Sensor (ultrasonic gas flowmeter) · Modbus register map

Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485) Modbus register map

Updated 19 November 2026

Short answer

Prosonic Flow G 500 is the remote-transmitter version of the Endress+Hauser ultrasonic gas flowmeter. With the Modbus RS485 option it is a Modbus RTU slave. This map covers flow, gas property and signal-quality values, totalizers, unit codes, diagnostics, serial settings and identification.

This page lists 44 Modbus registers for the Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Endress+Hauser’s own free documentation (linked below) and checked against it.

Manufacturer
Endress+Hauser
Model
Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485)
Equipment type
Sensor (ultrasonic gas flowmeter)
Registers
44 (14 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
247
Default serial
19200 baud, 8E1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Firmware
Valid as of device firmware 01.02.zz
Also known as
Prosonic Flow G 500
Source document
Description of Device Parameters Proline Prosonic Flow G 500 ultrasonic gas flowmeter · GP01133D/06/EN/02.24-00 · rev. 2024-01-31
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485)

Integration in brief

Read the process value floats (CDAB at the factory byte order) with function 03 or 04 and check Actual diagnostics (2732). Read the unit registers once so you know the engineering unit of each value.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2006Volume flowFLOAT32 CDABVolume flowRead
HR 2082Corrected volume flowFLOAT32 CDABCorrected volume flowRead
HR 2008Mass flowFLOAT32 CDABMass flowRead
HR 2014Flow velocityFLOAT32 CDABFlow velocityRead
HR 2731Actual diagnosticsUINT16Actual diagnosticsRead

Enable Modbus control & writes

The Modbus RS485 option must be ordered. Bus address, baud rate, parity and byte order are under Expert > Communication > Modbus configuration (registers 4910-4917).

