Sensor (water analysis transmitter) · Modbus register map
Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP) Modbus register map
Updated 17 November 2026
The Liquiline CM44x is Endress+Hauser's multichannel transmitter for Memosens pH, ORP, conductivity, oxygen, turbidity and similar sensors. With the Modbus option it exposes 16 configurable analog and 8 digital device variables, 4 analog and 8 digital write-back variables, diagnostics and per-sensor information blocks. This map covers those common blocks, with the sensor block shown for sensor 1.
This page lists 221 Modbus registers for the Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP) — 28 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Endress+Hauser’s own free documentation (linked below) and checked against it.
- Manufacturer
- Endress+Hauser
- Model
- Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP)
- Equipment type
- Sensor (water analysis transmitter)
- Registers
- 221 (28 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- 247
- Default serial
- 19200 baud, 8E1
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- Software 1.11.00 and later
- Also known as
- CM442, CM444, CM448, CM44P, CM44R, Liquiline CM442, Liquiline CM444, Liquiline CM448
Integration notes: Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP)
Assign the measured values you need to AI 1-16 in the transmitter menu, then read registers 0-63 (value, status, unit for each AI) with function 03 or 04 and decode floats as CDAB. Check each status byte is 0 before using the value.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | MODBUS_AI_1_VALUE | FLOAT32 CDAB | AI 1 value (e.g. main measured value) | Read |
| HR 2 | MODBUS_AI_1_STATUS | UINT16 | AI 1 status | Read |
| HR 3 | MODBUS_AI_1_UNIT | UINT16 | AI 1 unit code | Read |
| HR 4 | MODBUS_AI_2_VALUE | FLOAT32 CDAB | AI 2 value (e.g. temperature) | Read |
| HR 6 | MODBUS_AI_2_STATUS | UINT16 | AI 2 status | Read |
| HR 112 | MODBUS_DI_1_VALUE | UINT16 | DI 1 value (e.g. limit contact) | Read |
Enable Modbus control & writes
Menu Setup/General settings/Extended setup/Modbus/Settings: bus address (default 247, or set by the module's address switch), RTU/ASCII, baud (default 19200), parity (default even, 1 stop bit), byte order and watchdog. For TCP set the IP under .../Ethernet/Settings (DHCP by default) and use port 502. Assign sources to the device variables under Setup/Outputs.
Communication loss & watchdog
Modbus watchdog default 5 s (0-999 s, 0 = off), set in the Modbus settings menu. If no valid request arrives in that time the device raises diagnostic S969 and lights the red BF LED until the next valid request.
Byte order & addressing
- Floats are CDAB at the factory byte order but 32-bit integers and strings are most-significant-byte first.
- A hardware address set on the module's address switch overrides the menu address.
Network setup
- RS-485 termination is set on the module; input register 941 reports whether it is on.
- The 485/ETH module has a service switch that forces IP 192.168.1.212/24 while it is on.
Watch out for
- Values written to AO/DO are ignored unless their status register is written as 0 (good) in the same transfer.
- Up to 125 registers per read and 120 per write.
Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 522 | MODBUS_FRAMING_ERRORS | UINT32 | ABCD | Read | ||||
| IR | 524 | MODBUS_CRC_ERRORS | UINT32 | ABCD | Read | ||||
| IR | 526 | MODBUS_PARITY_ERRORS | UINT32 | ABCD | Read | ||||
| IR | 528 | MODBUS_01_EXCEPTIONS | UINT32 | ABCD | Read | ||||
| IR | 530 | MODBUS_02_EXCEPTIONS | UINT32 | ABCD | Read | ||||
| IR | 532 | MODBUS_03_EXCEPTIONS | UINT32 | ABCD | Read | ||||
| IR | 534 | MODBUS_04_EXCEPTIONS | UINT32 | ABCD | Read | ||||
| IR | 536 | ETHERNET_RECEIVED_FRAMES | UINT32 | ABCD | Read | ||||
| IR | 538 | ETHERNET_SEND_FRAMES | UINT32 | ABCD | Read | ||||
| IR | 540 | ETHERNET_VALID_FRAMES | UINT32 | ABCD | Read | ||||
| IR | 542 | ETHERNET_INVALID_FRAMES | UINT32 | ABCD | Read | ||||
| IR | 544 | ETHERNET_CRC_ERRORS | UINT32 | ABCD | Read | ||||
| IR | 546 | DEVICE_SW_VERSION | 16 characters. | STRING[16] | Read | ||||
| IR | 554 | DEVICE_BOOTLOADER_VERSION | 16 characters. | STRING[16] | Read | ||||
| IR | 562 | DEVICE_SERIAL | 32 characters. | STRING[32] | Read | ||||
