- Home
- Modbus register maps
- Teracom
- TST320 2-channel thermocouple module with Modbus RTU
Sensor (thermocouple input module) · Modbus register map
Teracom TST320 2-channel thermocouple module with Modbus RTU Modbus register map
Updated 19 November 2026
The TST320 is a DIN-rail Teracom module that reads two thermocouples (J, K, T, N, E, B, R, S) and serves them over Modbus RTU RS-485. It gives current, minimum and maximum temperatures in °C and °F as floats and scaled integers, with per-channel type, multiplier and offset.
This page lists 50 Modbus registers for the Teracom TST320 2-channel thermocouple module with Modbus RTU — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teracom’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teracom
- Model
- TST320 2-channel thermocouple module with Modbus RTU
- Equipment type
- Sensor (thermocouple input module)
- Registers
- 50 (11 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- TST320
- Source document
- TST320 User manual · Revision R1.6 · rev. 2026-10
Integration notes: Teracom TST320 2-channel thermocouple module with Modbus RTU
Set each channel's thermocouple type (PDU 2100 / 2110), then read the floats at PDU 100-103 or the x10 integers at PDU 400-401 with function 03.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 100 | TC1 temperature °C | FLOAT32 ABCD | TC1 temperature °C | Read |
| HR 102 | TC2 temperature °C | FLOAT32 ABCD | TC2 temperature °C | Read |
| HR 400 | TC1 temperature °C x 10 | INT16 | TC1 °C x10 | Read |
| HR 401 | TC2 temperature °C x 10 | INT16 | TC2 °C x10 | Read |
| HR 2100 | TC1 type | UINT16 | TC1 type | Read/write |
| HR 2110 | TC2 type | UINT16 | TC2 type | Read/write |
Enable Modbus control & writes
Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.
Byte order & addressing
- Baud rate and framing changes only take effect after the device is powered off and on again.
- Word order for every 32-bit value is set by the Data order register (PDU 13); check it before blaming the scaling.
Network setup
- Set unit ID (PDU 10), baud (PDU 11) and framing (PDU 12), then power-cycle the device.
- Terminate both ends of the RS-485 bus with 120 ohm; the built-in resistor is enabled by shorting the 485- and Term terminals. A daisy chain is recommended.
Teracom TST320 2-channel thermocouple module with Modbus RTU Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 10doc 40011 | RS-485 address | Modbus slave address of the device. | UINT16 | Read/write | ||||
| HR | 11doc 40012 | Baud rate | Serial baud rate; takes effect after a power cycle. | UINT16 | Read/write | ||||
| HR | 12doc 40013 | Parity, data, stop bits | Parity/data/stop framing; takes effect after a power cycle. | UINT16 | Read/write | 1 = 8 data bits, even parity, 1 stop (E81); 2 = 8 data bits, odd parity, 1 stop (O81); 3 = 8 data bits, no parity, 1 stop (N81) | |||
| HR | 13doc 40014 | Data order | Word order used for all 32-bit values. | UINT16 | Read/write | 1 = MSWF - most significant word first; 2 = LSWF - least significant word first | |||
| HR | 14doc 40015 | Device code | Fixed product identification code. | UINT16 | Read | ||||
| HR | 15doc 40016 | FW version | Firmware version number. | UINT16 | Read | ||||
| HR | 18doc 40019 | Vendor URL | Maker URL as UTF-8 text (64 bytes). | STRING[64] | Read | ||||
| HR | 86doc 40087 | Signed integer test value | INT16 | Read | |||||
| HR | 91doc 40092 | Unsigned integer test value | UINT16 | Read | |||||
| HR | 100doc 40101 | TC1 temperature °C | FLOAT32 | ABCD | °C | Read | |||
| HR | 102doc 40103 | TC2 temperature °C | FLOAT32 | ABCD | °C | Read | |||
