Sensor (digital indicator with alarms) · Modbus register map

Yokogawa UTAdvanced UM33A digital indicator with alarms Modbus register map

Updated 17 November 2026

Short answer

The UM33A is a single-input digital indicator with up to eight alarms in Yokogawa's UTAdvanced family. Its D registers map one-to-one onto Modbus holding registers. This map covers the process monitoring block: PV, input and A/D error flags, alarm and alarm-output states, latch states and parameter/option error words.

This page lists 12 Modbus registers for the Yokogawa UTAdvanced UM33A digital indicator with alarms — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yokogawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yokogawa
Model
UTAdvanced UM33A digital indicator with alarms
Equipment type
Sensor (digital indicator with alarms)
Registers
12 (0 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
UM33A
Source document
UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yokogawa UTAdvanced UM33A digital indicator with alarms

Integration in brief

Use the factory Modbus RTU setting, then read D2001-D2003 for errors and PV and D2011/D2037 for alarm and relay states.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2002PV_L1 measured valueINT16PV (D2003)Read
HR 2001PV1.E_L1 PV input error statusBITMAP16PV input error flags (D2002)Read
HR 2010ALM_L1 alarm 1-8 statusBITMAP16Alarm status (D2011)Read
HR 2036ALO_L1 alarm output 1-8 statusBITMAP16Alarm output status (D2037)Read

Enable Modbus control & writes

Set the communication setup parameters PSL, BPS, PRI, STP, DLN and ADR on the keypad (factory protocol is Modbus RTU).

Byte order & addressing

Network setup

Watch out for

Yokogawa UTAdvanced UM33A digital indicator with alarms Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

12 of 12 shown
Yokogawa UTAdvanced UM33A digital indicator with alarms Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2000doc D2001AD1.E A/D converter error statusBITMAP16Readbit 0 = PV input A/D converter error; bit 5 = PV input RJC error; bit 8 = PV input burnout error
HR2001doc D2002PV1.E_L1 PV input error statusBITMAP16Readbit 0 = PV input burnout; bit 4 = PV over-scale; bit 5 = PV under-scale
HR2002doc D2003PV_L1 measured value-5 to 105 % of input range, engineering value without decimal point.INT16Read
HR2010doc D2011ALM_L1 alarm 1-8 statusBITMAP16Readbit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON; bit 5 = Alarm 5 ON; bit 6 = Alarm 6 ON; bit 8 = Alarm 7 ON; bit 9 = Alarm 8 ON
HR2036doc D2037ALO_L1 alarm output 1-8 statusBITMAP16Readbit 0 = Alarm output 1 contact closed; bit 1 = Alarm output 2 contact closed; bit 2 = Alarm output 3 contact closed; bit 4 = Alarm output 4 contact closed; bit 5 = Alarm output 5 contact closed; bit 6 = Alarm output 6 contact closed; bit 8 = Alarm output 7 contact closed; bit 9 = Alarm output 8 contact closed
HR2065doc D2066DIMG message display statusBITMAP16Readbit 0 = Message 1 displayed; bit 1 = Message 2 displayed; bit 2 = Message 3 displayed; bit 4 = Message 4 displayed
HR2067doc D2068PA.ER parameter error statusBITMAP16Readbit 0 = System data error; bit 1 = Calibration value error; bit 2 = User default value error; bit 4 = Setup parameter error; bit 5 = Operation parameter error; bit 8 = Faulty FRAM; bit 10 = Control parameter error
HR2069doc D2070OP.ER option error statusBITMAP16Readbit 0 = E1 terminal hardware not responding; bit 8 = E1 communication error
HR2070doc D2071ALOLA1_L1 alarm latch-1 output statusBITMAP16Readbit 0 = Alarm 1 latch-1; bit 1 = Alarm 2 latch-1; bit 2 = Alarm 3 latch-1; bit 4 = Alarm 4 latch-1; bit 5 = Alarm 5 latch-1; bit 6 = Alarm 6 latch-1; bit 8 = Alarm 7 latch-1; bit 9 = Alarm 8 latch-1
HR2072doc D2073ALOLA2_L1 alarm latch-2 output statusBITMAP16Readbit 0 = Alarm 1 latch-2; bit 1 = Alarm 2 latch-2; bit 2 = Alarm 3 latch-2; bit 4 = Alarm 4 latch-2; bit 5 = Alarm 5 latch-2; bit 6 = Alarm 6 latch-2; bit 8 = Alarm 7 latch-2; bit 9 = Alarm 8 latch-2
HR2074doc D2075ALOLA3_L1 alarm latch-3 output statusBITMAP16Readbit 0 = Alarm 1 latch-3; bit 1 = Alarm 2 latch-3; bit 2 = Alarm 3 latch-3; bit 4 = Alarm 4 latch-3; bit 5 = Alarm 5 latch-3; bit 6 = Alarm 6 latch-3; bit 8 = Alarm 7 latch-3; bit 9 = Alarm 8 latch-3
HR2076doc D2077ALOLA4_L1 alarm latch-4 output statusBITMAP16Readbit 0 = Alarm 1 latch-4; bit 1 = Alarm 2 latch-4; bit 2 = Alarm 3 latch-4; bit 4 = Alarm 4 latch-4; bit 5 = Alarm 5 latch-4; bit 6 = Alarm 6 latch-4; bit 8 = Alarm 7 latch-4; bit 9 = Alarm 8 latch-4

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yokogawa UTAdvanced UM33A digital indicator with alarms

What Modbus registers does the Yokogawa UTAdvanced UM33A digital indicator with alarms have?

This map lists 12 registers: 12 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yokogawa UTAdvanced UM33A digital indicator with alarms Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists D register numbers; the Modbus reference is the D number with D replaced by 4 (D2003 = 42003) and the wire address is that minus 40001, as printed in the H No. column (07D2H).

What are the minimum Modbus registers to integrate the Yokogawa UTAdvanced UM33A digital indicator with alarms?

Start with HR 2002 PV_L1 measured value (PV (D2003)); HR 2001 PV1.E_L1 PV input error status (PV input error flags (D2002)); HR 2010 ALM_L1 alarm 1-8 status (Alarm status (D2011)); HR 2036 ALO_L1 alarm output 1-8 status (Alarm output status (D2037)).

How do I enable Modbus control of the Yokogawa UTAdvanced UM33A digital indicator with alarms?

Set the communication setup parameters PSL, BPS, PRI, STP, DLN and ADR on the keypad (factory protocol is Modbus RTU).

Where is the official Yokogawa UTAdvanced UM33A digital indicator with alarms Modbus documentation?

The source is UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual (IM 05P07A01-01EN 13th Edition), revision 2026-03, published free by Yokogawa at https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf.

More Yokogawa Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.