| IR | 578 | DISPLAY_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 626 | BASE_MODUL_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 642 | EXTENSION_MODUL_1_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 658 | EXTENSION_MODUL_2_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 674 | EXTENSION_MODUL_3_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 738 | EXTENSION_MODUL_7_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 754 | EXTENSION_MODUL_8_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 770 | SENSOR_1_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 786 | SENSOR_2_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 802 | SENSOR_3_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 818 | SENSOR_4_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 834 | SENSOR_5_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 850 | SENSOR_6_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 866 | SENSOR_7_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 882 | SENSOR_8_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 898 | FMSY1_MODUL_SER_NUM | 32 characters. | STRING[32] | Read | ||||
| IR | 941 | RS485_TERMINATION_STATE | 8-bit value in one register. | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 942 | ETHERNET_MAC | 6 characters. | STRING[6] | Read | ||||
| IR | 945 | CLEANINGACTIONSTATE_1 | 8-bit value in one register. | UINT16 | Read | 0 = Off; 1 = Waiting; 2 = Waiting; 3 = Pre-rinse; 4 = Cleaning; 5 = Postrinsing; 6 = Failsafe; 7 = Manual mode; 8 = Waiting for execution | |||
| IR | 946 | CLEANINGACTIONSTATE_2 | 8-bit value in one register. | UINT16 | Read | 0 = Off; 1 = Waiting; 2 = Waiting; 3 = Pre-rinse; 4 = Cleaning; 5 = Postrinsing; 6 = Failsafe; 7 = Manual mode; 8 = Waiting for execution | |||
| IR | 947 | CLEANINGACTIONSTATE_3 | 8-bit value in one register. | UINT16 | Read | 0 = Off; 1 = Waiting; 2 = Waiting; 3 = Pre-rinse; 4 = Cleaning; 5 = Postrinsing; 6 = Failsafe; 7 = Manual mode; 8 = Waiting for execution | |||
| IR | 948 | CLEANINGACTIONSTATE_4 | 8-bit value in one register. | UINT16 | Read | 0 = Off; 1 = Waiting; 2 = Waiting; 3 = Pre-rinse; 4 = Cleaning; 5 = Postrinsing; 6 = Failsafe; 7 = Manual mode; 8 = Waiting for execution | |||
| IR | 953 | HEARTBEAT_DEVICE_STATUS | FLOAT32 | CDAB | Read | ||||
| IR | 955 | HEARTBEAT_DEVICE_HEALTH_CONDITION | FLOAT32 | CDAB | % | Read | |||
| IR | 957 | MAINTENANCE_TIMER_VALUE | FLOAT32 | CDAB | Read | ||||
| IR | 959 | HEARTBEAT_INDEX_DEVICE | FLOAT32 | CDAB | Read | ||||
| IR | 965 | KEY_PERF_INDICATOR_DEVICE_AVAILABILITY | FLOAT32 | CDAB | % | Read | |||
| IR | 975 | KEY_PERF_INDICATOR_DEVICE_NUMBER_OF_FAILURES | UINT16 | Read | |||||
| IR | 1019doc X019 (sensor 1) | SENSOR_SERIAL_CH0 | Sensor 1 block. 16 characters. | STRING[16] | Read | ||||
| IR | 1027doc X027 (sensor 1) | SENSOR_HW_VERSION_CH0 | Sensor 1 block. 16 characters. | STRING[16] | Read | ||||
| IR | 1035doc X035 (sensor 1) | SENSOR_SW_VERSION_CH0 | Sensor 1 block. 16 characters. | STRING[16] | Read | ||||
| IR | 1043doc X043 (sensor 1) | SENSOR_MANUFACTURER_CH0 | Sensor 1 block. 32 characters. | STRING[32] | Read | ||||
| IR | 1059doc X059 (sensor 1) | SENSOR_ORDERCODE_CH0 | Sensor 1 block. 32 characters. | STRING[32] | Read | ||||
| IR | 1083doc X083 (sensor 1) | SENSOR_EXTREME_SPECIFIC_MIN_CH0 | Sensor 1 block. | FLOAT32 | CDAB | Read | |||
| IR | 1085doc X085 (sensor 1) | SENSOR_EXTREME_TEMP_MIN_CH0 | Sensor 1 block. | FLOAT32 | CDAB | °C | Read | ||
| IR | 1087doc X087 (sensor 1) | SENSOR_EXTREME_SPECIFIC_MAX_CH0 | Sensor 1 block. | FLOAT32 | CDAB | Read | |||
| IR | 1089doc X089 (sensor 1) | SENSOR_EXTREME_TEMP_MAX_CH0 | Sensor 1 block. | FLOAT32 | CDAB | °C | Read | ||
| IR | 1091doc X091 (sensor 1) | SENSOR_CURRENT_DIAG_SOURCETYPE_CH0 | Sensor 1 block. 8-bit value in one register. | UINT16 | Read | 0 = General; 1 = Temperature Input; 2 = Binary Input; 3 = Binary Output; 4 = Current Input; 5 = Current Output; 6 = Relay; 7 = Memosens Sensor; 8 = PID Controller; 9 = Cleaning; 10 = Limit switch; 11 = Binary formula result; 12 = Binary Input Module; 13 = Binary Output Module; 14 = Sample point | |||
| IR | 1092doc X092 (sensor 1) | SENSOR_CURRENT_DIAG_MODUL_CH0 | Sensor 1 block. 8-bit value in one register. | UINT16 | Read | 0 = Slot 1; 1 = Slot 1; 2 = Slot 2; 3 = Slot 3; 4 = Slot 4; 5 = Slot 5; 6 = Slot 6; 7 = Slot 7; 8 = Sampler; 9 = Software; 10 = Analyzer | |||
| IR | 1093doc X093 (sensor 1) | SENSOR_CURRENT_DIAG_PORT_CH0 | Sensor 1 block. 8-bit value in one register. | UINT16 | Read | ||||
| IR | 1094doc X094 (sensor 1) | SENSOR_CURRENT_DIAG_NE107_STATUS_CH0 | Sensor 1 block. NAMUR NE 107 category bits. | BITMAP16 | Read | bit 0 = Failure (F); bit 1 = Function check (C); bit 2 = Maintenance required (M); bit 3 = Out of specification (S) | |||
