Yokogawa UTAdvanced UM33A digital indicator with alarms Modbus register map
Updated 17 November 2026
The UM33A is a single-input digital indicator with up to eight alarms in Yokogawa's UTAdvanced family. Its D registers map one-to-one onto Modbus holding registers. This map covers the process monitoring block: PV, input and A/D error flags, alarm and alarm-output states, latch states and parameter/option error words.
This page lists 12 Modbus registers for the Yokogawa UTAdvanced UM33A digital indicator with alarms — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yokogawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yokogawa
- Model
- UTAdvanced UM33A digital indicator with alarms
- Equipment type
- Sensor (digital indicator with alarms)
- Registers
- 12 (0 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- UM33A
Integration notes: Yokogawa UTAdvanced UM33A digital indicator with alarms
Use the factory Modbus RTU setting, then read D2001-D2003 for errors and PV and D2011/D2037 for alarm and relay states.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2002 | PV_L1 measured value | INT16 | PV (D2003) | Read |
| HR 2001 | PV1.E_L1 PV input error status | BITMAP16 | PV input error flags (D2002) | Read |
| HR 2010 | ALM_L1 alarm 1-8 status | BITMAP16 | Alarm status (D2011) | Read |
| HR 2036 | ALO_L1 alarm output 1-8 status | BITMAP16 | Alarm output status (D2037) | Read |
Enable Modbus control & writes
Set the communication setup parameters PSL, BPS, PRI, STP, DLN and ADR on the keypad (factory protocol is Modbus RTU).
Byte order & addressing
- Wire address = D number - 1 (D2003 = 07D2H).
Network setup
- Factory defaults: Modbus RTU, 19200 bps, even parity, 1 stop bit, 8 data bits, address 1.
Watch out for
- Reading undefined (blank) D registers is not allowed and can upset the unit.
Yokogawa UTAdvanced UM33A digital indicator with alarms Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2000doc D2001 | AD1.E A/D converter error status | BITMAP16 | Read | bit 0 = PV input A/D converter error; bit 5 = PV input RJC error; bit 8 = PV input burnout error | ||||
| HR | 2001doc D2002 | PV1.E_L1 PV input error status | BITMAP16 | Read | bit 0 = PV input burnout; bit 4 = PV over-scale; bit 5 = PV under-scale | ||||
| HR | 2002doc D2003 | PV_L1 measured value | -5 to 105 % of input range, engineering value without decimal point. | INT16 | Read | ||||
| HR | 2010doc D2011 | ALM_L1 alarm 1-8 status | BITMAP16 | Read | bit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON; bit 5 = Alarm 5 ON; bit 6 = Alarm 6 ON; bit 8 = Alarm 7 ON; bit 9 = Alarm 8 ON | ||||
| HR | 2036doc D2037 | ALO_L1 alarm output 1-8 status | BITMAP16 | Read | bit 0 = Alarm output 1 contact closed; bit 1 = Alarm output 2 contact closed; bit 2 = Alarm output 3 contact closed; bit 4 = Alarm output 4 contact closed; bit 5 = Alarm output 5 contact closed; bit 6 = Alarm output 6 contact closed; bit 8 = Alarm output 7 contact closed; bit 9 = Alarm output 8 contact closed | ||||
| HR | 2065doc D2066 | DIMG message display status | BITMAP16 | Read | bit 0 = Message 1 displayed; bit 1 = Message 2 displayed; bit 2 = Message 3 displayed; bit 4 = Message 4 displayed | ||||
| HR | 2067doc D2068 | PA.ER parameter error status | BITMAP16 | Read | bit 0 = System data error; bit 1 = Calibration value error; bit 2 = User default value error; bit 4 = Setup parameter error; bit 5 = Operation parameter error; bit 8 = Faulty FRAM; bit 10 = Control parameter error | ||||
| HR | 2069doc D2070 | OP.ER option error status | BITMAP16 | Read | bit 0 = E1 terminal hardware not responding; bit 8 = E1 communication error | ||||
| HR | 2070doc D2071 | ALOLA1_L1 alarm latch-1 output status | BITMAP16 | Read | bit 0 = Alarm 1 latch-1; bit 1 = Alarm 2 latch-1; bit 2 = Alarm 3 latch-1; bit 4 = Alarm 4 latch-1; bit 5 = Alarm 5 latch-1; bit 6 = Alarm 6 latch-1; bit 8 = Alarm 7 latch-1; bit 9 = Alarm 8 latch-1 | ||||
| HR | 2072doc D2073 | ALOLA2_L1 alarm latch-2 output status | BITMAP16 | Read | bit 0 = Alarm 1 latch-2; bit 1 = Alarm 2 latch-2; bit 2 = Alarm 3 latch-2; bit 4 = Alarm 4 latch-2; bit 5 = Alarm 5 latch-2; bit 6 = Alarm 6 latch-2; bit 8 = Alarm 7 latch-2; bit 9 = Alarm 8 latch-2 | ||||
| HR | 2074doc D2075 | ALOLA3_L1 alarm latch-3 output status | BITMAP16 | Read | bit 0 = Alarm 1 latch-3; bit 1 = Alarm 2 latch-3; bit 2 = Alarm 3 latch-3; bit 4 = Alarm 4 latch-3; bit 5 = Alarm 5 latch-3; bit 6 = Alarm 6 latch-3; bit 8 = Alarm 7 latch-3; bit 9 = Alarm 8 latch-3 | ||||
| HR | 2076doc D2077 | ALOLA4_L1 alarm latch-4 output status | BITMAP16 | Read | bit 0 = Alarm 1 latch-4; bit 1 = Alarm 2 latch-4; bit 2 = Alarm 3 latch-4; bit 4 = Alarm 4 latch-4; bit 5 = Alarm 5 latch-4; bit 6 = Alarm 6 latch-4; bit 8 = Alarm 7 latch-4; bit 9 = Alarm 8 latch-4 |
Notes on this map
- All registers are 16-bit and read-only in this block (D2001-D2100).
