- Home
- Modbus register maps
- Radwag
- MW-01-A / MW-01-A7 mass converter
Sensor (weighing transmitter / mass converter) · Modbus register map
Radwag MW-01-A / MW-01-A7 mass converter Modbus register map
Updated 17 November 2026
The MW-01-A mass converter serves Modbus RTU on RS-485 and Modbus TCP (and RTU over TCP) on Ethernet. Input registers return mass, tare, unit, status, thresholds and dosing/adjustment state; holding registers take zero, tare, dosing and calibration commands plus threshold writes. Floats here are low word first, unlike Radwag's PUE indicators.
This page lists 20 Modbus registers for the Radwag MW-01-A / MW-01-A7 mass converter — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Radwag’s own free documentation (linked below) and checked against it.
- Manufacturer
- Radwag
- Model
- MW-01-A / MW-01-A7 mass converter
- Equipment type
- Sensor (weighing transmitter / mass converter)
- Registers
- 20 (9 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- MW-01-A, MW-01-A7
Integration notes: Radwag MW-01-A / MW-01-A7 mass converter
Read input registers (FC04) from offset 0: mass is a low-word-first float at offset 0 and the status bits at offset 5. Write bit 0 or 1 of the Command register (offset 256) to zero or tare, clearing it before repeating.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Mass | FLOAT32 CDAB | Mass | Read |
| IR 5 | Status | BITMAP16 | Status (stable, zero, errors) | Read |
| IR 4 | Unit | BITMAP16 | Displayed unit | Read |
| IR 32 | Dosing status | UINT16 | Dosing status | Read |
| HR 256 | Command | BITMAP16 | Zero / tare / dosing commands | Read/write |
Enable Modbus control & writes
Configure communication with the MwManager PC software under Parameters / Set Communication.
Byte order & addressing
- Floats are CDAB (low word first).
- Commands act on a bit being set; write 0 first to repeat the same command.
Network setup
- Use MwManager to set the RS-485 or Ethernet parameters.
Watch out for
- Do not reuse a PUE indicator template: the MW-01-A float word order and holding addresses differ.
Radwag MW-01-A / MW-01-A7 mass converter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Mass | Mass in the currently displayed unit. | FLOAT32 | CDAB | Read | |||
| IR | 2doc 30003 | Tare | Tare in the adjustment (calibration) unit. | FLOAT32 | CDAB | Read | |||
| IR | 4doc 30005 | Unit | Bit set shows the unit now displayed. | BITMAP16 | Read | bit 0 = gram [g]; bit 1 = kilogram [kg]; bit 2 = carat [ct]; bit 3 = pound [lb]; bit 4 = ounce [oz]; bit 5 = Newton [N] | |||
| IR | 5doc 30006 | Status | BITMAP16 | Read | bit 0 = Measurement correct (no error); bit 1 = Measurement stable; bit 2 = Indicating zero; bit 3 = Tared; bit 4 = In weighing range II; bit 5 = In weighing range III; bit 6 = NULL error; bit 7 = LH error; bit 8 = FULL error | ||||
| IR | 6doc 30007 | LO threshold | In the adjustment unit. | FLOAT32 | CDAB | Read | |||
| IR | 32doc 30033 | Dosing status | UINT16 | Read | 0 = Process disabled; 1 = Dosing in progress; 2 = Process stopped; 3 = Process finished | ||||
| IR | 33doc 30034 | Input status | Bitmask of converter inputs; the 8 low bits are the inputs, bit 0 = input 1. | UINT16 | Read | ||||
| IR | 34doc 30035 | Min | MIN threshold, adjustment unit. | FLOAT32 | CDAB | Read | |||
| IR | 36doc 30037 | Max | MAX threshold, adjustment unit. | FLOAT32 | CDAB | Read | |||
| IR | 38doc 30039 | Fast dosing threshold | Adjustment unit. | FLOAT32 | CDAB | Read | |||
| IR | 50doc 30051 | Adjustment status | State of the adjustment (calibration) process. | UINT16 | Read | 0 = Process finished correctly; 1 = Start mass / adjustment factor determination in progress; 2 = Range exceeded; 3 = Time exceeded; 4 = Process aborted; 5 = Awaiting data | |||
| HR | 256doc 40257 | Command | Set a bit to run that action once; clear it before repeating. | BITMAP16 | Read/write | bit 0 = Zero the platform; bit 1 = Tare the platform; bit 5 = Process start; bit 6 = Process stop; bit 8 = Start mass determination; bit 9 = Adjustment factor determination; bit 10 = Record adjustment parameters | |||
| HR | 257doc 40258 | Command with parameter | Set a bit to apply the matching parameter register below. | BITMAP16 | Read/write | bit 0 = Set tare value; bit 1 = Set LO threshold; bit 2 = Set outputs state; bit 3 = Set MIN threshold; bit 4 = Set MAX threshold; bit 5 = Set fast dosing threshold; bit 6 = Set precise dosing threshold; bit 9 = Set adjustment weight mass | |||
| HR | 258doc 40259 | Platform | Platform number for parameter commands (always 1). | UINT16 | Read/write | ||||
| HR | 259doc 40260 | Tare | Tare to set, adjustment unit. | FLOAT32 | CDAB | Read/write | |||
| HR | 261doc 40262 | LO threshold | LO threshold to set, adjustment unit. | FLOAT32 | CDAB | Read/write | |||
| HR | 263doc 40264 | Output state | Output mask to apply, bit 0 = output 1. | UINT16 | Read/write | ||||
| HR | 264doc 40265 | Min | MIN threshold to set. | FLOAT32 | CDAB | Read/write | |||
| HR | 266doc 40267 | Max | MAX threshold to set. | FLOAT32 | CDAB | Read/write | |||
| HR | 268doc 40269 | Fast dosing threshold | Fast dosing threshold to set. | FLOAT32 | CDAB | Read/write |
Notes on this map
- Floats are two registers with the low word first (CDAB): the manual's example has 30001 = 0x72B0 and 30002 = 0x3E68 giving 0.227, and its tare write example puts 0x0000 in the first register and 0x3F80 in the second.