| IR | 1095doc X095 (sensor 1) | SENSOR_CURRENT_DIAG_CODE_CH0 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 1096doc X096 (sensor 1) | SENSOR_CURRENT_DIAG_TIMESTAMP_CH0 | Sensor 1 block. | UINT32 | ABCD | Read | |||
| IR | 1098doc X098 (sensor 1) | SENSOR_NUMBER_ADDITIONAL_DIAG_CH0 | Sensor 1 block. 8-bit value in one register. | UINT16 | Read | ||||
| IR | 1099doc X099 (sensor 1) | SENSOR_PAST_DIAG_SOURCETYPE_CH0 | Sensor 1 block. 8-bit value in one register. | UINT16 | Read | 0 = General; 1 = Temperature Input; 2 = Binary Input; 3 = Binary Output; 4 = Current Input; 5 = Current Output; 6 = Relay; 7 = Memosens Sensor; 8 = PID Controller; 9 = Cleaning; 10 = Limit switch; 11 = Binary formula result; 12 = Binary Input Module; 13 = Binary Output Module; 14 = Sample preparation | |||
| IR | 1100doc X100 (sensor 1) | SENSOR_PAST_DIAG_MODUL_CH0 | Sensor 1 block. 8-bit value in one register. | UINT16 | Read | 0 = Slot 1; 1 = Slot 1; 2 = Slot 2; 3 = Slot 3; 4 = Slot 4; 5 = Slot 5; 6 = Slot 6; 7 = Slot 7; 8 = Sampler; 9 = Software; 10 = Analyzer | |||
| IR | 1101doc X101 (sensor 1) | SENSOR_PAST_DIAG_PORT_CH0 | Sensor 1 block. 8-bit value in one register. | UINT16 | Read | ||||
| IR | 1102doc X102 (sensor 1) | SENSOR_PAST_DIAG_NE107_STATUS_CH0 | Sensor 1 block. NAMUR NE 107 category bits. | BITMAP16 | Read | bit 0 = Failure (F); bit 1 = Function check (C); bit 2 = Maintenance required (M); bit 3 = Out of specification (S) | |||
| IR | 1103doc X103 (sensor 1) | SENSOR_PAST_DIAG_CODE_CH0 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 1104doc X104 (sensor 1) | SENSOR_PAST_DIAG_TIMESTAMP_CH0 | Sensor 1 block. | UINT32 | ABCD | Read | |||
| IR | 1106doc X106 (sensor 1) | OP_TIME_TOTAL_CH0 | Sensor 1 block. | FLOAT32 | CDAB | s | Read | ||
| IR | 1108doc X108 (sensor 1) | OP_TIME_ABOVE_SPEC_TEMP_CH0 | Sensor 1 block. | FLOAT32 | CDAB | s | Read | ||
| IR | 1110doc X110 (sensor 1) | OP_TIME_BELOW_SPEC_TEMP_CH0 | Sensor 1 block. | FLOAT32 | CDAB | s | Read | ||
| IR | 1112doc X112 (sensor 1) | OP_TIME_LAMP_LIFE_CH0 | Sensor 1 block. | FLOAT32 | CDAB | Read | |||
| IR | 1114doc X114 (sensor 1) | OP_TIME_STERILISATIONS_CH0 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 1115doc X115 (sensor 1) | OP_TIME_CIP_CYCLES_CH0 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 1116doc X116 (sensor 1) | OP_TIME_CAP_CALIBRATIONS_CH0 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 1117doc X117 (sensor 1) | OP_TIME_CAP_CALIB_TIMER_CH0 | Sensor 1 block. | FLOAT32 | CDAB | s | Read | ||
| IR | 1119doc X119 (sensor 1) | OP_TIME_CAP_STERILISATIONS_CH0 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 1120doc X120 (sensor 1) | OP_TIME_CAP_FILTER_CHANGED_CH0 | Sensor 1 block. | FLOAT32 | CDAB | s | Read | ||
| IR | 1122doc X122 (sensor 1) | CAL_COUNT_0_CH0 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 1123doc X123 (sensor 1) | CAL_COUNT_1_CH0 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 1124doc X124 (sensor 1) | CAL_COUNT_2_CH0 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 1125doc X125 (sensor 1) | CAL_COUNT_3_CH0 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 1142doc X142 (sensor 1) | CAL_METHOD_0_CH0 | Sensor 1 block. 8-bit value in one register. | UINT16 | Read | 0 = None; 1 = Numeric input; 2 = 1-point calibration; 3 = 2-point calibration; 4 = Multipoint Calibration; 5 = Table; 6 = Grab sample; 7 = Zero point; 8 = Air 100%% rh; 9 = H2O air-saturated; 10 = Air variable; 11 = Zero point sample; 12 = Slope sample; 13 = Offset; 14 = Slope; 15 = with temp. comp; 16 = without temp. comp; 17 = Standard addition; 18 = Numeric input; 19 = Numeric input zero point; 20 = Numeric input; 21 = Factory calib.; 22 = Test gas calibration; 23 = Value acquisition; 24 = 3-point calibration; 25 = Ext. Reference; 26 = Int. Reference; 27 = in water; 28 = in air | |||
| IR | 1143doc X143 (sensor 1) | CAL_METHOD_1_CH0 | Sensor 1 block. 8-bit value in one register. | UINT16 | Read | 0 = None; 1 = Numeric input; 2 = 1-point calibration; 3 = 2-point calibration; 4 = Multipoint Calibration; 5 = Table; 6 = Grab sample; 7 = Zero point; 8 = Air 100%% rh; 9 = H2O air-saturated; 10 = Air variable; 11 = Zero point sample; 12 = Slope sample; 13 = Offset; 14 = Slope; 15 = with temp. comp; 16 = without temp. comp; 17 = Standard addition; 18 = Numeric input; 19 = Numeric input zero point; 20 = Numeric input; 21 = Factory calib.; 22 = Test gas calibration; 23 = Value acquisition; 24 = 3-point calibration; 25 = Ext. Reference; 26 = Int. Reference; 27 = in water; 28 = in air | |||