- PV is sent without its decimal point; the position follows the input's decimal point setting.
- Alarm setpoints and setup parameters (D2501 onward) are not included in this map.
- Bits 3 and 7 are unused in the 8-alarm words; alarms 4 and 7 sit on bits 4 and 8.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yokogawa UTAdvanced UM33A digital indicator with alarms
What Modbus registers does the Yokogawa UTAdvanced UM33A digital indicator with alarms have?
This map lists 12 registers: 12 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yokogawa UTAdvanced UM33A digital indicator with alarms Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists D register numbers; the Modbus reference is the D number with D replaced by 4 (D2003 = 42003) and the wire address is that minus 40001, as printed in the H No. column (07D2H).
What are the minimum Modbus registers to integrate the Yokogawa UTAdvanced UM33A digital indicator with alarms?
Start with HR 2002 PV_L1 measured value (PV (D2003)); HR 2001 PV1.E_L1 PV input error status (PV input error flags (D2002)); HR 2010 ALM_L1 alarm 1-8 status (Alarm status (D2011)); HR 2036 ALO_L1 alarm output 1-8 status (Alarm output status (D2037)).
How do I enable Modbus control of the Yokogawa UTAdvanced UM33A digital indicator with alarms?
Set the communication setup parameters PSL, BPS, PRI, STP, DLN and ADR on the keypad (factory protocol is Modbus RTU).
Where is the official Yokogawa UTAdvanced UM33A digital indicator with alarms Modbus documentation?
The source is UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual (IM 05P07A01-01EN 13th Edition), revision 2026-03, published free by Yokogawa at https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf.
More Yokogawa Modbus register maps
- Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A - Sensor (program temperature controller)
Yokogawa UTAdvanced UP55A program controller
Yokogawa UP55A program controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A column).
Also known as: UP55A - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
Yokogawa UT35A and UT32A single-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UT32A-D loop 2 and UP35A/UP32A program items excluded).
Also known as: UT35A, UT32A, UT35A/MDL, UT32A/MDL - Sensor (limit controller)
Yokogawa UTAdvanced UT35A-L limit controller
Yokogawa UT35A-L limit controllers with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 12.
Also known as: UT35A-L - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT55A / UT52A digital indicating controller
Yokogawa UT55A and UT52A one- or two-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A program items excluded).
Also known as: UT55A, UT52A - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT75A digital indicating controller
Yokogawa UT75A one- or two-loop controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 14.
Also known as: UT75A
Other valves, actuators & sensors register maps
- Actuator / valve (pressure-independent characterised control valve)
Belimo 2-way EPIV DN 15-50 (Version 4.2) Modbus RTU
Belimo 2-way EPIV DN 15-50 Version 4 (EP..R2+(K)BAC) on Modbus RTU, per interface description edition 2025-09 / V4.2.
Also known as: EP..R2+BAC, EP..R2+KBAC, Electronic pressure-independent valve - Sensor (water analysis transmitter)
Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP)
Liquiline CM44x with the Modbus RS485 or Modbus TCP option, software 1.11.00 and later (SD01189C/07/EN/07.22). The CSFxx sampler and CA80xx analyzer blocks of the same guide are not included.
Also known as: CM442, CM444, CM448, CM44P, CM44R, Liquiline CM442, Liquiline CM444, Liquiline CM448 - Sensor (pressure transmitter)
KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)
KELLER X-Line transmitters with RS-485, Class.Group firmware 5.20-10.40 or later, 5.21 and 5.24 (protocol document version 3.7).
Also known as: Series 30X, Series 33X, Series 35X, Series 36X, Series 46X, PAA-33X, PR-33X, PA-36XW, Class.Group 5.20, Class.Group 5.21, Class.Group 5.24 - Sensor (leak detection controller)
RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave)
RLE LD5200 distance-read leak detection controller, user guide version 04.22 (firmware 2.3.1).
Also known as: LD5200 - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (flame detector)
Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU)
Teledyne Spyglass SG50-F optical flame detectors (IR3, UV-IR, IR3-H2 and HD video variants) with RS-485 Modbus RTU, communication manual SG50FMODBUS-EN rev 1.0.
Also known as: SG50-F, Spyglass SG50-F, IR3-HD, UV-IR, IR3, UV-IR-HD, IR3-H2-HD, IR3-H2, UV-IR-F, UV-IR-F-HD
All valves, actuators & sensors Modbus register maps →
Source: UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.