Byte order & addressing

Network setup

Watch out for

Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

44 of 44 shown
Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2006doc 2007 to 2008Volume flowUnit set by register 2103.FLOAT32CDABRead
HR2008doc 2009 to 2010Mass flowUnit set by register 2101.FLOAT32CDABRead
HR2010doc 2011 to 2012Energy flowUnit set by register 5786.FLOAT32CDABRead
HR2012doc 2013 to 2014Sound velocityUnit set by register 2600.FLOAT32CDABRead
HR2014doc 2015 to 2016Flow velocityUnit set by register 2600.FLOAT32CDABRead
HR2016doc 2017 to 2018TemperatureUnit set by register 2109.FLOAT32CDABRead
HR2018doc 2019 to 2020Wobbe indexUnit per the corresponding unit parameter.FLOAT32CDABRead
HR2057doc 2058 to 2067Order codeSTRING[20]Read
HR2082doc 2083 to 2084Corrected volume flowUnit per the corresponding unit parameter.FLOAT32CDABRead
HR2092doc 2093 to 2094PressureUnit set by register 2130.FLOAT32CDABRead
HR2094doc 2095 to 2096Methane fractionUnit per the corresponding unit parameter.FLOAT32CDABRead
HR2100doc 2101Mass flow unitUnit code; see the picklist in the manual.UINT16Read/write
HR2102doc 2103Volume flow unitUnit code; see the picklist in the manual.UINT16Read/write
HR2106doc 2107Density unitUnit code; see the picklist in the manual.UINT16Read/write
HR2108doc 2109Temperature unitUnit code; see the picklist in the manual.UINT16Read/write
HR2129doc 2130Pressure unitUnit code; see the picklist in the manual.UINT16Read/write
HR2597doc 2598 to 2599Dynamic viscosityUnit per the corresponding unit parameter.FLOAT32CDABRead
HR2599doc 2600Velocity unitUnit code; see the picklist in the manual.UINT16Read/write
HR2609doc 2610 to 2611Totalizer 1 valueTotalizer unit per its own setting.FLOAT32CDABRead
HR2611doc 2612 to 2613Totalizer 1 overflowNumber of overflows of totalizer value.FLOAT32CDABRead
HR2731doc 2732Actual diagnosticsCurrent diagnostic message (behaviour symbol, code and short text).UINT16Read
HR2733doc 2734Previous diagnosticsUINT16Read
HR2796doc 2797 to 2798Molar massUnit per the corresponding unit parameter.FLOAT32CDABRead
HR2798doc 2799 to 2800DensityUnit set by register 2107.FLOAT32CDABRead
HR2809doc 2810 to 2811Totalizer 2 valueTotalizer unit per its own setting.FLOAT32CDABRead
HR2811doc 2812 to 2813Totalizer 2 overflowNumber of overflows of totalizer value.FLOAT32CDABRead
HR3009doc 3010 to 3011Totalizer 3 valueTotalizer unit per its own setting.FLOAT32CDABRead
HR3011doc 3012 to 3013Totalizer 3 overflowNumber of overflows of totalizer value.FLOAT32CDABRead
HR4550doc 4551 to 4552Acceptance rateFLOAT32CDABRead
HR4909doc 4910Bus address1-247.UINT16Read/write
HR4911doc 4912BaudrateUINT16Read/write0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 115200; 8 = 230400
HR4912doc 4913Data transfer modeFactory setting RTU.UINT16Read/write0 = RTU; 1 = ASCII
HR4913doc 4914ParityEven, odd or none; see note on the conflicting picklist codes.UINT16Read/write
HR4914doc 4915Byte orderFloat byte sequence; factory 1-0-3-2.UINT16Read/write0 = 0-1-2-3; 1 = 3-2-1-0; 2 = 2-3-0-1; 3 = 1-0-3-2 (factory)
HR4915doc 4916 to 4917Telegram delayFLOAT32CDABmsRead/write
HR4958doc 4959 to 4960Signal strengthUnit per the corresponding unit parameter.FLOAT32CDABRead
HR4982doc 4983 to 4984Signal to noise ratioFLOAT32CDABRead
HR5785doc 5786Energy flow unitUnit code; see the picklist in the manual.UINT16Read/write
HR7002doc 7003 to 7008Serial numberSTRING[12]Read
HR7237doc 7238 to 7245Device nameSTRING[16]Read
HR7276doc 7277 to 7280Firmware versionSTRING[8]Read
HR22771doc 22772 to 22773TurbulenceUnit per the corresponding unit parameter.FLOAT32CDABRead
HR25789doc 25790 to 25791Calorific valueUnit per the corresponding unit parameter.FLOAT32CDABRead
HR26374doc 26375 to 26376Reference densityUnit per the corresponding unit parameter.FLOAT32CDABRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485)

What Modbus registers does the Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485) have?

This map lists 44 registers: 44 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed in the Modbus Application Protocol form, which the manual equates with Modicon 3XXXX/4XXXX numbers (its example: mass flow 2007 = 32007), and the scan list calls register addresses 1-based. Subtract 1 on the wire.

What byte order does the Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485)?

Start with HR 2006 Volume flow (Volume flow); HR 2082 Corrected volume flow (Corrected volume flow); HR 2008 Mass flow (Mass flow); HR 2014 Flow velocity (Flow velocity); HR 2731 Actual diagnostics (Actual diagnostics).

How do I enable Modbus control of the Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485)?

The Modbus RS485 option must be ordered. Bus address, baud rate, parity and byte order are under Expert > Communication > Modbus configuration (registers 4910-4917).

Where is the official Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485) Modbus documentation?

The source is Description of Device Parameters Proline Prosonic Flow G 500 ultrasonic gas flowmeter (GP01133D/06/EN/02.24-00), revision 2024-01-31, published free by Endress+Hauser at https://bdih-download.endress.com/files/DLA/005056A500261EDEB082ABAFE97D2713/GP01133DEN_0224-00.pdf.

More Endress+Hauser Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Description of Device Parameters Proline Prosonic Flow G 500 ultrasonic gas flowmeter · GP01133D/06/EN/02.24-00 · rev. 2024-01-31. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.