| HR | 120doc 40121 | TC1 min. temperature °C | FLOAT32 | ABCD | °C | Read | |||
| HR | 122doc 40123 | TC2 min. temperature °C | FLOAT32 | ABCD | °C | Read | |||
| HR | 140doc 40141 | TC1 max. temperature °C | FLOAT32 | ABCD | °C | Read | |||
| HR | 142doc 40143 | TC2 max. temperature °C | FLOAT32 | ABCD | °C | Read | |||
| HR | 200doc 40201 | TC1 temperature °F | FLOAT32 | ABCD | °F | Read | |||
| HR | 202doc 40203 | TC2 temperature °F | FLOAT32 | ABCD | °F | Read | |||
| HR | 220doc 40221 | TC1 min. temperature °F | FLOAT32 | ABCD | °F | Read | |||
| HR | 222doc 40223 | TC2 min. temperature °F | FLOAT32 | ABCD | °F | Read | |||
| HR | 240doc 40241 | TC1 max. temperature °F | FLOAT32 | ABCD | °F | Read | |||
| HR | 242doc 40243 | TC2 max. temperature °F | FLOAT32 | ABCD | °F | Read | |||
| HR | 400doc 40401 | TC1 temperature °C x 10 | INT16 | × 0.1 | °C | Read | |||
| HR | 401doc 40402 | TC2 temperature °C x 10 | INT16 | × 0.1 | °C | Read | |||
| HR | 420doc 40421 | TC1 min. temperature °C x 10 | INT16 | × 0.1 | °C | Read | |||
| HR | 421doc 40422 | TC2 min. temperature °C x 10 | INT16 | × 0.1 | °C | Read | |||
| HR | 440doc 40441 | TC1 max. temperature °C x 10 | INT16 | × 0.1 | °C | Read | |||
| HR | 441doc 40442 | TC2 max. temperature °C x 10 | INT16 | × 0.1 | °C | Read | |||
| HR | 500doc 40501 | TC1 temperature °F x 10 | INT16 | × 0.1 | °F | Read | |||
| HR | 501doc 40502 | TC2 temperature °F x 10 | INT16 | × 0.1 | °F | Read | |||
| HR | 520doc 40521 | TC1 min. temperature °F x 10 | INT16 | × 0.1 | °F | Read | |||
| HR | 521doc 40522 | TC2 min. temperature °F x 10 | INT16 | × 0.1 | °F | Read | |||
| HR | 540doc 40541 | TC1 max. temperature °F x 10 | INT16 | × 0.1 | °F | Read | |||
| HR | 541doc 40542 | TC2 max. temperature °F x 10 | INT16 | × 0.1 | °F | Read | |||
| HR | 620doc 40621 | TC1 min. temperature °C x 100 | INT32 | ABCD | × 0.01 | °C | Read | ||
| HR | 622doc 40623 | TC2 min. temperature °C x 100 | INT32 | ABCD | × 0.01 | °C | Read | ||
| HR | 640doc 40641 | TC1 max. temperature °C x 100 | INT32 | ABCD | × 0.01 | °C | Read | ||
| HR | 642doc 40643 | TC2 max. temperature °C x 100 | INT32 | ABCD | × 0.01 | °C | Read | ||
| HR | 700doc 40701 | TC1 temperature °F x 100 | INT32 | ABCD | × 0.01 | °F | Read | ||
| HR | 702doc 40703 | TC2 temperature °F x 100 | INT32 | ABCD | × 0.01 | °F | Read | ||
| HR | 720doc 40721 | TC1 min. temperature °F x 100 | INT32 | ABCD | × 0.01 | °F | Read | ||
| HR | 722doc 40723 | TC2 min. temperature °F x 100 | INT32 | ABCD | × 0.01 | °F | Read | ||
| HR | 740doc 40741 | TC1 max. temperature °F x 100 | INT32 | ABCD | × 0.01 | °F | Read | ||
| HR | 742doc 40743 | TC2 max. temperature °F x 100 | INT32 | ABCD | × 0.01 | °F | Read | ||
| HR | 1000doc 41001 | Reset min and max values | Write to clear the stored min/max values. | UINT16 | Read/write | ||||
| HR | 2100doc 42101 | TC1 type | UINT16 | Read/write | 0 = J type; 1 = K type; 2 = T type; 3 = N type; 4 = E type; 5 = B type; 6 = R type; 7 = S type | ||||
| HR | 2101doc 42102 | TC1 multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2103doc 42104 | TC1 offset | FLOAT32 | ABCD | Read/write | ||||
| HR | 2110doc 42111 | TC2 type | UINT16 | Read/write | 0 = J type; 1 = K type; 2 = T type; 3 = N type; 4 = E type; 5 = B type; 6 = R type; 7 = S type | ||||
| HR | 2111doc 42112 | TC2 multiplier | FLOAT32 | ABCD | Read/write | ||||
| HR | 2113doc 42114 | TC2 offset | FLOAT32 | ABCD | Read/write |
Notes on this map
- Addresses are taken from the manual's PDU address column (0-based); the logical column is the same number plus 40001, the holding-register offset the manual states.
