  4. TSH331 IP54 Modbus RTU humidity and temperature sensor

Sensor (humidity / temperature) · Modbus register map

Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor Modbus register map

Updated 19 November 2026

Short answer

The TSH331 is an IP54 humidity and temperature sensor from Teracom with a Modbus RTU RS-485 port, cable gland and screwless terminals. It reports temperature, humidity and dew point as floats and x100 integers in °C and °F.

This page lists 26 Modbus registers for the Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teracom’s own free documentation (linked below) and checked against it.

Manufacturer
Teracom
Model
TSH331 IP54 Modbus RTU humidity and temperature sensor
Equipment type
Sensor (humidity / temperature)
Registers
26 (8 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Firmware
v1.08 or later
Also known as
TSH331
Source document
TSH331 User manual · Rev. 1.5 · rev. 2026-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor

Integration in brief

Poll the float block PDU 100-105 or the integer block PDU 400-402 with function 03.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100Temperature °CFLOAT32 ABCDTemperature °C (float)Read
HR 102Humidity %RHFLOAT32 ABCDHumidity %RH (float)Read
HR 104Dew point °CFLOAT32 ABCDDew point °CRead
HR 400Temperature °C x 100INT16Temperature °C x100Read
HR 401Humidity %RH x 100UINT16Humidity x100Read

Enable Modbus control & writes

Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.

Byte order & addressing

Network setup

Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

26 of 26 shown
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR10doc 40011RS-485 addressModbus slave address of the device.UINT16Read/write
HR11doc 40012Baud rateSerial baud rate; takes effect after a power cycle.UINT16Read/write
HR12doc 40013Parity, data, stop bitsParity/data/stop framing; takes effect after a power cycle.UINT16Read/write1 = 8 data bits, even parity, 1 stop (E81); 2 = 8 data bits, odd parity, 1 stop (O81); 3 = 8 data bits, no parity, 1 stop (N81)
HR13doc 40014Data orderWord order used for all 32-bit values.UINT16Read/write1 = MSWF - most significant word first; 2 = LSWF - least significant word first
HR14doc 40015Device codeFixed product identification code.UINT16Read
HR15doc 40016FW versionFirmware version number.UINT16Read
HR18doc 40019Vendor URLMaker URL as UTF-8 text (64 bytes).STRING[64]Read
HR86doc 40087Signed integer test valueINT16Read
HR91doc 40092Unsigned integer test valueUINT16Read
HR100doc 40101Temperature °CFLOAT32ABCD°CRead
HR102doc 40103Humidity %RHFLOAT32ABCD%RHRead
HR104doc 40105Dew point °CFLOAT32ABCD°CRead
HR200doc 40201Temperature °FFLOAT32ABCD°FRead
HR202doc 40203Humidity %RHFLOAT32ABCD%RHRead
HR204doc 40205Dew point °FFLOAT32ABCD°FRead
HR400doc 40401Temperature °C x 100INT16× 0.01°CRead
HR401doc 40402Humidity %RH x 100UINT16× 0.01%RHRead
HR402doc 40403Dew point °C x 100INT16× 0.01°CRead
HR500doc 40501Temperature °F x 100INT16× 0.01°FRead
HR501doc 40502Humidity %RH x 100UINT16× 0.01%RHRead
HR502doc 40503Dew point °F x 100INT16× 0.01°FRead
HR2101doc 42102Temperature multiplierFLOAT32ABCDRead/write
HR2103doc 42104Temperature offset °CFLOAT32ABCD°CRead/write
HR2105doc 42106Temperature offset °FFLOAT32ABCD°FRead
HR2111doc 42112Humidity multiplierFLOAT32ABCDRead/write
HR2113doc 42114Humidity offsetFLOAT32ABCDRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor

What Modbus registers does the Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor have?

This map lists 26 registers: 26 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table prints both a PDU (wire) address and a logical address (PDU + 40001 for holding registers). 'documented' holds the logical number; the PDU number is what goes in the request, e.g. logical 40101 = PDU 100.

What byte order does the Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor?

Start with HR 100 Temperature °C (Temperature °C (float)); HR 102 Humidity %RH (Humidity %RH (float)); HR 104 Dew point °C (Dew point °C); HR 400 Temperature °C x 100 (Temperature °C x100); HR 401 Humidity %RH x 100 (Humidity x100).

How do I enable Modbus control of the Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor?

Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.

Where is the official Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor Modbus documentation?

The source is TSH331 User manual (Rev. 1.5), revision 2026-10, published free by Teracom at https://www.teracomsystems.com/download/modbus-rtu-waterproof-temperature-and-humidity-sensor-tsh331-user-manual/.