| IR | 1144doc X144 (sensor 1) | CAL_METHOD_2_CH0 | Sensor 1 block. 8-bit value in one register. | UINT16 | Read | 0 = None; 1 = Numeric input; 2 = 1-point calibration; 3 = 2-point calibration; 4 = Multipoint Calibration; 5 = Table; 6 = Grab sample; 7 = Zero point; 8 = Air 100%% rh; 9 = H2O air-saturated; 10 = Air variable; 11 = Zero point sample; 12 = Slope sample; 13 = Offset; 14 = Slope; 15 = with temp. comp; 16 = without temp. comp; 17 = Standard addition; 18 = Numeric input; 19 = Numeric input zero point; 20 = Numeric input; 21 = Factory calib.; 22 = Test gas calibration; 23 = Value acquisition; 24 = 3-point calibration; 25 = Ext. Reference; 26 = Int. Reference; 27 = in water; 28 = in air | |||
| IR | 1145doc X145 (sensor 1) | CAL_METHOD_3_CH0 | Sensor 1 block. 8-bit value in one register. | UINT16 | Read | 0 = None; 1 = Numeric input; 2 = 1-point calibration; 3 = 2-point calibration; 4 = Multipoint Calibration; 5 = Table; 6 = Grab sample; 7 = Zero point; 8 = Air 100%% rh; 9 = H2O air-saturated; 10 = Air variable; 11 = Zero point sample; 12 = Slope sample; 13 = Offset; 14 = Slope; 15 = with temp. comp; 16 = without temp. comp; 17 = Standard addition; 18 = Numeric input; 19 = Numeric input zero point; 20 = Numeric input; 21 = Factory calib.; 22 = Test gas calibration; 23 = Value acquisition; 24 = 3-point calibration; 25 = Ext. Reference; 26 = Int. Reference; 27 = in water; 28 = in air | |||
| IR | 1146doc X146 (sensor 1) | CAL_COUNT_ZERO_CH0 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 1151doc X151 (sensor 1) | CAL_METHOD_ZERO_CH0 | Sensor 1 block. 8-bit value in one register. | UINT16 | Read | 0 = None; 1 = Numeric input; 2 = 1-point calibration; 3 = 2-point calibration; 4 = Multipoint Calibration; 5 = Table; 6 = Grab sample; 7 = Zero point; 8 = Air 100%% rh; 9 = H2O air-saturated; 10 = Air variable; 11 = Zero point sample; 12 = Slope sample; 13 = Offset; 14 = Slope; 15 = with temp. comp; 16 = without temp. comp; 17 = Standard addition; 18 = Numeric input; 19 = Numeric input zero point; 20 = Numeric input 2-point; 21 = Factory calib.; 22 = Test gas calibration; 23 = Value acquisition; 24 = 3-point calibration; 25 = Ext. Reference; 26 = Int. Reference; 27 = in water; 28 = in air | |||
| IR | 1152doc X152 (sensor 1) | CAL_COUNT_TEMP_CH0 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 1157doc X157 (sensor 1) | CAL_METHOD_TEMP_CH0 | Sensor 1 block. 8-bit value in one register. | UINT16 | Read | 0 = None; 1 = Numeric input; 2 = 1-point calibration; 3 = 2-point calibration; 4 = Multipoint Calibration; 5 = Table; 6 = Grab sample; 7 = Zero point; 8 = Air 100%% rh; 9 = H2O air-saturated; 10 = Air variable; 11 = Zero point sample; 12 = Slope sample; 13 = Offset; 14 = Slope; 15 = with temp. comp; 16 = without temp. comp; 17 = Standard addition; 18 = Numeric input; 19 = Numeric input zero point; 20 = Numeric input; 21 = Factory calib.; 22 = Test gas calibration; 23 = Value acquisition; 24 = 3-point calibration; 25 = Ext. Reference; 26 = Int. Reference; 27 = in water; 28 = in air | |||
| IR | 1158doc X158 (sensor 1) | HEARTBEAT_SENSOR_STATUS_CH0 | Sensor 1 block. | FLOAT32 | CDAB | % | Read | ||
| IR | 1160doc X160 (sensor 1) | HEARTBEAT_SENSOR_HEALTH_CONDITION_CH0 | Sensor 1 block. | FLOAT32 | CDAB | % | Read | ||
| IR | 1162doc X162 (sensor 1) | MAINTENANCE_TIMER_VALUE_CH0 | Sensor 1 block. | FLOAT32 | CDAB | % | Read | ||
| IR | 1164doc X164 (sensor 1) | HEARTBEAT_INDEX_SENSOR_CH0 | Sensor 1 block. | FLOAT32 | CDAB | % | Read | ||
| IR | 1166doc X166 (sensor 1) | KEY_PERF_INDICATOR_SENSOR_AVAILABILITY_CH1 | Sensor 1 block. | FLOAT32 | CDAB | % | Read | ||
| IR | 1176doc X176 (sensor 1) | KEY_PERF_INDICATOR_SENSOR_NUMBER_OF_FAILURES_CH1 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 1189doc X189 (sensor 1) | KEY_PERF_INDICATOR_SENSOR_NUMBER_OF_CALIBRATIONS_CH1 | Sensor 1 block. | UINT16 | Read | ||||
| IR | 9000 | BUS_ADDRESS | 8-bit value in one register. | UINT16 | Read | ||||
| IR | 9001 | DEVICE_TAG | 32 characters. | STRING[32] | Read | ||||
| IR | 9017 | DEVICE_ID | 8-bit value in one register. | UINT16 | Read | 0 = Liquiline CM442; 1 = Liquiline CM448; 2 = Liquiport CSP44; 3 = Liquistation CSF48; 4 = Liquistation CSF22; 5 = Liquistation CSF33; 6 = Liquiline System CA80; 7 = Liquistation CSF34; 8 = Liquistation CSF39; 9 = Liquiline CM44P | |||