- All 32-bit values follow the Data order register (PDU 13): 1 = most significant word first (factory default), 2 = least significant word first. The map shows the default, ABCD.
- Left out: the 32-bit float/integer test-value registers (PDU 82-95), which only exist to check word order; the 16-bit test values are kept.
- Integer formats as the table lists them: x10 values are 16-bit signed; x100 current °C values are 16-bit signed, while the x100 min/max °C and all x100 °F values are 32-bit signed.
- A missing thermocouple returns NaN (float), -32768 (16-bit) or -2147483648 (32-bit).
- Min/max values are cleared through PDU 1000.
- Left out: the current-value °C x100 registers (PDU 600 and 602). The table calls them 16-bit signed but spaces them two registers apart like the 32-bit rows around them, so their size is unclear.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teracom TST320 2-channel thermocouple module with Modbus RTU
What Modbus registers does the Teracom TST320 2-channel thermocouple module with Modbus RTU have?
This map lists 50 registers: 50 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teracom TST320 2-channel thermocouple module with Modbus RTU Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table prints both a PDU (wire) address and a logical address (PDU + 40001 for holding registers). 'documented' holds the logical number; the PDU number is what goes in the request, e.g. logical 40101 = PDU 100.
What byte order does the Teracom TST320 2-channel thermocouple module with Modbus RTU use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Teracom TST320 2-channel thermocouple module with Modbus RTU?
Start with HR 100 TC1 temperature °C (TC1 temperature °C); HR 102 TC2 temperature °C (TC2 temperature °C); HR 400 TC1 temperature °C x 10 (TC1 °C x10); HR 401 TC2 temperature °C x 10 (TC2 °C x10); HR 2100 TC1 type (TC1 type); HR 2110 TC2 type (TC2 type).
How do I enable Modbus control of the Teracom TST320 2-channel thermocouple module with Modbus RTU?
Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.
Where is the official Teracom TST320 2-channel thermocouple module with Modbus RTU Modbus documentation?
The source is TST320 User manual (Revision R1.6), revision 2026-10, published free by Teracom at https://www.teracomsystems.com/download/tst320-2-channel-thermocouple-module-with-modbus-rtu-interface-tst320/.
More Teracom Modbus register maps
- Sensor (temperature / humidity data logger)
Teracom TCW210-TH temperature and humidity data logger
TCW210-TH per the Teracom TCW210-TH user manual Revision R1.26, firmware V2.012 or later.
Also known as: TCW210-TH, TCW210 - Sensor (Ethernet data logger / I/O module)
Teracom TCW220 Ethernet data logger
TCW220 per the Teracom TCW220 user manual Revision R4.24, firmware V2.012 or later.
Also known as: TCW220 - Sensor (Ethernet I/O module)
Teracom TCW241 Ethernet I/O module
TCW241 per the Teracom TCW241 user manual Revision R4.30, firmware v2.012 or later.
