMAP16Readbit 0 = DI_5 closed; bit 8 = DI_4 closed
HR3324doc 3325Digital input states (3325)Bit set = input closed, clear = open.BITMAP16Readbit 0 = DI_D closed; bit 8 = DI_6 closed
HR3325doc 3326Digital input states (3326)Bit set = input closed, clear = open.BITMAP16Readbit 0 = DI_F closed; bit 8 = DI_E closed
HR3328doc 3329Digital input A ratePaddlewheel and counter types only.FLOAT32CDABRead
HR3330doc 3331Digital input B ratePaddlewheel and counter types only.FLOAT32CDABRead
HR3332doc 3333Digital input C ratePaddlewheel and counter types only.FLOAT32CDABRead
HR3334doc 3335Digital input 1 ratePaddlewheel and counter types only.FLOAT32CDABRead
HR3336doc 3337Digital input 2 ratePaddlewheel and counter types only.FLOAT32CDABRead
HR3338doc 3339Digital input 3 ratePaddlewheel and counter types only.FLOAT32CDABRead
HR3340doc 3341Digital input 4 ratePaddlewheel and counter types only.FLOAT32CDABRead
HR3342doc 3343Digital input 5 ratePaddlewheel and counter types only.FLOAT32CDABRead
HR3344doc 3345Digital input 6 ratePaddlewheel and counter types only.FLOAT32CDABRead
HR3346doc 3347Digital input D ratePaddlewheel and counter types only.FLOAT32CDABRead
HR3348doc 3349Digital input E ratePaddlewheel and counter types only.FLOAT32CDABRead
HR3350doc 3351Digital input F ratePaddlewheel and counter types only.FLOAT32CDABRead
HR3360doc 3361Digital input A totalFlowmeter, feed verification and counter types only.FLOAT32CDABRead
HR3362doc 3363Digital input B totalFlowmeter, feed verification and counter types only.FLOAT32CDABRead
HR3364doc 3365Digital input C totalFlowmeter, feed verification and counter types only.FLOAT32CDABRead
HR3366doc 3367Digital input 1 totalFlowmeter, feed verification and counter types only.FLOAT32CDABRead
HR3368doc 3369Digital input 2 totalFlowmeter, feed verification and counter types only.FLOAT32CDABRead
HR3370doc 3371Digital input 3 totalFlowmeter, feed verification and counter types only.FLOAT32CDABRead
HR3372doc 3373Digital input 4 totalFlowmeter, feed verification and counter types only.FLOAT32CDABRead
HR3374doc 3375Digital input 5 totalFlowmeter, feed verification and counter types only.FLOAT32CDABRead
HR3376doc 3377Digital input 6 totalFlowmeter, feed verification and counter types only.FLOAT32CDABRead
HR3378doc 3379Digital input D totalFlowmeter, feed verification and counter types only.FLOAT32CDABRead
HR3380doc 3381Digital input E totalFlowmeter, feed verification and counter types only.FLOAT32CDABRead
HR3382doc 3383Digital input F totalFlowmeter, feed verification and counter types only.FLOAT32CDABRead
HR3680doc 3681Analog output 1 percent outputFLOAT32CDAB%Read
HR3682doc 3683Analog output 2 percent outputFLOAT32CDAB%Read
HR3684doc 3685Analog output 3 percent outputFLOAT32CDAB%Read
HR3686doc 3687Analog output 4 percent outputFLOAT32CDAB%Read
HR3696doc 3697Analog output 1 mA valueFLOAT32CDABmARead
HR3698doc 3699Analog output 2 mA valueFLOAT32CDABmARead
HR3700doc 3701Analog output 3 mA valueFLOAT32CDABmARead
HR3702doc 3703Analog output 4 mA valueFLOAT32CDABmARead
HR20640doc 20641Sensor input 1 Low Low alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20642doc 20643Sensor input 1 low alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20644doc 20645Sensor input 1 high alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20646doc 20647Sensor input 1 high high alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20648doc 20649Sensor input 1 manual tempWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20650doc 20651Sensor input 1 temp hi alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20652doc 20653Sensor input 1 temp lo alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20654doc 20655Sensor input 1 alarm deadbandWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20656doc 20657Sensor input 1 dampingWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20658doc 20659Sensor input 1 deviation from primary sensorWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20670doc 20671Sensor input 2 Low Low alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20672doc 20673Sensor input 2 low alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20674doc 20675Sensor input 2 high alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20676doc 20677Sensor input 2 high high alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20678doc 20679Sensor input 2 manual tempWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20680doc 20681Sensor input 2 temp hi alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20682doc 20683Sensor input 2 temp lo alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20684doc 20685Sensor input 2 alarm deadbandWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20686doc 20687Sensor input 2 dampingWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20688doc 20689Sensor input 2 deviation from primary sensorWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20700doc 20701Sensor input 3 Low Low alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20702doc 20703Sensor input 3 low alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20704doc 20705Sensor input 3 high alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20706doc 20707Sensor input 3 high high alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20708doc 20709Sensor input 3 manual tempWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20710doc 20711Sensor input 3 temp hi alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20712doc 20713Sensor input 3 temp lo alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20714doc 20715Sensor input 3 alarm deadbandWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20716doc 20717Sensor input 3 dampingWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20718doc 20719Sensor input 3 deviation from primary sensorWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20730doc 20731Sensor input 4 Low Low alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20732doc 20733Sensor input 4 low alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20734doc 20735Sensor input 4 high alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20736doc 20737Sensor input 4 high high alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20738doc 20739Sensor input 4 manual tempWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20740doc 20741Sensor input 4 temp hi alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20742doc 20743Sensor input 4 temp lo alarmWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20744doc 20745Sensor input 4 alarm deadbandWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20746doc 20747Sensor input 4 dampingWritable set point; range depends on sensor type.FLOAT32CDABRead/write
HR20748doc 20749Sensor input 4 deviation from primary sensorWritable set point; range depends on sensor type.FLOAT32CDABRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option

What Modbus registers does the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option have?

This map lists 128 registers: 128 holding registers. 40 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Sections 4.5.1 and 4.6.1 state that the published addresses are 1-based and the packet is 0-based; subtract 1 on the wire (sensor 1 calibrated value 3001 / 43001 is wire address 3000).

What byte order does the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option?

Start with HR 3000 Sensor input 1 calibrated value (Sensor input 1 calibrated value); HR 3002 Sensor input 2 calibrated value (Sensor input 2 calibrated value); HR 3048 Sensor input 1 temperature calibrated value (Sensor input 1 temperature); HR 3096 Analog input 1 scaled value (Analog input 1 scaled value); HR 3321 Digital input states (3322) (Digital input states (DI_C / DI_1)); HR 20642 Sensor input 1 low alarm (Sensor input 1 low alarm set point); HR 20644 Sensor input 1 high alarm (Sensor input 1 high alarm set point).

How do I enable Modbus control of the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option?

The Modbus TCP/IP option must be installed/enabled on the WebMaster; set point writes need software v14 or higher.

What happens when the Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option loses Modbus communication?

An idle TCP connection is closed after 1 minute of inactivity; up to 10 connections are accepted.

Where is the official Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option Modbus documentation?

The source is WebMaster / WebMaster ONE Modbus TCP/IP Option Instruction Manual (180422 Rev G), revision 2014-02, published free by Walchem at https://www.walchem.com/Literature/Controllers/WM/180422_WM1%20Modbus_V17.pdf.

More Walchem Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: WebMaster / WebMaster ONE Modbus TCP/IP Option Instruction Manual · 180422 Rev G · rev. 2014-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.