| HR | 0 | MODBUS_AI_1_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 2 | MODBUS_AI_1_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 3 | MODBUS_AI_1_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 4 | MODBUS_AI_2_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 6 | MODBUS_AI_2_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 7 | MODBUS_AI_2_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 8 | MODBUS_AI_3_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 10 | MODBUS_AI_3_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 11 | MODBUS_AI_3_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 12 | MODBUS_AI_4_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 14 | MODBUS_AI_4_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 15 | MODBUS_AI_4_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 16 | MODBUS_AI_5_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 18 | MODBUS_AI_5_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 19 | MODBUS_AI_5_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 20 | MODBUS_AI_6_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 22 | MODBUS_AI_6_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 23 | MODBUS_AI_6_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 24 | MODBUS_AI_7_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 26 | MODBUS_AI_7_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 27 | MODBUS_AI_7_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 28 | MODBUS_AI_8_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 30 | MODBUS_AI_8_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 31 | MODBUS_AI_8_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 32 | MODBUS_AI_9_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 34 | MODBUS_AI_9_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 35 | MODBUS_AI_9_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 36 | MODBUS_AI_10_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 38 | MODBUS_AI_10_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 39 | MODBUS_AI_10_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 40 | MODBUS_AI_11_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 42 | MODBUS_AI_11_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 43 | MODBUS_AI_11_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 44 | MODBUS_AI_12_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 46 | MODBUS_AI_12_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 47 | MODBUS_AI_12_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 48 | MODBUS_AI_13_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 50 | MODBUS_AI_13_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 51 | MODBUS_AI_13_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 52 | MODBUS_AI_14_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 54 | MODBUS_AI_14_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 55 | MODBUS_AI_14_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 56 | MODBUS_AI_15_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 58 | MODBUS_AI_15_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 59 | MODBUS_AI_15_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 60 | MODBUS_AI_16_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 62 | MODBUS_AI_16_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 63 | MODBUS_AI_16_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 64 | CURRENTOUT_01_PV_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 66 | CURRENTOUT_01_PV_STATUS | 8-bit value in one register. | UINT16 | Read | ||||
| HR | 67 | CURRENTOUT_01_PV_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 68 | CURRENTOUT_02_PV_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 70 | CURRENTOUT_02_PV_STATUS | 8-bit value in one register. | UINT16 | Read | ||||
| HR | 71 | CURRENTOUT_02_PV_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 72 | CURRENTOUT_03_PV_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 74 | CURRENTOUT_03_PV_STATUS | 8-bit value in one register. | UINT16 | Read | ||||
| HR | 75 | CURRENTOUT_03_PV_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 76 | CURRENTOUT_04_PV_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 78 | CURRENTOUT_04_PV_STATUS | 8-bit value in one register. | UINT16 | Read | ||||
| HR | 79 | CURRENTOUT_04_PV_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 80 | CURRENTOUT_05_PV_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 82 | CURRENTOUT_05_PV_STATUS | 8-bit value in one register. | UINT16 | Read | ||||
| HR | 83 | CURRENTOUT_05_PV_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 84 | CURRENTOUT_06_PV_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 86 | CURRENTOUT_06_PV_STATUS | 8-bit value in one register. | UINT16 | Read | ||||