Also known as: TCW241 - Energy meter (Ethernet energy monitoring / data logger)
Teracom TCW260 Ethernet energy monitoring module
TCW260 per the Teracom TCW260 user manual Revision R1.19, firmware V3.009 or later.
Also known as: TCW260 - Sensor (Ethernet analog / digital output module)
Teracom TCW280 Ethernet analog output module
TCW280 per the Teracom TCW280 user manual TCW280_R1.8.
Also known as: TCW280 - Sensor (1-Wire to Modbus gateway)
Teracom TCW320x-WMG 1-Wire to Modbus gateway
TCW320E-WMG (Ethernet) and TCW320W-WMG (Wi-Fi) per the user manual Revision R1.0; both share one fixed register map.
Also known as: TCW320E-WMG, TCW320W-WMG - Energy meter (S0 pulse counter / digital input module)
Teracom TDI340 4-channel S0 pulse counter with Modbus RTU
TDI340 per the Teracom TDI340 user manual Revision R1.11, firmware V1.06 or later.
Also known as: TDI340 - Sensor (relay output module)
Teracom TDO340 4-channel Modbus RTU relay output module
TDO340 per the Teracom TDO340 user manual Revision R1.2, firmware V1.03 or later.
Also known as: TDO340 - Sensor (water leak detector)
Teracom TSF400-4 water-leak detector with Modbus RTU
TSF400-4 per the Teracom TSF400-4 user manual Revision R1.2.
Also known as: TSF400-4 - Sensor (humidity / temperature)
Teracom TSH300v3 RS-485 humidity and temperature sensor
TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.
Also known as: TSH300, TSH300v3 - Sensor (humidity / temperature)
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor
TSH331 per the Teracom TSH331 user manual Rev. 1.5, firmware v1.08 or later.
Also known as: TSH331 - Sensor (CO2 / pressure)
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
TSM400-4-CP per the Teracom TSM400-4-CP user manual TSM400-4-CP-R1.9.
Also known as: TSM400-4-CP - Sensor (CO2 / humidity / temperature / pressure)
Teracom TSM400-4-CPTH Modbus CO2, humidity, temperature and pressure multi-sensor
TSM400-4-CPTH per the Teracom TSM400-4-CPTH user manual TSM400-4-CPTH-R1.9.
Also known as: TSM400-4-CPTH - Sensor (humidity / temperature)
Teracom TSM400-4-TH Modbus humidity and temperature sensor
TSM400-4-TH per the Teracom TSM400-4-TH user manual TSM400-4-TH-R1.10.
Also known as: TSM400-4-TH - Sensor (temperature)
Teracom TST300v3 / TST300v4 RS-485 precision temperature sensor
TST300v3/v4 per the Teracom TST300v3/v4 user manual Revision R1.19.
Also known as: TST300, TST300v3, TST300v4 - Sensor (AC/DC voltage transducer)
Teracom TSV300 AC/DC voltage transducer with Modbus RTU
TSV300 per the Teracom TSV300 user manual Revision R1.4, firmware V1.06 or later.
Also known as: TSV300
Other remote i/o modules register maps
- Sensor (Ethernet analog input module)
Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP)
BusWorks XT1211-000 (current) and XT1221-000 (voltage) per user's manual 8500951K.
Also known as: XT1211-000, XT1221-000, XT1211, XT1221, BusWorks XT1211, BusWorks XT1221 - Sensor / remote digital I/O module
ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)
tM-P4C4 (4 DI + 4 DO), tM-C8 (8 DO) and tM-P8 (8 DI) with the Modbus RTU protocol selected, per the tM Series DIO User Manual Rev A1.4.
Also known as: tM-P4C4, tM-C8, tM-P8 - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS52 resistance input module
Unipi Extension xS52 RS-485 module per the Unipi Extension xS52 Modbus map v2.0.
Also known as: Unipi Extension xS52, xS52 - Sensor / remote I/O module
Brainboxes ED-588 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-588 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-588, ED588
All remote i/o modules Modbus register maps →
Source: TST320 User manual · Revision R1.6 · rev. 2026-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.