Sensor (thermocouple input module) · Modbus register map

Teracom TST320 2-channel thermocouple module with Modbus RTU Modbus register map

Updated 19 November 2026

Short answer

The TST320 is a DIN-rail Teracom module that reads two thermocouples (J, K, T, N, E, B, R, S) and serves them over Modbus RTU RS-485. It gives current, minimum and maximum temperatures in °C and °F as floats and scaled integers, with per-channel type, multiplier and offset.

This page lists 50 Modbus registers for the Teracom TST320 2-channel thermocouple module with Modbus RTU — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teracom’s own free documentation (linked below) and checked against it.

Manufacturer
Teracom
Model
TST320 2-channel thermocouple module with Modbus RTU
Equipment type
Sensor (thermocouple input module)
Registers
50 (11 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
TST320
Source document
TST320 User manual · Revision R1.6 · rev. 2026-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Teracom TST320 2-channel thermocouple module with Modbus RTU

Integration in brief

Set each channel's thermocouple type (PDU 2100 / 2110), then read the floats at PDU 100-103 or the x10 integers at PDU 400-401 with function 03.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100TC1 temperature °CFLOAT32 ABCDTC1 temperature °CRead
HR 102TC2 temperature °CFLOAT32 ABCDTC2 temperature °CRead
HR 400TC1 temperature °C x 10INT16TC1 °C x10Read
HR 401TC2 temperature °C x 10INT16TC2 °C x10Read
HR 2100TC1 typeUINT16TC1 typeRead/write
HR 2110TC2 typeUINT16TC2 typeRead/write

Enable Modbus control & writes

Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.

Byte order & addressing

Network setup

Teracom TST320 2-channel thermocouple module with Modbus RTU Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