| HR | 87 | CURRENTOUT_06_PV_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 88 | CURRENTOUT_07_PV_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 90 | CURRENTOUT_07_PV_STATUS | 8-bit value in one register. | UINT16 | Read | ||||
| HR | 91 | CURRENTOUT_07_PV_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 92 | CURRENTOUT_08_PV_VALUE | FLOAT32 | CDAB | Read | ||||
| HR | 94 | CURRENTOUT_08_PV_STATUS | 8-bit value in one register. | UINT16 | Read | ||||
| HR | 95 | CURRENTOUT_08_PV_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read | ||||
| HR | 96 | CURRENTOUT_01_MA_VALUE | Current output signal; the table prints the unit as ampere. | FLOAT32 | CDAB | Read | |||
| HR | 98 | CURRENTOUT_02_MA_VALUE | Current output signal; the table prints the unit as ampere. | FLOAT32 | CDAB | Read | |||
| HR | 100 | CURRENTOUT_03_MA_VALUE | Current output signal; the table prints the unit as ampere. | FLOAT32 | CDAB | Read | |||
| HR | 102 | CURRENTOUT_04_MA_VALUE | Current output signal; the table prints the unit as ampere. | FLOAT32 | CDAB | Read | |||
| HR | 104 | CURRENTOUT_05_MA_VALUE | Current output signal; the table prints the unit as ampere. | FLOAT32 | CDAB | Read | |||
| HR | 106 | CURRENTOUT_06_MA_VALUE | Current output signal; the table prints the unit as ampere. | FLOAT32 | CDAB | Read | |||
| HR | 108 | CURRENTOUT_07_MA_VALUE | Current output signal; the table prints the unit as ampere. | FLOAT32 | CDAB | Read | |||
| HR | 110 | CURRENTOUT_08_MA_VALUE | Current output signal; the table prints the unit as ampere. | FLOAT32 | CDAB | Read | |||
| HR | 112 | MODBUS_DI_1_VALUE | 8-bit value in one register. | UINT16 | Read | 0 = False; 1 = True | |||
| HR | 113 | MODBUS_DI_1_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 114 | MODBUS_DI_2_VALUE | 8-bit value in one register. | UINT16 | Read | 0 = False; 1 = True | |||
| HR | 115 | MODBUS_DI_2_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 116 | MODBUS_DI_3_VALUE | 8-bit value in one register. | UINT16 | Read | 0 = False; 1 = True | |||
| HR | 117 | MODBUS_DI_3_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 118 | MODBUS_DI_4_VALUE | 8-bit value in one register. | UINT16 | Read | 0 = False; 1 = True | |||
| HR | 119 | MODBUS_DI_4_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 120 | MODBUS_DI_5_VALUE | 8-bit value in one register. | UINT16 | Read | 0 = False; 1 = True | |||
| HR | 121 | MODBUS_DI_5_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 122 | MODBUS_DI_6_VALUE | 8-bit value in one register. | UINT16 | Read | 0 = False; 1 = True | |||
| HR | 123 | MODBUS_DI_6_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 124 | MODBUS_DI_7_VALUE | 8-bit value in one register. | UINT16 | Read | 0 = False; 1 = True | |||
| HR | 125 | MODBUS_DI_7_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 126 | MODBUS_DI_8_VALUE | 8-bit value in one register. | UINT16 | Read | 0 = False; 1 = True | |||
| HR | 127 | MODBUS_DI_8_STATUS | Quality of the value. | UINT16 | Read | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 250 | MODBUS_DO_01_VALUE | 0 = false, 1-255 = true. | UINT16 | Read/write | ||||
| HR | 251 | MODBUS_DO_01_STATUS | Write 0 (good) or the device ignores the value. | UINT16 | Read/write | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 252 | MODBUS_DO_02_VALUE | 0 = false, 1-255 = true. | UINT16 | Read/write | ||||
| HR | 253 | MODBUS_DO_02_STATUS | Write 0 (good) or the device ignores the value. | UINT16 | Read/write | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 254 | MODBUS_DO_03_VALUE | 0 = false, 1-255 = true. | UINT16 | Read/write | ||||
| HR | 255 | MODBUS_DO_03_STATUS | Write 0 (good) or the device ignores the value. | UINT16 | Read/write | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 256 | MODBUS_DO_04_VALUE | 0 = false, 1-255 = true. | UINT16 | Read/write | ||||
| HR | 257 | MODBUS_DO_04_STATUS | Write 0 (good) or the device ignores the value. | UINT16 | Read/write | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 258 | MODBUS_DO_05_VALUE | 0 = false, 1-255 = true. | UINT16 | Read/write | ||||
| HR | 259 | MODBUS_DO_05_STATUS | Write 0 (good) or the device ignores the value. | UINT16 | Read/write | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 260 | MODBUS_DO_06_VALUE | 0 = false, 1-255 = true. | UINT16 | Read/write | ||||