- Left out: 'Precise dosing threshold' (input offset 40, holding offset 270) and 'Adjustment weight mass' (holding offset 272), because the table lists them as float with a length of 1 register, which cannot both be right.
- The manual's write examples label registers as 40000 + offset (40257 = 'command with parameter' at offset 257, tare at 40259/40260 = offsets 259-260), so they agree with the offset column on the wire; the output-mask example (40502/40507) is copied from another product and does not fit this map. This map follows the table's offset column.
- Settings (address, baud, IP) are made with Radwag's MwManager PC software; the Modbus manual gives no defaults.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Radwag MW-01-A / MW-01-A7 mass converter
What Modbus registers does the Radwag MW-01-A / MW-01-A7 mass converter have?
This map lists 20 registers: 11 input registers, 9 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Radwag MW-01-A / MW-01-A7 mass converter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables list a 0-based Offset next to a 30001/40001-style Modbus address; the offset goes on the wire (mass = offset 0 = 30001, Command = offset 256 = 40257).
What byte order does the Radwag MW-01-A / MW-01-A7 mass converter use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Radwag MW-01-A / MW-01-A7 mass converter?
Start with IR 0 Mass (Mass); IR 5 Status (Status (stable, zero, errors)); IR 4 Unit (Displayed unit); IR 32 Dosing status (Dosing status); HR 256 Command (Zero / tare / dosing commands).
How do I enable Modbus control of the Radwag MW-01-A / MW-01-A7 mass converter?
Configure communication with the MwManager PC software under Parameters / Set Communication.
Where is the official Radwag MW-01-A / MW-01-A7 mass converter Modbus documentation?
The source is Software manual MODBUS - Communication Protocol of MW-01-A Mass Converter (ITKP-41-01-11-21-EN), revision 2021-11, published free by Radwag at https://radwag.com/document/en/user-manual-modbus-communication-protocol-of-mw-01-a-mw-01-a7-mass-converter__MODBUS-MW-01-A-ITKP-41-01-11-21-EN.pdf.
More Radwag Modbus register maps
Other valves, actuators & sensors register maps
- Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Actuator / valve (ventilation damper and VAV actuator)
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Swegon REACT demand-controlled-ventilation dampers with the Modbus actuators named in the sheet (309C-024-150-MB/SL8/ST15/SWE, 227VM-024-**-MB/SWE), sheet dated 2018-11-08.
Also known as: REACT A, REACT Modbus, Swegon REACT damper, 309C-024-150-MB/SL8/ST15/SWE, 227VM-024-MB/SWE - Sensor (humidity / temperature)
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor
TSH331 per the Teracom TSH331 user manual Rev. 1.5, firmware v1.08 or later.
Also known as: TSH331 - Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series - Sensor (humidity and temperature transmitter)
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
HMDW110-series duct, wall and outdoor transmitters and TMI110 ordered with the Modbus RTU option (user guide M211726EN-L).
Also known as: HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110 - Sensor transmitter (host for Vaisala probes)
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)
Indigo510 and Indigo520 transmitter registers (unit ID 240) over Modbus TCP (user guide M212287EN-AJ).
Also known as: Indigo510, Indigo520, Indigo500 series
All valves, actuators & sensors Modbus register maps →
Source: Software manual MODBUS - Communication Protocol of MW-01-A Mass Converter · ITKP-41-01-11-21-EN · rev. 2021-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.