50 of 50 shown
Teracom TST320 2-channel thermocouple module with Modbus RTU Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR10doc 40011RS-485 addressModbus slave address of the device.UINT16Read/write
HR11doc 40012Baud rateSerial baud rate; takes effect after a power cycle.UINT16Read/write
HR12doc 40013Parity, data, stop bitsParity/data/stop framing; takes effect after a power cycle.UINT16Read/write1 = 8 data bits, even parity, 1 stop (E81); 2 = 8 data bits, odd parity, 1 stop (O81); 3 = 8 data bits, no parity, 1 stop (N81)
HR13doc 40014Data orderWord order used for all 32-bit values.UINT16Read/write1 = MSWF - most significant word first; 2 = LSWF - least significant word first
HR14doc 40015Device codeFixed product identification code.UINT16Read
HR15doc 40016FW versionFirmware version number.UINT16Read
HR18doc 40019Vendor URLMaker URL as UTF-8 text (64 bytes).STRING[64]Read
HR86doc 40087Signed integer test valueINT16Read
HR91doc 40092Unsigned integer test valueUINT16Read
HR100doc 40101TC1 temperature °CFLOAT32ABCD°CRead
HR102doc 40103TC2 temperature °CFLOAT32ABCD°CRead
HR120doc 40121TC1 min. temperature °CFLOAT32ABCD°CRead
HR122doc 40123TC2 min. temperature °CFLOAT32ABCD°CRead
HR140doc 40141TC1 max. temperature °CFLOAT32ABCD°CRead
HR142doc 40143TC2 max. temperature °CFLOAT32ABCD°CRead
HR200doc 40201TC1 temperature °FFLOAT32ABCD°FRead
HR202doc 40203TC2 temperature °FFLOAT32ABCD°FRead
HR220doc 40221TC1 min. temperature °FFLOAT32ABCD°FRead
HR222doc 40223TC2 min. temperature °FFLOAT32ABCD°FRead
HR240doc 40241TC1 max. temperature °FFLOAT32ABCD°FRead
HR242doc 40243TC2 max. temperature °FFLOAT32ABCD°FRead
HR400doc 40401TC1 temperature °C x 10INT16× 0.1°CRead
HR401doc 40402TC2 temperature °C x 10INT16× 0.1°CRead
HR420doc 40421TC1 min. temperature °C x 10INT16× 0.1°CRead
HR421doc 40422TC2 min. temperature °C x 10INT16× 0.1°CRead
HR440doc 40441TC1 max. temperature °C x 10INT16× 0.1°CRead
HR441doc 40442TC2 max. temperature °C x 10INT16× 0.1°CRead
HR500doc 40501TC1 temperature °F x 10INT16× 0.1°FRead
HR501doc 40502TC2 temperature °F x 10INT16× 0.1°FRead
HR520doc 40521TC1 min. temperature °F x 10INT16× 0.1°FRead
HR521doc 40522TC2 min. temperature °F x 10INT16× 0.1°FRead
HR540doc 40541TC1 max. temperature °F x 10INT16× 0.1°FRead
HR541doc 40542TC2 max. temperature °F x 10INT16× 0.1°FRead
HR620doc 40621TC1 min. temperature °C x 100INT32ABCD× 0.01°CRead
HR622doc 40623TC2 min. temperature °C x 100INT32ABCD× 0.01°CRead
HR640doc 40641TC1 max. temperature °C x 100INT32ABCD× 0.01°CRead
HR642doc 40643TC2 max. temperature °C x 100INT32ABCD× 0.01°CRead
HR700doc 40701TC1 temperature °F x 100INT32ABCD× 0.01°FRead
HR702doc 40703TC2 temperature °F x 100INT32ABCD× 0.01°FRead
HR720doc 40721TC1 min. temperature °F x 100INT32ABCD× 0.01°FRead
HR722doc 40723TC2 min. temperature °F x 100INT32ABCD× 0.01°FRead
HR740doc 40741TC1 max. temperature °F x 100INT32ABCD× 0.01°FRead
HR742doc 40743TC2 max. temperature °F x 100INT32ABCD× 0.01°FRead
HR1000doc 41001Reset min and max valuesWrite to clear the stored min/max values.UINT16Read/write
HR2100doc 42101TC1 typeUINT16Read/write0 = J type; 1 = K type; 2 = T type; 3 = N type; 4 = E type; 5 = B type; 6 = R type; 7 = S type
HR2101doc 42102TC1 multiplierFLOAT32ABCDRead/write
HR2103doc 42104TC1 offsetFLOAT32ABCDRead/write
HR2110doc 42111TC2 typeUINT16Read/write0 = J type; 1 = K type; 2 = T type; 3 = N type; 4 = E type; 5 = B type; 6 = R type; 7 = S type
HR2111doc 42112TC2 multiplierFLOAT32ABCDRead/write
HR2113doc 42114TC2 offsetFLOAT32ABCDRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Teracom TST320 2-channel thermocouple module with Modbus RTU

What Modbus registers does the Teracom TST320 2-channel thermocouple module with Modbus RTU have?

This map lists 50 registers: 50 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Teracom TST320 2-channel thermocouple module with Modbus RTU Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table prints both a PDU (wire) address and a logical address (PDU + 40001 for holding registers). 'documented' holds the logical number; the PDU number is what goes in the request, e.g. logical 40101 = PDU 100.

What byte order does the Teracom TST320 2-channel thermocouple module with Modbus RTU use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Teracom TST320 2-channel thermocouple module with Modbus RTU?

Start with HR 100 TC1 temperature °C (TC1 temperature °C); HR 102 TC2 temperature °C (TC2 temperature °C); HR 400 TC1 temperature °C x 10 (TC1 °C x10); HR 401 TC2 temperature °C x 10 (TC2 °C x10); HR 2100 TC1 type (TC1 type); HR 2110 TC2 type (TC2 type).

How do I enable Modbus control of the Teracom TST320 2-channel thermocouple module with Modbus RTU?

Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.

Where is the official Teracom TST320 2-channel thermocouple module with Modbus RTU Modbus documentation?

The source is TST320 User manual (Revision R1.6), revision 2026-10, published free by Teracom at https://www.teracomsystems.com/download/tst320-2-channel-thermocouple-module-with-modbus-rtu-interface-tst320/.

More Teracom Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: TST320 User manual · Revision R1.6 · rev. 2026-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.