| HR | 261 | MODBUS_DO_06_STATUS | Write 0 (good) or the device ignores the value. | UINT16 | Read/write | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 262 | MODBUS_DO_07_VALUE | 0 = false, 1-255 = true. | UINT16 | Read/write | ||||
| HR | 263 | MODBUS_DO_07_STATUS | Write 0 (good) or the device ignores the value. | UINT16 | Read/write | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 264 | MODBUS_DO_08_VALUE | 0 = false, 1-255 = true. | UINT16 | Read/write | ||||
| HR | 265 | MODBUS_DO_08_STATUS | Write 0 (good) or the device ignores the value. | UINT16 | Read/write | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 266 | MODBUS_AO_01_VALUE | FLOAT32 | CDAB | Read/write | ||||
| HR | 268 | MODBUS_AO_01_STATUS | Write 0 (good) or the device ignores the value. | UINT16 | Read/write | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 269 | MODBUS_AO_01_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read/write | ||||
| HR | 270 | MODBUS_AO_02_VALUE | FLOAT32 | CDAB | Read/write | ||||
| HR | 272 | MODBUS_AO_02_STATUS | Write 0 (good) or the device ignores the value. | UINT16 | Read/write | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 273 | MODBUS_AO_02_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read/write | ||||
| HR | 274 | MODBUS_AO_03_VALUE | FLOAT32 | CDAB | Read/write | ||||
| HR | 276 | MODBUS_AO_03_STATUS | Write 0 (good) or the device ignores the value. | UINT16 | Read/write | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 277 | MODBUS_AO_03_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read/write | ||||
| HR | 278 | MODBUS_AO_04_VALUE | FLOAT32 | CDAB | Read/write | ||||
| HR | 280 | MODBUS_AO_04_STATUS | Write 0 (good) or the device ignores the value. | UINT16 | Read/write | 0 = Good; 1 = Uncertain; 2 = Bad; 3 = Not assigned | |||
| HR | 281 | MODBUS_AO_04_UNIT | Unit code (table 7.1 of the guide). | UINT16 | Read/write |
Notes on this map
- Word order depends on the device's Byte order setting. At the factory default 1-0-3-2 a FLOAT is sent mantissa-low word first and sign/exponent word second, i.e. CDAB, which is what this file uses.
- The guide says every data type longer than 2 bytes other than FLOAT is sent like a string, most significant byte first at the default setting, so UNSIGNED32 values are listed as ABCD.
- UNSIGNED8 values occupy one full register.
- The AI/DI device variables carry whatever source is assigned to them in the transmitter menu (Setup/Outputs/Modbus); their unit code (table 7.1) tells what the value is. Units are therefore blank here.
- Status bytes: 0 good, 1 uncertain, 2 bad, 3 not assigned. AO and DO values written by the PLC are used only when their status is written as 0.
- Sensor blocks repeat per channel: sensor N uses registers N000-N999 (sensor 1 = 1000-1999). Only sensor 1 is listed; add (N-1) x 1000 for the others.
- DATETIME fields (7 bytes in 4 registers, packed date/time) are left out because the format is a packed structure, not a plain number.
- Current output values 96-110 are labelled in ampere in the table although the names say mA; check scaling against the analog output on site.
- A parameter has to be read or written in full; reading half of a FLOAT or string returns a slave-device-failure exception.
- The guide says function codes 03 and 04 return the same data, but it also gives separate input and holding tables that reuse the same numbers: diagnostics (input) and configuration (holding) both start at 500, and the sensor block (input) and sensor setup (holding) both start at X000. Because the guide does not settle which content a read returns at those numbers, every register that sits on such a clash is left out: the whole configuration block 500-736 (communication settings, byte order, watchdog, device tag, PID setpoints) and input registers 500-521, 594-625, 690-737 and sensor X000-X018.
- Timestamps (UNSIGNED32) count seconds since 1 January 1970.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP)
What Modbus registers does the Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP) have?
This map lists 221 registers: 97 input registers, 124 holding registers. 28 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide states that its register numbers start at 0 exactly as sent on the wire, and that Modicon-style PLCs must add 1. So AI 1 value (register 0) is 40001 in Modicon terms.
What byte order does the Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)) and CDAB (low word first (word-swapped)). Each register's order is in the Order column.
What are the minimum Modbus registers to integrate the Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP)?
Start with HR 0 MODBUS_AI_1_VALUE (AI 1 value (e.g. main measured value)); HR 2 MODBUS_AI_1_STATUS (AI 1 status); HR 3 MODBUS_AI_1_UNIT (AI 1 unit code); HR 4 MODBUS_AI_2_VALUE (AI 2 value (e.g. temperature)); HR 6 MODBUS_AI_2_STATUS (AI 2 status); HR 112 MODBUS_DI_1_VALUE (DI 1 value (e.g. limit contact)).
How do I enable Modbus control of the Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP)?
Menu Setup/General settings/Extended setup/Modbus/Settings: bus address (default 247, or set by the module's address switch), RTU/ASCII, baud (default 19200), parity (default even, 1 stop bit), byte order and watchdog. For TCP set the IP under .../Ethernet/Settings (DHCP by default) and use port 502. Assign sources to the device variables under Setup/Outputs.
What happens when the Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP) loses Modbus communication?
Modbus watchdog default 5 s (0-999 s, 0 = off), set in the Modbus settings menu. If no valid request arrives in that time the device raises diagnostic S969 and lights the red BF LED until the next valid request.
Where is the official Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP) Modbus documentation?
The source is Liquiline CM44x / Liquistation CSFxx / Liquiline System CA80xx - Data transmission via Modbus (Special Documentation) (SD01189C/07/EN/07.22), revision 2022-07, published free by Endress+Hauser at https://bdih-download.endress.com/files/DLA/005056A500261EECB9FE4A363A4B4FD5/SD01189CEN_07.22.pdf.
More Endress+Hauser Modbus register maps
- Sensor (electromagnetic flowmeter)
Endress+Hauser Proline Promag 300 electromagnetic flowmeter (Modbus RS485)
Promag 300 with the Modbus RS485 communication option, parameter description GP01053D/06/EN/04.22.
Also known as: Promag 300, Promag P 300, Promag H 300, Promag W 300 - Sensor (electromagnetic flowmeter)
Endress+Hauser Proline Promag 400 electromagnetic flowmeter (Modbus RS485)
Proline Promag 400 transmitters with the Modbus RS485 output, as described in GP01045D/06/EN/02.21.
Also known as: Promag D 400, Promag L 400, Promag W 400, Proline 400 Modbus RS485 - Sensor (ultrasonic gas flowmeter)
Endress+Hauser Proline Prosonic Flow G 300 ultrasonic gas flowmeter (Modbus RS485)
Prosonic Flow G 300 with the Modbus RS485 communication option, parameter description GP01131D/06/EN/02.24-00.
Also known as: Prosonic Flow G 300 - Sensor (ultrasonic gas flowmeter)
Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485)
Prosonic Flow G 500 with the Modbus RS485 communication option, parameter description GP01133D/06/EN/02.24-00.
Also known as: Prosonic Flow G 500 - Sensor (clamp-on ultrasonic flowmeter)
Endress+Hauser Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485)
Proline Prosonic Flow W 400 clamp-on flowmeter with the Modbus RS485 output, as described in GP01207D/06/EN/01.24.
Also known as: Prosonic Flow W 400
Other valves, actuators & sensors register maps
- Sensor (pressure transmitter)
KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)
KELLER X-Line transmitters with RS-485, Class.Group firmware 5.20-10.40 or later, 5.21 and 5.24 (protocol document version 3.7).
Also known as: Series 30X, Series 33X, Series 35X, Series 36X, Series 46X, PAA-33X, PR-33X, PA-36XW, Class.Group 5.20, Class.Group 5.21, Class.Group 5.24 - Sensor (leak detection controller)
RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave)
RLE LD5200 distance-read leak detection controller, user guide version 04.22 (firmware 2.3.1).
Also known as: LD5200 - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (flame detector)
Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU)
Teledyne Spyglass SG50-F optical flame detectors (IR3, UV-IR, IR3-H2 and HD video variants) with RS-485 Modbus RTU, communication manual SG50FMODBUS-EN rev 1.0.
Also known as: SG50-F, Spyglass SG50-F, IR3-HD, UV-IR, IR3, UV-IR-HD, IR3-H2-HD, IR3-H2, UV-IR-F, UV-IR-F-HD - Sensor (CO2 / humidity / temperature / pressure)
Teracom TSM400-4-CPTH Modbus CO2, humidity, temperature and pressure multi-sensor
TSM400-4-CPTH per the Teracom TSM400-4-CPTH user manual TSM400-4-CPTH-R1.9.
Also known as: TSM400-4-CPTH - Sensor (dew point transmitter)
Vaisala DMT153 dew point transmitter (Modbus RTU)
DMT153 trace-moisture dew point transmitter, Modbus RTU interface (user guide M213149EN-B).
Also known as: DMT153, DRYCAP DMT153
All valves, actuators & sensors Modbus register maps →
Source: Liquiline CM44x / Liquistation CSFxx / Liquiline System CA80xx - Data transmission via Modbus (Special Documentation) · SD01189C/07/EN/07.22 · rev. 2022-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.